ENVIRO C34 Linear Gas Fireplace Installation Guide

June 15, 2024
Enviro

ENVIRO C34 Linear Gas Fireplace

ENVIRO-C34-Linear-Gas-Fireplace-product

Product Information

Specifications

  • Model: C34 FIREPLACE
  • Installation Reference Guide: C-16871
  • Minimum Framing Dimensions:
    • Depth: 20″ (508 mm)
    • Width: 45″ (1143 mm)
    • Header Height: 38″ (965 mm)
    • Rough Opening Height: 43.5″ (1105 mm)
    • Enclosure Ceiling: 65″ (1651 mm)
  • Vent Size: Co-axial 5 x 8
  • Clearance to Combustibles:
    • A – Finishing edge to side wall: 7″ (229 mm)
    • B – Minimum clearance to enclosure ceiling: 65″ (1651 mm)
    • C – Minimum clearance to mantel height: See Chart
    • D – Front of the door to the edge of floor protection: 0″ (0 mm)
    • E – Minimum alcove width: 50″ (1270 mm)

Product Usage Instructions

Minimum Framing Dimensions
The minimum framing dimensions for the C34 FIREPLACE are as follows:

  • Depth: 20″ (508 mm)
  • Width: 45″ (1143 mm)
  • Header Height: 38″ (965 mm)
  • Rough Opening Height: 43.5″ (1105 mm)
  • Enclosure Ceiling: 65″ (1651 mm)

Clearance to Combustibles
The clearance to combustibles for the C34 FIREPLACE is as follows:

  • A – Finishing edge to side wall: 7″ (229 mm)
  • B – Minimum clearance to enclosure ceiling: 65″ (1651 mm)
  • C – Minimum clearance to mantel height: See Chart
  • D – Front of door to the edge of floor protection: 0″ (0 mm)
  • E – Minimum alcove width: 50″ (1270 mm)

Non-Combustible Board Placement
For framing, use either metal studs or concrete boards. Non-combustible boards should be placed as follows:

  • Combustible: 456 1/2
  • Non-Combustible: 13 3/4

Minimum Venting Requirements
The minimum venting requirements for the C34 FIREPLACE are as follows:

  • Minimum Venting Requirements: 20″ (509 mm)
  • Mantel Projections: 50″ (1272 mm)
  • Mantle Height: See Chart

CSS Front Vent – Overall Dimensions
The overall dimensions for the CSS Front Vent of the C34 FIREPLACE are as follows:

  • Dimension 1: 12.18
  • Dimension 2: 12.24
  • Dimension 3: 1.39
  • Dimension 4: 13.64
  • Dimension 5: 14.92
  • Dimension 6: 8.00
  • Dimension 7: 0.50
  • Dimension 8: 2.63
  • Dimension 9: 0.88
  • Dimension 10: 6.07
  • Dimension 11: 8.42
  • Dimension 12: 7.67
  • Dimension 13: 6.17
  • Dimension 14: 10.72
  • Dimension 15: 9.75
  • Dimension 16: 2.48
  • Dimension 17: 4.65
  • Dimension 18: 4.75

CSS Side Vent – Dimensions
The dimensions for the CSS Side Vent of the C34 FIREPLACE are as follows:

  • Dimension 1: 36.00
  • Dimension 2: 7.47
  • Dimension 3: 9.75

CSS Combustible Facing Kit Dimensions
The dimensions for the CSS Combustible Facing Kit of the C34 FIREPLACE are as follows:

  • Dimension 1: 26.00
  • Dimension 2: 4.75
  • Dimension 3: 9.95
  • Dimension 4: 9.95
  • Dimension 5: 9.95
  • Dimension 6: .50
  • Dimension 7: 2.00

CSS Outlet Dimensions
The dimensions for the CSS Outlet of the C34 FIREPLACE are as follows:

  • Min. Top and Bottom standoff: 25/8 (6.7 cm)
  • Outlet Finished Opening Size: C34 – 33″ (83.8 cm), C44 – 43″ (109.2 cm), C60 – 59″ (149.9 cm)

Venting Clearances – Front Vent
The venting clearances for the front vent of the C34 FIREPLACE are as follows:

  • Minimum Ceiling: 80″ (203 cm)
  • C72 Min. Ceiling: 91″ (231 cm)

Side Brace
The side brace requirements for the C34 FIREPLACE are as follows:

  • Min. Height: 39″ (99 cm)
  • Length of 5 dia. flex vent (not supplied): Min. Vent – 20″ (50.8 cm)
  • Min. Depth: Min. Depth

Optional Step – Cool Surface System Part 3
The optional step for the Cool Surface System Part 3 of the C34 FIREPLACE is as follows:

  • Min. Height: C34 – 45″ (114 cm), C44 – 55″ (140 cm), C60 – 71″ (180 cm), C72 – 83″ (211 cm)

Optional Step – Cool Surface System Part 2
The optional step for the Cool Surface System Part 2 of the C34 FIREPLACE is as follows:

  • Min. Height to Ceiling: 14.50, 15.00 (38 cm)
  • Min. to Ceiling: 5″ (12.5 cm)
  • Gap Shown: 3/4″ (2 cm)
  • Min. Ceiling Height: 18.75″ (48 cm)
  • Min. Distance to the wall from standoff: 5.00″ (13 cm)
  • Min. Distance to Ceiling: 4.5″ (11.5 cm)
  • *15.75″ (40 cm)

Optional Step – Cool Surface System Part 1
The optional step for the Cool Surface System Part 1 of the C34 FIREPLACE is as follows:

  • Dimensions: 9 / 2 / 11 / 7 / 32 / 37 / 25 / 2 / 3 / 2 / 2 7/

FAQ

Q: What are the minimum framing dimensions for the C34 FIREPLACE?
A: The minimum framing dimensions for the C34 FIREPLACE are as follows:

  • Depth: 20″ (508 mm)
  • Width: 45″ (1143 mm)
  • Header Height: 38″ (965 mm)
  • Rough Opening Height: 43.5″ (1105 mm)
  • Enclosure Ceiling: 65″ (1651 mm)

Q: What is the vent size for the C34 FIREPLACE?
A: The vent size for the C34 FIREPLACE is Co-axial 5 x 8.

Q: What is the clearance to combustibles for the C34 FIREPLACE?
A: The clearance to combustibles for the C34 FIREPLACE is as follows:

  • A – Finishing edge to side wall: 7″ (229 mm)
  • B – Minimum clearance to enclosure ceiling: 65″ (1651 mm)

REFER TO OWNER’S MANUAL FOR SPECIFIC INSTALLATION REQUIREMENTS AND ADDITIONAL PRODUCT INSTRUCTIONS

Minimum Framing Dimensions

  • Depth 20” 508 mm
  • Width 45” 1143 mm
  • Header Height 38” 965 mm
  • Rough Opening Height 43.5” 1105mm
  • Enclosure Ceiling 65” 1651 mm

ENVIRO-C34-Linear-Gas-Fireplace-fig- \(1\)

Note: Vent size = Co-axial 5 x 8”

Clearance to Combustibles

  • A – Finishing edge to the side wall 7″ 229mm
  • B – Minimum clearance to enclosure ceiling 65″ 1651 mm
  • C – Minimum clearance to mantel height See Chart See Chart
  • D – Front of the door to the edge of floor protection 0″ 0 mm
  • E – Minimum alcove width 50″ 1270 mm

Non-Combustible Board Placement

Minimum Venting Requirements

The minimum permitted venting is shown below. The framing height to the center of the thimble is 50”. Minimum venting must include a 12” vertical section and a 90-degree elbow which is then terminated horizontally. For a vertical termination please follow the vent pipe manufacturer’s installation instructions for vertical vent termination framing. A minimum of 1 in. (25 mm) clearance on all sides of the vertical vent pipe must be maintained. For every 12” of horizontal run there must be a 1/4” of rise. 1” of clearance between framing and venting must be maintained at all times. 2” above the venting and 3” above an elbow.

Fireplace Dimensions

Mantel Projections

Mantel graph dimensions are measured from the bottom of the fireplace, if you wish to reference the mantel height from the tiling edge subtract 15 inches (381mm) from the mantel height depicted on the graph. If you plan to install a TV above your fireplace refer to the appropriate section of the owner’s manual for available options. It is acceptable to install a combustible mantel over top of the non-combustible board. If you are activating the Cool Surface System you are eligible to subtract 12” (305mm) from the mantel height shown in this diagram. See page 6 for more details.

ENVIRO-C34-Linear-Gas-Fireplace-fig- \(6\)

OPTIONAL STEP

Cool Surface System Part 1

Dimensions

ENVIRO-C34-Linear-Gas-Fireplace-fig- \(7\) ENVIRO-C34-Linear-Gas-Fireplace-fig- \(9\)

Cool Surface System Part 2

Framing & Rough Opening – Front Vent
CSS Outlet Min. Top and Bottom standoff = 25/8” (6.7 cm) All C Series

ENVIRO-C34-Linear-Gas-Fireplace-fig- \(10\)

Venting Clearances – Front Vent
Shown here are the minimum framing and clearances for the CSS when the fireplace is installed with the minimum allowable vent length:

  • Min. Ceiling Clearance from top of CSS outlet = 4” (10.2 cm)
  • Min. Ceiling Clearance in wall from top of CSS Body = 55/8” (14.3 cm) CSS Body Min. Rear standoff = 2¾” (69.8 cm)ENVIRO-C34-Linear-Gas-Fireplace-fig- \(11\)

Cool Surface System Part 3

Framing & Clearances – CSS Side Vent

ENVIRO-C34-Linear-Gas-Fireplace-fig- \(12\)ENVIRO-C34-Linear-Gas-Fireplace-fig- \(13\)

Cool Surface System Part 4

Framing & Revised Mantle Clearances – Front Vent

ENVIRO-C34-Linear-Gas-Fireplace-fig- \(14\)

Framing & Revised Mantle Clearances – Side Vent

ENVIRO-C34-Linear-Gas-Fireplace-fig- \(15\)

TV Installation Considerations

  • If you are planning to mount a TV above your fireplace some considerations must be made to ensure it is protected from the heat.
  • During testing, temperatures did not exceed 121°F (49°C) midway up the front wall (see figures on right). There is no guarantee that these temperatures will not harm the longevity of your
  • TV. Make sure to consult your TV manufacturer’s specifications to find the maximum allowable operating temperature. Since every home and installation is unique, temperatures should be verified at the time of installation if possible. If desired, front wall temperatures can be lowered to 104°F (40°C) with the use of a mantle (see CSS TV clearances with Mantle figure). See the revised mantle clearances chart above. A TV should not be installed if temperatures exceed the manufacturer’s maximum allowable temperature.ENVIRO-C34-Linear-Gas-Fireplace-fig- \(16\)

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Enviro User Manuals

Related Manuals