ENVIRO C72 Fireplace Installation Guide
- June 16, 2024
- Enviro
Table of Contents
- ENVIRO C72 Fireplace
- Product Information
- Product Usage Instructions
- Minimum Framing Dimensions
- Clearance to Combustibles
- Non-Combustible Board Placement
- Minimum Venting Requirements
- Fireplace Dimensions
- Mantel Projections
- OPTIONAL STEP
- TV Installation Considerations
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
ENVIRO C72 Fireplace
Product Information
Specifications
- Depth: 20″ (508 mm)
- Width: 83″ (2108 mm)
- Header Height: 38″ (965 mm)
- Rough Opening Height: 43.5″ (1105 mm)
- Enclosure Ceiling: 84″ (2134 mm)
- Vent Size: Co-axial 5 x 8
Product Usage Instructions
Minimum Framing Dimensions
To ensure proper installation of the C72 Fireplace, follow these minimum
framing dimensions:
- Clearance from framing studs to venting: 1″ (25 mm)
Clearance to Combustibles
Ensure proper clearance of combustible materials:
- A – Finishing edge to side wall: 7″ (229 mm)
- B – Minimum clearance to enclosure ceiling: 84″ (2134 mm)
- C – Minimum clearance to mantel height: See chart
- D – Front of the door to the edge of floor protection: 0 mm
- E – Minimum alcove width: 88″ (2235 mm)
Non-Combustible Board Placement
When framing the fireplace, use the following non-combustible board placement:
- Framing: Metal Stud
- Concrete Board: Combustible
- Drywall Sidewall: Non-combustible
Minimum Venting Requirements
For proper venting, follow these minimum requirements:
- Venting Depth: 20″ (508 mm)
- Non-combustible Zone: 19″ (483 mm)
- Centre of Thimble: Use one 24″ and one 6″ to achieve a minimum 67 1/2″ (1714 mm) rise
Fireplace Dimensions
For proper installation, the following dimensions should be considered:
- Electrical Inlet Left Side: 38″ (965 mm)
- Gas Inlet Right Side: 9 1/4″ (232 mm)
- Gas Inlet Bottom (Optional): 9 1/4″ (232 mm)
Mantel Projections
The mantel projections for the fireplace are as follows:
- 47 1/2″ Mantle
- 46 1/2″ Mantle
- 45 1/2″ Mantle
- 44 1/2″ Mantle
- 43 1/2″ Mantle
- 42 1/2″ Mantle
- 41 1/2″ Mantle
- 4″ Mantle
C72 CSS Front Vent – Overall Dimensions
The overall dimensions for the C72 CSS front vent are as follows:
- Width: 12.18″
- Height: 13.64″
- Depth: 8.42″
CSS Side Vent – Dimensions
The dimensions for the CSS side vent are as follows:
- Width: 36.00″
- Height: 26.00″
- Depth: 4.75″
C72 CSS Combustible Facing Kit Dimensions
The dimensions for the C72 CSS combustible facing kit are as follows:
- Width: 2.04″
- Height: 2.48″
- Depth: 9.95″
CSS Outlet Min. Top and Bottom Standoff
The minimum top and bottom standoff for the CSS outlet is 25/8″ (6.7 cm) for
all C Series.
Venting Clearances – Front Vent
Ensure proper venting clearances for the front vent:
- Minimum Ceiling: 80″ (203 cm)
- C72 Min. Ceiling: 91″ (231 cm)
FAQ
-
Q: What are the minimum framing dimensions for the C72 Fireplace?
A: The minimum framing dimensions require a clearance of 1″ (25 mm) from framing studs to venting. -
Q: What are the clearance requirements for combustible materials?
A: The clearance requirements are as follows:- A – Finishing edge to side wall: 7″ (229 mm)
- B – Minimum clearance to enclosure ceiling: 84″ (2134 mm)
- C – Minimum clearance to mantel height: See chart
- D – Front of door to the edge of floor protection: 0 mm
- E – Minimum alcove width: 88″ (2235 mm)
-
Q: What type of venting is required for the C72 Fireplace?
A: The vent size required is Co-axial 5 x 8. -
Q: What are the minimum venting requirements?
A: The minimum venting requirements include a venting depth of 20″ (508 mm) and a non-combustible zone of 19″ (483 mm). The centre of the thimble should have a minimum rise of 67 1/2″ (1714 mm). -
Q: What are the dimensions of the C72 CSS front vent?
A: The dimensions of the C72 CSS front vent are as follows:- Width: 12.18″
- Height: 13.64″
- Depth: 8.42″
Minimum Framing Dimensions
Depth | 20” | 508 mm |
---|---|---|
Width | 83” | 2108 mm |
Header Height | 38” | 965 mm |
Rough Opening Height | 43.5” | 1105mm |
Enclosure Ceiling | 84” | 2134 mm |
Note: Vent size = Co-axial 5 x 8” |
Clearance to Combustibles
- A – Finishing edge to side wall 7″ 229 mm
- B – Minimum clearance to enclosure ceiling 84″ 2134 mm
- C – Minimum clearance to mantel height See Chart See Chart
- D – Front of door to edge of floor protection 0″ 0 mm
- E – Minimum alcove width 88″ 2235 mm
Non-Combustible Board Placement
Minimum Venting Requirements
Minimum permitted venting is shown below. The framing height to the center of the thimble is 67.5”. Minimum venting must include a 24” & 6” vertical section and a 90 degree elbow which is then terminated horizontally. For a vertical termination please follow the vent pipe manufacturer’s installation instructions for vertical vent termination framing. A minimum of 1 in. (25 mm) clearance on all sides of the vertical vent pipe must be maintained. For every 12” of horizontal run there must be a 1/4” of rise. 1” of clearance between framing and venting must be maintained at all times. 2” above the venting and 3” above an elbow.
Fireplace Dimensions
Mantel Projections
Mantel graph dimensions are measured from the bottom of the fireplace, if you wish to reference the mantel height from the tiling edge subtract 15 inches (381mm) from the mantel height depicted on the graph. If you plan to install a TV above your fireplace refer to the appropriate section of the owner’s manual for available options. It is acceptable to install a combustible mantel over top of the non-combustible board. If you are activating the Cool Surface System you are eligible to subtract 12” (305mm) from the mantel height shown in this diagram. See page 6 for more details.
OPTIONAL STEP
Cool Surface System Part 1
Dimensions
Cool Surface System Part 2
Framing & Rough Opening – Front Vent
CSS Outlet Min. Top and Bottom standoff = 25/8” (6.7 cm) All C Series
Venting Clearances Front Vent
- Shown here are the minimum framing and clearances for the CSS when the fireplace is installed with the minimum allowable vent length:
- Min. Ceiling Clearance from top of CSS outlet = 4” (10.2 cm)
- Min. Ceiling Clearance in wall from top of CSS Body = 55/8” (14.3 cm) CSS Body Min. Rear standoff = 2¾” (69.8 cm)
Cool Surface System Part 3
Framing & Clearances – CSS Side Vent
Cool Surface System Part 4
TV Installation Considerations
If you are planning to mount a TV above your fireplace some considerations must be made to ensure it is protected from the heat.
During testing, temperatures did not exceed 121°F (49°C) midway up the front wall (see figures on right). There is no guarantee that these temperatures will not harm the longevity of your TV. Consult your TV manufacturer’s specifications to find the maximum allowable operating temperature. Since every home and installation is unique, temperatures should be verified at the time of installation if possible. If desired, front wall temperatures can be lowered to 104°F (40°C) using a mantle (see CSS TV clearances with Mantle figure). See the revised mantle clearances chart above. A TV should not be installed if temperatures exceed the manufacturer’s maximum allowable temperature.