ALPICAIR ACMI-22VRDC1D Indoor Industrial Air Conditioner Owner’s Manual
- June 17, 2024
- ALPICAIR
Table of Contents
Owner’s Manual
Original Instructions
Commercial Air Conditioners
Multi Variable Air Conditioners
Cassette Type Indoor Unit
Models:
ACMI-22VRDC1D ACMI-28VRDC1D
ACMI-36VRDC1D ACMI-45VRDC1D
ACMI-50VRDC1D ACMI-56VRDC1D
ACMI-63VRDC1D ACMI-71VRDC1D
ACMI-80VRDC1D ACMI-90VRDC1D
ACMI-100VRDC1D ACMI-112VRDC1D
ACMI-125VRDC1D ACMI-140VRDC1D
ACMI-160VRDC1D
Thank you for choosing commercial air conditioners. Please read this Owner’s Manual carefully before operation and retain it for future reference.
To Users
Thank you for selecting our product. Please read this instruction manual carefully before installing and using the product, so as to master and correctly use the product. In order to guide you to correctly install and use our product and achieve expected operating effect, we hereby instruct as below:
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsibility for their safety. Children should be supervised to ensure that they do not play with the appliance.
- In order to ensure reliability of product, the product may consume some power under stand-by status for maintaining normal communication of system and preheating refrigerant and lubricant. If the product is not to be used for long, cut off the power supply; please energize and preheat the unit in advance before reusing it.
- Please properly select the model according to actual using environment, otherwise it may impact the using convenience.
- This product has gone through strict inspection and operational test before leaving the factory. In order to avoid damage due to improper disassembly and inspection, which may impact the normal operation of unit, please do not disassemble the unit by yourself. You can contact with the special maintenance center of our company if necessary.
- When the product is faulted and cannot be operated, please contact with our maintenance center as soon as possible by providing the following information.
- Contents of nameplate of product (model, cooling/heating capacity, product No., ex-factory date).
- Malfunction status (specify the situations before and after the error occurs).
- All the illustrations and information in the instruction manual are only for reference. In order to make the product better, we will continuously conduct improvement and innovation. We have the right to make necessary revision to the product from time to time due to the reason of sales or production, and reserve the right to revise the contents without further notice.
- The final right to interpret for this instruction manual belongs to AlpicAir.
Exception Clauses
Manufacturer will bear no responsibilities when personal injury or property loss is caused by the following reasons:
- Damage the product due to improper use or misuse of the product;
- Alter, change, maintain or use the product with other equipment without abiding by the instruction manual of manufacturer;
- After verification, the defect of product is directly caused by corrosive gas;
- After verification, defects are due to improper operation during transportation of product;
- Operate, repair, maintain the unit without abiding by instruction manual or related regulations;
- After verification, the problem or dispute is caused by the quality specification or performance of parts and components that produced by other manufacturers;
- The damage is caused by natural calamities, bad using environment or force majeure.
Safety Notices (Please be Sure to Abide)
WARNING: If not abide strictly, it may cause severe damage to the unit or
the people.
NOTE: If not abide strictly, it may cause slight or medium damage to the
unit or the people.
This sign indicates that the operation must be prohibited. Improper operation
may cause severe damage or death to people.
** This sign indicates that the items must be observed. Improper operation
may cause damage to people or property.
WARNING!**
This product can’t be installed at corrosive, inflammable or explosive
environment or the place with special requirements, such as kitchen.
Otherwise, it will affect the normal operation or shorten the service life of
the unit, or even cause fire hazard or serious injury. As for above special
places, please adopt special air conditioner with anti-corrosive or anti-
explosion function.
This Multi VRF System shall only be connected to an appliance suitable for the
same refrigerant.
All units in Manual Cover is a partial unit, complying with partial unit of
IEC 60335-2-40:2018, and must only be connected to other units that have been
confirmed as complying to corresponding partial unit requirements of this
international standard.
The electrical interface shall comply with electrical security requirement,
current shall be referred to the table of “Dimension of power cord and
capacity of air switch” in Section 3.4, and safety class of construction is Ⅰ.
| Please install the unit according to instructions in this manual. Read this
manual carefully before starting up or checking the machine.| | Installation
should be performed by dealer or
qualified technicians. Do not install the product by yourself.
Improper installation may result in water leakage, electric
shock or fire hazard.
---|---|---|---
| Make sure the local power supply is in accordance with units before
installation, and
check the power supply carefully.| | This air conditioner must be properly
grounded through the receptacle to avoid electric shock. The grounding wire
shouldn’t be connected with gas pipe, water pipe, lightning arrester or
telephone line.
| Please use specialized accessories or parts to carry out installation, or
water leakage, electric shock, fire hazard may resulted.| | R410A refrigerant
can produce poisonous gas once it meets fire, so please ventilate the room
immediately if refrigerant leaks out during installation.
| Diameter of power cord must be large enough. Damaged power cord and
connecting wire must be replaced by specialized electric cable.| | After the
power cord is connected, please install the cover of electric box to avoid
danger.
| Nitrogen must be charged according to technical requirements.| | Short
circuit is forbidden. Do not cancel the pressure switch in case the unit may
be damaged.
| For units with wired controller, do not connect power supply until the wired
controller is well installed. Otherwise, the wired controller cannot be used.|
| When the installation is finished, please check and make sure the drain
pipe, pipeline and electric wire are all well connected in order to avoid
water leakage, refrigerant leakage, electric shock or fire hazard.
| Do not extend fingers or objects into air outlet or air return grille.| | If
you use gas heater or petroleum heater in the same room, please open the door
or window to maintain good air circulation in case the room
may lack of oxygen.
| Never start or stop the air conditioner by inserting or removing the power
cord.| | Do not turn off the air conditioner until it runs for at least 5
minutes. Otherwise, oil-return of the compressor will be affected.
| Children are not allowed to operate the air conditioner.| | Do not operate
the air conditioner with wet hands.
| Please turn the unit off and unplug your air conditioner before cleaning.
Otherwise, itmay cause electric shock or personal injury.| | Do not spray
water on the air conditioner or it will cause malfunction or electric shock.
| Do not expose the air conditioner directly to water or place it in a damp
or corrosive
environment.| | Connect power supply 8 hours before operation. Do not
disconnect power if you want to stop the unit in a short period of time, e.g.
in one night (This is for protecting the compressor).
| Volatile liquid like thinner or gasoline will damage the appearance of air
conditioner Please use soft dry cloth or wet cloth with mild detergent to
clean the outer case of air conditioner.| | During Cooling mode, indoor
temperature should not be set too low. Keep the difference between indoor temp
and outdoor temp within 5 ℃.
| If abnormal condition occurs (e.g. unpleasant smell), please turn off the
unit at once and
disconnect power supply. Then contact our service center. If the air
conditioner continues to operate despite of abnormal
condition, the unit may be damaged and it may cause electric shock or fire
hazard.)| | Do not repair the air
conditioner by yourself. Improper repair will cause
electric shock or fire hazard. Please contact our service center and have it
repaired by professional technicians.
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision. Install units according to
national wiring codes.
If the supply cord is damaged, it must be replaced by the manufacturer or its
service agent or a similarly qualified person in order to avoid a hazard.
An all-pole disconnection device which has at least 3mm clearances in all
poles, and disconnection must be incorporated in the fixed wiring in
accordance with the wiring rules.
AlpicAir will not assume responsibility for any personal injury or property
loss caused by improper installation, improper debugging, unnecessary repair
or not following the instructions of this manual.
Any personal injury or property loss caused by improper installation, improper
debug, unnecessary repair or not following the instructions of this manual
should not be the responsibility of AlpicAir.
Correct Disposal of this product
This marking indicates that this product should not be disposed with other
household wastes throughout the EU. To prevent possible harm to the
environment or human health from uncontrolled waste disposal, recycle it
responsibly to promote the sustainable reuse of material resources. To return
your used device, please use the return and collection systems or contact the
retailer where the product was purchased. They can take this product for
environmental safe recycling.
Product Introduction
2.1 Names of Key Components
2.2 Rated Working Condition
– | Indoor Side Condition | Outdoor Side Condition |
---|---|---|
Dry Bulb Temp℃ | Wet Bulb Temp℃ | Dry Bulb Temp℃ |
Rated Cooling | 27 | 19 |
Rated Heating | 20 | 15 |
Preparations for Installation
NOTE! This picture is for reference only, please refer to the actual
product; the unit of dimension is mm.
3.1 Standard Fittings
Use the following provided accessories according to the requirement.
No. | Name | Appearance | Q’ty | Usage |
---|---|---|---|---|
1 | Wireless controller | 1 | To control the indoor unit. | |
2 | Paper pattern for installation | 1 | Locate the drill hole on ceiling. | |
3 | Tapping screw with washer | 4 | Fix paper pattern. | |
4 | Washer fixing plate | 4 | Prevent the washer from falling off. | |
5 | Drain Hose Assembly | 1 | To connect with the hard PVC drain pipe. | |
6 | Special Nut | 2 | ACMI-22~50VRDC1D | |
1 | ACMI-56~160VRDC1D | |||
7 | Corrugated pipe | 1 | ACMI-56~160VRDC1D | |
8 | M10 Washer | 10 | To be used together with the hanger bolt for installing |
the unit.
No.| Name| Appearance| Q’ty| Usage
---|---|---|---|---
9| Insulation| | 2| To insulate the gas/ liquid pipe
10| Sponge| | 4| To insulate the drain pipe.
11| Fastener| | 4| To fasten the sponge.
3.2 Installation Position Selection
- The appliance shall not be installed in the laundry.
- The location should be able to withstand the weight of unit.
- The water can be drained conveniently from drainage pipe.
- There should be no obstruction near air inlet and air outlet.
- Follow the installation distance required in the fig below to ensure sufficient space for maintenance.
- The installation location should be far from heat sources, flammable or explosive gas, or smog spread in the air.
- The indoor unit, outdoor unit, power cord and connection electricity wire should be at least 1m from television and radio in order to prevent interference and noise (Even though 1m distance is ensure, there may be noise if the electric wave is too strong).
Unit: mm
Model | H(mm) |
---|---|
ACMI-22~100VRDC1D | 275 |
ACMI-112~160VRDC1D | 325 |
NOTES!
- The unit shall be installed in accordance with national standards or local regulations.
- Only qualified personnel can carry out installation work, please contact with local dealer before installation.
- Make sure all the installation work completed before energizing.
- The appliances are not accessible to general public.
3.3 Requirements of Communication Wire Selection
NOTE!
If air conditioner used under strong electronic-magnetic interference
circumstance, STP (shielded twisted pair) communication cable must be adopted.
3.3.1 Selection of communication wire between indoor unit and wired controller
Wire type| Total length of communication wire between indoor unit and wired
controller (m)| Wire diameter (mm²)| Wire standard| Remark
---|---|---|---|---
Light/normal PVC hose| L≤250| 2×0.75~2×1.25| IEC 60227-5| 1. Total length of
communication line can’t exceed 250m.
2. The cord shall be Circular cord (the cores shall be twisted together).
3. If unit is installed in places with intense magnetic field or strong
interference, it is necessary to use shielded wire.
3.3.2 Selection of Communication Wire between Indoor Unit and Indoor Unit (or outdoor unit)
Wire type
| Total length of communication wire between indoor unit and indoor unit(outdoor unit) (m)| Wire diameter (mm²)| Wire standard|
Remark
---|---|---|---|---
Light/normal PVC hose| L≤1000| ≥2×0.75| IEC 60227-5| 1. If the wire diameter
is enlarged to 2×1mm², the total communication length line can reach 1500m.
2. The cord shall be Circular cord (the cores shall be twisted together).
3. If unit is installed in places with intense magnetic field or strong
interference, it is necessary to use shielded wire.
3.4 Wiring Requirement
Dimension of power cord and capacity of air switch.
Model
|
Power Cord Size
| Air Switch Capacity (A)| Minimum Sectional Area of Ground Wire (mm²)|
Minimum Sectional Area of Power Cord (mm²)
---|---|---|---|---
ACMI-22VRDC1D|
220-240V-1ph-50Hz 208-230V-1ph-60Hz
| 6| 1.0| 1.0
ACMI-28VRDC1D| 6| 1.0| 1.0
ACMI-36VRDC1D| 6| 1.0| 1.0
ACMI-45VRDC1D| 6| 1.0| 1.0
ACMI-50VRDC1D| 6| 1.0| 1.0
ACMI-56VRDC1D| 6| 1.0| 1.0
ACMI-63VRDC1D| 6| 1.0| 1.0
ACMI-71VRDC1D| 6| 1.0| 1.0
ACMI-80VRDC1D| 6| 1.0| 1.0
ACMI-90VRDC1D| 6| 1.0| 1.0
ACMI-100VRDC1D| 6| 1.0| 1.0
ACMI-112VRDC1D| 6| 1.0| 1.0
ACMI-125VRDC1D| 6| 1.0| 1.0
ACMI-140VRDC1D| 6| 1.0| 1.0
ACMI-160VRDC1D| 6| 1.0| 1.0
NOTES!
- An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring.
- The circuit breaker and power cord specification in above sheet is based on max power (max current) of the unit.
- The power cord specification in above sheet is based on ambient temperature of 40 ℃.
- If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
- The circuit breaker specification in above sheet is based on ambient temperature of 40 ℃. If the working condition is different, please adjust it according to the specification sheet of circuit breaker.
Installation Instructions
4.1 Indoor Unit Installation
4.1.1 Ceiling Opening Dimension and Suspension Bolt Position.
Unit: mm
Model | A | B | C | D | E |
---|---|---|---|---|---|
ACMI-22~160VRDC1D | 950 | 890 | 840 | 680 | 780 |
4.1.2 Suspend the Indoor Unit
(1) Drill bolt holes and install bolts.
-
Stick the reference cardboard on the installation position; drill 4 holes according to the hole site on the cardboard as shown in Fig.4.1.2; diameter of drilling hole is according to the diameter of expansion bolt and the depth is 60-70mm, as shown in Fig.4.1.3.
-
Insert the M10 expansion bolt into the hole and then knock the nail into the bolt, as shown in Fig.4.1.4.
NOTE! The length of bolt depends on the installation height of the unit, bolts are field supplied.
(2) Install the indoor unit temporarily.
Assemble suspension bolt on the expansion bolt, attach the hanger bracket to
the suspension bolt. Be sure to fix it securely by using a nut and washer from
upper and lower sides of the hanger bracket. The washer fixing plate will
prevent the washer from falling.
(3) The usage of paper pattern.
Refer to paper pattern of installation for ceiling opening dimension. The
center of ceiling opening is indicated on the paper pattern. Fix the paper
pattern to the unit with 4 screws and fix the corners of the waterspout at the
drainage pipe by screws.
(4) Adjust the unit to the right position.
(5) Check the level of the unit.
The indoor unit is equipped with build-in water pump and float switch, verify
the levelness of 4 directions by level gauge or vinyl tube (filled with water)
respectively.
(6) Remove the washer locating plate and then tighten the nut on it.
(7) Remove the paper pattern.
- Nut(field supplied)
- Washer(provided)
- Hoisting stand
- Washer fixing plate(provided)
Fig.4.1.5
- Level meter
- Paper pattern
- Center of ceiling opening
- Screw(provided)
Fig.4.1.6
4.2 Refrigerant Pipe Connection
- Aim the flaring port of copper pipe at the center of screwed joint and then tighten the flaring nut with hand as shown in Fig.4.2.
-
Tighten the flaring nut with torque wrench.
Torque for tightening nutPipe diameter (mm)| Torque (N·m)
Φ6.35| 15~30
Φ9.52| 35~40
Φ12.7| 45~50
Φ15.9| 60~65
Φ19.05| 70~75 - Use pipe bend when bending the pipe and the bending angle should not be too small.
- Wrap the connection pipe and joint with sponge and then tie them firmly with tape.
4.3 Drainage Pipe Installation and Drainage System Testing
4.3.1 Notice for Installation of Drain Pipe
- It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines which are likely to produce corrosive or peculiar smell to prevent the smell from entering indoors or corrupt the unit.
- It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water from pouring in and cause property loss or personal injury.
- Condensate drain pipe should be connected into special drain system for air conditioner.
- The drainage pipe should be short and the gradient downwards should be at least 1%~2% in order to drain condensation water smoothly.
- The diameter of drainage hose should be bigger or equal to the diameter of drainage pipe joint.
- Install drainage pipe according to the following fig and arrange insulation to the drainage pipe. Improper installation may lead to water leakage and damp the furniture and other things in the room.
- You can buy normal hard PVC pipe used as the drainage pipe. During connection, insert the end of PVC pipe into the drainage hole and then tighten it with drainage hole and wire binder. Can’t connect the drainage hole and drainage hole with glue.
- When the drainage pipelines are used for several units, the position of pipeline should be about 100mm lower than the drainage port of each unit. In this case, thicker pipes should be applied.
4.3.2 Drainage Pipe Installation
-
Drainage pipe should have the same diameter or larger diameter than the connecting pipes (PVC pipe, outside diameter 25mm, thickness≥1.5mm).
-
Keep drainage pipe short and sloping downwards at a gradient of at least 1% for preventing forming air bubbles.
-
If the gradient of drainage pipe could not meet the installation requirements, raising pipe should be applied.
-
Insert the drainage hose into drain socket, tighten the metal clamp securely.
-
Warp the sealing pad over drain hose and metal clamp for heat insulation.
-
Make sure to perform insulation work for all drainage piping in order to prevent any possible water drop due to dew condensation.
-
Apply the suitable diameter for converging drainage pipe according to the operating capacity of the unit.
Unit:mm
-
The installation height of raising pipe for drainage should be lower than B. The gradient from raising pipe towards drainage direction should be at least 1%~2%. If the raising pipe is vertical with the unit, the raising height should be less than C, as shown in Fig. 4.3.3.
1 Ceiling
2 Drain hose(bending is not allowed)
3 Hanger bracket
4 Drainage pipe
5 Metal clamp
Fig.4.3.3Model| A| B| C
---|---|---|---
ACMI-22~160VRDC1D| 220| 980| 930 -
Drain pipes should have a downward slope of at least 1%~2%, in order to prevent pipes from sagging, install hanger bracket at intervals of 1000~1500mm.
-
During the installation, distance from soft drain pipe to the gasket is C mm when the bolt is tightened. It is not allowed to apply PVC or other related glue in the joints of two ends of drain pipe.
Model| C
---|---
ACMI-22~160VRDC1D| 15±3
4.3.3 Test of Drainage System
- Please test drainage system after electric work is finished.
Inject approximately 1L purified water to drain pan from air vent, ensure that not to splash the water over the electrical components (e.g. water pump. etc.).
- In case of commissioning finished, please energize the IDUs and switch to cooling or dry mode, meanwhile, the water pump operates, you can check the draining through the transparent part of drain socket.
- If communication wire is not connected, communication malfunction “C0” will occur after 60s of energizing. In this case, the water pump operates automatically. Check if the water pump drains normally drains normally through drainage port. The water pump will stop automatically after running for 10min.
- During the test, please carefully check the drainage joint, make sure no any leakage occur.
- It’s strongly recommend to do the drain test before ceiling decoration.
4.4 Panel Installation
4.4.1 Notices for Installation
-
Improper decorative panel installation could cause the following problems.
-
Ensure that its clearance-free between decoration panel and ceiling board after installation, if not, please adjust the body position.
-
Connect the decoration panel terminals (Female) to body terminals (male) as shown in Fig.4.4.3.
4.4.2 Panel Installation
- Detach the panel’s Corner Cap, there is a mark “piping side” on one of the 4 corners, adjust the panel direction so as to keep the mark and fittings on the same corner.
- Temporality hang the panel to body (there is four hangers on each corner of the panel, hang the hangers to corresponding hooks on the body), as shown in Fig.4.4.4.
- Detach the air inlet grille from panel, make a wiring connection of signal receiver. Notices that the connection wire not stuck in the middle of body and panel, or may cause air leakage and lead to condensation water drop.
- Tighten 4 screws at each corner of panel respectively, fix the panel on the body firmly.
- After tightening screws, reinstall the air inlet grille.
1 Hook up
2 Hang buckle
3 Position of fittings
4 Step motor of louver
5 Indoor unit
6 Ceiling
7 Air outlet
8 Decoration panel
9 Sealing material
4.5 Wired Controller Installation
Wired controller is optional accessory. If wired controller is needed, please
contact your local dealer and install the wired controller according to the
instruction manual.
NOTE!
Do perform the commissioning operation before first use, automatic addressing
or other settings, please refer to the manual of ODU.
Wiring Work
WARNING!
Before obtaining access to terminals, all supply circuits must be
disconnected.
NOTES!
- Units must be earthed securely, or it may cause electric shock.
- Please carefully read the wiring diagram before carry out the wiring work, incorrect wiring could cause malfunction or even damage the unit.
- The unit should be powered by independent circuit and specific socket.
- The wiring should be in accordance with related regulations in order to ensure the units reliable running.
- Install circuit breaker for branch circuit according to related regulations and electrical standards.
- Keep cable away from refrigerant pipings, compressor and fan motor.
- The communication wires should be separated from power cord and connection wire between indoor unit and outdoor unit.
- Adjust the static pressure via wired controller according to site circumstance.
5.1 Connection of Wire and Patch Board Terminal
- The connection of wire (as shown in Fig.5.1.1).
- Strip about 25mm insulation of the wire end by stripping and cutting tool.
- Remove the wiring screws on the terminal board.
- Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in accordance with screw.
- Use the screwdriver for tightening the terminal.
- The connection of stranded wire (as shown in Fig.5.1.2).
- Strip about 10mm insulation of the end of stranded wire by stripping and cutting tool.
- Loosen the wiring screws on terminal board.
- Insert the wire into the ring tongue terminal and tighten by crimping tool.
- Use the screwdriver for tightening the terminal.
5.2 Power Cord Connection
NOTES!
- Every unit should be equipped with a circuit breaker for short-circuit and overload protection.
- During operation, all indoor units connected to the same outdoor unit system must be kept energized status. Otherwise, the unit can’t operate normally.
Note:
- Connect wires for single-phase unit according to figure 1 and connect wires for three-phase unit according to figure 2 .As for some areas where there’s no neutral wire, please refer to the wiring diagram of unit for details.
- The maximum connection quantity “n” for indoor unit is decided by the capacity of outdoor unit. Please refer to the unit capacity of unit for details.
Fig.5.2
(1) Detach the electric box lid.
(2) Let the power cord pass through the wiring through-holes.
(3) Connect wires according to Fig.5.2.
(4) Fix the power cord with wiring clamp.
5.3 Connection of Communication Wire between Indoor Unit and Outdoor Unit (or Indoor Unit)
-
Detach the electric box lid.
-
Let the Communication cable pass through the wiring through-holes.
-
Connect the communication wire to terminal D1 and D2 of indoor 4-bit wiring board, as shown in Fig.5.3.1.
-
Fix the communication cable with clamp of electric box.
-
For more reliable communication, make sure connect the terminal resistor to the most downstream IDU of the communication bus (terminal D1 and D2), as shown in Fig. 5.3.2, terminal resistor is provided with each ODU.
5.4 Connection of Communication Wire for Wired Controller
- Detach the electric box lid.
- Let the communication wire pass through the wiring through-holes.
- Connect the communication wire to terminal H1 and H2 of indoor 4-bit wiring board.
- Fix the communication wire with clamp.
- Wiring instructions of signal receiver and wired controller:
- Wired controller is shown as Fig.5.4.1, wireless controller is shown as
Fig.5.4.2, signal receiver is provided with panel as standard accessory.
- Both IDU and wired controller are equipped with signal receiver, and
available for wireless control respectively.
5.5 Instructions on Connecting Wired Controller and Indoor Units Network
- Communication wire of indoor unit and outdoor unit (or indoor unit) is connected to D1, D2.
- Wired controller is connected to H1, H2.
- One indoor unit can connect two wired controllers that must be set as master one and slave one.
- One wired controller can control 16 indoor units in maximum at the same time (as shown in Fig.5.5).
NOTES!
- The type of indoor units must be the same if they are controlled by the same wired controller.
- When the indoor unit is controlled by two wired controllers, the addresses of the two wired controllers should be different through address setting. Address 1 is for main controller; Address 2 is for slave controller. Detailed setting please refer to the instruction manual of wired controller.
Routine Maintenance
WARNING:
- Do turn off the unit and cut off the main power supply when cleaning the air conditioner to avoid electric shock or injury.
- Stand at solid table when cleaning the unit.
- Do not clean the unit with hot water whose temperature is higher than 45 ℃ to prevent fade or deformation.
- Do not dry the filters by fire, or it may catch fire or become deformed.
- Clean the filter with a wet cloth dipped in neutral detergent.
- Please contact after-sales service staff if there is abnormal situation.
- Non-professional person is not allowed to open the air-in grille of indoor unit.
6.1 Cleaning of Filter
- Remove the filters from inlet of IDU. Use a vacuum cleaner to remove dust. If the filters are dirty, wash them with warm water and mild detergent, and dry the filters in the shade.
- If the unit used in the environment with much dust, please clean it regularly (usually once every two weeks).
6.2 Maintenance before the Seasonal Use
- Check if the air inlet and air outlet of indoor and outdoor unit are blocked.
- Check if securely grounded.
- Check if all the power cord and communication cable are securely connected.
- Check if any error code displayed after energized.
6.3 Maintenance after the Seasonal Use
- Set the unit in fan mode for half a day in a sunny day to dry the inner part of unit;
- When the unit won’t be used for a long time, please cut off power supply for energy saving; the characters on the wired controller screen will disappear after cutting off the power supply.
Table of Error Codes for Indoor Unit
Error Code | Content | Error Code | Content | Error Code | Content |
---|---|---|---|---|---|
L0 | Indoor Unit Error | LA | Indoor Units Incompatibility Error | d9 | Jumper Cap |
Error
L1| Indoor Fan Protection| LH| Low Air Quality Warning| dA| Indoor Unit
Network Address Error
L2| E-heater Protection| LC| ODU-IDU Incompatibility
Error
| dH| Wired Controller PCB Error
L3| Water Full Protection| d1| Indoor Unit PCB Error| dC| Capacity DIP Switch
Setting Error.
L4| Wired Controller Power Supply Error| d3| Ambient Temperature Sensor Error|
dL| Outlet Air Temperature Sensor Error
L5| Freeze protection| d4| Inlet Pipe Temperature
Sensor Error
| dE| Indoor Unit CO2 Sensor Error
L7| No Master Indoor Unit Error| d6| Outlet Pipe Temperature Sensor Error| dy|
Water Temperature Sensor Error
L8| Power Insufficiency Protection| d7| Humidity Sensor Error| C0|
Communication Error
L9| Quantity Of Group Control Indoor Units Setting Error| d8| Water
Temperature Error| AJ| Filter Cleaning Reminder
o1| Low Bus bar Voltage of Indoor Unit| o2| High Bus bar Voltage of Indoor
Unit| o3| IPM Module Protection of Indoor Unit
o4| Failure Startup of Indoor Unit| o5| Overcurrent Protection of Indoor Unit|
o6| Current Detection Circuit Malfunction of Indoor Unit
o7| Desynchronizing Protection of Indoor Unit| o8| Communication Malfunction
of Indoor Unit’s Drive| o9| Communication Malfunction of Main Mater of Indoor
Unit
oA
| High Temperature of Indoor Unit’s Module|
ob
| Malfunction of Temperature
Sensor of Indoor Unit’s Module
|
oC
| Charging Circuit Malfunction of Indoor Unit
db| Special Code: Field Debugging Code
Troubleshooting
The air conditioner is not expected to be serviced by users. Incorrect repair may cause electric shock or fire, so please contact an authorized service center for professional service. The following checks prior to contact may save your time and money.
Phenomenon | Troubleshooting |
---|
The unit can’t start.
| ① Power supply is not connected.
② Circuit breaker tripping caused by leakage of electricity.
③ Input voltage is too low.
④ Defect of main PC-board.
The unit stops after running for a while.
| ① The inlet or outlet of ODU or IDU are blocked by obstacle.
② Control loop is abnormal
③ Set the unit in cooling mode when outdoor ambient temperature is higher
than 43℃.
Poor cooling effect.
| ① The filter is dirty.
② Too heavy heat load of room (e.g. too many people).
③ Door or windows is open.
④ Inlet and outlet of IDU are blocked.
⑤ Setting temperature is too high.
⑥ Refrigerant is insufficient (e.g. refrigerant leakage).
Poor heating effect.
| ① The filter is dirty.
② Door or window is open.
③ Setting temperature is too low.
④ Refrigerant is insufficient (e.g. refrigerant leakage).
⑤ Outdoor ambient temperature is lower than -5℃.
⑥ Abnormality of control circuit.
Indoor fan doesn’t start up during heating.
| ① At starting, the IDU fan could not operate till the heat exchange become
hot, for preventing delivering the cool air.
② At defrosting, the IDU fan stopped due to system switch to cooling mode.
For preventing delivering the cool air, and resume operating after defrosting.
NOTE!
If air conditioner still fails to work normally after checking and handling as
described above, please stop using it immediately and contact local service
center for assistance.