audio-technica ATUC-50 Digital Wired Conference System Instructions
- June 17, 2024
- Audio-Technica
Table of Contents
- audio-technica ATUC-50 Digital Wired Conference System
- Product Usage Instructions
- Introduction
- About This Conference System
- Features of ATLKEXT165
- Set Menu Items
- Connecting devices
- Ethernet cable
- Connecting an amplifier
- ATUC-IR System
- IR System Connections and Configuration
- Troubleshooting
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
audio-technica ATUC-50 Digital Wired Conference System
Product Information
Specifications
- Main Unit: ATUC-50
- Conference System Type: Digital Wired Conference System
- Gooseneck Microphone with LED Ring: ATUC-M43H/58H/M32L
- Discussion Unit: ATUC-50DU
- Interpretation Unit: ATUC-50INT
- Control Unit: ATUC-50CU
- Integration Unit: ATUC-50IU
- Link Extender: ATLK-EXT165
- IR Transmitter Unit: ATUC-IRA
- IR Distributor: ATUC-IRD
- Charger: ATCS-B60
Product Usage Instructions
ATUC-50 System
Example of Wired System Connections
The ATUC-50 system requires the following connections:
- Connect the 50DU/INT to the 50CU using appropriate cables.
- Connect multiple 50DU/INTs together using the provided cables.
- Connect the microphone (ATUC-M) to the 50DU/INT.
- Connect an amplifier to the system.
- Turn on the 50CU and test the 50DU operations.
- Connect the system to a network.
- Connect a computer or mobile device to the network.
ATUC-IR System
Example of IR System Connections
The ATUC-IR system requires the following connections:
- Connect the IRA and IRCU using appropriate cables.
- Connect the microphone (ATUC-M) to the IRDU.
- Start the IRDU.
- Set the Device ID for the IRDU.
ATUC-50/IR Hybrid System
Example of Hybrid System Connections
The ATUC-50/IR hybrid system requires a combination of wired and IR system connections. Please refer to the manual for detailed instructions on how to set up the hybrid system.
Specifications
The specifications for the ATUC-50 system are as follows:
- Main Unit: ATUC-50
- Conference System Type: Digital Wired Conference System
- Gooseneck Microphone with LED Ring: ATUC-M43H/58H/M32L
- Discussion Unit: ATUC-50DU
- Interpretation Unit: ATUC-50INT
- Control Unit: ATUC-50CU
- Integration Unit: ATUC-50IU
- Link Extender: ATLK-EXT165
- IR Transmitter Unit: ATUC-IRA
- IR Distributor: ATUC-IRD
- Charger: ATCS-B60
Instruction manual – Main Unit Edition –
ATUC-50
Digital Wired Conference System
Gooseneck Microphone with LED Ring ATUC-M43H/58H/M32L Discussion Unit ATUC-
50DU Interpretation Unit ATUC-50INT Control Unit ATUC-50CU Integration Unit
ATUC-50IU Link Extender ATLK-EXT165
ATUC-IR
Hybrid Infrared Conference System
Gooseneck Microphone with LED Ring ATUC-M43H/58H/M32L IR Discussion Unit ATUC-
IRDU Hybrid Control Unit ATUC-IRCU
Hybrid Control Unit (Dante-Enabled) ATUC-IRCUDAN
IR Transmitter Unit ATUC-IRA
IR Distributor ATUC-IRD Charger ATCS-B60
e
Table of Contents
Introduction …………………………………… 4
About this manual………………………………………….. 4 About the information in this manual
………………………………. 4 About the configuration of this manual…………………………….. 4 About
registered trademarks and copyrights …………………….. 4 Included accessories for the
ATUC50CU ………….. 4 Included accessories for the ATUC50IU …………… 4 Included
accessories for the ATLKEXT165 ……….. 4 Included accessories for the
ATUCIRCU/IRCUDAN………………………………………. 4 Included accessories for the ATUCIRDU……………
5 Included accessories for the ATUCIRA …………….. 5 Included accessories for the
ATCSB60 …………….. 5 System placement ………………………………………….. 5 Installing the CU(s)
in a rack…………………………………………… 5 Unbalanced connection …………………………………………………… 5 AC
power cord connection………………………………………………. 5 When cleaning the
units………………………………………………….. 5
About This Conference System…………… 6
Features ………………………………………………………… 6 Features of ATUC-50/ATUC-IR system
…………………………… 6 About Audio-Technica LINK …………………………………………… 6 Features of ATUC-
50CU …………………………………………………. 6 Features of ATUC-50DU/INT ………………………………………… 6
Features of the ATUC-IRCU/IRCUDAN …………………………. 6 Features of ATUC-
IRDU…………………………………………………. 7 Features of ATUC-IRA ……………………………………………………. 7
Features of ATUC-50IU ………………………………………………….. 7 Features of ATLK-
EXT165………………………………………………. 7 Features of ATUC-M43H/58H/32L ………………………………… 7
Optional products (sold separately by Audio Technica) …….. 7
ATUC-50 System ………………………………. 8
Example of wired system connections……………… 8
Part Names and Functions ………………… 9
ATUC50CU…………………………………………………….. 9 Front panel …………………………………………………………………….. 9
Rear panel…………………………………………………………………….. 11 ATUC50DU ………………………………………………….. 12
ATUC50INT………………………………………………….. 13 Common to ATUC50DU/INT ………………………….. 14 ATUCM
……………………………………………………….. 14 ATUC50IU ……………………………………………………. 15
ATLKEXT165………………………………………………… 21 Changing settings from ATUC50CU ………………. 22
Entering letters …………………………………………….23 Overview of the Interpretation Unit
(ATUC50INT) ……………………………………………….. 24
Wired System Connections and Configuration ……………………………….. 26
Connecting devices ………………………………………. 26 1 Connecting 50DU/INT to
50CU………………………………. 26 2 Connecting the 50DU/INTs together………………………… 27 3
Connecting the microphone ATUC-M to the
50DU/INT ……………………………………………………………… 37 4 Connecting an amplifier
…………………………………………… 37 5 Turning on the 50CU and testing 50DU operations ……. 37
6 Connecting to a network ………………………………………….. 38 7 Connecting a computer or
mobile device to a
network …………………………………………………………………… 38
ATUC-IR System……………………………… 40
Example of IR system connections …………………. 40
Part Names and Functions (ATUC-IR System) …………………………… 41
ATUCIRCU/ATUCIRCUDAN …………………………… 41 Front panel …………………………………………………………………… 41
Rear panel…………………………………………………………………….. 43 ATUCIRDU …………………………………………………… 44
Range of light reception ………………………………………………… 46 ATUCM ………………………………………………………..
46 ATUCIRA ……………………………………………………… 47 ATUCIRD……………………………………………………… 48 ATCSB60
……………………………………………………… 49 Using the Charger …………………………………………………………. 50 Using
Dante …………………………………………………. 51 Connecting IRCUDAN in a Network ……………………………… 51
Changing settings on the ATUCIRCU/ATUCIRCUDAN …………………………… 54 Entering letters
…………………………………………. 55
2
e
IR System Connections and Configuration ……………………………….. 56
Connecting devices ………………………………………. 56 1 Connecting IRA and
IRCU……………………………………….. 56 2 Connecting the microphone ATUC-M to the IRDU …… 56
3 Starting the IRDU ……………………………………………………. 57 4 Setting Device ID for IRDU
……………………………………… 57
ATUC-50/IR Hybrid System ………………. 59
Example of hybrid system connections ………….. 59
Hybrid System Connections and Configuration ……………………………….. 60
About Wired System and IR System Connections and Configuration …………………….. 60
Information…………………………………… 63
Troubleshooting …………………………………………… 63 ATUC-50CU/ATUC-IRCU/ATUC-IRCUDAN ………………
63 ATUC-IRCUDAN…………………………………………………………. 64 ATUC-50DU/INT…………………………………………………………
64 ATUC-50IU …………………………………………………………………. 65 ATLK-EXT165
……………………………………………………………… 65 ATUC-IRDU ………………………………………………………………… 65 ATUC-IRA
…………………………………………………………………… 66 Error messages …………………………………………….. 67
Specifications ……………………………….. 71
ATUC50CU specifications……………………………… 71 General specifications
…………………………………………………… 71 Input/output specifications …………………………………………… 72
ATUC50DU/INT specifications ………………………. 73 General specifications
…………………………………………………… 73 Input/output specifications …………………………………………… 74
ATUC50IU specifications ………………………………. 75 General specifications
…………………………………………………… 75 Input/output specifications …………………………………………… 76
ATLKEXT165 specifications…………………………… 77 General specifications
…………………………………………………… 77 ATUCM43H/58H specifications ……………………… 78 ATUCM32L
specifications …………………………….. 79 ATUCIRCU/ATUCIRCUDAN specifications ……… 80
General specifications …………………………………………………… 80 Input/output specifications
…………………………………………… 81 ATUCIRDU specifications ……………………………… 82 General
specifications …………………………………………………… 82 Input/output specifications
…………………………………………… 82 ATUCIRA specifications ………………………………… 83 Input/output
specifications …………………………………………… 83 ATUCIRD specifications………………………………… 83
ATCSB60 specifications………………………………… 83
3
e
Introduction
About this manual About the information in this manual
The images and screenshots shown in this manual may differ from the actual
product.
About the configuration of this manual
In this manual, the “Main Unit Edition”, there is information about the
digital wired conference system ATUC-50 and the hybrid infrared system ATUC-IR
products. For how to use Web Remote, see the ” Web Remote Edition”. For how to
install ATUC-IRs, see the “ATUC-IR Installation Edition”.
Device names The device names are abbreviated as follows. · 50CU: “Control
Unit” ATUC-50CU · 50DU: “Discussion Unit” ATUC-50DU · 50INT: “Interpretation
Unit” ATUC-50INT · ATUC-M: “Gooseneck Microphone with LED Ring” ATUC-
M43H/ATUC-M58H/ATUC-M32L · 50IU: “Integration Unit” ATUC-50IU · EXT: “Link
Extender” ATLK-EXT165 · IRCU: “Hybrid Control Unit” ATUC-IRCU · IRCUDAN:
“Hybrid Control Unit (Dante-Enabled)” ATUC-
IRCUDAN · IRDU: “IR Discussion Unit” ATUC-IRDU · IRA: “IR Transmitter Unit”
ATUC-IRA · IRD: “IR Distributor” ATUC-IRD · B60: “Charger” ATCS-B60
Some abbreviated names are used as follows. CU: W hen indicating the ATUC-
50CU, ATUC-IRCU, and ATUC-
IRCUDAN collectively DU: W hen indicating both the ATUC-50DU and the ATUC-IRDU
Symbols
Indicates the page(s) where you can find more detailed
or related information.
NOTICE Indicates a risk that may result in malfunction or damage to the device.
Indicates supplementary information as well as tips & advice for operations.
[ ]
Indicates menu items on the Web Remote screen.
Operations on mobile devices
Operations in this manual assume that you are using a computer as a control
device. Alternatively you can use a mobile device such as a tablet. Instead of
clicking or double-clicking, operate the application by tapping.
About registered trademarks and copyrights
· Apple, the Apple logo, iPad and Mac OS are trademarks of Apple Inc.,
registered in the U.S. and other countries. App Store is a service mark of
Apple Inc.
· Google Play and the Google Play logo are registered trademarks or trademarks
of Google Inc.
· Other product names, service names, logos and/or company names used in this
manual are trademarked and copyrighted properties of their respective owners
and/or licensors.
® In this manual, the TM and mark may not be specified.
Included accessories for the ATUC-50CU
· AC power cord · Euroblock connector (9 pieces)
Included accessories for the ATUC-50IU
· Euroblock connector (13 pieces (Green x 3, Black x 10))
Included accessories for the ATLKEXT165
· Euroblock connector · Power cable · Table mount kit (Table mount x 2, Screw
x 4)
Included accessories for the ATUC-IRCU/IRCUDAN
· AC power cord · Euroblock connector (9 pieces)
4
e
Included accessories for the ATUC-IRDU
· Rechargeable battery cover (2 pieces)
Included accessories for the ATUC-IRA
· Mounting bracket (1 piece) · Fastening screws for mounting bracket (2
pieces)
Included accessories for the ATCS-B60
AC power cord connection
Be sure to connect the AC power cord into a properly grounded wall outlet.
Improper grounding can cause electrical shock.
When cleaning the units
Do not use any solvents or chemicals such as benzine, thinner, alcohol or
electrical contact cleaner and protector. Doing so may cause deformation,
damage and malfunction of the units.
- AC adapter
System placement
Installing the CU(s) in a rack
Rack requirements for the CU · EIA standard compatible 19-inch rack · 1U-size rack mounting · Rack equipped with safety guardrails to support the CU and a
board on which the CU is to be placed
When installing the CU(s) in a rack, keep the temperature within the rack below 45°C (113°F). High temperature may damage the internal components, causing a malfunction. Leave a space of 10cm or more on each side (top, right and left, rear) between the CU and other devices or the rack.
Rack mounting angles are fixed to the CU using the following screws. When using screws other than those listed here, check the specifications. · S TIGHT tapping screws with nominal diameter 4×6mm* - Substitutable for M4×6mm machine screws
Unbalanced connection
Since induction noises tend to occur due to difference in electric potential
of chassis: · Keep the chassis between each device at the same electric
potential. · Use the same power system. · Connect to the GND (ground) terminal
or chassis ground of each
device.
5
e
About This Conference System
Features
Features of ATUC50/ATUCIR system
· Audio processing by the feedback processor and the like enables clear-
sounding conversations
· Up to 6 interpretation units (ATUC-50INT) can be connected. · The maximum
number of discussion units (ATUC-50DU),
integration units (ATUC-50IU), and interpretation units (ATUC50INT) that can
be connected on the IRCU is a total of 500 units (IRCU x 1 + 2 CU link units,
200 IRDU units, and 300 50DU units) and on the 50CU is a total of 300 units
(for 3 CU link units). · Either daisy-chain or ring connection can be made
with Cat5e or higher cables (shielded cables with conductor size of 24AWG or
higher in diameter are recommended). · 3 selectable conference modes: Free
Talk Mode, Request Talk Mode, and Full Remote Mode · 2-language
interpretation, 3-language interpretation, and 3-language relay interpretation
are supported (ATUC-50INT) · The recording function enables you to record
audio onto a USB device (mass storage device) · Controllable using Web Remote
and an external control device · Design with future expansion considered ·
Layout of hybrid infrared conference system can be easily changed and
operations are flexible.
About AudioTechnica LINK
The system uses Audio-Technica’s proprietary LINK format for power supply and
signal transmission between the control units and discussion units, etc.
Audio-Technica LINK is compatible with the Ethernet standards and allows a
simple installation using universal Cat5e or higher cable connections. (A
shielded cable with conductor size of 24AWG or higher in diameter is
recommended.) Transmission of high-speed signals with low-latency allows
stable control and uncompressed audio signal transmission.
Features of ATUC50CU
· Power supply and control is possible for a maximum of 100 discussion units
(ATUC-50DU) (depending on the cable lengths ATLK-EXT165 may be required)
· Up to 300 discussion units (ATUC-50DU) can be connected by cascade-
connection
· 4 configurable balanced matrix output plus 1 unbalanced output that outputs
the same audio as Output 1
· 2 Mic/Line inputs, 2 monaural AUX inputs, and 2 return inputs
- 2 return channels are available for both bilingual simultaneous interpretation and the language of the floor holder
· Conference mode: Free Talk, Request Talk, and Full Remote · Priority mode: First-press priority and later-press (FIFO, LIFO)
priority · Talk mode: Manual mode, Voice activation mode · Web Remote enables you to easily change settings and control
attendees’ right to talk during conference · Up to 4 channels (WAV: up to 4 channels, MP3: up to 2 channels)
can be recorded on a USB device (mass storage device) · Audio processing by the feedback suppressor and the like enables
the control unit to deliver high-quality sound · Design with future expansion and renewal considered
Features of ATUC50DU/INT
· An LED ring enables power supply via 3-pin balanced connector while offering both high sound quality and user flexibility
· Standard 3-pin microphones can be connected · A microphone pre-amplifier using discrete transistors reduces
noise; moreover individual gain is adjustable · A high-quality and high- resolution speaker · Designed for the high sound qualities of 24 bit/48 kHz · Equipped with multiple independent indicators (microphone ring
LED, (talk) button, multicolored LEDs on rear side of discussion unit (ATUC- 50DU)) · High-visibility indicators associated with the headphone volume adjustment buttons and monitor channel selection buttons · Optional removable bottom weight for improved stability · 2 RJ-45 terminals for connecting discussion units (ATUC-50DU); 1 expansion RJ-11 terminal for future expansions · 1 headphone output jack with a monitoring channel switch function
Features of the ATUCIRCU/IRCUDAN
· Updated model has expanded FPGA, and the basic functions are the same as the 50CU
· Supports operation on wired conference systems, infrared conference systems, and hybrid conference systems
· One system can control up to 300 discussion units (100 50DU units and 200 IRDU units, plus ATLK-EXT165 may be required depending on the number of connected units, cable lengths, and number of antennas)
· Up to 500 conference microphones can be connected in cascade connections (300 50DU units and 200 IRDU units)
· Dante equipped models are also available
6
e
Features of ATUCIRDU
· One IRDU unit is shared by two people to support 2-person conversation mode.
Equipped with two headphone outputs with independent volume adjustments
· Equipped with two multifunction buttons that can be flexibly changed as
appropriate to user’s applications
Features of ATUCIRA
· White IR cover and slender style provide subtle design that can be installed
in a variety of locations
· Using BNC terminal makes it possible to do multiplex transmissions by
connecting one cable
· Reliable design prevents installation mistakes with LEDs that indicate power
supply status
Features of ATUC50IU
· Discussion units that can be embedded in the ATUC-50 system · Configure the
system simply by connecting the microphones,
speakers, headphones, etc. · GPIO control terminal built in for monitoring
conditions and
controlling external devices · Equipped with 2 RJ-45 terminals for connecting
discussion units
(ATUC-50DU), etc. · Designed for the high sound qualities of 24 bit/48 kHz ·
Integration unit (ATUC-50IU) can be set from the Web Remote
for the chairperson/delegate names · Conference Mode and volume can be set for
each integration unit
(ATUC-50IU)
Features of ATUCM43H/58H/32L
· Equipped with an LED ring that enables power supply via 3-pin balanced
connector while offering both high sound quality and user flexibility
· Structural design reduces vibration between microphone connectors and
discussion units
· Adopted double layer pop filter · Improves RF measures against external
radio waves · Double gooseneck design makes installation flexible (ATUC-
M43H and ATUC-M58H) · Super directional design allows capture of distant
sounds (ATUC-
M32L)
Optional products (sold separately by Audio Technica)
Model number
Name
Use
ATUC-DUWT DISCUSSION UNIT Use this to improve the WEIGHT PLATE stability of discussion unit installation.
AT8643
RACK MOUNT KIT
Use this when rack mounting half-rack sized products, such as link extenders (ATLKEXT165).
Features of ATLKEXT165
· Connects to any Audio Technica device, such as a control unit (ATUC-50CU),
or discussion unit (ATUC-50DU), and is equipped with two RJ-45 terminals that
can expand the discussion system
· Remote mode that automatically starts from the control unit (ATUC-50CU)
· Has a standalone mode that can be started by operating the front panel
· Equipped with GPO terminal that notifies external devices when an
overcurrent (2.6 A) is detected in the power supplied from RJ-45 terminals
7
e
ATUC-50 System
Example of wired system connections
Windows/Mac
Web Remote Control
Tablet
Web Remote Control
50CU (extension)
50CU (extension)
USB device (mass storage device) to be used for recording/SFX
50CU (primary)
Microphone
CD player
AP
Router Switching hub
Amplifier
Speaker
Recorder
INT IU
EXT
50DU EXT
50DU
IU
IU
The number of connectable units differs depending on the system configuration that you are using. For more details, refer to page 28.
8
e
Part Names and Functions
ATUC-50CU Front panel
Power switch Turns the power of the 50CU on and off.
USB terminal The following operations are possible by connecting a USB device
(mass storage device) such as a USB flash drive or USB hard drive. · Recording
sound · Playing buzzer and chime · Importing/exporting preset data · Firmware
update
NOTICE · Supports FAT16 and FAT32 file systems · Maximum storage capacity: 2TB
· Maximum file size: 2GB · Does not support USB hubs. · Do not use extension
cables. · Do not attempt to use USB devices (mass storage devices) that have
been cracked, deformed or repaired using adhesive tape or the like. · Do not
save or create any files or folders unnecessary for this system on the USB
device (mass storage device); doing so may affect system operations. · The
50CU is not compatible with USB devices (mass storage device) with special
functions such as a security function.
USB access indicator Indicates the connection status of the USB device (mass
storage device). · In an access state: lit green
NOTICE · Do not remove the USB device (mass storage device) while the
indicator is lit green; doing so may destroy data.
REC (recording) indicator Indicates the recording status. · In a recording
state: lit green · In a recording-pause state: blinks green · While not
recording: remains off
NOTICE · If you remove the USB device (mass storage device) while in a
recording state or recording-pause state, the recorded file may not be written
correctly. Do not remove the USB device (mass storage device) during
recording.
DU POWER (DU power supply) indicator · In a normal state: lit green · In an
abnormal state (such as when a voltage drop occurs in the 48-V output system):
blinks green · In a 50DU/INT disconnected state: remains off
DU CHAIN indicator · In a normal state: lit green · In an abnormal state (such
as when 50DU communications fail): blinks green · In a 50DU/INT disconnected
state: remains off
CU LINK indicator · In a CU Link state: lit green · In an abnormal state (such
as when 50CU communications fail): blinks green · In a 50CU link cut-off
state: remains off
Remote (remote control) indicator · In a communication state: lit green · In
an abnormal state (such as when failing in external transmission retry):
blinks green · In a non-communication state: remains off
SIGNAL/PEAK indicator Indicates the audio signal level as follows: 60dBFS or
higher: lit green 20dBFS or higher: lit amber 2dBFS or higher: lit red
Adjust the audio signal level such that the indicator will not light red.
Display
BACK button Returns to the previous or upper screen/item. Press and hold this
button to return to the HOME screen from any screen.
9
e
Jog dial/ENTER button Rotate the jog dial to select the desired item and then
press the ENTER button to confirm. Rotating the jog dial also adjusts the
setting values.
· Locking the operation buttons (Key Lock function) Press the BACK button and
ENTER button simultaneously for over 2 seconds to activate the Key lock
function, and thus lock all front panel operations except for the Power
switch.
· Unlocking the operation buttons When the operation buttons are locked, press
the BACK button and ENTER button simultaneously for over 2 seconds to unlock
the operation buttons.
Display and jog dial operations:
HOME screen
1
2
3
4
The item with is the currently selected item. By rotating the jog dial, move to select the operation you want to perform and then press the ENTER button.
1 Master level adjustment (Lvl)
Master level -50 -40 -30 -20 -12 -6 0 6 12 Peak (dBu)
- Rotate the jog dial to adjust the CU output level (OUTPUT 1). · While pressing the ENTER button, rotate the jog dial to adjust
the level in 10-step increments. · Be sure that the Peak indicator does not light up while
adjusting the level.
2 Recording operations (Rec)
R (Remaining recording time)/E (Elapsed recording time) display -50 -40 -30 -20 -12 -6 0 6 12 Peak (dBu)
3 Conference preparation (Pst)
· [1] Recall Presets : Rotate the jog dial to move “>” to the item you want to
recall and then press the ENTER button to confirm.
· [2] Conf. Setup : Change or check the conference settings. Rotate the jog
dial to move “>” to the item you want to change or check and then press the
ENTER button to confirm. Pst Menu Items: Settings can also be configured via
Web Remote. The item names in parentheses ( ) are used for Web Remote. [1]
Recall Presets [2] Conf. Setup 01 Conference Mode (Conference Mode) 02 NOM
(Number of Open Mics) 03 Auto Mic Off (Auto Mic OFF) 04 Override Mode
(Override Mode) 05 Max Queue (Maximum in Queue) 06 MicON Trigger (Mic ON
Trigger / Mic ON Trigger for Priority) 07 MicON Hold Time (Mic ON Hold Time)
08 Interrupt Option (Interrupt Option)
· Items that can be configured from [2] Conf. Setup differ depending on the
conference mode.
· For details on items, see “Menu items” in the Web Remote Manual.
4 Configuring settings (Set) Rotate the jog dial to move “>” to the desired
item or value and then press the ENTER button to confirm.
For details on setting items, see “Set Menu Items” ( page 22).
- Rotate the jog dial to select Rec (Start recording)/ Pau (Pause)/Stp (Stop)/R or E (Recording time display) and then press the ENTER button to confirm.
· Select the time display on the top right side of the screen using the jog dial and then press the ENTER button to switch the display between R (Remaining recording time)/E (Elapsed recording time).
· To adjust the recording level, move to the recording level meter at the top left of the screen to display Rec Lvl and then press the ENTER button to enter recording level adjustment mode. Rotate the dial to adjust the recording level being sure that the Peak indicator does not light up.
· While pressing the ENTER button, rotate the jog dial to adjust the level in 10-step increments.
10
e
Rear panel
- The serial number label is located on the top panel.
NOTICE · Refer also to the instruction manuals supplied with the external
devices.
· Be careful NOT to connect the Ethernet cable from your network device to the
CU LINK terminal or DU CHAIN terminal. This can cause damage to the connected
device.
NETWORK terminal · RJ-45 · Use for connecting to a local area network when
controlling from an external device via the Web Remote Control or IP
remote function ( page 38)
CU LINK A/B terminals, DU CHAIN C/D terminals · RJ-45
· Use for cascading multiple 50CUs. ( page 36)
· You can also configure these terminals as 50DU/IU/INT
terminals. ( page 27)
DU CHAIN A/B terminals · RJ-45 · Use for connecting 50DU/IU/INT. You can
daisy-chain multiple 50DU/IU/INTs as well as connect multiple 50DU/ IU/INTs in
a ring using the A/B terminals.
· By cascade-connecting multiple 50CUs, up to 300 50DU/IU/INTs can be
connected. However, there is a
maximum of 6 INTs. ( page 36).
Analog output (balanced) terminals: OUTPUT 1-4 (BAL) · Euroblock · Pin
arrangement: “+” Hot/”” Cold/”G” GND
Analog output (unbalanced) terminals: OUTPUT1 (UNBAL) · Euroblock · Pin
arrangement: “SIG” Signal (2 systems)/”G” GND
Analog input (unbalanced) terminals: INPUT (AUX) · RCA
Analog input (balanced) terminals: INPUT (MIC/LINE 1-2) · Euroblock · Pin
arrangement: “+” Hot (supports phantom power)/ “” Cold (supports phantom
power)/”G” GND · The input type can be switched between MIC and LINE
Analog input (balanced) terminal: INPUT (INTERPRETATION RETURN 1-2) ·
Euroblock · Pin arrangement: “+” Hot/”” Cold/”G” GND · Inputs audio signals
from simultaneous interpretation system
Ground screw Since the supplied AC power cord has a three-pronged plug, as
long as your AC power wall outlet is grounded properly, the CU will also be
grounded properly.
AC Inlet (AC IN) Connect the supplied AC power cord.
NOTICE · Do not plug in the AC power cord until all other connections,
including 50CU extension and 50DU/IU/ INTs, have been completed.
· Be sure that the CU is securely grounded to a single ground point. Grounding
to multiple ground points can cause ground loops, resulting in noise
generation such as a humming noise.
11
e
ATUC-50DU
Display When changing monitor channel or adjusting the volume level, the
currently set value is displayed.
Microphone release lever Microphone jack
Connect a microphone. · A typical 3-pin XLR type microphone as well as the
ATUC-M
series microphone can be connected. </> Monitor channel selection buttons
When operating the </> monitor channel selection buttons, the currently
selected monitor channel is shown on the display .
FL: Monitors speech from the floor channel. 01-03: Monitors speech from groups
1 to 3. Speech interpreted by interpretation units is added to the speech from
groups 1 to 3 when INTs are connected on the same system. /+ Headphone volume
adjustment buttons When operating the /+ headphone adjustment buttons, the
current volume level (0 to 20) is shown on the display . Built-in speaker
Outputs conference audio. (talk) LED Displays DU talk status. · While talking:
lit red · When requested to talk (in standby mode): blinks green · W hen talk
request is rejected: blinks green (quickly blinks 4 times)
· The LED colors can be changed. See the Web Remote Edition.
(talk) button Press this button to send a request to talk. Press the button again to finish talking or cancel the request to talk. DUs designated as a priority DU can cut other DU speakers short and mute other DUs by pressing this button.
Operations when the (talk) button is pressed briefly:
Conference mode
Current state
Mic ON Trigger mode
Button
Voice
Talk OFF Talk ON
Free Talk
Requesting to talk
Cancel request
(Not acceptable)
Talk ON Talk OFF
Talk OFF Request to talk
Request Talk
Requesting to talk
Cancel request
Talk ON Talk OFF
Full Remote
–
– (External control only)
- On priority DUs, operations of the priority DUs are same as in Free Talk Mode regardless of the conference mode.
Operations when the (talk) button is pressed and held: Only for Priority DUs with [Can Cut/Mute] set to on
Mic ON Trigger mode
Current state
Button
Voice
Press the button for 2 seconds or less
Button/Voice
Cut mode Mute mode
Press and hold the button for over 2 seconds
Talk OFF Talk ON
Talk ON Talk OFF
(Not acceptable)
Talk ON(1)
Talk ON stays active(1)
Talk ON(2)
Talk ON stays active(2)
1 All specified DUs will be in Talk OFF state. 2 All specified DUs will be in mute state.
12
e
ATUC-50INT
VOL. A
B
Display · Character on the left: Displays the current monitor channel. F:
Monitors speech from the floor channel (speech from all meeting participants).
1: Monitors speech from language group 1. · Digit on the right: Displays the
language group (1 to 3) assigned to the INT output. When adjusting the volume
level, the set value is displayed.
Microphone release lever
Microphone jack Connect a microphone. A typical 3-pin XLR type microphone as
well as the ATUC-M series microphone can be connected.
Monitor channel selection button Switches the speech from the floor channel
and the speech from language group 1 each time it is pressed.
VOL. Headphone volume adjustment button When operating this button, the
current volume level (0 to 20) is shown on the display . The volume is
adjusted by operating the / buttons while in this state. Operating this button
while the volume level is displayed takes you back to the monitoring channel
display.
A / B Interpretation languages selection buttons (only available in bi-
directional interpretation) This function is only available when bi-
directional interpretation has been selected. (Outgoing language A/Outgoing
language B) Switches the location of the interpretation speech being output
according to the interpretation pattern.
(Talk) LED Displays INT talk status.
(Talk) button Press this button to talk. Press the button again to finish
talking.
13
e
Common to ATUC-50DU/INT
ATUC-M
Microphone Ring LED
Lights red when the microphone is activated. Blinks red while waiting to talk.
Connector
Headphone jack Speech from the selected monitor channel is output.
Rear LED The LED color can be set for each 50DU. This is useful when dividing
50DUs into groups by color. The LED color can be changed from Web Remote.
NOTICE · Color settings cannot be done for INTs. The settings stay at their
default.
Extension terminal
DU/CU connection terminals ( page 26)
Bottom cover Covering the terminals protects them from dust and also prevents
cables from becoming unplugged. Therefore, after connecting cables to each
terminal, be sure to attach the bottom cover.
Serial number
14
e
25 13.5
ATUC-50IU
5
100 116 100 86
5 12
38
24 50
173
100
117
5
Because the IU is intended to be embedded in a table, etc., when it is used, the user interfaces, such as displays, operating terminals, and input/ output terminals, can be customized according to their usage environment. Specifications for the interfaces are as follows.
Microphone input terminal
Pin number
Signal name
1
GND
2
COLD
3
HOT
4
RING LED
Explanation
Microphone input GND Microphone input balance Supplies a phantom power supply
of +48 V (possible to toggle on/off ) For controlling ATUC-M LED
Terminal color
Green
Speaker output terminal
Pin number
Signal name
Explanation
Terminal color
5
HOT
6
COLD
Speaker output 1.4 W, 8 (impedance over 4 )
Green
- We recommend using a shielded wire for the speaker output terminal. The GND shield in this case is connected to the GND pin (9).
Headphone output terminal
Pin number
Signal name
7
L ch
8
R ch
9
GND
Headphone output 15 mW 32
Headphone output GND
Explanation
Terminal color
Green
15
e
Status output terminal
Pin number
Signal name
10
TALK LED : OPEN/CLOSE
11
TALK LED : LOW/HI
12
FLOOR LED
13
LANGUAGE1 LED
14
LANGUAGE2 LED
15
LANGUAGE3 LED
Operation input terminal
Pin number
Signal name
16
CHANNEL
17
VOL. UP
18
VOL. DOWN
19
TALK ON
20
CUT/MUTE
21
TALK ON (INVERT)
Power supply output terminal
Pin number
Signal name
22
5 V
23
GND
General purpose input terminals (GPI)
Pin number
Signal name
24
GPI0
25
GPI1
26
GPI2
27
GPI3
28
GPI4
29
GPI5
30
GPI6
31
GPI7
Explanation
Talk ON: Close Talk OFF: Open Requesting to talk (waiting): blinks Talk
request is rejected: blinks quickly
Terminal for AT8657/LED and U891RCx Talk ON: +5 V Talk OFF: 0 V On/off
operations are synchronized with the open/close operations for the TALK LED
pin (10)
Selecting the floor channel on the monitor channel When selected: Close When
unselected: Open
Selecting group 1 on the monitor channel When selected: Close When unselected:
Open
Selecting group 2 on the monitor channel When selected: Close When unselected:
Open
Selecting group 3 on the monitor channel When selected: Close When unselected:
Open
Terminal color
Black
Explanation
Selecting the monitor’s channel
Adjusting the headphones’ volume
Request to talk Yes: Close No: Open Request to mute/cut microphone Yes: Close
No: Open AT8657/LED dedicated terminal Request to talk Yes: +5 V No: 0 V The
function of this pin is the same as that of the TALK ON pin (19) *W hen there
is a TALK ON or TALK ON (INVERT) request to talk, the system handles them both
as requests to talk.
Terminal color
Black
Explanation
Power supply for LED is 5 V Power supply GND
Terminal color
Black
Explanation
General purpose input terminal 0 General purpose input terminal 1 General
purpose input terminal 2 General purpose input terminal 3 General purpose
input terminal 4 General purpose input terminal 5 General purpose input
terminal 6 General purpose input terminal 7
Terminal color
Black
16
e
General purpose output terminals (GPO)
Pin number
Signal name
32
GPO0
33
GPO1
34
GPO2
35
GPO3
36
GPO4
37
GPO5
38
GPO6
39
GPO7
Explanation
General purpose output terminal 0 General purpose output terminal 1 General
purpose output terminal 2 General purpose output terminal 3 General purpose
output terminal 4 General purpose output terminal 5 General purpose output
terminal 6 General purpose output terminal 7
Terminal color
Black
- You can assign functions to the general purpose input/output terminals (GPI and GPO) on the web remote’s settings screen.
Audio Technica LINK terminal Connect the Audio Technica products and configure
the system.
NOTICE · Power is supplied to external devices from the 5 V pin (22); however
this pin has a maximum rating of +5 VDC at 100 mA. When you use this, select a
circuit or current limit (resistance value) so that the rating is not
exceeded.
· If this is used beyond its ratings, it may cause the product to malfunction,
but even more so, it may cause fires or unforeseen accidents.
17
e
Example of a user interface connection
123 456 789
10 11 12 13 14 15 16 17 18 19 20 21
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
TALK LED OPEN/CLOSE
FLOOR LED
LANGUAGE 1 LANGUAGE 2 LANGUAGE 3
LED
LED
LED
CHANNEL VOL. UP VOL. DOWN TALK ON CUT/MUTE
22 10
22 12
22 13
22 14
22 15
16 23
17 23
18 23
19 23
20 23
GPI 0
GPI 7
GPO 0
GPO 7
24 23
31 23
22 32
22 39
Inputpin IN (23pin GND)
Output pin (22pin 5V) IN
Max. 7 7mmAA
When using with the ATUC-M
XLXRLR ReRceecpetpatacclele
1 FG 2 3
ATUC-50IU
1 GND 2 COLD 3 HOT 4 RING LED
18
e
When using with the AT8657/LED
1
5
23 4
ATUC-50IU
1 GND 2 COLD 3 HOT
11 TALK LED: LOW/HI 21 TALK ON (INVERT)
When using with the U891RCx
BK: GND WH: LED CONTROL BL: CONTACT CLOSURE
RD: COLD YL: HOT SH: GND
- Do the following settings for the U891RCx. SW.FUNCTION: MOM. ON CONTROL: LED Remote
Mounting an IU · When securing in two directions Align the IU with the edge of a table, etc., and then fasten it with screws.
ATUC-50IU 1 GND 2 COLD 3 HOT
11 TALK LED: LOW/HI 19 TALK ON 23 GND
19
e
- When securing on only one side Leave about 2 mm of the screws out when you fasten them to the table, and then hang the IU on them. Slide the IU downward, and then tighten the screws to secure the IU.
Suspend screws about 2 mm
Tighten screws securely · You can also mount the IU inverted or sideways. W hen mounting, fasten at a minimum of two places with screws.
20
e
ATLK-EXT165
Mode switch
Remote mode
This mode allows the CU to automatically start the unit.
Standalone mode
This mode allows you to operate the EXT by itself.
We recommend using the remote mode if you are using the EXT. Use the following
procedure to turn the EXT’s mode switch on and off manually in standalone
mode. If you change the order of operations, the 50DU that is connected may
not be recognized correctly. · To turn on the power
Turn on 50CU power Turn on mode switch of EXT · To turn off the power
Turn off mode switch of EXT Turn off CU power
Power indicator
Audio Technica LINK Device indicator Indicates the connection status of devices that support Audio Technica LINK. · Connected: Lit · Unconnected: Unlit
Data indicator · Establishing link (data not transmitted): Lit · Transmitting data: Blinking · No link: Unlit
Cooling fan
Audio Technica LINK POWER STATUS output terminal Open: Power inactive
Close: Power active
Audio-Technica LINK A/B terminals · RJ-45
· Use to connect the devices that support Audio-Technica LINK.
AC inlet (AC IN) Connect the supplied AC power cord.
21
e
Changing settings from ATUC-50CU
You can change 50CU settings by selecting “Set” on the HOME screen of the display. Changeable items are as follows. For more detailed settings and individual settings for each 50DU/ IU/INT, use Web Remote.
- After changing the network setting item(s), restart the 50CU to enable the setting values.
Set Menu Items
[1] System Setting 01 Device Name 02 Link Port Set
03 CU Link Mode
04 CU Error Notice 05 IP Setting
01 IP Config Mode 02 IP Address 03 Subnet Mask 04 Gateway Address 06 Allow
Discovery 07 IP Ctrl Setting 01 IP Ctrl Port No 02 IP Ctrl Ntfy 03 Audio Level
Ntfy 04 M-cast Adrs 05 M-cast Port No 08 Auto Mode Change 01 Auto Mode Change
02 Hold Time(Err) 09 NTP Setting 01 NTP 02 NTP Adrs 03 NTP Port 04 Time Zone
05 DST 06 DST Start Date 07 DST Start Time 08 DST End Date 09 DST End Time 10
Login Password 01 Admin.Pwd.Login 02 Admin.Password 03 Opr.Pwd.Login 04
Opr.Password 11 Reset All Dflt.
[2] System Info 01 Name 02 Serial Number 03 FW Version 04 IP Config Mode 05 IP
Address 06 Subnet Mask 07 Gateway Address 08 Mac Address 09 Allow Discovery 10
IP Ctrl Port No 11 IP Ctrl Ntfy 12 Audio Level Ntfy 13 M-cast Adrs 14 M-cast
Port No 15 NTP 16 NTP Adrs 17 NTP Port 18 Time Zone 19 CU Link Status
ATUC-50CU CU A/B, DU C/D Primary, Extension Pass Thru, Extension Last Unit On,
Off
Auto, Static 0.0.0.0 – 255.255.255.255 0.0.0.0 – 255.255.255.255 0.0.0.0 –
255.255.255.255 On, Off
00001 – 65535 On, Off On, Off 0.0.0.0 – 255.255.255.255 00001 – 65535
On, Off 20, 30, 40 seconds
On, Off 0.0.0.0 – 255.255.255.255 00001 – 65535 UTC 12:00 to +14:00 On, Off
1/1 – 12/31 0:00 – 23:00 1/1 – 12/31 0:00 – 23:00
On, Off Displays password On, Off Displays password
Displays current settings
20 CU Link Mode 21 No.ofExtensionCU 22 Total No.of DU 23 Total No.of IU 24
Total No.of INT [3] Audio Setting 01 MIC/LINE Input 1
01 Input Type 02 Input Gain 03 Level 04 Phantom Power 05 Mix to Floor 02
MIC/LINE Input 2 01 Input Type 02 Input Gain 03 Level 04 Phantom Power 05 Mix
to Floor 03 AUX Input 01 Level 02 Mix to Floor 04 DU SP Output Lvl 05 DU Floor
Lock 06 VoiceDetectSens 07 Auto to Mic2 In [4] Recorder Setting 01 Rec Format
02 RecordingQuality 03 No.of Rec CH
04 Rec Source CH1
05 Rec Source CH2
06 Rec Source CH3
07 Rec Source CH4
08 Auto Track 09 Filename Prefix [5] Conference 01 Conference Mode 02 NOM 03
Auto Mic Off
04 Override Mode
05 Max Queue 06 MicON Trigger 07 MicON Hold Time 08 Interrupt Option [6]
Logging 01 Logging
22
e
Mic, Line +4dBu, Line 0dBV 60dB to 16dB , 120 to +10dB On, Off On, Off
Mic, Line +4dBu, Line 0dBV 60dB to 16dB , 120 to +10dB On, Off On, Off
, 120 to +10dB On, Off 0 – 20 On, Off 5, 4, 3, 2, 1, 0, 1, 2, 3, 4, 5
On, Off
WAV, MP3 64, 128, 192, 256, 320kbps 1 to 4 (WAV), 1 to 2 (MP3) Floor, Group 0,
Group 1, Group 2, Group 3, Language 1, Language 2, Language 3, Remote Lang. 1,
Remote Lang. 2, Mic/Line 1, Mic/Line 2, Mic/ Line 1&2 Mix Floor, Group 0,
Group 1, Group 2, Group 3, Language 1, Language 2, Language 3, Remote Lang. 1,
Remote Lang. 2, Mic/Line 1, Mic/Line 2, Mic/ Line 1&2 Mix Floor, Group 0,
Group 1, Group 2, Group 3, Language 1, Language 2, Language 3, Remote Lang. 1,
Remote Lang. 2, Mic/Line 1, Mic/Line 2, Mic/ Line 1&2 Mix Floor, Group 0,
Group 1, Group 2, Group 3, Language 1, Language 2, Language 3, Remote Lang. 1,
Remote Lang. 2, Mic/Line 1, Mic/Line 2, Mic/ Line 1&2 Mix Off, 15, 30 min, 1,
2 hour Displays filename prefix
Free Talk, Request Talk, Full Remote 1 to 10 5 to 60sec ,Off No Override,
FIFO, LIFO (depending on Conference Mode) 0-150 All Button, All Voice,
Individual 1.0 to 10.0 seconds Cut, Mute
On, Off
02 Destination
[7] Presets 01 Recall Presets 02 Save Presets 03 Import Presets 04 Export
Presets 05 Boot Up Preset
Internal, USB
Recalls presets Saves presets Imports presets Exports presets Calls presets at
boot up
Entering letters
For example, when entering letters from [4] Recorder Setting 09 Filename
Prefix , follow the procedure below.
1 Rotate the jog dial to select a letter.
You can use the following characters. (1) Password A to Z, a to z, 1 to 9, 0
(2) Device Name A to Z, a to z, 1 to 9, 0, ! # $ ( ) * + , – . : ; < = > ? @
, (space) (3) Filename Prefix A to Z, a to z, 1 to 9, 0, ! # $ ( ) + , – . ; = ? @
, (space)
2 Press the ENTER button to enter the selected
letter.
The cursor moves to the right.
3 Repeat steps 1 and 2 to enter desired text.
To delete characters you have just entered, follow the procedure below. · To
move the cursor to the character you want to edit:
(1) While pressing and holding the BACK button, rotate the jog dial to move
the cursor.
(2) Release the BACK button. · To delete characters you have just entered:
(1) Move the cursor to the character you want to delete. (2) While pressing
and holding the BACK button, press the
ENTER button. The character at the current cursor position will be deleted.
· When the cursor flashes in “” state at the end of the text, the character
just before the cursor will be deleted.
· To change characters you have just entered: (1) Move the cursor to the
character you want to edit. (2) Rotate the jog dial to select the desired
character.
· To finish editing: (1) When the cursor is in “” blinking state, press the
ENTER button. When editing ends, the cursor will move to the end of the text
and “” will blink.
4 To enter the text, when the cursor is in the “_”
blinking state, press the ENTER button.
Displays Completed! followed by the file name.
23
e
Overview of the Interpretation Unit (ATUC-50INT)
- Up to 6 interpretation units can be connected. · The maximum number of 50DU/IU/INT connections is 300
(when three CUs are linked). · INTs can only be connected to the primary 50CU. They cannot be
connected to extension 50CUs.
Digital Conference System ATUC-50 with the additional Interpretation Unit ATUC-50INT enables the following three types, (1) to (3), of interpretation. This section explains a brief overview of operations assuming that you have set the interpretation languages as in the following table.
Audio Group 1
English
Language Name
Audio Group 2
Japanese
Audio Group 3
French
(1) Interpretation using two languages (2 Languages)
· While in the 2 Languages interpretation mode, you can select from three
interpretation patterns (see table below).
· For instance, when the interpretation pattern “English Japanese” is set, “F”
appears as the character on the left in the display , and “2” appears as the
digit on the right. At this time, the speech from the floor channel is heard
through the monitor channel. Additionally, interpreted speech that is input
from the microphone of the INT is output to Audio Group 2 (the Japanese
group).
· When the bi-directional interpretation pattern is selected, the
interpretation system is established with just this INT1. Pressing the
interpretation languages selection button switches the interpretation patterns
between “Japanese English (Outgoing language A)” and “English Japanese
(Outgoing language B)”, simultaneously switch the interpreted speech being
output. Whichever interpretation pattern you selected, “Japanese English
(Outgoing language A)” or “English Japanese (Outgoing language B)”, it is not
saved. W hen the system is started, the interpretation pattern is “Japanese
English (Outgoing language A)”.
“Hello”
Monitored
speech
B
Interp”reted speech”
Audio Group 1 English
Audio Group 2 Japanese
“TInhtaernpkreyteodus”peech
A
Monitore”dspeech ”
Interpretation Interpattern preter
Monitored speech
Character on the left
Output destination group
Digit on the right
English Japanese
A + B
Outgoing language A
English
1
Outgoing language B
Japanese
2
Floor*
F*
English Japanese
B
Japanese
2
Japanese English
A
English
1
- Interpreters can do a switch operation to monitor the audio of language group 1 (key language)
24
e
(2) Interpretation using three languages (3 Languages)
· While in the 3 Languages interpretation mode, you can select from nine
interpretation patterns (see table below).
· Although there are three ways to do combinations within 2 Languages, the
basic operations are the same as those for 2 Languages interpretation.
Audio Group 1 English
“Hello” Monitored
speech
Interpreted speech
“Thank you”
B ” ”
Interpreted speech
A
Monitored
speech
” ”
Audio Group 2 Japanese
Instpeer”eprcehted” ” sMpoenietcohr”ed
M”Hosnepiletlooerc”ehd Intesrpperee”cYtheeds”
D C
E F
- Out of the three languages, the language of Audio Group 1 is used as the key language (in this case it is English), and relay interpretation is possible. (diagram below)
· When interpreting from French to Japanese, for example, Interpreter C first interprets “French English”. Interpreter B switches the monitor channel to the key language “1”, listens to the English interpretation from interpreter C, and then interprets “English Japanese”.
· Other than that, the basic operations are the same as those for 2 languages.
Audio Group 1
English (Key language)
Monitored speech “Hello”
“Thank you”
Interpreted speech
” ”
Interpreted
B
speech
Interpreted speech
” ”
Audio Group 2 Japanese
A
” ” Monitored
speech
sMpoenie”tcohOrueid” “MIensrtpceier”eprcehted
“HMeoslnlpoite”oercehd Intesrppereecteh”dYes”
“IBntoesnrpjpoereuecrth”ed Mosnpiet”oeOrcehudi”
Audio Group 3 French
Interpretation
pattern
Interpreter
Moni- Character tored on the speech left
Output destination group
Digit on the right
2
- Interpreters can do a switch operation to monitor the audio of language group 1 (key language)
“MInetersrcppi”er”eBetcoIenhdntjeosrpuperr”eetcehd Mosnpiteo”eOrcehudi”
D C
Interpretation between these
languages is unnecessary.
Audio Group 3 French
Interpreta- Intertion pattern preter
Monitored speech
Character on the left
Output destination group
Digit on the right
English Japanese
A + B
Floor/ English
F/1
(switched by interpreter)
Outgoing language A
English
1
Outgoing language B
Japanese
2
English French
C + D
Floor/ English
F/1
(switched by interpreter)
Wired System Connections and Configuration
Connecting devices
NOTICE · Do not plug in the supplied AC power cord until all other connections
have been completed.
· Insert the plugs all the way in. Loose connections may cause malfunctions or
noise.
· Check the plug orientations. · Refer also to the instruction manuals
supplied with the
external devices. · Although connecting the 50CUs, 50DUs, and INTs are
described here, because basic IU connections are the same as those for 50DUs,
refer to how to connect the DUs when connecting IUs. However, refer to the
table “Relationship of the LAN cable length, number of units
connected and number of EXTs required” ( page 29,
33) regarding the number of IUs to connect.
Entire system connection diagram (1) Refer also to the entire system
connection diagram (2) ( page
38)
When securing a 50DU/INT to a desk or table, use the screw holes (3 holes) on
the bottom side of the 50DU/INT (screw: M3, P=0.5, within 6 mm from the bottom
side to the tip of the screw).
95 30
45
87 (103.5)
3 2
1
1 Connecting 50DU/INT to 50CU
1 Place the 50CUs and 50DU/INTs.
NOTICE · Install the units on a flat surface. Dropping a unit may
1
cause damage to the unit and/or personal injury.
- When installing the 50CU in a rack, read the precautions
in advance ( page 5).
1
2 Connect the 50DU/INTs to the DU CHAIN A/B
terminals.
5
4
Speaker
Amplifier
NOTICE · Use straight cables. (Shielded cables with conductor size of 24AWG or
higher in diameter are recommended.)
· Using flat-type cables or unshielded cables may cause noise and affect other
devices.
· Be sure to establish a ground connection.
Ethernet cable
26
e
- Remove the 50DU/INT bottom cover to connect the Ethernet cables. To remove the bottom cover, pinch together the latches on both sides.
· On the 50DU/INT, the 50DU/50CU connection terminals are not differentiated, so you can connect to either the left or right terminal.
2 Connecting the 50DU/INTs together
To ATUC-50CU
Ring connection: Connect the 50DU/INTs to each of the DU CHAIN A/B terminals
and then connect together the last 50DU/INTs together to form a ring. Even if
a connection failure occurs somewhere in the ring, since the connection is
recognized as 2 daisy chains using the DU CHAIN A/B terminals, the influence
of the failure can be minimized and you can continue operating.
One more ring connection can be made by configuring these terminals as the DU
CHAIN C/D terminals.
Ethernet cable
Ethernet cable
1 Connect the 50DU/INTs according to the
installation environment and operation method.
Daisy-chain connection: Connect the 50DU/INTs in a series to the DU CHAIN A/B
(C/ D) terminals. Compared to a ring connection, a daisy-chain connection
enables the 50DU/INTs to be placed even farther from the 50CU.
Even if a connection failure occurs, since the connection is recognized as 2
daisy chains using the DU CHAIN A/B terminals, you can carry on conference
control.
· Combining different connection types is also possible, such as a ring
connection using the DU CHAIN A/B terminals and daisy-chain connections using
the DU CHAIN C/D terminals.
If a connection failure occurs here, all the connections to the last DU/INT are disabled.
Final 50DU/INT
Final 50DU/INT
Daisy-chain connection
Ring connection
2 Expand the system with EXT.
By adding EXT to the system, you can increase the number of 50DU/INT
connections and extend the distance of the total extension length of the
connecting cable (LAN cable).
For instance, you can connect a total of 100 50DUs/INTs, 50 units on either
terminal, by connecting an EXT near the B terminal when using a daisy-chain
connection on both the DU CHAIN A and B terminals.
27
e
Maximum number of connections for each terminal/each 50CU in Standalone mode
Maximum number of terminal connections in a DU CHAIN
Daisy Chain
A
B
C
D
Total
50
50
50
50
100*
Ring
50
50
100
- The maximum number of units that can be connected is up to 100 units to each terminal on the DU CHAIN by using the EXT.
- IUs consume more power than 50DUs, so the number of units shown in the table cannot be connected. If you connect that many, it may damage the 50CUs or the EXTs.
Refer to the table “Relationship of the LAN cable length, number of units connected and number of EXTs required” ( page 29, 33) regarding
the number of IUs that can be connected.
Maximum number of connections for each terminal/each CU when using 3 CU LINKs
ATUC-50CU Primary
ATUC-50CU Extension *max 2pcs
Maximum number of terminal connections
in a DU CHAIN
Maximum number of terminal connections in a DU CHAIN
System Total
50CU x 2
A
B
NOTICE · Up to 6 INTs can be connected to the primary 50CU.
28
e
Daisy-chain connection
ATUC-50CU
L1
L2
L2
ATUC-50DU
L2
L1
L3
L2
L2
ATLK-EXT165
NOTICE · For a 50CU-50DU-50DU-…50DU-EXT connection, the distance between the [50DU-EXT] is L1. · W hen it is EXT-50DU-…-50DU-50DU-, the distance for [EXT- 50DU] is L3.
Relationship of the LAN cable length, number of units connected and number of EXTs required: Daisy-chain connection
Length of cables
1-port daisy-chain connection (using DUs)
1-port daisy-chain connection (using IUs)
50CU50DU
L1
10 m
50DU50DU
L2
1.5 m
EXT-50DU L3 10 m
Number of 50DUs connected
1 to 45 units 46 to 50 units
Number of EXTs needed
0 units 1 unit
Number of IUs connected
1 to 30 units 31 to 45 units
Number of EXTs needed
0 units 1 unit
50 m
1.5 m
10 m
1 to 36 units 37 to 50 units
0 units 1 unit
1 to 24 units 25 to 39 units
0 units 1 unit
100 m
1.5 m
10 m
1 to 24 units 25 to 50 units
0 units 1 unit
1 to 16 units 17 to 33 units
0 units 1 unit
10 m
2.0 m
10 m
1 to 29 units 44 to 50 units
0 units 1 unit
1 to 27 units 28 to 43 units
0 units 1 unit
50 m
2.0 m
10 m
1 to 34 units 35 to 50 units
0 units 1 unit
1 to 23 units 24 to 37 units
0 units 1 unit
100 m
2.0 m
10 m
1 to 24 units 25 to 50 units
0 units 1 unit
1 to 16 units 17 to 33 units
0 units 1 unit
10 m
5.0 m
10 m
1 to 33 units 34 to 50 units
0 units 1 unit
1 to 25 units 26 to 39 units
0 units 1 unit
50 m
5.0 m
10 m
1 to 27 units 28 to 50 units
0 units 1 unit
1 to 20 units 21 to 34 units
0 units 1 unit
100 m
5.0 m
10 m
1 to 20 units 21 to 48 units
0 units 1 unit
1 to 14 units 15 to 30 units
0 units 1 unit
29
e
Length of cables
50CU50DU
L1
50DU50DU
L2
EXT-50DU L3
2-port daisy-chain connection (using 50DUs)
2-port daisy-chain connection (using IUs)
Number of 50DUs
connected
Maximum number of
units connected
Number of EXTs needed
Number of IUs connected
Maximum number of
units connected
Number of EXTs needed
1 to 25 × 2 units
(total 50 units)
0 units 1 to 16 × 2 units
(total 32 units)
0 units
26 to 50 × 2 units
(total 100 units)
2 units 17 to 39 × 2 units
(total 78 units)
2 units
1 to 23 × 2 units
(total 46 units)
0 units 1 to 15 × 2 units
(total 30 units)
0 units
24 to 50 × 2 units
(total 100 units)
2 units 16 to 37 × 2 units
(total 74 units)
2 units
1 to 20 × 2 units
(total 40 units)
0 units 1 to 13 × 2 units
(total 26 units)
0 units
21 to 50 × 2 units
(total 100 units)
2 units 14 to 35 × 2 units
(total 70 units)
2 units
1 to 25 × 2 units
(total 50 units)
0 units 1 to 16 × 2 units
(total 32 units)
0 units
26 to 50 × 2 units
(total 100 units)
2 units 17 to 37 × 2 units
(total 74 units)
2 units
1 to 23 × 2 units
(total 46 units)
0 units 1 to 15 × 2 units
(total 30 units)
0 units
24 to 50 × 2 units
(total 100 units)
2 units 16 to 36 × 2 units
(total 72 units)
2 units
1 to 20 × 2 units
(total 40 units)
0 units 1 to 12 × 2 units
(total 24 units)
0 units
21 to 50 × 2 units
(total 100 units)
2 units 13 to 34 × 2 units
(total 68 units)
2 units
1 to 24 × 2 units
(total 48 units)
0 units 1 to 16 × 2 units
(total 32 units)
0 units
25 to 50 × 2 units
(total 100 units)
2 units 17 to 35 × 2 units
(total 70 units)
2 units
1 to 22 × 2 units
(total 44 units)
0 units 1 to 14 × 2 units
(total 28 units)
0 units
23 to 50 × 2 units
(total 100 units)
2 units 15 to 33 × 2 units
(total 66 units)
2 units
1 to 19 × 2 units
(total 38 units)
0 units 1 to 12 × 2 units
(total 24 units)
0 units
20 to 48 × 2 units
(total 96 units)
2 units 13 to 31 × 2 units
(total 62 units)
2 units
30
e
Length of cables
50CU50DU
50DU50DU
EXT50DU
4-port daisy-chain connection (using 50DUs) 4-port daisy-chain connection (using IUs)
Number of 50DUs connected
Maximum number of
units connected
Number of EXTs needed
Number of IUs connected
Maximum number of
units connected
Number of EXTs needed
A/B: 1 to 15 × 2 units C/D: 1 to 10 × 2 units
(total 50 units)
A/B: 0 units C/D: 0 units
A/B: 1 to 10 × 2 units C/D: 1 to 6 × 2 units
(total 32 units)
A/B: 0 units C/D: 0 units
A/B: 16 to 30 × 2 units C/D: 11 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 11 to 30 × 2 units C/D: 7 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 1 to 15 × 2 units C/D: 1 to 10 × 2 units
(total 50 units)
A/B: 0 units C/D: 0 units
A/B: 1 to 9 × 2 units C/D: 1 to 6 × 2 units
(total 30 units)
A/B: 0 units C/D: 0 units
A/B: 16 to 30 × 2 units C/D: 11 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 10 to 30 × 2 units C/D: 7 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 1 to 14 × 2 units C/D: 1 to 10 × 2 units
(total 48 units)
A/B: 0 units C/D: 0 units
A/B: 1 to 8 × 2 units C/D: 1 to 6 × 2 units
(total 28 units)
A/B: 0 units C/D: 0 units
A/B: 15 to 30 × 2 units C/D: 11 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 9 to 30 × 2 units C/D: 7 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 1 to 15 × 2 units C/D: 1 to 10 × 2 units
(total 50 units)
A/B: 0 units C/D: 0 units
A/B: 1 to 10 × 2 units C/D: 1 to 6 × 2 units
(total 32 units)
A/B: 0 units C/D: 0 units
A/B: 16 to 30 × 2 units C/D: 11 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 11 to 30 × 2 units C/D: 7 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 1 to 15 × 2 units C/D: 1 to 10 × 2 units
(total 50 units)
A/B: 0 units C/D: 0 units
A/B: 1 to 9 × 2 units C/D: 1 to 6 × 2 units
(total 30 units)
A/B: 0 units C/D: 0 units
A/B: 16 to 30 × 2 units C/D: 11 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 10 to 30 × 2 units C/D: 7 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 1 to 14 × 2 units C/D: 1 to 10 × 2 units
(total 48 units)
A/B: 0 units C/D: 0 units
A/B: 1 to 8 × 2 units C/D: 1 to 6 × 2 units
(total 28 units)
A/B: 0 units C/D: 0 units
A/B: 15 to 30 × 2 units C/D: 11 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 9 to 30 × 2 units C/D: 7 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
31
e
Length of cables
50CU50DU
50DU50DU
EXT50DU
4-port daisy-chain connection (using 50DUs) 4-port daisy-chain connection (using IUs)
Number of 50DUs connected
Maximum number of
units connected
Number of EXTs needed
Number of IUs connected
Maximum number of
units connected
Number of EXTs needed
A/B: 1 to 15 × 2 units C/D: 1 to 10 × 2 units
(total 50 units)
A/B: 0 units C/D: 0 units
A/B: 1 to 10 × 2 units C/D: 1 to 6 × 2 units
(total 32 units)
A/B: 0 units C/D: 0 units
A/B: 16 to 30 × 2 units C/D: 11 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 11 to 29 × 2 units C/D: 7 to 20 × 2 units
(total 98 units)
A/B: 2 units C/D: 2 units
A/B: 1 to 15 × 2 units C/D: 1 to 10 × 2 units
(total 50 units)
A/B: 0 units C/D: 0 units
A/B: 1 to 9 × 2 units C/D: 1 to 6 × 2 units
(total 30 units)
A/B: 0 units C/D: 0 units
A/B: 16 to 30 × 2 units C/D: 11 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 10 to 29 × 2 units C/D: 7 to 20 × 2 units
(total 98 units)
A/B: 2 units C/D: 2 units
A/B: 1 to 14 × 2 units C/D: 1 to 10 × 2 units
(total 48 units)
A/B: 0 units C/D: 0 units
A/B: 1 to 8 × 2 units C/D: 1 to 6 × 2 units
(total 28 units)
A/B: 0 units C/D: 0 units
A/B: 15 to 30 × 2 units C/D: 11 to 20 × 2 units
(total 100 units)
A/B: 2 units C/D: 2 units
A/B: 9 to 28 × 2 units C/D: 7 to 20 × 2 units
(total 96 units)
A/B: 2 units C/D: 2 units
32
e
Ring connection
ATUC-50CU
L1
L1
L2
L2
ATUC-50DU
L1
L2
L2
L1
ATLK-EXT165
L3
L2
L2
L3
NOTICE · For a 50CU-50DU-50DU-…50DU-EXT connection, the distance between the [50DU-EXT] is L1. · W hen it is EXT-50DU-…-50DU-50DU-, the distance for [EXT- 50DU] is L3.
Relationship of the LAN cable length, number of units connected and number of EXTs required: Ring connection
Length of cables
1-ring connection (using 50DUs)
1-ring connection (using IUs)
50CU50DU
L1
10 m
50DU50DU
L2
1.5 m
EXT-50DU L3 10 m
Number of 50DUs connected
1 to 45 units 46 to 50 units
Number of EXTs needed
0 units 1 unit
Number of IUs connected
1 to 30 units 31 to 50 units
Number of EXTs needed
0 units 2 units
50 m
1.5 m
10 m
1 to 36 units 37 to 50 units
0 units 2 units
1 to 24 units 25 to 50 units
0 units 2 units
100 m
1.5 m
10 m
1 to 24 units 25 to 50 units
0 units 2 units
1 to 16 units 17 to 48 units
0 units 2 units
10 m
2.0 m
10 m
1 to 43 units 44 to 50 units
0 units 1 unit
1 to 29 units 30 to 50 units
0 units 2 units
50 m
2.0 m
10 m
1 to 34 units 35 to 50 units
0 units 2 units
1 to 23 units 24 to 50 units
0 units 2 units
100 m
2.0 m
10 m
1 to 24 units 25 to 50 units
0 units 2 units
1 to 16 units 17 to 48 units
0 units 2 units
10 m
5.0 m
10 m
1 to 33 units 34 to 50 units
0 units 2 units
1 to 25 units 26 to 50 units
0 units 2 units
50 m
5.0 m
10 m
1 to 27 units 28 to 50 units
0 units 2 units
1 to 20 units 21 to 50 units
0 units 2 units
100 m
5.0 m
10 m
1 to 20 units 21 to 50 units
0 units 2 units
1 to 14 units 15 to 45 units
0 units 2 units
33
e
Length of cables
50CU50DU
50DU50DU
EXT50DU
2-ring connection (using DUs)
Number of 50DUs connected
Maximum number of
units connected
Number of EXTs needed
1 to 25 × 2 units
(total 50 units)
0 units
26 to 50 × 2 units
(total 100 units)
4 units
1 to 23 × 2 units
(total 46 units)
0 units
24 to 50 × 2 units
(total 100 units)
4 units
1 to 20 × 2 units
(total 40 units)
0 units
21 to 50 × 2 units
(total 100 units)
4 units
1 to 25 × 2 units
(total 50 units)
0 units
26 to 50 × 2 units
(total 100 units)
4 units
1 to 23 × 2 units
(total 46 units)
0 units
24 to 50 × 2 units
(total 100 units)
4 units
1 to 20 × 2 units
(total 40 units)
0 units
21 to 50 × 2 units
(total 100 units)
4 units
1 to 24 × 2 units
(total 48 units)
0 units
25 to 50 × 2 units
(total 100 units)
4 units
1 to 22 × 2 units
(total 44 units)
0 units
23 to 50 × 2 units
(total 100 units)
4 units
1 to 19 × 2 units
(total 38 units)
0 units
20 to 50 × 2 units
(total 100 units)
4 units
2-ring connection (using IUs)
Number of IUs connected
Maximum number of
units connected
Number of EXTs needed
1 to 16 × 2 units
(total 32 units)
0 units
17 to 40 × 2 units
(total 80 units)
4 units
1 to 15 × 2 units
(total 30 units)
0 units
16 to 38 × 2 units
(total 76 units)
4 units
1 to 13 × 2 units
(total 26 units)
0 units
14 to 38 × 2 units
(total 76 units)
4 units
1 to 16 × 2 units
(total 32 units)
0 units
17 to 40 × 2 units
(total 80 units)
4 units
1 to 15 × 2 units
(total 30 units)
0 units
16 to 38 × 2 units
(total 76 units)
4 units
1 to 12 × 2 units
(total 24 units)
0 units
13 to 38 × 2 units
(total 76 units)
4 units
1 to 16 × 2 units
(total 32 units)
0 units
17 to 39 × 2 units
(total 78 units)
4 units
1 to 14 × 2 units
(total 28 units)
0 units
15 to 37 × 2 units
(total 74 units)
4 units
1 to 12 × 2 units.
(total 24 units)
0 units
13 to 35 × 2 units
(total 70 units)
4 units
The values in the tables above are calculated based on the following
assumptions. · The number of 50DUs that can be connected is based on the
assumption that the ATUC-M is used. · The number of IUs that can be connected
is based on the assumption that ATUC-M, TALK LED, FLOOR LED, 8- speaker units,
32-
impedance headphones, and GPO terminals with LED x 4 (7 mA each) are being
used. · Given that Cat5e or higher cables are used. (Shielded cables with
conductor size of 24AWG or higher in diameter are recommended.) · 1-port
daisy-chain connection/1 ring connection: Given that one of the DU CHAIN A/B
terminals is connected in a 50DU/IU daisy chain
or that the A-B terminal is connected in a ring. · 2-port daisy-chain
connection: Given that the same number of 50DUs/IUs are daisy-chained to the
DU CHAIN A/B terminals. · 4-port daisy-chain connection: Given that the same
number of 50DUs/IUs are daisy-chained to both the DU CHAIN A/B terminals and
the same number of DUs/IUs are daisy-chained to the DU CHAIN C/D terminals. ·
2-ring connections: Given that one ring connection is used for the DU CHAIN
A-B terminals and for the DU CHAIN C-D terminals.
34
e
NOTICE · When connecting 50DUs/IUs, never exceed the number of connectable
50DUs/IUs and the connectable length. It may damage the 50CU or the EXTs.
· Depending on the CU settings, you can also connect the DUs/IUs to the CU
LINK terminals by configuring them as DU CHAIN C/D terminals. However, if the
number of the DUs connected to the DU CHAIN A/B terminals has not reached the
maximum, be sure to connect them to the DU CHAIN A/B terminals.
· The above table and notes are the same for the INT and 50DU. However, a
maximum number of 6 INTs can be connected to one system.
· The combinations shown above are representative examples. For other
combinations, please inquire with our sales representative.
· The position in which to connect the EXTs should have the same number of
50DUs (A, B, and C in the following diagram) between EXT-EXT as there are
between 50CU-EXT connected to the 50CU 1 port. For example, do the connections
as follows for an L1 = 10 m, L2 = 1.5 m, and L3 = 10 m, with 50 units
connected to a 1 port daisy-chain connection.
A=17
ATUC-50CU L1
L2
L2
L1
ATUC-50DU
ATLK-EXT165
B=17
L3 L2
L2
L3
C=16
L3
L2
L2
35
e
CU Link connection: Up to 3 50CUs can be cascaded (cascade 50CUs using the CU
LINK A/B terminals as shown below). Set one of the 50CUs as the primary unit.
Since up to 100 50DU/INTs can be connected to each 50CU, if you use 3 CUs, up
to 300 50DU/INTs can be connected in total.
Follow the procedure below to cascade CUs. Connect the CU LINK A terminal on
the 1st extension 50CU to the CU LINK B terminal on the primary 50CU. When
cascading 2 extension 50CUs, connect the CU LINK A terminal on the 2nd
extension 50CU to the CU LINK B terminal on the 1st extension 50CU. Primary
50CU
Terminal A is not used.
- You can either daisy-chain ( page 27) or ring ( page
- 50DU/INTs to each 50CU.
NOTICE · When using only one 50CU without a CU Link connection, be sure to set [CU Link Settings] to [Primary]. If [CU Link Setting] is set to [Extension Pass Through] or [Extension Last Unit], we cannot assure operations.
· Up to 6 INTs can be connected to the primary 50CU. They cannot be connected to extension 50CUs.
3 Attach the bottom cover to the 50DU/INT.
After connecting the Ethernet cables to the 50DUs/INTs, attach the bottom cover to each 50DU/INT. · The Ethernet cable is fixed securely between the 50DU/INT
and the bottom cover. This helps reduce the weight of the 50DU/INT which bears on the Ethernet cables. · To lead the cable out to the rear side, use the through hole . To lead the cable out to the bottom side, use the through holes .
1st extension 50CU
up to 100 units
Bottom cover
2nd extension 50CU
up to 100 units (INTs cannot be connected)
4 Attach the optional bottom weight to the 50DU/
INTs.
· W hen using 50DU/INTs that are not secured to desktops or tabletops, it is
recommended to use the optional bottom weight (330g) for secure placement.
· To purchase the optional accessories, contact our sales team.
up to 100 units (INTs cannot be connected)
Primary/Extension (CU Link Mode ):
Primary 1st extension 50CU 2nd extension 50CU
50CU
2-CU LINK [Primary] [Extension Last Unit]
–
3-CU LINK [Primary] [Extension Pass Through] [Extension Last Unit]
36
e
3 Connecting the microphone ATUCM to the 50DU/INT
1 Connect the ATUCM to the microphone jack on
the 50DU/INT.
ATUC-M
ATUC-50DU/INT NOTICE · Insert the ATUC-M connector in until you hear a
clicking sound. · Do not attempt to lift up the 50DU/INT by grabbing
onto the ATUC-M. Be sure to hold the main body of the 50DU/INT when lifting it
up. · Slowly bend or extend the flexible part of the ATUC-M. Do not apply
excessive force to the ATUC-M when bending it. · W hen disconnecting the
ATUC-M from the 50DU/INT, securely hold the connector while pressing down the
microphone release lever and then remove the ATUC-M. · Before
connecting/disconnecting the ATUC-M, be sure to turn off the power. If you do
not turn off the power, malfunction may occur.
NOTICE · When connecting external devices to IN/OUT terminals, do so after
cutting the phantom power supply of the external devices. If you leave the
phantom power supply on, it may cause unexpected malfunctions.
· When connecting external devices, refer also to the instruction manuals
supplied with them.
5 Turning on the 50CU and testing 50DU operations
After checking that all the connections from steps 1 to 4 have been done
properly, follow the procedure below to turn on the power of the 50CU.
1 Check that all the PA devices such as an amplifier
and mixer are off.
2 Connect the supplied AC power cord to the 50CU.
NOTICE · Be sure to use the supplied AC power cord. Using an AC power cord
other than the supplied one may cause problems such as damage to the 50CU,
which can be very dangerous.
· Be sure to connect the AC power cord into a properly grounded wall outlet.
Improper grounding can cause electrical shock.
· Be sure that the 50CU is securely grounded to a single ground point.
Grounding to multiple ground points can cause ground loops, resulting in noise
generation such as a humming noise
Connecting an amplifier
1 Connect an amplifier to the OUTPUT BAL.
terminal.
Connect an amplifier to amplify sound. Connect a speaker via the amplifier.
3 Press the power button.
OUTPUT BAL. terminal Amplifier
Speaker
NOTICE · When one or two extension 50CUs are connected to the system, turn on
the power of the primary 50CU and extension 50CU(s) at the same time. If the
time period between each power-on time is significantly long, a successful CU
Link may not be established.
· Configure the network setting from the 50CU ( page
22) as necessary.
37
e
4 After the 50CU starts up, press the (talk) button
of each 50DU to confirm operation.
NOTICE · When the 50DUs are placed close to each other, excessively raising
the volume of the 50DU speakers may cause howling. In such a case, move the
50DUs farther away from each other or decrease the volume.
5 After checking that the 50DUs are operating, turn
off the 50CU before proceeding to the next step for connecting the 50CU to a
network device.
NOTICE · If the power of the amplifier is on, first turn off the power of the
amplifier.
Entire system connection diagram (2)
Web Remote Control
7
Tablet
Web Remote Control
7
Computer
AP Router
Switching hub
6
5
6 Connecting to a network
Configure the detailed conference system settings via Web Remote by connecting
the 50CU to a network.
1 Use an Ethernet cable to connect the 50CU to a
switching hub via the NETWORK terminal.
NOTICE · Be careful NOT to connect the Ethernet cable from your network device
to the CU LINK terminal or DU CHAIN terminal. This can cause damage to the
connected device.
NETWORK terminal
Ethernet cable
Switching hub
7 Connecting a computer or mobile device to a network
About network settings · If there is a DHCP server running on the network, the
50CU
automatically configures network settings including the IP address. · If there
is no DHCP server running on the network, manually configure network settings
including the IP address from the Set
Menu System Setting ( page 10).
· W hen configuring settings manually, inquire with the network manager
regarding setting items.
NOTICE · We decline any and all responsibility for communication errors and
failures regarding your network environment and external devices.
· Disable the firewall setting on your computer. Otherwise, “Locate” will not
recognize the 50CU.
NETWORK terminal
Ethernet cable
Computer
Switching hub
Mobile device AP
38
e
To connect the 50CU directly to your Windows PC/ Mac using an Ethernet cable
If your computer is equipped with an NIC (Network Interface Card), you can
also connect the 50CU directly to the computer using an Ethernet cable. NOTICE
· Be careful NOT to connect the Ethernet cable from the
computer to the CU LINK terminal or DU CHAIN terminal. This can cause damage
to the computer.
1 Use an Ethernet cable (straight) to connect the
NETWORK terminal on the 50CU and the Ethernet terminal on a computer/Mac.
2 In the network settings on your Windows PC/Mac,
select “Obtain an IP address automatically” on your Windows PC, or “Using
DHCP” on your Mac, and then save the settings.
3 Start up the 50CU and from the Set Menu System Info IP Config Mode , select
Auto . ( page 10).
4 Press the BACK button to close the Set Menu.
· After changing the network setting item(s), restart the 50CU to enable the
setting values.
Since there is no DHCP server, IP addresses are automatically assigned to the
Windows PC/Mac and the 50CU using the APIPA (Automatic Private IP Addressing)
feature.
39
e
ATUC-IR System
Example of IR system connections
Device equipped with Dante*
Windows/Mac
Web Remote Control
Tablet
Web Remote Control
AP
CD player Microphone USB device for recording/SFX (mass storage device)
IRCU
IRD
Router Switching hub
Amplifier
Speaker
Recorder IRD
IRA
IRA
IRA
IRA
IRA
IRA
IRDU
IRDU
IRDU
*The ATUC-IRCUDAN can be connected to Dante-enabled devices.
IRDU
40
e
IRDU
IRDU
Part Names and Functions (ATUC-IR System)
ATUC-IRCU/ATUC-IRCUDAN Front panel
Power switch Turns the power on and off.
USB terminal The following operations are possible by connecting a USB device
(mass storage device) such as a USB flash drive or USB hard drive. · Recording
sound · Playing buzzer and chime · Importing/exporting preset data · Upgrading
the firmware
NOTICE · Supports FAT16 and FAT32 file systems · Maximum storage capacity: 2
TB · Maximum file size: 2 GB · Does not support USB hubs. · Do not use
extension cables. · Do not attempt to use USB devices (mass storage devices)
that have been cracked, deformed or repaired using adhesive tape or the like.
· Do not save or create any files or folders unnecessary for this system on
the USB device (mass storage device). Doing so may affect system operations. ·
The IRCU/IRCUDAN are not compatible with USB devices (mass storage device)
with special functions such as a security function.
USB access indicator Indicates the connection status of the USB device (mass
storage device). · In an access state: lit green
NOTICE · Do not remove the USB device (mass storage device) while the
indicator is lit green; doing so may destroy data.
REC (recording) indicator Indicates the recording status. · In a recording
state: lit green · In a recording-pause state: blinks green · While not
recording: remains off
NOTICE · If you remove the USB device (mass storage device) while in a
recording state or recording-pause state, the recorded file may not be written
correctly. Do not remove the USB device (mass storage device) during
recording.
DU CHAIN indicator · In a normal state: lit green · In an abnormal state (such
as when IRDU communications fail): blinks green · In a DU disconnected state:
remains off
IRDU LINK indicator · In a normal state: lit green · In an abnormal state
(such as when IRDU communications fail): blinks green · In an IRDU
disconnected state: remains off
CU LINK indicator · In a CU Link state: lit green · In an abnormal state (such
as when failing in communication with a CU): blinks green · In a CU Link cut-
off state: remains off
REMOTE (remote control) indicator · In a communication state: lit green · In
an abnormal state (such as when failing in external transmission retry):
blinks green · In a non-communication state: remains off
SIGNAL/PEAK indicator Indicates the audio signal level as follows: 60dBFS or
higher: lit green 20dBFS or higher: lit amber 2dBFS or higher: lit red
Adjust the level so it does not light red while operating.
Display
BACK button Returns to the previous or upper screen/item. Press and hold this
button to return to the HOME screen from any screen.
41
e
Jog dial/ENTER button Rotate the jog dial to select the desired item and then
press the ENTER button to confirm. Rotating the jog dial also adjusts the
setting values.
· Locking the operation buttons (Key Lock function) Press the BACK button and
ENTER button simultaneously for over 2 seconds to activate the Key lock
function, and thus lock all front panel operations except for the Power
switch.
· Unlocking the operation buttons When the operation buttons are locked, press
the BACK button and ENTER button simultaneously for over 2 seconds to unlock
the operation buttons.
Display and jog dial operations:
HOME screen
1
2
3
4
The item with is the currently selected item. By rotating the jog dial, move to select the operation you want to perform and then press the ENTER button.
1 Master level adjustment (Lvl)
Master level -50 -40 -30 -20 -12 -6 0 6 12 Peak (dBu)
- Rotate the jog dial to adjust the IRCU output level (OUTPUT 1).
· While pressing the ENTER button, rotate the jog dial to adjust the level in 10-step increments.
· Be sure that the Peak indicator does not light up while adjusting the level.
2 Recording operations (Rec)
R (Remaining recording time)/E (Elapsed recording time) display -50 -40 -30 -20 -12 -6 0 6 12 Peak (dBu)
3 Conference preparation (Pst)
· [1] Recall Presets : Rotate the jog dial to move “>” to the item you want to
recall and then press the ENTER button to confirm.
· [2] Conf. Setup : Change or check the conference settings. Rotate the jog
dial to move “>” to the item you want to change or check and then press the
ENTER button to confirm. Pst Menu Items: Settings can also be configured via
Web Remote. The item names in parentheses ( ) are for Web Remote. [1]Recall
Presets [2]Conf. Setup 01 Conference Mode (Conference Mode) 02 NOM (Number of
Open Mics) 03 Auto Mic Off (Auto Mic OFF) 04 Override Mode (Override Mode) 05
Max Queue (Maximum in Queue) 06 MicON Trigger (Mic ON Trigger / Mic ON Trigger
for Priority) 07 MicON Hold Time (Mic ON Hold Time) 08 Interrupt Option
(Interrupt Option)
· Items that can be configured from [2] Conf. Setup differ depending on the
conference mode.
· For details on items, see “Menu items” in the Web Remote Manual.
4 Configuring settings (Set) Rotate the jog dial to move “>” to the desired
item or value and then press the ENTER button to confirm. For details on
setting items, see “Set Menu Items” (page 54).
- Rotate the jog dial to select Rec (Start recording)/ Pau (Pause)/Stp (Stop)/R or E (Recording time display) and then press the ENTER button to confirm.
· Select the time display on the top right side of the screen using the jog dial and then press the ENTER button to switch the display between R (Remaining recording time)/E (Elapsed recording time).
· To adjust the recording level, move to the recording level meter at the top left of the screen to display Rec Lvl and then press the ENTER button to enter recording level adjustment mode. Rotate the dial to adjust the recording level being sure that the Peak indicator does not light up.
· While pressing the ENTER button, rotate the jog dial to adjust the level in 10-step increments.
42
e
Rear panel
- The serial number label is located on the top panel.
NOTICE · Refer also to the instruction manuals supplied with the external
devices.
· Be careful NOT to connect the Ethernet cable from your network device to the
CU LINK terminal or DU CHAIN terminal. This can cause damage to the connected
device.
NETWORK terminal · RJ-45 · Use for connecting to a local area network when controlling from an external device via the Web Remote Control or IP remote function.
Dante network terminals (ATUC-IRCUDAN) · RJ-45 · Connect to Dante audio network, or use for connections when controlling externally through Web Remote/IP remote. · The primary terminal and secondary terminal mode settings are shown in the following table.
Mode
Connected device
Primary
Secondary
Switched
Dante network Web Remote/external control
Dante network Web Remote/external control
Redundant
Dante network (primary) Web Remote/external control
Dante network (secondary)
Split (Default)
Web Remote/external control
Dante network
CU LINK A/B terminals, DU CHAIN C/D terminals · RJ-45 · Use for cascading
multiple CUs. · You can also configure these terminals as DU/IU/INT terminals.
DU CHAIN A/B terminals · RJ-45 · Use for connecting DU/IU/INT. You can daisy-
chain multiple DU/IU/INTs as well as connect multiple DU/IU/INTs in a ring
using the A/B terminals.
Analog output (balanced) terminals: OUTPUT 1-4 (BAL) · Euroblock · Pin
arrangement: “+” Hot/”” Cold/”G” GND
Analog output (unbalanced) terminals: OUTPUT1 (UNBAL) · Euroblock · Pin
arrangement: “SIG” Signal (2 systems)/”G” GND
Infrared input/output terminals: IR ANT Use for connecting ATUC-IRA. · BNC
connector
Analog input (unbalanced) terminals: INPUT (AUX) · RCA
Analog input (balanced) terminals: INPUT (MIC/LINE 1-2) · Euroblock · Pin
arrangement: “+” Hot (supports phantom power)/”” Cold (supports phantom
power)/”G” GND · The input type can be switched between MIC and LINE
Analog input (balanced) terminal: INPUT (INTERPRETATION RETURN 1-2) ·
Euroblock · Pin arrangement: “+” Hot/”” Cold/”G” GND · Inputs audio signals
from simultaneous interpretation system
Ground screw Since the supplied AC power cord has a three-pronged plug, as
long as your AC power wall outlet is grounded properly, the CU will also be
grounded properly.
AC inlet (AC IN) Connect the supplied AC power cord.
NOTICE · Do not plug in the AC power cord until all other connections,
including CU extension and DU/IU/INT/ IRDUs, have been completed.
· Be sure that the CU is securely grounded to a single ground point. Grounding
to multiple ground points can cause ground loops, resulting in noise
generation such as a humming noise.
43
e
ATUC-IRDU
PUSH
Built-in speaker Outputs conference audio.
Microphone release button
Microphone jack Connect a microphone. * A typical 3-pin XLR type microphone or
an ATUC-M series microphone, can be connected.
Multifunction LED Indicates the state of talking on the IRDU. · While talking:
lit red · While requesting to talk: blinks green · When talk request is
rejected: blinks green (blinks 4 times quickly, then turns off ) · Talking
off: off · Self-muting: lit white
· The LEDs can change to 9 colors. See the Web Remote Edition.
Multifunction button Press this button to send a request to talk. Press the
button again to finish talking or cancel the request to talk. Also, if
priority is set to on for an IRDU, pressing and holding this button can stop
other IRDUs from talking or mute their audio.
When Priority Is Off
Two Person Mode
Conference Mode
Talk Mode
Left Button Right Button
Voice
Self Mute Self Mute
Free Talk
All Button Toggle
Self Mute
Talk ON
OFF
Push to Talk
–
Talk ON
Request to All Button
Talk
Toggle
Self Mute
Talk ON
Full Remote
–
Self Mute Self Mute
Talk ON
Free Talk
All Button Talk ON Talk ON Toggle (speaker 1) (speaker 2)
Push to Talk
Talk ON (speaker 1)
Talk ON (speaker 2)
Full Remote
–
Self Mute Self Mute
44
e
When Priority Is On Talk Mode
All Button Toggle Push to Talk
Voice
Left Button* Cut/Mute Permit Next Cut/Mute Permit Next
Right Button Talk ON Talk ON Self Mute Self Mute
- Depends on the “Left Button Function Assign” setting.
(talk) LED
Cut/mute LED > monitor channel selection buttons While you use these buttons, the currently selected monitor channel appears on the display. · FL: Audio from floor channel · 01 – 03: Audio from groups 1 to 3. Display When changing the monitor channel or adjusting the volume level, the currently set value is displayed. Power LED The dot on the far right is always lit while the power is on. Infrared transmitter Rear LED Indicates the talking state and the remaining charge in the batte r y. · While talking: lit · While requesting to talk: blinks · Talking off: off (can be changed to dimmer) · Battery low: blinks orange · The LEDs can change to 9 colors.
Headphone jack Speech from the selected monitor channel is output.
/+ Headphone volume adjustment buttons When operating these buttons, the
current volume level (0 to 20) is shown on the display.
Power switch
AC adapter jack
Rechargeable battery/rechargeable battery cover release button
Service jack
45
e
Range of light reception
The range at which the IRDU can receive infrared light is shown below.
ATUC-M
Microphone Ring LED Lights red when the microphone is activated. Blinks red
while waiting to talk. Connector
46
e
ATUC-IRA
Power LED Lights when the power to the IRCU is on, after wiring is complete.
Hook for mounting Use to mount on the mounting bracket (included accessory).
BNC connector * The BNC cable is not an included accessory.
47
e
ATUC-IRD
BNC connectors
Connect to BNC cables. Mounting holes
Holes used to mount IRD. · The BNC cable is not an included accessory.
48
e
ATCS-B60
<Charger (top view)>
Charging state indicator LED · Charging: Lights red · Charging complete:
Lights green · Error: Flashes red
Power switch Turns the power on and off.
AC adapter connector Connect the connector from the AC adapter.
<Charger (side view)>
49
e
Using the Charger
LED indicators · Charging (lights red) · Charging complete (lights green) ·
Error (flashes red)
1 Insert the rechargeable battery into the charger slot. If a rechargeable
battery is facing the wrong way, the LED does not light.
2 Charging state indicator LED lights red. If a charging error occurs, the LED
flashes red. If this happens, insert the rechargeable battery again.
3 Charging is complete when the charging state indicator LED lights green.
Charging finishes within about 5.5 hours. Charging times vary depending on the
charge remaining in the rechargeable batteries.
NOTICE · Operating temperature is 10 to 30°C and storage temperature is 0 to
20°C. · Remove the rechargeable batteries from the B60 if they will not be
used for an extended period of time. If you leave the rechargeable batteries
in the B60, while its power is turned off, for a long period of time, the
rechargeable batteries will over discharge, which may drastically shorten
their service lives or prevent them from recharging. If you will not be using
the rechargeable batteries for a long time, store them without charging them,
and then recharge them before you use them. · They can be recharged about 300
times.
50
e
Using Dante
The IRCUDAN supports Dante network audio. It is possible to output ATUC-IR
audio to a Dante device or to input audio from a Dante device to an IRCU. For
details about Dante network audio, see the Audinate home page
(www.audinate.com).
Connecting IRCUDAN in a Network
Network terminal mode settings
1. Explanation for setting up from OLED Set menu System settings Network
Config, and then set Config Mode.
2. Setting up from Web Remote See the Web Remote Edition of the instruction
manual.
· The settings can also be changed from the Dante Controller (an application
provided by Audinate) For details about Dante Controller, see the Audinate
home page (www.audinate.com).
Connections in different modes
Switched (default settings)
PC
Mobile device
Device equipped with Dante
PRIMARY SECONDARY
Switching hub
Device equipped with Dante
PRIMARY SECONDARY
Device equipped
PC
with Dante
PRIMARY SECONDARY
- Switching hubs used in Dante networks must be gigabit compatible. Refer to the Audinate page for specifications required for switching hubs that can be used.
Connect Dante audio and the external control of the IRCU to either the primary or secondary terminal. As shown in the diagram, you can connect a PC or Dante device directly to the network port on the IRCU.
51
e
Redundant Audio
Switching hub
Switching hub
SECONDARY PRIMARY
Device equipped with Dante
SECONDARY PRIMARY
In redundant audio mode, independent networks for both the primary and
secondary are needed. If a fault occurs, for whatever reason, on the Dante
primary side network, the system automatically switches to the Dante audio on
the secondary network.
Split
PC
Mobile device
Switching hub
Device equipped with Dante
PRIMARY SECONDARY
Switching hub
In split audio mode, independent networks for both the primary and secondary are needed. The primary is the IRCU external control terminal and the secondary is the Dante audio terminal.
IRCU Dante channel list
No
Dante transmission channel
1 Active Mic 1
2 Active Mic 2
3 Active Mic 3
4 Active Mic 4
5 Active Mic 5
6 Active Mic 6
7 Active Mic 7
8 Active Mic 8
9 Active Mic 9
10 Active Mic 10
Dante Receiving channel Mic/Line 1 Mic/Line 2 Aux L Aux R Language1-1 Language1-2 Language2-1 Language2-2 Language3-1 Langauge3-2
52
e
No
Dante transmission channel
11 Mic/Line 1
12 Mic/Line 2
13 Aux L
14 Aux R
15 Retrun 1
16 Return 2
17 Output 1
18 Output 2
19 Output 3
20 Output 4
21 Group 0
22 Group 1
23 Group 2
24 Group 3
25 Floor
26 Language 1
27 Language 2
28 Language 3
Dante Receiving channel
53
e
Changing settings on the ATUC-IRCU/ ATUC-IRCUDAN
You can change IRCU/IRCUDAN settings by selecting “Set” on the HOME screen of
the display. Changeable items are as follows. For more detailed settings and
individual settings for each DU/IU/ INT, use Web Remote.
· If you change the network setting item(s), then you must restart the
IRCU/IRCUDAN to enable the setting values.
Set Menu Items
[1] System Setting 01 Device Name 02 Link Port Set 03 CU Error Notice 04
Network Config
01 Config Mode
02 Latency
05 IP Setting 01 IP Port Set. 01 IP Config Mode 02 IP Address 03 Subnet Mask
04 Gateway Address 02 Dante Port Set. 01 IP Config Mode 02 IP Address 03
Subnet Mask 04 Gateway Address
06 Allow Discovery 07 IP Ctrl Setting
01 IP Ctrl Port No 02 IP Ctrl Ntfy 03 Audio Level Ntfy 04 M-cast Adrs 05
M-cast Port No 08 Auto Mode Change 01 Auto Mode Change 02 Hold Time(Err) 09
NTP Setting 01 NTP 02 NTP Adrs 03 NTP Port 04 Time Zone 05 DST 06 DST Start
Date 07 DST Start Time 08 DST End Date 09 DST End Time 10 Infrared Setting 01
IRDU No toDetect 02 Limit NOM
ATUC-IR CU A/B, DU C/D On, Off
Switched, Redundant Audio, Split 250 sec, 500 sec, 1 msec, 2 msec, 5 msec
Auto, Static 0.0.0.0 – 255.255.255.255 0.0.0.0 – 255.255.255.255 0.0.0.0 –
255.255.255.255
Auto, Static 0.0.0.0 – 255.255.255.255 0.0.0.0 – 255.255.255.255 0.0.0.0 –
255.255.255.255 On, Off
00001 – 65535 On, Off On, Off 0.0.0.0 – 255.255.255.255 00001 – 65535
On, Off 20, 30, 40 seconds
On, Off 0.0.0.0 – 255.255.255.255 00001 – 65535 UTC 12:00 – +14:00 On, Off
1/1 – 12/31 0:00 – 23:00 1/1 – 12/31 0:00 – 23:00
0 – 200 On, Off
03 IRDU Band 01 Band A 02 Band B 03 Band C 04 Band D 05 Band E 06 Band F 07
Band G 08 Band H 09 Band I 10 Band J
11 Login Password 01 Admin.Pwd.Login 02 Admin.Password 03 Opr.Pwd.Login 04
Opr.Password
12 Reset All Dflt.
[2] System Info 01 Device Name 02 Serial Number 03 ATUC-IR CUFW Ver 04 ATUC-IR
IRFW Ve 05 IP Config Mode 06 IP Address 07 Subnet Mask 08 Gateway Address 09
Mac Address 10 Dante 01 Device Name 02 Firmware Ver. 03 Config Mode 04 Connect
Status-P 05 IP Mode-P 06 IP Address-P 07 Subnet Mask-P 08 Gateway Adrs-P 09
Mac Address-P 10 Connect Status-S 11 IP Mode-S 12 IP Address-S 13 Subnet
Mask-S 14 Gateway Adrs-S 15 Mac Address-S 16 Latency 11 Allow Discovery 12 IP
Ctrl Port No 13 IP Ctrl Ntfy 14 Audio Level Ntfy 15 M-cast Adrs 16 M-cast Port
No 17 NTP 18 NTP Adrs 19 NTP Port 20 Time Zone 21 CU Link Status 22
No.ofExtensionCU
54
e
Enabled, Disabled Enabled, Disabled Enabled, Disabled Enabled, Disabled
Enabled, Disabled Enabled, Disabled Enabled, Disabled Enabled, Disabled
Enabled, Disabled Enabled, Disabled
On, Off Displays password On, Off Displays password
Displays current settings
23 Total No.of IRDU 24 Total No.of DU 25 Total No.of IU 26 Total No.of INT [3]
Audio Setting 01 MIC/LINE Input 1
01 Input Type 02 Input Gain 03 Level 04 Phantom Power 05 Mix to Floor 01
MIC/LINE Input 1 01 Input Type 02 Input Gain 03 Level 04 Phantom Power 05 Mix
to Floor 03 AUX Input 01 Input Type 02 Level 03 Mix to Floor 04 DU SP Output
Lvl 05 DU Floor Lock 06 VoiceDetectSens 07 Auto to Mic2 In [4] Recorder
Setting 01 Rec Format 02 No.of Rec CH
03 Rec Source CH1
04 Rec Source CH2
05 Rec Source CH3
06 Rec Source CH4
07 Auto Track 08 Filename Prefix [5] Conference Mode 01 Conference Mode 02 NOM
Mic, Line +4dBu, Line 0dBV, Dante 24dB – +20dB , 120 – +10dB On, Off On,
Off
Mic, Line +4dBu, Line 0dBV, Dante 24dB – +20dB , 120 – +10dB On, Off On,
Off
Analog, Dante , 120 – +10dB On, Off 0 – 20 On, Off 5, 4, 3, 2, 1, 0, 1, 2,
3, 4, 5 On, Off
03 Auto mic Off
04 Override Mode
05 Max Queue
06 MicON Trigger
07 MicON Hold Time 08 Interrupt Option [6] Logging 01 Logging 02 Destination
[7] Presets 01 Recall Presets 02 Save Presets 03 Import Presets 04 Export
Presets 05 Boot Up Preset
5 – 60sec, Off No Override, FIFO, LIFO (depending on Conference Mode) 0 – 150
All Button Toggle, All Voice, All Push-to-Talk 1.0 – 10.0 seconds Cut, Mute
On, Off Internal, USB
Recalls presets Saves presets Imports presets Exports presets Calls presets at
boot up
Entering letters
Entering text is the same operation as for the 50CU. Refer to
“Entering letters” (page 23)
WAV, MP3
1 – 4 (WAV), 1 – 2 (MP3)
Floor, Group 0, Group 1, Group 2, Group 3, Language 1, Language 2, Language 3,
Remote Lang. 1, Remote Lang. 2, Mic/Line 1, Mic/ Line 2, Mic/Line 1&2 Mix
Floor, Group 0, Group 1, Group 2, Group 3, Language 1, Language 2, Language 3,
Remote Lang. 1, Remote Lang. 2, Mic/Line 1, Mic/ Line 2, Mic/Line 1&2 Mix
Floor, Group 0, Group 1, Group 2, Group 3, Language 1, Language 2, Language 3,
Remote Lang. 1, Remote Lang. 2, Mic/Line 1, Mic/ Line 2, Mic/Line 1&2 Mix
Floor, Group 0, Group 1, Group 2, Group 3, Language 1, Language 2, Language 3,
Remote Lang. 1, Remote Lang. 2, Mic/Line 1, Mic/ Line 2, Mic/Line 1&2 Mix
Off, 15, 30 min, 1, 2 hour
Displays filename prefix
Free Talk, Request Talk, Full Remote
1 – 10
55
e
IR System Connections and Configuration
Connecting devices
1 Connecting IRA and IRCU
NOTICE · Do not plug in the supplied AC power cord until all other connections
have been completed.
· When connecting devices, plug the connectors securely all the way in. Loose
connections may cause malfunctions or noise.
· Check the plug orientations. · Refer also to the instruction manuals
supplied with the
external devices.
Entire system connection diagram
1 Install the IRCU and IRA.
NOTICE · Install the IRCU on a flat surface. Dropping a unit may cause damage
to the unit and/or personal injury.
· When installing the IRCU in a rack, read the precautions
in advance ( page 5).
· Refer to the Instruction Manual – Installation Edition to install the IRA.
2 Use BNC cable to connect the IRCU and IRA.
1
24
2 Connecting the microphone ATUCM to the IRDU
1 Connect the ATUCM to the microphone jack on
the IRDU.
56
e
NOTICE · Insert it until you hear a click.
· Do not lift the IRDU by holding the ATUC-M. Be sure to hold the main body of
the IRDU when holding it.
· Slowly bend or extend the flexible part of the ATUC-M. Do not apply
excessive force to the ATUC-M when bending it.
· W hen disconnecting the ATUC-M from the IRDU, securely hold the connector
while pressing down the microphone release button and then remove the ATUC-M.
· Before connecting/disconnecting the ATUC-M, be sure to turn off the power.
If you do not turn off the power, a malfunction may occur.
When removing the rechargeable batteries: While pressing the rechargeable
battery/rechargeable battery cover release button, slide the rechargeable
battery in the direction of the arrow.
Press to remove rechargeable batteries
3 Starting the IRDU
1 Insert the rechargeable batteries into the IRDU.
Insert the rechargeable batteries into the bottom of the IRDU. Then, just
slide the rechargeable batteries in the direction of the arrow to secure them.
There is a click sound so you can confirm that the batteries are securely
mounted.
NOTICE · You can install two rechargeable batteries, but one is enough to
operate. If you install both rechargeable batteries, power is consumed from
the first one.
· The IRDUs do not have a recharging function. To recharge them, use Audio
Technica’s specialized charger ( ATC S -B 6 0 ) .
If you are using an AC adapter (sold separately): Attach the rechargeable
battery covers to the IRDU.
NOTICE · Extend the cord of the AC adapter through the hole for the cord.
· Do not pinch the cord when you attach the rechargeable battery covers. Doing
so may cause the cord to break.
4 Setting Device ID for IRDU
You need to set individual IDs for each IRDU before you can use them. They
cannot be used correctly if you do not set the ID numbers. There are two
setting methods. “Auto Setting” automatically assigns an ID in the order the
IRDUs are connected to the IRCU. With “Manual Setting”, you set the ID on the
IRDU itself. · This setting is done only one time and the ID numbers are
recorded in memory. · You can use 200 ID numbers, from 001 to 200, but no
other
numbers can be set. (All the numbers are set to 001 at the factory.)
Auto setting:
While pressing the “BACK” button, turn on the IRCU to enter the device ID
setting mode.
When “audio-technica ATUC-IR” appears in the OLED, release the “BACK” button.
Wait until the OLED display changes to “ATUC-IRDU Device ID Auto Assign
Mode…”, then, while pressing the “<“/”>” monitor channel selection buttons,
turn on each IRDU one at a time in order.
The IDs are automatically assigned in the order in which you turn the IRDUs
on. After you have confirmed the ID, press the right multifunction button to
set the ID. You can also set any ID you want by doing the same operation as
“Manual Setting”.
After setting all the IDs, restart the IRCU.
57
e
NOTICE · For any DUs that were not assigned an ID, such as due to poor
infrared transmissions, turn off their power, and then, while pressing on the
“<“/”>” monitor channel selection buttons, turn on the power and perform “Auto
Setting” or “Manual Setting” to specify the ID.
Manual settings: While pressing the “<“/”>” monitor channel selection
buttons, press the power switch. Look at the display to input the ID number
you want.
<Example: To set ID number “152”> 1 While pressing the “<“/”>” monitor channel
selection buttons,
press the power switch. 2 Press the “<“/”>” buttons so the 2 appears as the
first digit. 3 Press the left multifunction button to set the second digit. 4
Press the “<“/”>” buttons so the 5 appears as the second digit. 5 Press the
left multifunction button to set the third digit. 6 Press the “<“/”>” buttons
so the 1 appears as the third digit. 7 Press the right multifunction button to
apply the setting.
(After step 7, you can use the system in regular modes.) Additional procedures
closely follow the procedures for the ATUC-
50 system. Refer to “4 Connecting an amplifier” (page 37) in
” Wired System Connections and Configuration”.
58
e
ATUC-50/IR Hybrid System
The ATUC-50 wired conference system and the ATUC-IR infrared conference systems can be combined, and operated as a hybrid conference system. Refer to both the wired conference system and infrared conference system sections in this manual to operate a hybrid conference system.
Example of hybrid system connections
Windows/Mac
Web Remote Control
Tablet
Web Remote Control
AP
50CU (Extension)
50CU (Extension)
USB device for recording/SFX (mass storage device)
Microphone
IRCU (Primary)
CD player
IU EXT
DU EXT
INT DU
IU
IU
Router Switching hub
Amplifier
Speaker
Recorder IRD
IRA
IRA
IRA
IRD IRDU
IRDU
IRDU
IRA
IRA
IRA
59
e
IRDU
IRDU
IRDU
Hybrid System Connections and Configuration
About Wired System and IR System Connections and Configuration
Refer to both the wired conference system and infrared conference system
sections in this manual regarding connections and configurations to operate a
hybrid conference system.
” Wired System Connections and Configuration” (page 26) “IR System Connections
and Configuration” (page 56)
IRCU (Primary)
50CU (Extension)
50CU (Extension)
DU (Max. 100 units)
DU (Max. 100 units)
DU (Max. 100 units)
IRD
IRD
IRA
IRDU (Max. 200 units)
Maximum number of connections for each terminal/each CU in Standalone mode
Maximum number of terminal connections in a DU CHAIN
A
B
C
D
Total
Maximum number of IR connections
Daisy-chain
50
50
50
50
100
connection
200
Ring connection
50
50
100
System total
300 300
- The maximum number of units that can be connected to each terminal on the DU CHAIN by using the EXT is 100 units.
· IUs consume more power than 50DUs, so the number of units shown in the table cannot be connected without the use of the appropriate number of EXTs. If you connect that many without the use of the appropriate number of EXTs, it may damage the CUs or the EXTs.
Refer to the table “Relationship of the LAN cable length, number of units connected and number of EXTs required” (page 29, 33)
regarding the number of IUs that can be connected.
60
e
Maximum number of connections for each terminal/each CU when using 3 CU links
IRCU Primary
50CU Extension max. 2 units
Maximum number of terminal connections in a DU
CHAIN
Maximum number of
IR
A
B
Total connections
Maximum number of terminal connections in a DU CHAIN
System total
50CU x 2
A
B
Total
Total
Daisy-chain connection
50
50
100
200
Ring connection
50
50
50
50
50
100
200
500
50
100
350
NOTICE · Up to 6 INTs can be connected to the primary.
61
e
About CU link connections: IRCU/IRCUDAN as primary and up to 2 50CUs as
extension can be cascaded (use the CU LINK A/B terminals for connections as
shown below). Since up to 100 50DU/INTs can be connected to each CU, if you
use 3 CUs, up to 300 50DU/INTs can be connected in total.
Follow the procedure below to cascade CUs. Connect the CU LINK A terminal on
the 1st extension CU to the CU LINK B terminal on the primary CU. When
cascading 2 extension CUs, connect the CU LINK A terminal on the 2nd extension
CU to the CU LINK B terminal on the 1st extension CU.
IRCU/IRCUDAN primary
Terminal A is not used.
1st 50CU extension
Up to 100 units
Primary/Extension (CU Link Mode ):
2 CU LINK
1st extension Extension last unit
2nd extension –
3 CU LINK
Extension pass-through Extension last unit
NOTICE · Settings on the IRCU/IRCUDAN that is the primary are not needed.
- You can either daisy-chain (page 27) or ring (page 27) 50DU/INTs to each CU.
NOTICE · Up to 6 INTs can be connected to the primary CU. They cannot be connected to extension CUs.
· If you are using CU LINK connections, do not use the
Boot Up Preset function (page 55) because it will not
operate correctly.
2nd 50CU extension
Up to 100 units (INTs cannot be connected)
Up to 100 units (INTs cannot be connected)
62
e
Information
Troubleshooting
If a problem should arise, first check the following: 1. Check your
connections. 2. Verify that the system is being operated as described in this
instruction manual. 3. Check that the external devices are operating properly.
Check the operation while the devices are not connected to the CU. 4. Restart
your network devices. If any unit in the system is not operating properly,
check the items listed in the table below. If the symptom is not covered on
the checklist below, contact our sales representative.
W hen you contact us, you may be asked the firmware version. Please check the
firmware version by following the procedure below.
To check from Web Remote: [Settings & Maintenance] [System Settings]
[Utilities] or [Settings & Maintenance] [System Info] To check on the CU
display: Set Log in as Administrator or Operator System Info
ATUC50CU/ATUCIRCU/ATUCIRCUDAN
Symptom
Cause/Solution
Cannot turn on the power.
Check that the AC power cord is connected properly.
Check the connection of the microphone.
Check and adjust the MIC/LINE 1/2 settings.
The connected microphone does not work.
To check from Web Remote: [Settings & Maintenance] [Install Settings] [CU Audio] [Input Settings]
To check on the CU display: Set Log in as Administrator or Operator Audio Setting
Check the connections of all devices.
Plug the connection cables all the way in.
The sound from the connected speaker Check that the inputs and outputs of all devices are connected properly.
is distorted or cannot be heard.
Check that terminal pin assignments (Hot/Cold/GND, etc.) are correct.
Check that the cables are not damaged.
Check and adjust the setting of the connected amplifier.
Cannot record sound.
Check the remaining memory on the USB device (mass storage device).
Reconnect the USB device (mass storage device) or try with a different USB
device (mass storage device).
Check that the recording channel set from [Rec source] is correct.
Although recording has performed properly, when playing the recorded files using a device such as a computer, no sound is heard.
To check from Web Remote: [Settings & Maintenance] [Install Settings] [Recorder] [USB Recorder Settings] To check on the CU display: Set Log in as Administrator or Operator Recorder Setting
Page page 37 page 11
page 10
page 11 –
page 11 page 11
–
page 10
63
e
Symptom You forget the password.
Cause/Solution
Follow the procedure below to reset the password. Display the HOME screen of
the CU display and then while pressing the BACK
button on the CU front panel, rotate the jog dial clockwise until it clicks 3
times. While pressing the BACK button, rotate the jog dial counterclockwise
until it
clicks 3 times. While pressing the BACK button, press the ENTER button.
Page page 9
ATUCIRCUDAN
Symptom Cannot get recognition from Dante controller.
Dante audio is not being input. Dante audio is not being output.
Cause/Solution Check the connections of the LAN cables. Check the Dante
network settings.
To check from Web Remote: [Settings & Maintenance] [System Settings]
[Network/Dante] Check whether the audio routing on Dante controller is
correct. Check whether the input audio settings on Web Remote are correct.
“DANTE” must be selected as the type for input settings in [Settings &
Maintenance] [Install Settings] [CU Audio] [Input Settings] screen. Check
whether the audio routing on Dante controller is correct.
Page page 51 page 54
page 55
–
ATUC50DU/INT
Symptom Cannot turn on the power.
The (talk) button does not function.
No sound is output from the headphone jack.
Cause/Solution
Check the connection to the CU or other DUs/INTs.
Depending on the conference mode or setting, the (talk) button may not
function. Check the conference mode settings.
To check from Web Remote: [Settings & Maintenance] [Install Settings]
[Conference] [Conference Mode] To check on the CU display: Set Log in as
Administrator or Operator Conference Mode The settings of the interpretation
unit(s) may cause speech to be output incorrectly, even if the talk button is
pressed to speak. Check the settings of the interpretation unit(s).
To check from Web Remote: [Settings & Maintenance] [Install Settings]
[Interpretation] [Interpretation Settings] [Interpretation Mode] and [Settings
& Maintenance] [Install Settings] [Interpretation] [INT Unit Settings]
[Interpretation Languages] Insert the headphone plug all the way in.
Raise the volume with the + button.
Use the monitor channel selection button(s) of the DU/INT to confirm that you
can monitor speech from the channel you want.
Page pages 26,
27
page 10
–
pages 12,
13 pages 12,
13
64
e
Symptom
No sound is output from the built-in speaker.
The ATUC-M does not operate. If you read the preset, the settings changed from
the last settings.
Cause/Solution
Check the connection of the DUs.
Plug the Ethernet cable all the way in.
Check that the cables are not damaged.
From [Settings & Maintenance] [Install Settings] [DU/IU] [DU/IU Detail
Settings], check that the [Speaker] setting is set to [Enabled].
Adjust the speaker level.
To check from Web Remote: [Settings & Maintenance] [Install Settings] [DU/IU]
[Global DU/IU Settings] [Speaker Level] To check on the CU display: Set Log in
as Administrator or Operator Audio Setting DU SP Output Lvl
Speech is not output from the built-in speaker of the INTs.
Insert the ATUC-M connector into the microphone jack on the DU/INT until a
clicking sound is heard.
For DUs: From [Settings & Maintenance] [Install Settings] [DU/IU] [DU/IU
Detail Settings], check the setting of [Microphone].
For the INTs: From [Settings & Maintenance] [Install Settings]
[Interpretation] [INT Unit Settings] [INT Unit Detail Settings] check the
setting of [Microphone].
· Check that [Phantom Power] is not set to [Off ]. · Check that [Input Gain]
is not too low.
Check that the preset data is correct.
Check that the number and topology of the DUs/INTs have not changed since the
last time.
Page page 27
–
page 10
page 37
–
–
ATUC50IU
Symptom Cannot turn on the power.
Cause/Solution Check the connection to the CU or other DUs/INTs.
Page
pages 26, 27
ATLKEXT165
Symptom Cannot turn on the power.
Cause/Solution Check that the AC power cord is connected properly.
Page page 37
ATUCIRDU
Symptom Cannot turn on the power.
Cause/Solution Check the installation of the rechargeable batteries. Check the remaining charge in the rechargeable batteries.
Page page 57 page 50
65
e
Symptom
Cause/Solution
Check the installation locations of the IRDUs and IRAs.
Initialization operation does not end (LEDs continue flashing).
There may be a limit on the number of IRDUs that are detected at system start. Check the infrared setting again. [Settings & Maintenance] [System Settings] [Infrared] If this is the case, connection is possible by operating any button on the IRDU.
Depending on the conference mode or settings, the (talk) button may not function. Check the conference mode settings.
To check from Web Remote: The (talk) button does not function. [Settings & Maintenance] [Install Settings] [Conference] [Conference Mode]
To check on the CU display: Set Log in as Administrator or Operator Conference Mode
Check the installation locations of the IRDUs and IRAs.
The sound from the connected microphone is distorted or cannot be heard.
Check the ID settings of the device.
There may be interference with the infrared. The problem may be solved by the
settings for the infrared frequency that you are using. [Settings &
Maintenance] [System Settings] [Infrared] [IRDU Band]
Insert the headphone plug securely all the way in.
No sound is output from the headphone jack.
Raise the volume with the + button on the IRDU.
Use the monitor channel selection button(s) to confirm that you can monitor
speech from the channel you want.
From [Settings & Maintenance] [Install Settings] [DU/IU] [DU/IU Detail Settings], check that the [Speaker] setting is set to [Enabled].
Adjust the speaker level.
No sound is output from the built-in speaker.
To check from Web Remote: [Settings & Maintenance] [Install Settings] [DU/IU] [Global DU/IU Settings] [Speaker Level]
To check on the CU display: Set Log in as Administrator or Operator Audio Setting DU SP Output Lvl
Page –
page 54
page 10
page 57 page 54 page 45 page 45 page 45 page 27
page 10
ATUCIRA
Symptom
Cannot turn on the power to ATUCIRA.
Cause/Solution Check the connections of the cables. Check that the cables are not damaged.
Page page 56
66
e
Error messages
- Error messages displayed on the Web Remote screen and CU displays are as follows. · The states of the CU LED error indicators are described together with the CU display error messages. · If the same error persists even after the following remedies are taken, or when the unit(s) requires repair or parts replacement, contact our
sales representative.
Web Remote Resume Data Error 1
Preset Data Error 2
DU Power Error
3
DU Communication Error 4
DU Ring to Daisy 5
DU Daisy to Ring 6
Number of DU Decreased 7
DU Exceeds 100 Units 8
INT Unit Exceeds 6 Units 9
DU A/B: Exceeds 50 Units 10
DU C/D: Exceeds 50 Units 11
CU Communication Error 12
CU Link OFF 13
Network Communication 14 Error
CU display (LED indicators) Resume Data Err
Pst Data Err
DU Power Err (DU CHAIN: blinks green)
DU Comm Err (DU CHAIN: blinks green) DU Ring to Daisy (DU CHAIN: blinks green)
DU Daisy to Ring (DU CHAIN: blinks green)
DU Number Decrease (DU CHAIN: blinks green)
DU Exceeds 100pcs (DU CHAIN: blinks green)
INT Exceeds 6pcs (DU CHAIN: blinks green)
DU A/B Exceeds 50pcs (DU CHAIN: blinks green) DU C/D Exceeds 50pcs (DU CHAIN:
blinks green) CU Comm Err (CU LINK: blinks green) CU Link OFF (CU LINK: blinks
green) Network Comm Err (REMOTE: blinks green)
State/remedies
Failed to read the resume information. · The unit was started up using the
second from the last setting or default
setting. Although there is no functional limitation, be sure to restart the
unit to check that the same error does not occur again.
Failed to read the preset data. · This error may occur when you recall the
default preset or the preset which
you successfully recalled last time. Although there is no functional
limitation, be sure to restart the unit to check that the same error does not
occur again.
An error occurred when power was supplied to the DU. · Voltage may fall at the
48V output. After disconnecting all DUs from the CU, restart the CU. If the
same error occurs again, the CU requires repair. If the same error does not
occur again in but the error occurs again after connecting the DUs, there may
be a damaged cable or DU. Identify the damaged cable or DU for replacement or
repair.
DU individual settings cannot be configured. · Check that there is no DU
connection error.
The DU topology has been changed (from ring to daisy). · If this error occurs
even though you did not change the DU connection,
check that there is no DU connection error.
The DU topology has been changed (from daisy to ring). · If this error occurs
even though you did not change the DU connection,
check that there is no DU connection error.
The number of connected DUs decreased. · If this error occurs even though you
did not change the DU connection,
check that there is no DU connection error.
More than 100 DUs are connected to the DU CHAIN A/B/C/D terminals in total. ·
Connect 100 DUs or less to each CU.
More than 6 INTs are connected to the DU CHAIN A/B/C/D terminals in total. ·
Connect 6 INTs or less to CU.
More than 50 DUs are connected to the DU CHAIN A/B terminals in total. ·
Connect 50 DUs or less to the DU CHAIN A/B terminals in total.
More than 50 DUs are connected to the DU CHAIN C/D terminals in total. ·
Connect 50 DUs or less to the DU CHAIN C/D terminals in total.
A communication error occurred between the CUs. · Check that there is no CU
connection error.
CU Link is cancelled. · If this error occurs unexpectedly, check that there is
no CU connection error.
(1) A network communication error occurred. (2) An IP command communication
error occurred. · Check that there is no network connection error.
67
e
Web Remote USB Access Error 15
USB Format Error 16
Failed
CU display (LED indicators) USB Access Err
USB Format Err
Failed
17
File Export Failed 18
File Import Failed 19
USB Write Error
20
USB Write Err
Failed. Please turn power OFF. CU FW Update Err
21
Please Turn Pwr OFF
Failed. Please turn power OFF. IRCU FW Update Err
22
Please Turn Pwr OFF
Failed. Please turn power OFF. DU FW Update Err Please Turn Pwr OFF
23
Failed. Please turn power OFF. INT FW Update Err Please Turn Pwr OFF
24
State/remedies
An error occurred when accessing the USB device (mass storage device). · Check
that the USB device (mass storage device) has no problems. · Check that the
same error does not occur with another USB device (mass
storage device).
There is a problem with the USB device (mass storage device). · Check the
format of the USB device (mass storage device). · Use a USB device (mass
storage device) formatted with FAT16 or FAT32.
(1) The setting cannot be configured due to some system errors. · Try to
configure the setting again and check whether the same error occurs
again.
(2) Playback operation cannot be performed. · Check that the USB device (mass
storage device) is connected properly. · Check that the file you want to play
is in the USB device (mass storage
device). · Check that the format of the file you want to play is correct. (You
can check
by, for example, playing the file with another playback device.)
(3) Recording operation cannot be performed. · Check that the USB device (mass
storage device) is inserted in the CU. · Check that write protection is
disabled on the USB device (mass storage
device). · Check the space available on the USB device (mass storage device).
· Check that the USB device (mass storage device) has no problems. · Check
that the same error does not occur with another USB device (mass
storage device).
(4) The preset data cannot be exported. · Check that the USB device (mass
storage device) has no problems. · Check that the same error does not occur
with another USB device (mass
storage device).
(5) The preset data cannot be imported. · Check that the USB device (mass
storage device) has no problems. · Check that the same error does not occur
with another USB device (mass
storage device).
The data log cannot be saved onto the USB device (mass storage device). ·
Check that the USB device (mass storage device) is inserted to the CU. · Check
that write protection is disabled on the USB device (mass storage
device). · Check the space available on the USB device (mass storage device).
· Check that the USB device (mass storage device) has no problems. · Check
that the same error does not occur with another USB device (mass
storage device).
An error occurred during the CU firmware update. · Turn off the power and
restart the CU.
An error occurred during the IRCU firmware update. · Turn off the power and
restart the system.
An error occurred during the DU firmware update. · Turn off the power and
restart the CU.
(W hen the update cannot be performed for the 1st DU, or an error occurs
during the update process and the update cannot be continued.)
An error occurred during the INT unit firmware update. · Turn off the power
and restart the CU.
(W hen the update cannot be performed for the 1st INT, or an error occurs
during the update process and the update cannot be continued.)
68
e
Web Remote
CU display (LED indicators)
Failed. Please turn power OFF. IU FW Update Err Please Turn Pwr OFF
25
Completed except serial numbers below. Please turn power OFF.
Part of DU Failed Please Turn Pwr OFF
26 XXXXXXXX XXXXXXXX (Displays a list of 8-digit serial numbers of DUs for which the update cannot be performed.)
Completed except serial numbers below. Please turn power OFF.
Part of INT Failed Please Turn Pwr OFF
27 XXXXXXXX XXXXXXXX (Displays a list of 8-digit serial numbers of INTs for which the update cannot be performed.)
Completed except serial numbers below. Please turn power OFF.
Part of IU Failed Please Turn Pwr OFF
28 XXXXXXXX XXXXXXXX (Displays a list of 8-digit serial numbers of IUs for which the update cannot be performed.)
Data acquisition error. 29
Data Acquisition Err
Unable to Set
Unable to Set
30 Can’t.ReducePriority
All DUs will be turned off to Turn OFF All DU? apply the changes. Do you wish
to proceed?
31
Unable to control. 32
Unable to Ctrl
State/remedies
An error occurred during the IU firmware update. · Turn off the power and
restart the CU.
(W hen the update cannot be performed for the 1st IU, or an error occurs
during the update process and the update cannot be continued.)
The DU firmware update has been completed but the update cannot be performed
for some DUs. The serial numbers of DUs for which the update cannot be
performed will be listed on the pop-up screen. Write them down. Turn off the
power. Disconnect the DUs with the serial numbers you wrote down. Perform
emergency update for the DUs you disconnected in step . For details on how to
perform the emergency update, contact our sales representative.
The INT unit firmware update has been completed but the update cannot be
performed for some INTs. The serial numbers of INTs for which the update
cannot be performed will be listed on the pop-up screen. Write them down. Turn
off the power. Disconnect the INTs with the serial numbers you wrote down.
Perform emergency update for the INTs you disconnected in step . For details
on how to perform the emergency update, contact our sales representative.
The IU firmware update has been completed but the update cannot be performed
for some IUs. The serial numbers of IUs for which the update cannot be
performed will be listed on the pop-up screen. Write them down. Turn off the
power. Disconnect the IUs with the serial numbers you wrote down. Perform
emergency update for the IUs you disconnected in step . For details on how to
perform the emergency update, contact our sales representative.
Failed to acquire data through operation via Web Remote or the CU display. ·
Perform the operation again and check whether the same error occurs.
(1) Unusable characters are contained in the string of letters you have
entered. · Delete unusable characters.
(2) The change cannot be applied because the entered values are out of the
permitted range or the change is not allowed. · Enter values within the
permitted range. · Check that the unit is in a state where changes are allowed
and then perform
the operation again and check whether the same error occurs.
(3) The setting of [Number of Open Mics] (NOM ) cannot be changed due to the
current number of priority DUs. · Set a different number for [Number of Open
Mics] (NOM ) or change the
number of priority DUs.
(4) Since recording, recording pause, or file reading process is under way,
any recording-related settings cannot be configured. · Stop recording and then
perform the operation again.
(5) You must turn off the microphones for all of the DUs in order to change
the settings. · Selecting [Yes] forces the microphones for all of the DUs off
and changes the
settings.
(1) Since recording, recording pause, or file reading process is under way,
the operation cannot be performed. (2) Due to other reasons, the operation
cannot be performed. (Operations except changing settings cannot be
performed.) · Stop recording and then perform the operation again.
69
e
Web Remote
Number of IRDU exceeds 33 available IR Bands
CU display (LED indicators)
Pst Recall Err
Dante Communication Error 34
Dante Comm Err
Number of priority units
exceeds maximum. Reduced
35 priority channels.
–
Unable to set. Number of
priority channels exceeds
36 maximum.
–
Recording Failed
37
–
Device ID XXX , Battery 1 Low
38
–
Device ID XXX , Battery 1
39 Depleted
–
Device ID XXX , Battery 2 Low
40
–
Device ID XXX , Battery 2
41 Depleted
–
Device ID XXX, IRDU Not
42 Responding
–
Boot Error XXX
43
–
Chg to FreeTalk Mode
44
–
Forcible FW Update
45
–
Connect USB Device
46
–
with FW Update File
Warning 60D
47
–
State/remedies
The preset file cannot be read. The number in [Number of Open Mics] exceeds
the number of [IRDU Band] that are enabled. · Set [Limit NOM to Enabled IR
Bands] in [Infrared Settings] to [Off ].
A communication error occurred with the Dante board. · Turn off the power and
restart the system. Confirm that the same error does
not occur when the system is restarted.
The number of DUs which are set as priority DUs exceeded the limit due to CU
Link. Decrease the number of priority DUs. (Deactivate the priority setting
for some DUs.) · Check the priority DUs and change the setting as necessary.
The maximum number of DUs that can be designated as priority DU is 1 unit less
than the specified value for [Number of Open Mics] (NOM ). No more DUs can be
designated as a priority DU. · Change the setting value for the NOM or DU
priority setting.
A recording function error occurs such as a recording error not due to
recording operations via Web Remote. · Check that no error occurs during
recording on the CU. If an error occurs,
solve the problem according to the error.
There is low remaining power in battery 1 in the IRDU with device ID XXX. ·
Replace battery 1.
There is no remaining power in battery 1 in the IRDU with device ID XXX. ·
Replace battery 1.
There is low remaining power in battery 2 in the IRDU with device ID XXX. ·
Replace battery 2.
There is no remaining power in battery 2 in the IRDU with device ID XXX. ·
Replace battery 2.
There is no response from IRDU with device ID XXX. · Refer to the installation
manual to confirm that the installation environment
for the IRDU and IRA is correct, and then redo the previous operation.
An error occurred while booting the CU. (XXX indicate an error code.) ·
Restart the CU and check whether the same error occurs. If the same error
occurs again, the CU requires repair.
Since a communication error occu
References
- Global Support|Audio-Technica Corporation オーディオテクニカ
- Audinate - Pioneering the future of AV
- Audio-Technica Corporation | Headphones, Microphones & Turntables | Audio-Technica
- Manual-Hub.com – Free PDF manuals!
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>