Camden CV-110SPK Standalone Keypad/Prox Access Control Instruction Manual
- June 17, 2024
- Camden
Table of Contents
- Camden CV-110SPK Standalone Keypad/Prox Access Control
- Installation Instructions
- Packing List
- Description
- Features
- Quick Reference Programming Guide
- Specifications
- Installation
- Wiring
- To Reset to Factory Default
- Anti-Tamper Alarm
- Sound and Light indication
- Interfacing to an Access Control System
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Camden CV-110SPK Standalone Keypad/Prox Access Control
Standalone Keypad/Prox Access Control
Installation Instructions
Packing List
Qty | Name | Remarks |
---|---|---|
111221 | KeypadUser manual Screwdriver Wall plugsSelf-tapping screws Torx | |
screw | **0.8” x 2.4” (20 mm×60 mm) 0.24” x 1.2” (6 mm×30 mm)** |
0.16” x 1.1” (4 mm×28 mm) 0.12” x 0.24” (3 mm×6 mm)
Description
The CV-110SPK is a single door multifunction standalone keypad with a wiegand output for interfacing to an access control system or remote card reader. It is suitable for mounting either indoor or outdoor in harsh environments. It is housed in a strong, sturdy and vandal proof Zinc Alloy electroplated case. The electronics are fully potted so the unit is waterproof and conforms to IP68. This unit supports up to 2000 users in either a Card, 4 digit PIN, or a Card + PIN option. The built-in prox card reader supports 125KHZ EM cards. The unit has many extra features including lock output current short circuit protection, wiegand output, and a backlit keypad. These features make the unit an ideal choice for commercial and industrial applications such as factories, warehouses, laboratories, banks and prisons.
Features
- 2000 users, supports Card, PIN, Card + PIN
- Backlit keys
- Zinc Alloy Electroplated anti-vandal case
- Waterproof, conforms to IP68
- • Easy to install and program
- Wiegand 26 output for connection to a controller-
- Full programming from the keypad
- Can be used as a stand-alone keypad
- Wiegand 26 input for connection to external reader
- Adjustable Door Output time, Alarm time, Door Open time
- Very low power consumption (30mA)
- Fast operating speed, <20ms with 2000 users
- Lock output current short circuit protection
- Built in light dependent resistor (LDR) for anti-tamper
- Built in buzzer
- Red, Yellow and Green LEDS status indicators
Quick Reference Programming Guide
Specifications
Operating Voltage | 12V DC ±10% |
---|---|
User Capacity | 2,000 |
Card Reading Distance | 1.25” to 2.4” (3 cm to 6 cm) |
Active Current | < 60mA |
Idle Current | 25±5 mA |
Lock Output Load | Max 3A |
Alarm Output Load | Max 20mA |
Operating Temperature | -49°F to 140°F (-45°C to 60°C) |
Operating Humidity | 10% – 90% RH |
Waterproof | Conforms to IP 68 |
Adjustable Door Relay time | 0 – 99 seconds |
Adjustable Alarm Time | 0 – 3 minutes |
Wiegand Interface | Wiegand 26 bit |
Wiring Connections | Electric Lock, Exit Button, External Alarm, External |
Reader
Dimensions| 5 15/16” H x 1 3/4” W x 1” D (150 mm x 44 mm x 25 mm)
Installation
- Remove the back cover from the keypad using the supplied special screw driver
- Drill 2 holes on the wall for the Self tapping screws and 1 hole for the cable
- Put the supplied wall plugs into the two holes
- Attach the back cover firmly to the wall with the 2 Self tapping screws
- Thread the cable through the cable hole
- Attach the keypad to the back cover
Wiring
Color | Function | Description |
---|---|---|
Pink | BELL_A | Doorbell |
Pale Blue | BELL_B | Doorbell |
Green | D0 | Wiegand output D0 |
White | D1 | Wiegand output D1 |
Grey | ALARM | Alarm negative (alarm positive connected 12 V+) |
Yellow | OPEN | Exit button (the other end connected GND) |
Brown | D_IN | Door Contact switch (the other end connected GND) |
Red | 12V+ | 12V + DC Regulated Power Input |
Black | GND | 12V – DC Regulated Power Input |
Blue | NO | Relay Normally Open |
Purple | COM | Relay Common |
Orange | NC | Relay Normally Closed |
Common power supply diagram
To Reset to Factory Default
- Disconnect power from the unit
- Press and hold # key while powering the unit back up
- On hearing two “Beeps” release # key, system is now back factory settings
Note : Only the installer data is restored, user data will not be affected.
Anti-Tamper Alarm
The unit uses a LDR (light dependent resistor) as an anti-tamper alarm. If the keypad is removed from the cover, the tamper alarm will operate.
Sound and Light indication
Operation Status| Red Light| Green Light| Yellow Light|
Buzzer
---|---|---|---|---
Power on| –| Bright| –| Beep
Stand by| Bright| –| –| –
Press keypad| –| –| –| Beep
Operation successful| –| Bright| –| Beep
Operation failed| –| –| –| Beep/Beep/Beep
Enter into programming mode| Bright| –| –| –
In the programming mode| –| –| Bright| Beep
Exit from the programming mode| Bright| –| –| Beep
Open the door| –| Bright| –| Beep
Alarm| Bright| –| –| Alarm
Detailed Programming Guide
User Settings
Door Settings
Interfacing to an Access Control System
In this mode the keypad provides a 26 bit wiegand output. The wiegand data lines can be connected to any controller which supports the 26 bit wiegand protocol.
Keypad 8 bit Burst Mode
Every key pressed generates an 8 bit data stream that is transmitted over the wiegand bus.
Key | Output | Key | Output |
---|---|---|---|
0 | 11110000 | 6 | 10010110 |
1 | 11100001 | 7 | 10000111 |
2 | 11010010 | 8 | 01111000 |
3 | 11000011 | 9 | 01101001 |
4 | 10110100 | * | 01011010 |
5 | 10100101 | # | 01001011 |
5502 Timberlea Blvd., Mississauga, ON Canada L4W 2T7
www.camdencontrols.com Toll Free:
1.877.226.3369
File: Standalone Keypad/Prox Access Control Installation Instructions.indd R3
Revision: 05/03/2018
Part No.: 40-82B190