Instruction Manual
Operator manual: ADELSystem reserves the right to change the contents of this document without prior notice.
QUICK START
Quick start for CBI60, please refer to Section: 7; 10.3.1; 13
“ALL IN ONE” DC UPS SERIES
Thank you for having chosen one of our products for your work.
We are certain that it will give the utmost satisfaction and be a notable help
on the job.
GENERAL DESCRIPTION
Thanks to “All In One” CBI series of DC-UPS, it will be possible to optimize
the power management of your system with one single, extremely compact and
cost-effective device, connected directly to the mains.
The available power is automatically distributed between load and battery
giving priority to the load.
Battery can supply the load even with mains so the output power to the load
can be twice the nominal power if it is required (Power Boost). When mains
failure occurs, the load continues to be supplied by the battery in backup
mode. It is also possible to switch on the device with no mains directly from
battery. The “Battery Care” algorithm performs rapid and automatic charging,
battery charge optimization during time, flat batteries recovery and real time
diagnosis during installation and operation. Temperature compensation is
possible by connecting the temperature sensor probe. The real time auto-
diagnostic system monitors battery faults such as sulphated battery, shorted
cells, accidental reverse polarity connection or disconnection of the battery.
Each fault is signaled by a blink code of Diagnosis Led or via Modbus (only in
some models) in order to be easily detected and removed during the
installation and after sales. The continuous monitoring of battery efficiency
reduces risk of battery damage and allows a safe operation in permanent
connection. Predefined curves can be selected by jumpers or DIP switch to
optimize the charge of different battery types: Open Lead Acid, AGM and Gel
Lead Acid; Ni-Cd are rechargeable using the same device. Charging curves can
be customized via Modbus (only in some models). Output dry contacts are used
to signal both backup and fault conditions. A rugged casing with bracket for
DIN rail mounting provides IP20 protection degree.
MAIN CHARACTERISTICS
- Universal input voltage: single-phase 115–230-277 Vac
- Load output:24 Vdc 3,5,10,20A; 12 Vdc 3,6,10,15,35A 48 Vdc 5,10A
- Battery output:24 Vdc 3,5,10,20A; 12 Vdc 3,6,10,15,35A; 48 Vdc 5,10A
- “All In One” solution: power supply + battery charger + backup module in one single device connected directly to the mains
- Suited for different battery types: Open Lead Acid, Sealed Lead Acid, AGM and Gel Lead Acid; Ni-Cd and Li-ion are available as options. Four stage charging curve for Lead Acid batteries: 5-stage IUoU (Recovery, Bulk, Absorption, Float, Refresh Battery) plus Recovery stage for deeply discharged batteries
- Automatic diagnosis of battery status and battery Life Test function (Battery Care)
- Switching technology with high efficiency
- Protected against short circuit, overload and inverted polarity
- Output dry contact for signaling Low Battery or Battery Replacement and Fault system. CBI60 have only Mosfet Connections.
- Output dry contact for signaling Mains or Backup
- IP20 protection degree
- Space saving on DIN rail
SAFETY AND WARNING NOTES
- WARNING – Explosion Hazard. Do not disconnect Equipment unless power has been switched off or the area is known to be non-hazardous.
- WARNING – Explosion Hazard. Substitution of components may impair suitability for class I, Division 2.
- WARNING – Switch off the system before connecting the module. Never work on the machine when it is live. The device must be installed in according with UL508 or UL60950. The device must have a suitable isolating facility outside the power supply unit, via which can be switched to idle. Danger of fatal Injury!
- WARNING – Residual voltage. Wait for 10 seconds before operating on the device CBI2420A and CBI485A.
CONNECTION
6.1 CONNECTION TERMINAL AND WIRING
The following cable cross-sections may be used:
| Solid (mm 2 )| Stranded (mm 2 )| AWG|
Torque (Nm)| Stripping Length| All In One (Size)
---|---|---|---|---|---|---
In:| 0.2 – 2.5| 0.2 – 2.5| 24 – 14| 0.5 – 0.6 Nm| 7 mm| Size 1 and 2
4.0| 6.0| 30 – 10| 0.8 – 1.0 Nm| 7 mm| Size 3 and 4
Out:| 0.2 – 2.5| 0.2 – 2.5| 24 – 14| 0.5 – 0.6 Nm| 7 mm| Size 1 and 2
4.0| 6.0| 30 – 10| 0.8 – 1.0 Nm| 7 mm| Size 3 and 4
Signal:| 0.2 – 2.5| 0.2 – 2.5| 24 – 14| 0.5 – 0.6 Nm| 7 mm| All types
Connection by the screw, type 2.5 mm2 or 4.0 mm2 terminal blocks. Wiring
terminal shall be marked to indicate the proper connection for the power
supply. Use copper cables only, for supply connections, use wires suitable for
at least 75°C.
6.2 INPUT LINE SYSTEM 6.3 OUTPUT POWER CONNECTIONS: LOAD AND BATTERY
6.3.1 Normal connection
Typical application for All In One device, one output for Load “DC Bus”, one
Input / Output for connection to the battery.
N°1 battery (12 Vdc) for CBI 12xx;
N°2 battery (12 Vdc) connected in Series for CBI 24xx;
N°4 battery (12 Vdc) connected in Series for CBI 48xx; 6.3.2 Parallel connection
“Redundancy” Parallel connection “Redundancy”
Power supplies can be paralleled in case of redundancy concept, to obtain a
higher system reliability. Redundant systems may support N+1 redundancy to
safeguard against single-point failures, or to enable hot-swapping of a failed
supply without system impact. The simplest way is to put two CBI in parallel.
In case one power supply unit fails, the other one is automatically able to
support the load current without any interruption. To separate completely a
hypothetical device failure, it is necessary add the decoupling diodes which
are included in the Redundancy Module MR220. Recommendations for building
redundant power systems: a) Use separate input fuses for each CBI. b) Monitor
the individual CBI units by three LED. Each unit has two relays: Mains or
backup and Low Battery or Battery Replacement (faulty situation). This feature
reports a faulty unit; see Relay Contact Rating for any technical detail. c)
When possible, connect each power supply to different phases or circuits
6.3.3 Parallel connection “Redundancy One Battery Source”
Parallel connection “Redundancy” is also possible with the CBI 600W:
CBI1235AP, CBI2420AP, CBI4810AP Power supplies can be paralleled in case of
redundancy concept only for the power supply function but not for the battery
energy. Redundant systems may support N+1 redundancy to safeguard against
single-point failures, or to enable hotswapping of a failed supply without
system impact.
The simplest way is to put two CBI in parallel. In case one power supply unit
fails, the other one is automatically able to support the load current without
any interruption. To separate completely a hypothetical device failure, it is
necessary add the decoupling diodes which are included in the Redundancy
Module MR220. Recommendations for building redundant power systems: a) Use
separate input fuses for each CBI. b) Monitor the individual CBI units by
three LED. Each unit has two relays: Mains or backup and Low Battery or
Battery Replacement (faulty situation). This feature reports a faulty unit;
see Relay Contact Rating for any technical detail. c) When possible, connect
each power supply to different phases or circuits.
The redundancy it is not reliable in Back Up situations because the battery
connected are only one branch.
It is necessary to use a standard UTP or order Cable code: ERJ.CBI.004 for
RJ45, and connect to Aux2 of each device. The communication protocol is based
on CAN2.0A standard.
6.3.4 Parallel connection “Double Power”
Power
supply can be paralleled to increase the output power, devices can be
paralleled for 1+1=2 to obtain the double power of a single unit. Only SIZE 3
devices in the specific “P” version (i.e.CBI1235AP, CBI2420AP, CBI4810AP) can
be connecter in parallel to attain the sum of the current at the same output
voltage. It is necessary to use a standard UTP or order Cable code:
ERJ.CBI.004 for RJ45, and connect to Aux2 of each device. The communication
protocol is based on CAN2.0A standard.
In this way the system has only One output for the Load and One output for the
battery.
a) Use separate input fuses for each CBI.
b) Make sure that the two CBI have the same settings: Battery type, Charging
level current, Time buffering, Life test…
c) Automatic configuration, Master-Slave. The devices decide themselves their
Master and Slave assignment randomly. The assignment is done at every power
on, or after the connection of the RJ45 cable.
Master device provide all the visual signals, the Slave device maintain the
diagnosis LED always ON.
d) Use the alarm contacts of both the two devices and deliver them as needed.
e) For Start Battery there are two way, without mains voltage:
– push start button on both units
– connect Cable “RTCONN” on position 5, to connect pushbutton on a front
panel.
6.3.5 Series connection:
It is
possible to connect as many units in series as needed, provided the sum of the
output voltage does not exceed 150Vdc. a) Voltages with a potential above
60Vdc are not SELV anymore and can be dangerous. Such voltages must be
installed with a protection against touching. b) For serial operation use
power supplies of the same type. c) Earthing of the output is required when
the sum of the output voltage is above 60Vdc. d) Keep an installation
clearance of 10 mm (left/right) between two power supplies and avoid
installing the power supplies on top of each other. Note: Avoid return voltage
(e.g. from a decelerating motor or battery) which is applied to the output
terminals.
6.4 OUTPUT LOAD (MAINS INPUT ON)
The output Load in normal mode, Mains Input Vac Voltage present, follows the
charging battery dc output voltage. The minimum and maximum range stabilized
are the following:
CBI 12xx:11 – 14,4 Vdc; 15,5 Vdc for NiCd (Without battery connected out.
Voltage fixed at 12Vdc)
CBI 24xx:22 – 28.8 Vdc; 30 Vdc for NiCd (Without battery connected out.
Voltage fixed at 24Vdc)
CBI 48xx:44 – 57.6 Vdc; 62 Vdc for NiCd (Without battery connected out.
Voltage fixed at 48Vdc)
Thanks to the All In One units, it will be possible to manage the power. The
available power, is automatically allocated between load and battery:
supplying power to the load is the first priority of the unit; thus it is not
necessary to double the power and also the power available for the battery
will go to the load if the load requires it.
In “Power Boost Mode” the maximum current on the load output is the 2 times
the rated current 2 x In (Iload = In+ Ibatt) in continuous operation and 3
times the rated current 3 x In (Iload = 2In+ Ibatt) for 4 seconds; after this
power the devices is electrically protected against overload and short
circuit.
- In “Power Boost Mode”, if the the battery provide current to the load for longer than 4 minutes, the device outputs a message (8 Blink) to warn that the battery is discharging.
- If the Mains Input Voltage fall below a Threshold level (50% of the Typ. Vac input) the battery is immediately connected to the Output Load, without any interruption.
- Voltage dips: In this situation the voltage in the output load is the same of the battery.
- To Avoid deep battery discharge, the battery will supply the load until battery voltage reaches the minimum V/cell. Below this level the device automatically switches off to prevent Deep discharge and battery damage.
6.5 OUTPUT LOAD: TIME BUFFERING MODE (MAINS INPUT OFF)
Some example of buffering time depending on LOAD Output in function to the Ah
of the battery.
Buffering Time| BATT1.2 Ah| BATT 3 Ah| BATT7.2 Ah|
BATT12 Ah| BATT100 Ah
---|---|---|---|---|---
Load 1.5 A| 20 min| 60 min| 200 min| 400 min| /
Load 3 A| 8 min| 30 min| 120 min| 240 min| /
Load 5 A| 3 min| 15 min| 55 min| 100 min| /
Load 7.5 A| 2 min| 10 min| 30 min| 60 min| /
Load 10 A| No| 7 min| 20 min| 45 min| 20 h
Load 12 A| No| 3 min| 12 min| 30 min| 600 min
Load 15 A| No| No| 9 min| 20 min| 400 min
Load 20 A| No| No| 7 min| 13 min| 240 min
LAY-OUT AND CONNECTIONS
1 | Battery |
---|---|
2 | Load |
3 | Charging Current Limiter |
4 | Fault System |
5 | Mains-BackUp |
6 | Mains-BackUp LED |
7 | Fault LED |
8 | Diagnosis LED |
9 | Config/Start From Battery |
10 | Input Vac |
11 | Aux 1 (RJTemp) |
12 | Start From Battery (Connector) |
13 | Aux 2 |
14 | Aux 3 |
15 | Buffering Time |
16 | Bus Termination |
17 | 12/24 Output |
18 | Battery Config. |
19 | Battery Config, All device Functions |
20 | Aux 4 “Ethernet” |
21 | Network Communic. LED |
22 | ADELBus (CAN) |
23 | Rectifier Alarm |
24 | PE (Aux 4 screen) |
INPUT AND OUTPUT LOAD AND BATTERY CONNECTION
8.1.1 Input AC Port L – N:
No.10
Single phase Switching Power Supplies L, N, PE .
Size 2 and Size 3 BRIDGE ONLY for input 115 Vac, and connect L, N, PE .
8.1.2 Battery Connection Port:
No.1: Connect the battery between: terminal 3 (–) and 4 (+)
One battery (12 Vdc) for CBI12xx;
Two battery (12 Vdc) connected in Series for CBI24xx;
Four battery (12 Vdc) connected in Series for CBI48xx;
8.1.3 Output Load:
No.2:Connect this Output to the load, terminal 1 (–) and 2 (+).
8.2 SELECT OUTPUT VOLTAGE (ONLY SIZE4 CBI280)
No.17: Caution: Switch off the system before setting the Jumper. The Jumper is
detected at the device power-up only.
Output Voltage Selection| | Jumper
24V Output Voltage
---|---|---
Output Voltage Selection| | No Jumper
12V Output Voltage
DRIVE AND MONITORING
9.1 FAULT – STATUS CONDITIONS
9.2 ISOLATED RELAY (SIZE:1,2,3,4):
9.2.1 STATUS: Mains or Backup: Input Mains On/Off.
- No.5 Relay Contacts: 5, 6, 7
- No.6: Led
9.2.2 FAULT: Low Battery, Battery Replacement, Faulty Battery or Faulty System
- No.4 Relay Contacts: 8,9,10
- No.8: Led DIAGNOSIS: Diagnosis of the system through “blinking code” light signal
9.2.3 Back Up and Fault: Relay and LED Conditions
| Port N°5 – Led N°6 Mains/Back-Up| Port N°4 – Led N°7 Fault Battery
---|---|---
Relay:| | 5-6 Closed OK| 5-7 Closed| 8-9 Closed OK|
8-10 Closed
Mains Input Vac| ON| ■ – led off| | ■ – led off|
OFF| | ■ – led On (1)| ■ – led off|
Battery SOC less than 30%| YES| | ■ – led On| | ■ – led On (2)
NO| | ■ – led On| ■ – led off|
Battery or system Fault?| YES| ■ – led off| | | ■ – led On
NO| ■ – led off| | ■ – led off|
Note:
- Contact relay Mains/Back switch at least 5 seconds after disconnection of Power.
- See Diagnosis Led
9.2.4 Relay Contact Rating:
Max.DC1: 30 Vdc 1 A; AC1: 60 Vac 1A: Resistive load (EN 60947-4-1).Min.1mA at
5 Vdc: Min. permissive load
9.3 NOT ISOLATED OUTPUT (SIZE 5):
9.3.1 STATUS: Mains or Backup “Input Mains On/Off“.
- No.5 Output ON: open drain referred to Load negative terminal; requires an external DC power source (max 48Vdc) – drain current: 20 mA Nom ; 40 mA Max for 3 sec
- No.6: Led ON
9.3.2 FAULT 1: Low Battery, Battery Replacement, Faulty Battery or Faulty System
- No.4 Output ON: open drain referred to Load negative terminal; requires an external DC power source (max 48Vdc) –drain current: 20 mA Nom ; 40 mA Max for 3 sec
- No.8: Led DIAGNOSIS: Diagnosis of the system through “blinking code” light signal
9.3.3 FAULT 2: Rectifier Alarm
- No.4 Output ON: open drain referred to Load negative terminal; requires an external DC power source (max 48Vdc) – drain current: 20 mA Nom ; 40 mA Max for 3 sec
- No.8: Led DIAGNOSIS: Diagnosis of the system through “blinking code” light signal
9.4 CHARGING MODE STATUS
| Status| Diagnosis (No.8)| Fault
Battery (No.7)
---|---|---|---
Charging Type| Float| 1 Blink/2 sec| OFF
Absorption| 1 Blink/sec| OFF
Bulk| 2 Blink/sec| OFF
Recovery| 5 Blink/sec| OFF
9.5 FAULTY BATTERY / FAULTY SYSTEM
System Auto Diagnosis| Reverse polarity or high battery Voltage (over 32.5Vdc
for CBI 24xxA)| 1 Blink/pause | ON
---|---|---|---
Battery not connected| 2 Blink/pause | ON
Battery element in Short Circuit| 3 Blink/pause | ON
Overload or short circuit on the load| 4 Blink/pause | ON
Bad battery; Internal impedance Bad or Bad battery wire connection| 5
Blink/pause | ON
Life test not possible| 6 Blink/pause | ON
Rectifier Alarm| 7 Blink/pause | ON
Boost condition; battery discharge after 4 min. of overload.| 8 Blink/pause |
ON
Internal fault| 9 Blink/pause | ON
Low battery (under 18.5Vdc for CBI 24xxA) Only if started from battery, no
Mains input, from Jumper N°5 or Push Bottom| 10 Blink/pause | ON
Master-Slave connection lost between the master and slave on parallel
configuration, (AP device only 500W)| 11 Blink/pause | ON
Mains detector failure| 12 Blink/pause | ON
Bad battery wire connection; Parallel mode on Slave Device (AP device only
500W)| 13 Blink/pause | ON
Device over-termperature Alarm| 14 Blink/pause | ON
Boost condition; battery discharge after 4 min. of overload; Parallel mode on
Slave Device (AP device only 500W)| 15 Blink/pause | ON
Calibration error| 16 Blink/pause | ON
9.6 START FROM BATTERY ONLY, NO INPUT MAINS VAC
No. 9: Push-button, for 3 sec., in the front panel to switch ON the system
without the “Mains input Vac” but only the battery connected. (Not present in
CBI 2410XX and CBI 485XX) No.12 /Jumper n.5) has the same function of remote
start from battery, via RTCONN cable connected in the Push-button mounted on
front Panel of the external system. Standard function for all products, Size 2
only with code CBI2410A/S and CBI485A/S. Do not leave jumper in this position,
otherwise the system will discharge completely the battery. Only push button.
9.7 BUFFERING TIME SETTING
No.15: On Size 3 and Size 4 models it is possible to set a buffering time. The
desired value can be selected on the rotary switch 15. Buffering time is
initiated when the mains is switched OFF. The LOAD output will be ON for the
selected time.
Switch position | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
---|---|---|---|---|---|---|---|---|---|---|
Buffering Time (min.) | ∞ | 0.5 | 2 | 5 | 10 | 15 | 20 | 30 | 45 | 60 |
If the switch is in position 0, the LOAD output will be in ON state until the
battery is completed discharged.
In any case, to prevent damage the unit disconnects the batteries when a
minimum voltage level is reached.
The LOAD output will be in ON state until the battery it is completed
discharged.
For Size 1 and 2 units it is possible to request factory customized versions
with specific buffering time setting, choosing the extension CBIxxxxASDx.
For Size 5 units please refere to section 9.
BATTERY CARE
The Battery Care philosophy is based on algorithms that implement rapid and
automatic charging, battery charge optimization during time, flat batteries
recovery and real time diagnostic during installation and operation. Elements
in short circuit, accidental reverse polarity connection, disconnection of the
battery, can easily be detected and removed by help of Blink Code of Diagnosis
Led, during the installation and after sale. Each device is suited for all
battery types, it is possible setting predefined curves for Open Lead Acid,
Sealed Lead Acid, Gel, Ni-Cd, Li-Ion. They guarantee battery reliability in
time by continuously testing the internal impedance status, avoiding any
possible risk of damage and granting a permanent, reliable and safe connection
of the battery to the power supply. The system is able, through a battery
stimulation circuit with algorithms of evaluation of the detected parameter,
to recognize sulphated batteries or batteries with a short-circuited element.
Battery Test: Automatic. Every 60 sec. battery connection check. Every 220
minutes in Float charge, battery efficiency test. Battery Faults can be
monitored by relay and led blinking.
10.1 BATTERY CHARGE IN TEMPERATURE COMPENSATED ENVIRONMENT
No. 11 Remove the window label to find the connector: Auxiliary Output “AUX 1”
It is possible to connect the Temperature sensor probe and apply it on the
battery.The function of the probe is for temperature battery compensation.
With this it is possible to meet the requirements of the EN54- fire
certification. 10.1.1
Battery Temperature Compensation Charge (not for LI-ion)
Connecting the cable RJTEMP (supplied separately) to Auxiliary Output AUX1,
the CBI will adjust the battery charging voltage in relation to the Battery
temperature :
Fast Charge: Open Lead, AGM, Gel | Float charge: Open Lead, AGM, Gel |
---|
+/- 5mV/°C x n. of Cells from -8°C to +60°C
+140 ÷ -200 mV/Cell compared to the value at 20°C| +/- 3mV/°C x n. of Cells
from -20°C to +60°C
+120 ÷ -120 mV/Cell compared to the value at 20°C
Fast Charge: Ni-Cd| Float charge: Ni-Cd
+/- 2.5 mV/°C x n. of Cells from -20°C to +60°C
+100 ÷ -100 mV/Cell compared to the value at 20°C| +/- 2.5 mV/°C x n. of Cells
from -20°C to +60°C
+100 ÷ -100 mV/Cell compared to the value at 20°C
10.2 CHARGING CURRENT LIMITER:
No.3 In order to protect the battery from excessive charging currents, the
device allows to limit the maximum charge current by adjusting the trimmer
from 20% (Size 1, 2, 5) or 10% (Size 3, 4) to 100% of the rated current. To
determine the maximum battery charge current, see the battery manufacturer’s
Data Sheet or, if not available, consider that typically the maximum charge
current is 10% of Ah’s rated battery current, for both Lead Acid Li-ion and
NiCd batteries.
10.3 BATTERY MANAGEMENT CONFIGURATIONS
Completely automatic, all devices are suitable to charge most batteries
types thank to User Selectable charging curves. They can charge open lead
acid, sealed lead acid, Gel, Ni-Cd and Li-Ion. It is possible to change or add
other charging curves connecting the device to a DPY351 or ADELViewSystem.
10.3.1 Battery Management Configurations (Sizes 1, 2, 3, 4)
No.18 Preliminary Operations: One device for all battery types.
Caution: Switch off the system before Setting the jumper. Only jumper in
position 6 is Refreshed also with power ON.
10.3.2 Battery Management Configurations (Size 5: CBI60)
Note: it is also possible to configure the device via Webserver (section 13).
In normal operation the LED bargraph (No.19 in sect.7) gives an indication of
the current (0 to 100% of In) as follows:
– In charge mode with mains: battery charge current with solid light
– In backup mode without mains: battery discharge current with blinking light
– In boost mode with mains: battery discharge current with flickering light
To display the current device configuration on the LED bargraph press the
Config/Start button (No.9 in sect.7) briefly (< 1 sec). The display returns to
normal operation after 10 seconds. Please refer to the pictures at the end of
this section.
To change the device configuration complete the procedure below (note: if the procedure is not completed no settings are saved; the procedure is aborted is no command is given for 60s).
-
* With battery disconnected:
▪ press the Config/Start button (No.9 in sect.7) for more than 2 seconds, until the first led starts blinking
▪ press briefly the button to cycle through the battery types as shown by LEDs 1,2,3 (please refer to the pictures at the end of this section) then confirm with a long press until the 4 th LED starts blinking
▪ LED 4: Config Mode: ON/OFF -
Long press to enable all other configurations via Web Server and ADELViewSystem (Led ON).
-
Short press to configure all parameters from Device only (Led OFF)
▪ If Config Mode was selected, the procedure terminates here
▪ LED 5: Option: not used: continue with a short-press
▪ LED 6: Life Test; long press to enable the function (Led ON), short press to disable
▪ LED 7: Fast Charge; long press to enable the function (Led ON), short press to disable
▪ LED 8: UPS Disable; long press to disable the UPS function (Led ON), short press tom keep it enabled
▪ LED 9: Buffering time: press briefly the button to select the max backup duration, then
confirm with a long press. The current selection is shown with other LEDs blinking together with LED 9 as follows: -
Led 1: 30 sec; Led 2: 120 sec; Led 3: 300 sec; Led 4: 10 min; Led 5: 15 min; Led 6: 20 min; Led 7: 30 min; Led 8: 45 min; All leds: Infinite time
-
Note: the last selection (infinite time) is confirmed automatically also with a short press
-
More values can be selected by with DPY351 or ADELVIEWSystem
▪ End Programming: the device show the selected configuration for 10 seconds then resumes normal operation,- With battery connected:
▪ press the Config/Start button (No.9 in sect.7) for more than 2 seconds, until the 5th led starts blinking
▪ follow the procedure above from step “LED 5: Option” (Battery Type and Config Mode can be changed only when the battery is not connected).
- With battery connected:
Note:
-
Do not leave the jumper in position 5 (Size 1, 3) or position 6 (Size 2) or Battery Start (Size 4); otherwise, in Backup mode the battery is discharged completely close to zero.
For Size 2 CBI2410A/S or CBI485A/S are required (/S means start with battery functions, otherwise only start with Input Mains) -
For the CBI2420A, CBI1235A, CBI4810A, CBI size1 SDXX, CBI size2 SDXX, the function “fast charge” is replaced by “UPS disable”:
o Contact closed: back-up (UPS) enabled. The System shuts down after xx min., depending on the Buffering time selected.
For devices CBI size1 SDXX, CBI size2 SDXX, depends on time minutes required in SD version. To maintain the contact always closed insert the jumper permanently.
o Contact open: Inhibit backup function. No UPS enabled.
o Fot CBI2420A, CBI1235A, CBI4810A: the function is not enabled if Time Buffering is in position Zero. In position Zero, the jumper Fast is enabled otherwise the function is “UPS disable”.
o In the CBI size1 SDXX, CBI size2 SDXX,: the Jumper Fast, it is always enabled -
Jumper present in Fast Charge means also that every 288h, the device goes in “Cycling Refresh
Charging”. This mode continues for 85 minutes at the same voltage condition: e.g. 2.4V/Cell for Lead Acid Batteries. -
The Li-Ion curve is available starting from release: Size1:12Vdc Output: S13 R6; 24Vdc Output: S13
R7 Size2: 24Vdc Output: S92 R3 Size3:12Vdc, 24Vdc, 48Vdc Output: S40 R13 Size4: S130 R5 -
With this selection it is possible to change the parameters of the selected chemistry.
a. First, select the battery chemistry
b. Select “Config Mode”.
c. Change the parameters with DPY351 or ADELVIEWSystem. After update, it is possible to disconnect the programmer and use the device as standalone device.
d. If “Config Mode” is disable, all parameters are reset to their default values for the selected chemistry
e. In “Config mode”: it is possible to change the Float voltage and the Bulk voltage. To change the Bulk Voltage you have to modify the Holding register 40073 Bulk and 40077 Absorption.
f. In “Config Mode”, the Jumper Size3 or Switch Size4 for Fast Charge loses his function. All functions are driven from the Holding Register settings.
10.4 DIAGNOSTIC AND CONTROLS
All CBI devices support the user during installation and operation. A Blink
code of Diagnosis Led allows to discriminate among various possible faults.
Error conditions, “LED Battery Fault” ON and “LED Diagnosis” blinking with
sequence; see Display Signal section.
- Check for accidental disconnection of the battery cables and immediately switch off the output power.
- Battery not connected: If the battery is not connected the device provides alarm within 10 sec.
- Test of quality wire connections: During Float charge the quality (resistance) on the battery connection is checked every 60 sec. This to detect if the cable connection has been properly made.
- Battery in Open Circuit or Sulphated: In Float charging mode, the All In One performs internal impedance test every 220 minutes.
- Reverse Polarity check: If the battery is connected with inverted polarity, the All In One is automatically protected.
- Test of battery voltage connections: Appropriate voltage check, to prevent connection of wrong battery types, above or below nominal voltage.
- End of Charge check : When the battery is fully charged, the device automatically switches in Float charging mode.
- Check for Battery Cells in short circuit: thanks to specific algorithms of evaluation, the Alle In One recognizes batteries with shorted cells. In Float charge every 220 minutes a short-circuit test is carried out.
10.5 PROTECTION FEATURES
- On the primary side: the device is equipped whit an internally fuse. If the internal fuse is blown, most likely there is a fault in the device. In that case, the device must be returned to factory for repair.
- On the secondary side Battery and load: The device is electrically protected against short circuits and overload.
- Polarity Inversion: the module is automatically protected against inversion of battery polarity.
- Over current and output short circuit: the unit limits the output current (see the technical data).
- Deep discharge: not possible. The unit disconnects the battery when a minimum voltage level is reached.
10.6 CHARGING CURVE
Automatic multi-stage operation and real time diagnostic allows fast recharge
and recovery of deep discharged batteries, adding value and reliability to the
system hosting the CBI device. The type of charging is Voltages stabilized and
Current stabilized IUoU. Five charging phases are identified by a flashing
code on a Diagnosis LED. To maintain the Output Load close to the nominal
voltage (12, 24, 48), don’t insert jumper in position 6 to disable fast
charge. Fast Charge means also that every 288h, the device goes in “Cycling
Refresh Charging” for 85 minutes at 2.4V/Cell.
10.7 THERMAL BEHAVIOUR
Surrounding air temperature 50°C. For ambient temperature above 50°C, the
output current must be reduced by 2.5% per °C. Max 70°C At the temperature of
70°C the output current will be 50% of In. The equipment does not switch off
in case of ambient temperature above 70°C or thermal overload. The devices are
protected for Over temperature conditions “worst case”; in this situation the
device shuts down the output and automatically restarts when the inner
temperature falls within limit.
MODBUS (SIZE 3 – 4)
Some devices are fitted with a Modbus “RTU” communication protocol port;
Modbus requires that only one device be the Master, all other devices must be
slave.
Hardware interface: RS485.
11.1 ELECTRICAL CHARACTERISTICS
The unit is a SLAVE in a MODBUS network, with the following specifications:
Transmission mode: | MODBUS RTU |
---|---|
Electrical Interface: | RS485 half-duplex serial line |
Baud rate: | 4800 / 9600 / 19200 / 38400 (default) bps |
Data format: | 8 data bits |
Parity: | even (default) / odd / none |
Stop bits: | 1 (parity odd or even) / 1 or 2 selectable (parity none) |
Slave address: | configurable in the range 1 (default) to 247 |
Connector type: | RJ45 |
Cable: | wire RJ-45 plug |
| Size3 – 4
---|---
Connector name| AUX2 – AUX3
Pinout (see fig. above)| A = pin 5, B = pin 4, Common = pin 3
11.2 HOW TO CONNECT THE DEVICE TO MODBUS
11.2.1 Daisy Chain general connection Diagram
To connect the device to Modbus, please use AUX2 and AUX3 Port.
- Port: AUX 2 No. 13 is Present only in Sizes 3 and Sizes 4, MODBUS connection via RJ45 connector.
- Port: AUX 3 No. 14 Present only in Size 4. The function is the same of Auxiliary Output “AUX 2”
11.2.2 Connection Diagram Size3 and 4
- RJCONN45: normal RJ45 cable also provided by ADELSystem. It is possible to connect in daisy chain up to 32 devices, max distance 1000m, from the Output AUX2 and Aux3.
- In the connection scheme shown above, each slave device must have a unique Modbus device address for proper communication. In order to avoid signal noise, the use of line termination resistors (120 Ohm) is recommended. The effect of signal noise becomes more relevant with long cable length and/or high baud rates. The serial Modbus connection uses an RS485 port for connection between the master port and the corresponding interfaces of the slave according to the EIA/TIA RS485 standard.
- RJUSB280: cable interface RS485 – USB, max length 2m, for connection to PC
- Note: If both, DPY351 and ADELViewSystem, are running in the same network at the same time, The DPY351 must by set in Modbus “Viewmode”.
- RJ45COUPLER: is a T connection RJ45 for daisy Chain with CBI Size3 and 4
11.2.3 Bus Termination (Size 3)
The fail safe and Line termination resisteo for the RS-485 bus, are not
provided inside the device and must be installed externally, if necessary,
according to the following scheme.
Fail-safe:
-
560 Ohm (Pull Up) to 5 V: Not Present
-
560 Ohm (Pull Down) to common: Not Present
Load Terminations: -
120 Ohm (LT) between lines A – B: Not Present
11.2.4 Bus Termination (Size 4)
No.16: The Size 4 device includes a full “fail safe” polarization and the bus
termination. In the CBI2801224A the fail safe function and line terminators
can be individually enabled or disabled by means of the dipswitches located on
its front panel, as shown in the following figure:
Fail-safe:
- Fail Safe A, 560 Ohm (Pull Up) to 5 V
- Fail Safe B, 560 Ohm (Pull Down) to 0 V
- Terminations: 120 Ohm (between Modbus lines)
- Terminations: 120 Ohm (between Can lines)
11.3 HOW TO CONFIGURE MODBUS
AUX2 and AUX3 ports, are provided for the connection to an external device
like: RTU, PC , DPY351.
- For the connection to RTU, PLC or similar devices, refer to the instruction manuals “Modbus specifications” available in the Web Site: www.adelsystem.com
- For configuration and monitoring of the parameters inside the devices, download and install “ADELViewSystem” from the Web Site: www.adelsystem.com.
- Download the Modbus table from Web Site: www.adelsystem.com, section Additional Data, with details About all dataand parameters exchanged betwin a CBI and a Master Device.
- For the Monitoring and Configurations of one or more ADELSystem devices from enduser friendly , please use the Plug and Play unit DPY351.
- For all details of Modbus configuration refer to the instruction manuals “Modbus specifications” available from the Web Site: www.adelsystem.com, section Additional Data.
ADELBUS CONNECTIONS
ADELBus is the ADELSystem network to interconnect devices via Modbus and
CANBUS protocols.
ADELBus is used as power management system for all connected equipment, such
as the DC-Ups, Battery Charger, Power Supply.
Every compatible device with
ADELBus is equipped with one or two data ports.
The devices are simply chained together, forming a local data network.
Monitoring panels such as the DPY351 can be used for monitoring and
controlling all connected ADELBus equipment.
12.1 EVENT BASED COMMANDS
With the ADELBus, a device can be programmed to initiate an action on another
connected device. This is done by means of event-based commands.
12.2 HOW TO SET UP AN ADELBUS NETWORK
Connections between the devices are made by standard straight ADELBus cables.
ADELSystem can supply these cables. These (CAT5) cables are also commonly
available at computer supply stores. Twisted pair cable with shield is
recommended for CAN connection in noisy environment.
Up to 32 ADELBus devices can be connected together.
The power for the network can be provided directly to the connected devices
through the ADELBus cable.
Otherwise, if that is not sufficient, it is necessary to connect the device by
the + and – terminals of connector 1 .
12.3 HOW TO SET ADELBUS NETWORK WITH MORE THAN ONE DPY351 (MODBUS VIEW
MODE)
In a Modbus network there can only be one master. Normally the DPY351 is the
master, it polls the network and it receives information from other ADELSystem
devices, which are the slaves. If it is necessary to connect N DPY351 in the
same ADELBus network, then N-1 displays shall be configured in View Mode. In
this case only one DPY351 is a master and it polls the devices, the other
DPY351s receive the data from the Bus and they take the information into
consideration only if these parameters are originated from a device in their
list, otherwise they ignore the information.
View Mode is useful also when the master of the network is an external device
such as a PC, but there is the need to monitor the status of the network from
other places.
To configure the DPY351 in View Mode it is necessary to go in:
Menu>Menu Config>Other Settings>Modbus View Mode.
ETHERNET CONFIGURATION
Configuration of the Ethernet interface by HTTP server via the Web browser:
13.1 CONNECT HTTP SERVER FOR THE FIRST TIME
Connect the deviceto the network with a standard CAT5e or better LAN cable
plugged in to the Aux4 connector (RJ45) on the bottom of the unit, as shown in
section 7 drawing Size5. The CBI60 is factoryconfigured to operate with a
fixed IP address (192.168.1.100) on the standard HTTP port (number 80).
A different static IP address can be assigned to the CBI60 or a dynamic IP
address can be assigned using the DHCP protocol. The network configuration can
be carried out using the internal webserver. Type the IP address of the CBI60
into any browser’s address bar (as an example “192.168.1.100”) then the login
page appears requesting the username and the password .
To access the internal webserver, at the login page, the following credentials
must be used:
Username: admin
Password: admin
Note: after 20 minutes of inacticity the login credentials must be entered
again.
13.1.1 Customizing the ethernet interface and services
In the main page, the following groups of parameters and other information are
displayed:
- Account
- TCP/IP Configuration
- SNMP
- Device status
- Device settings
- Systen information
13.1.2 Account:
The Account group (Fig. 6) allows the customization of the data for the HTTP
server login page. Any changes must be confirmed with the “Apply” button at
the bottom of the page. 13.1.3 TCP/IP Configuration
Fig. 7 shows the TCP/IP Configuration group with parameter default values.
They allow unique identification of the unit in the network. If “Dynamic (DHCP)” is selected,
the IP address is automatically assigned by a DHCP server, that must be active
on the network; in this case the System IP, Subnet Mask and Gateway textboxes
show the assigned values and are not editable.
HTTP Port allows redirecting the HTTP traffic to a port different than the
standard HTTP port 80. In that case, access to the HTTP server from a browser
must be made using the syntax http://ipaddress.portnumber.
As an example, if the IP address is 192.168.1.100 and the selected HTTP port
is 5678 then the following IP string should be entered in the browser
http://192.168.1.100:5678.
The CBI60 supports access using the Virtual LAN protocol. In the case “VLAN
ID” checkbox is not selected the CBI60 will not operate in the VLAN. If “VLAN
ID” checkbox is selected then a “VLAN ID” textbox will appear and should be
populated with an ID in the range 1 thru 4094, matching the one of the VLAN
the unit is operating in.
Any changes must be confirmed with the “Apply” button at the bottom of the
page.
13.1.4 SNMP
The CBI60 can act as SNMP manager. An ADELsystem MIB table file is provided
which consists of a list of parameters that can be remotely read, or read-
written through the SNMP protocol. Each parameter (OID) is mapped one-to-one
to a Modbus RTU holding register. Refer to the document “Adelsystem parameter
table” for the description of each parameter and the corresponding OID for the
SNMP.
All the
fields in the SNMP group of settings allow a maximum of 31 characters, except
“System Description” and “System Location”, which allow 255 characters
maximum. The “Read-only community” and “Read-write community” values must
match those of the SNMP environment the unit operates in, otherwise the device
management using SNMP will not be possible.
Any changes must be confirmed with the “Apply” button at the bottom of the
page.
13.1.5 Device status
This group shows the main operating parameters of the device. 13.1.6 Device settings
This group replicates the settings also accessible on the CBI60 front panel by
pressing the CONFIG button (refer to section 10.3.2of this manual). Any
changes must be confirmed with the “Apply” button at the bottom of the page.
“Battery type” selects the battery chemistry from a drop-down list.
If “Configuration mode” is selected Led 4 ON, the following parameters
(Lifetest, Fast charge, UPS enable and Buffering time) cannot be changed as
they are controlled remotely via Modbus or SNMP.
If “Configuration mode” is not selected Led 4 OFF, the following settings are
available: “Lifetest”, “Fast charge”, “UPS disable” and “Buffering time”.
The following information “Charging current limiter” is read-only and
corresponds to the position of the charging current limiting trimmer on the
front panel (see sectgion: 10.2).
Finally the “Reset” button allows to reboot the device remotely, only if no
battery connected. Current settings will be maintained. Any changes not saved
with the “Apply” button will be lost. 13.1.7 System information
This group shows detailed information on device and the installed software
components, to be communicated to the service technician if requested. Fig. 10
shows example information: the actual values may be different.
The “Update” button allows to update the application software. Only valid
software images for the CBI60 will be accepted. Update is only possible when
the device is powered from mains. 13.1.8 Saving the customized parameters
To save the changes into the CBI60 non volatile memory press the “Apply”
button at the bottom of the page.
13.2 HOW TO PUT INTO DEFAULT VALUES THE DEVICE (CUSTOMER SERVICE)
13.2.1 Resetting the customized parameters to their default values
In case the login user name or password was forgotten, or the TCP/IP
configuration was set incorrectly and the device is no longer reachable,
please follow this procedure to restore the default settings:
- Turn OFF the device
- Press the CONFIG button on the front panel and keep it pressed
- Turn ON the device and continue to keep the button pressed (all the 9 configuration LEDs will stay ON during this time)
- After 5 seconds the 4 top configuration LEDs (n. 6 to 9) will blink alternatively in pairs and the LED 1 will blink slowly showing “Option 1”
- Release the button
- Now click briefly on the button to select one of 4 options, as shown by the config LEDs 1 to 4. The options are:
- 1: forces Dynamic (DHCP) IP Addressing Mode (DHCP) until reboot; the TCP/IP configuration must be changed on the HTTP server in order to make this setting permanent.
- 2: system recovery application, only to be used if instructed by customer service
- 3: restore login credentials, TCP/IP and SNMP settings to factory default
- 4: restore the complete device to factory settings – WARNING: all user’s settings and logs will be lost, including the battery type selection.
Confirm the choice by keeping the CONFIG button pressed for 5 seconds until LEDs 6 to 9 stop blinking.
PC SHUTDOWN
For the Shutdown PC please refer to the special White Paper in the Web Site
STANDARD AND CERTIFICATIONS
15.1.1 Electrical Safety for Mounting:
Device assembling: UL508, IEC/EN 60950 (VDE 0805) and EN 50178 (VDE 0160).
Installation: IEC/EN 60950. Input / Output separation: SELV EN 60950-1 and
PELV EN 60204-1. Double or reinforced insulation. Safety of Electrical
Equipment Machines: EN 60204-1.
according to EMC 2014/30/UE and Low voltage directive 2014/35/UE
15.1.2 Safety Standards:
EN IEC 62368-1: 2014/AC:2015
15.1.3 EMC Standards Immunity:
EN 61000-4-2, EN 61000-4-3, EN 61000-6-2, EN 61000-4-4, EN 61000-4-5.
15.1.4 EMC Standards Emission:
EN 61000-6-4, EN 61000-6-3, EN 61000-3-2 (see data sheet for each device)
15.1.5 Conformity to:
EN60950/UL60950-1 and CSA C22.2 No. 60950-1-07 (Information Technology
Equipment) – Safety –
Part1: General Requirement.
Device is intended to be installed in a cabinet protected from external shocks
or damages.
Electrical safety EN54-4 Fire Detection and fire alarm systems
DIN41772: Charging curve; DIN41773: Characteristic Curve for charging Lead
Acid and Nickel-Cadmium batteries.
15.1.6 Approvals:
Devices, CBI243A, CBI245A, CBI123A, CBI126A, CBI1210A,CBI2410A and \S, CBI485A
and \S, CBI1235A, CBI2420A, CBI4810A
EN60950 / UL60950-1 and CSA C22.2 No. 60950-1-07 (Information Technology
Equipment) – Safety –
Part1: General Requirement.
DIN RAIL MOUNTING:
**** All modules must have a minimum vertical and horizontal distance of 10 cm to this power supply in order to guarantee sufficient auto convection. Depending on the ambient temperature and load of the device, the temperature of the housing can become very high.
TECHNICAL DATA
For all technical data, please download the data sheet on the relevant Website for the specific Product
BATTERY BANK
18.1 BATTERY BANK 12V
- BATT 123: Battery Bank 1 Battery+Enclosure
- BATT 123DIN: Battery Bank 1 Battery+Enclosure DIN
- BATT 127: Battery Bank 1 Battery+Enclosure
- BATT 127DIN:Battery Bank 1 Battery+Enclosure DIN
- BATT 1212: Battery Bank 1 Battery+Enclosure
18.2 BATTERY BANK 24V
- BAT1.2VRLA: Battery Bank 2 Batteries+Enclosure DIN
- BAT3.4VRLA: Battery Bank 2 Batteries+Enclosure DIN
- BAT7.2VRLA: Battery Bank 2 Batteries+Enclosure DIN
- BAT12VRLA: Battery Bank 2 Batteries+Enclosure
- BTH1.2VRLA: Battery Bank Enclosure No Battery DIN
- BTH3.4VRLA: Battery Bank Enclosure No Battery DIN
- BTH7.2VRLA: Battery Bank Enclosure No Battery DIN
- BTH12VRLA: Battery Bank Enclosure No Battery
ACCESSORIES
19.1 DIGITAL CABLE
- RJTB500
- RJ45COUPLER
- DPYCONN500
- RJCONN45
- RJUSB500
- RJUSB280
- RJUSBSD
19.2 TEMPERATURE SENSORS
- RJTEMP451
- RJTEMP453
- RJTEMP111
- RJTEMP113
19.3 CABLE CONNECTORS
- RTCONN
19.4 REDUNDANCY
- MR220 DECOUPLER
MONITOR & CONTROL
20.1.1 DPY351 CONTROL PANEL
20.1.2 DPY353 DISPLAY PANEL
20.1.3 DPY354 “ADELVIEW SYSTEM” PC SOFTWARE