ADELSYSTEM HELIOS CB Series Smart Battery Charger Instruction Manual
- June 13, 2024
- ADELSYSTEM
Table of Contents
ADELSYSTEM HELIOS CB Series Smart Battery Charger Instruction Manual
Product Using Instruction
Thank you for having chosen one of our products for your work.
We are certain that it will give the utmost satisfaction and be a notable help
on the job.
General Description
The CB series is a “Switching technology” and “Battery Care philosophy” since many years parts of the know-how ADEL system, led to the development of this advanced multi-stage battery charging, completely automatic and suited to meet the most advanced requirements of battery manufacturers. The Battery Care concept is based on algorithms that implement rapid and automatic cycle of battery charging, battery charge optimization during time, flat batteries recovery and real time diagnostic during installation and operation. The Real Time Auto-diagnostic system, monitoring battery faults such as, elements in short circuit, accidental reverse polarity connection, disconnection of the battery, they can easily be detected and removed by help of Blink Code of Diagnosis Led; during the installation and after sell. Each device is suited for all battery types, jumper selection sets a predefined curves for: Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd and Niamh. A rugged casing with bracket for DIN rail mounting provide IP20 protection degree. Only for CB1224xAJ it is available the CAN output, according to the J1939 protocol to connect the device to other electronic units.
Main Characteristics
-
Input: Single-phase 115 – 230 – 277 Vac
-
Output Battery: 24 Vdc 5 A; 12 Vdc 6 A
CAN output according to the J1939 (only CB1224xAJ model) -
Suited for the following battery types: Open Lead Acid, Sealed Lead Acid, lead Gel and Ni-Cd.
-
Automatic diagnostic of battery status. Charging curve IUoUo, constant voltage and constant current Battery Life Test function (Battery Care)
-
Switching technology
-
Four charging levels: Boost, Absorption, Float and Recovery
-
Protected against short circuit, Over Load and inverted polarity
-
Signal output (contact free) for discharged or damaged battery
-
Protection degree IP20 – DIN rail; Space saving
Safety and warning notes
WARNING – Explosion Hazard Do not disconnect Equipment unless power has
been switched off or the area is known to be non-hazardous.
WARNING – Explosion Hazard. Substitution of components may impair
suitability for class I, Division 2.
WARNING – Switch off the system before connecting the module. Never work
on the machine when it is live. The device must be installed in according to
UL508. The device must have a suitable isolating facility outside the power
supply unit, via which can be switched to idle. Danger of fatal Injury!
Connection (terminal and wiring):
Cable Connection: The following cable cross-sections may be used:
| Solid (mm2 )| Stranded (mm2 )| AWG| Torque (Nm)| Stripping Length| 1 Phase L
N PE Input AC| 1 Phase L N PE Input AC
---|---|---|---|---|---|---|---
In:| 0.2 – 2.5| 0.2 – 2.5| 24 – 14| 0.5 – 0.6 Nm| 7 mm| |
Out:| 0.2 – 2.5| 0.2 – 2.5| 24 – 14| 0.5 – 0.6 Nm| 7 mm
Signal:| 0.2 – 2.5| 0.2 – 2.5| 24 – 14| 0.5 – 0.6 Nm| 7 mm
CANBUS L| 0.2 – 1.5| 0.2 – 1.5| 24 – 16| 0.25 Nm| 7 mm
CANBUS H| 0.2 – 1.5| 0.2 – 1.5| 24 – 16| 0.25 Nm| 7 mm
Use only copper cables that are designed for operating temperatures of > 75 °C. Wiring terminal shall be marked to indicate the proper connection for the power supply.
Output Power connections:
**Normal connection
Typical application:**
- One battery (12Vdc) for 12 Vdc Output Set No Jumper in Pos.5
- Two battery (12Vdc) for 24 Vdc Output Set Jumper in Pos. 5 (See the table below at the point No. 2.)
Operating and Display Element:
**
CB12245A
CB12245AJ**
No. 1: Input AC Port pin. L – N:
1 Phase Switching Power Supplies L, N, PE .
No. 2: Battery Management Configurations
Preliminary Operations: One device for all battery types.
Completely automatic, all devices are suitable to charge most batteries types
thank to User Selectable charging curves. They can charge open lead acid,
sealed lead acid, Gel and Ni-Cd batteries. It is possible to change or add
other charging curves connecting the device to a portable PC.
Caution: Switch off the system before setting the jumper.
Battery Type Selection| Jumper Position| Float charge
(Volt/Cell)| Fast/Bulk charge (Volt/Cell)
---|---|---|---
Open Lead| | 2.23| 2.40
Sealed Lead Low| | 2.25| 2.40
Gel Battery| | 2.30| 2.40
NiCd – NiMh| | 1.40 – (12V) 10cells 1.40 – (24V) 20cells| 1.50 – (12V) 10cells
1.50 – (24V) 20cells
Li-Ion (Only CB12245AJ)| | 3.45 (12V:4 cells) (24V:8 cells)| 3.65 (12V:4
cells) (24V:8 cells)
CEC (In conformity| | 2.23| 2.40
to Californian Rule)| improve the Energy Efficiency Compliant to: California
Code of Regulations, Title 20, Division 2, Chapter 4, Article 4. Appliance
Efficiency Regulations, Sections 1601 through 1609 Alarm Relay it is driven
for only 5 sec. when happen an Alarm 3-4 Closed Alarm Relay it is driven only
for 5 sec. when happen an Alarm; contact 3-4 closed.
Functional Setting| | Function|
Jumper Fast Charge Enable| | Jumper present: Fast charge enabled. This
function is a hot swap (is possible to enable or disable with mains on).
Output Voltage Configuration (Pos. 5)| 5| Jumper Not Present:| 12 V
Output
24 V Output
Power Supply Function (Pos. 6)| 6| Jumper Present: Power supply function
enabled.|
No. 3: Signal Ports (output Isolated):
Connections for Fault Alarm Relay: Low Battery, Fault connections
systems, Battery replacement. Contact: 3,4,5
Relay Contact Rating:
Max.DC1: 30 Vdc 1A; AC1: 60 Vac 1A: Resistive load (EN 60947-4-1)
Min.1mA at 5Vdc: Min. permissive load
Signal Output port true table: | Led N°8 Battery Fault |
---|---|
Battery or system Fault? | YES |
NO | – led off 3-4 Closed |
Battery or system Fault?(In conformity to Californian Rule) jumper 1-3 ON | |
YES | – led off 3-4 Closed (only for 5 sec.) |
NOTE: (*) In Recovery the LED Battery Fault (No.8) is OFF but the Relay
is in failure mode (3-5 Closed) to indicate a battery with very low voltage.
No. 4: Battery Connection Port:
Connect the battery between pin. 1 (+) and 2 (–).
One battery 12 V for 12 Vdc Output;
Two battery 12 V for 24 Vdc Output;
No. 5: Output Voltage Configuration
The device can work at 12Vdc or at 24Vdc setting a jumper. This setting must
be do with mains off. This jumper set the voltage of the batteries connected
at the CB, is most important to check the correct voltage value on the
batteries.
If is connected a wrong battery the device show the fault indication of 1
blink.
No. 6: Enable Power Supply
This function allow the Battery Charger to function like a Power Supply. To
enable this function the operator must insert a jumper in Pos. 6 Enable Power
Supply with the CB unpowered. When the device is turned ON we will have
voltage to the output terminals OUTPUT BATTERY even if the battery is not
present. After about 10 sec. without detecting a battery, the CB signals with
2 blink the status of “Battery Not Connected” and switches the alarm relay. If
the battery was already present at power on or if it is connected at a later
time, the CB detects the battery and starts to charge. If there is no fault
deactivates, the alarm relay and the LED DIAGNOSIS indicate the charging
status.
In Back Up (no Mains) and cell voltage < 2.18V (Pb batteries) or < 1.37V (NiCd
batteries) for more than 30 sec. the device turns off completely.
No. 7 and 8 Display Signals
No.8: Led Battery Fault connections systems, Battery Fault
No.7: Led Diagnosis. Diagnosis of the system through “blinking code”
signal
Auto diagnosis of the system Reverse polarity or wrong battery voltage (for
example: CB set for 24Vdc and battery 12Vdc)
Monitoring Control Chart:| State| LED Diagnosis (No.7)|
LED Battery Fault (No.8)
---|---|---|---
Charging Type| Float| 1 Blink/ 2 sec| OFF
Absorption| 1 Blink/sec| OFF
Bulk| 2 Blink/sec| OFF
Recovery (*)| 5 Blink/sec| OFF
1 Blink/pause
| ON
Battery Not connected| 2 Blink/pause
| ON
Element in Short Circuit| 3 Blink/pause
| ON
Over Load or Short Circuit on the load (with Enable Power Supply)| 4
Blink/pause
| ON
Alarm Low Battery Voltage: 12Vdc, range 8-10 Vdc| 9 Blink/pause
| ON
Wrong Battery selection| 10 Blink/pause
| ON
NOTE: (*) In Recovery the LED Battery Fault (No.8) is OFF but the Relays
is in failure mode (3-5 Closed) to indicate a battery with very low voltage.
No. 9: Charging Level Current:
It is possible set the max recharging current for the batteries by trimmer
(Charging Level).
The current adjustment goes from 10% ÷ 100% of In. Set the maximum charging
current between 10% and 20% of the battery capacity.
No. 10: CAN output:
The CAN protocol is defined as the set of rules for transmitting and receiving
messages in a network of electronic devices. The CAN bus has a high error
identification capability, reducing the probability of receiving a wrong
message to almost zero. The CAN bus is based on two lines, called H and L
(high and low), that work in differential mode effectively canceling the
common mode noise.
The bus line termination network must be added depending on the system design,
as the device does not include one. Of the several protocols based on CAN bus,
the CB12245AJ implements SAE J1939 as detailed in the document
“ADELSYSTEM_J1939_specification_R2” and the product specific parameter map,
that can be downloaded from www.adelsystem.com
or requested from the Adelsystem Customer Support service.
Charging Curve
Automatic multi-stage operation and real time diagnostic allows fast recharge
and recovery of deep discharged batteries, adding value and reliability to the
system hosting the CB device. The type of charging is Voltages stabilized and
Current stabilized IUoUo.
Four charging modes are identified by a flashing code on a Diagnosis LED.
To maintain the Output Load in lower Voltage state, do not put jumper in
position 4, in this case no boost charge but only Float charge.
| State| Diagnosis LED| Battery Fault LED| Time for
CB1224xA| Time for CB1224xAJ
---|---|---|---|---|---
Charging Type| Float| 1 Blink/ 2sec| OFF| –| 288h max
Absorption| 1 Blink/sec| OFF| 5h max| 4h max (8h for NiCd)
Bulk| 2 Blink/sec| OFF| 15h max (8 for NiCd)| 15h max
Recovery| 5 Blink/sec| OFF| 60sec| 240h max
**CB1224xA-CB1224xAJ Charging Diagram
Battery Care** The Battery Care philosophy is base on algorithms that
implement rapid and automatic charging, battery charge optimization during
time, flat batteries recovery and real time diagnostic during installation and
operation. The Real Time Auto-diagnostic system, monitoring battery faults
such as, elements in short circuit, accidental reverse polarity connection,
disconnection of the battery, they can easily be detected and removed by help
of Blink Code of Diagnosis Led; during the installation and after sell. Each
device is suited for all battery types, by means of jumpers it is possible
setting predefined curves for Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd
(option). They guarantees battery reliability in time by continuously testing
the internal impedance status, avoids any possible risk of damages and grants
also a permanent, reliable and safe connection of the battery to the power
supply. The system, through a battery stimulation circuit with algorithms of
evaluation of the detected parameter, is able to recognize batteries with a
short-circuited element. Battery test: Automatic.
Every time a battery will be connected to the Battery Charger, the device will
do followings check: reverse battery polarity, wrong battery connected (like
batteries 24 – 36Vdc or higher) with Jumper n.5 not present = Battery charger
for 12Vdc. After 120 minutes, with jumper in pos. 5 present (24 Vdc output
configuration) the device make the test of wrong battery connected like
batteries 12Vdc.
Every 240 minutes, make the test element in short circuit.
Diagnostic Type Checks:
Check for accidental disconnection of the battery cables
The device detects accidental disconnection and immediately switched off the
output power.
Battery not connected
If the battery is not connected no output power.
Reverse Polarity check
If the battery it is connected with inverted polarity, the device is
automatically protected.
Test of battery voltage connections
Appropriate voltage check, to prevent connection of wrong battery types, more
or less than the nominal voltage.
End of Charge check
When the battery it is completely full, the device automatically switch in
Float charging mode.
Check for Battery Cells in short circuit
Thanks to specific algorithms of evaluation, the CBs recognize batteries with
cells in internal short circuit.
In Float charge every 4 hours test of element in short circuit.
Diagnosis of battery and device
All CB devices support the user during installation and operation. A Blink
code of Diagnosis Led allows to discriminate
among various possible faults.
Error conditions, “LED Battery Fault” ON and “LED Diagnosis” blinking with
sequence; see Display Signal section.
Protection Features
On the primary side
The device is equipped whit an internally fuse. If the internal fuse is
activated, it is most probable that there is a fault in
the device. If happen, the device must be checked in the factory.
On the secondary side Battery and load
The device is electrically protected against short circuits and overload.
Inversion polarity
The module it is automatically protected against inversion of battery polarity
and connection of load inverted.
Over current and output short circuit
The unit limits the output current (see the technical data).
Thermal behaviour
Surrounding air temperature 50°C. For ambient temperature of over 50°C, the
output current must be reduced by 2.5% per °C. Max 70°C At the temperature of
70°C the output current will be 50% of In. The equipment does not switch off
in case of ambient temperature above 70°C or thermal overload. The devices are
protected for Over temperature conditions “worst case”; in this situations the
device Shut-down the output and automatic restart when temperature inside
fall.
CAN Connections
This document describes how to communicate with the Adelsystem devices which
are equipped with a CAN interface
using the SAE J1939 protocol.
Electrical characteristics
The CAN interfaces onboard the Adelsystem J1939 devices operate at 250kbit/s.
Depending on the device type, the bus line termination network can be present
inside the device or it has to be provided externally if needed. Refer to the
device user manual for further information.
General characteristics
At powerup, the device initiates the address-claiming process as per the
J1939-81 network management, which consists of the assignment to the device of
a source address that is unique among the devices on the bus. After such
assignment, data exchange can take place. Exchanged data is specified in the
specific device parameters map, which is a companion to this document.
Each parameter in the map is transmitted by the device to the broadcast
address, irrespective of belonging to monitoring, history, configuration or
alarm group. The column “Transmission Rate” in the map specifies whether each
parameter is broadcast in a timed manner (in this case the period is
specified) or only when its value changes (on change). However, immediately
after source address negotiations, the device broadcasts all the parameters as
a reference for any subsequent change that may occur. Monitoring and alarm
parameters are read-only parameters and are transmitted as described. History
and configuration parameter values are broadcast by the device through the SPN
and PGNs referenced in the map as any other parameter, but are all transmitted
only at powerup and on-change.
History parameters can be cleared by writing to PGN 65490 (0xFFD2), which
consists of SPN 523000 to 523002.
- SPN 523000: specifies the source address of the device which is the target of the history clearing command.
- SPN 523001: specifies the SPN associated to the history to be cleared. Such SPN is reported in the “SPN” column of the parameters map.
SPN523002: must contain the history clear command, which is 0x00.
| PGN| byte 0| byte 1| byte 2| byte 3| byte 4|
byte 5| byte 6| byte 7
---|---|---|---|---|---|---|---|---|---
Clear history| 65490| Target source address(SPN 523000)| History SPN to clear
(SPN 523001)| History value to write(SPN 523002)| |
Clear Total Run Time history (SPN 520321)| 65490| device source address(0x00
is default)| 0x81| 0xF0| 0x07| 0x00| 0x00| don’t care| don’t care
| LSB| | | MSB|
same as 520321 decimal
In addition to being autonomously broadcast using the timed and on-change transmission mechanism, each parameter in the map can be separately requested using PGN 59904 (Request PGN) as per J1939-81 network management and specifying in the data field the PGN the requested parameter belongs to; alternatively, the transmission of the whole set of on-change PGN can be requested using PGN 65492 which consists of SPN 523006 (source address of the device whose map is being requested). The structure of PGN 65492 is shown in the following table.
| PGN| byte 0
---|---|---
Transmit all the on-change PGNs| 65492| Target source address (SPN 523006)
Device configuration using the CAN interface
All the parameters in the map are always broadcast autonomously and histories
can always be cleared. However, for enhanced control and flexibility, the
device has two operation modes: monitoring and configuration mode.
At power-up the device is in monitoring mode unless the jumpers 1-2-3 are
present at power-up. Refer to the following figure to locate the jumpers on
the device front panel.
Note that other jumpers may be inserted e.g. to enable the power supply
function (ENABLE POWER SUPPLY jumper) or to select the 24V output (SELECTION
OUT VOLTAGE jumper). These two features can only be enabled at powerup using
the jumpers.
When the device is in monitoring mode, the battery charging algorithm is set
through the jumpers 1, 2 and 3 at power-up and cannot be changed until the
next power-cycling. In monitoring mode the device uses the hardware controls,
broadcasts all the parameters in the map as described and allows clearing the
histories.
When the device is powered up as shown in the previous figure, i.e. all the
three jumpers 1-2-3 inserted, it is in configuration mode. As such, it ignores
all the hardware controls (except the ENABLE POWER SUPPLY and SELECTION OUT
VOLTAGE jumpers) and uses the parameter values stored in the device non-
volatile memory.
When the device is in configuration mode, it is also possible to modify the
configuration parameters.
Configuration parameters can be set by writing to PGN 65491 (0xFFD3), which
consists of SPN 523003 to 523005.
- SPN 523003: specifies the source address of the device which is the target of the parameter setting command.
- SPN 523004: specifies the SPN associated to the configuration parameter to be set. Such SPN is reported in the “SPN” column of the parameters map.
- SPN 523005: must contain the value to be set
For further clarification, setting the bulk charge (SPN 520335) value to 2410mV/cell is displayed:
| PGN| byte 0| byte 1| byte 2| byte 3| byte 4|
byte 5| byte 6| byte 7
---|---|---|---|---|---|---|---|---|---
Parameter set| 65491| Target source address (SPN 523003)| Parameter SPN to
write (SPN 523004)| Setting value (SPN 523005)|
Set bulk charge (SPN 520335)| 65491| device source address, 0x00 default|
0x8F| 0xF0| 0x07| 0x00| 0x6A| 0x09| don’t care
| LSB| | | MSB| LSB| MSB|
same as 520335 decimal| same as 2410 decimal
The following table summarizes the operating modes
| Monitoring mode| Configuration mode
---|---|---
Device control and configuration| -front panel controls| -user
configuration from the non-volatile memory-front panel controls ignored except
ENABLE POWERSUPPLY and SELECTION OUT VOLTAGE jumpers
CAN operations| -map transmission (autonomously and upon
request)-history clearing-networking (address change, PGN requests issued
through PGN59904 including NAMEand UID)| -map transmission (autonomously and
upon request)-history clearing-networking (address change, PGN requests issued
through PGN59904 including NAME and UID)-device configuration-factory settings
Networking
Device identification on a J1939 network is done according to the device
source address and the J1939 device NAME. Both the source address and the
J1939 NAME must be unique on a given J1939 bus. Prior to exchanging data, a
device that goes on bus must claim its source address along with its J1939
NAME. In case two devices claim the same source address, several possibilities
exist according to the device capabilities.
All the Adelsystem J1939 devices are arbitrary address capable: if the claimed
address is already in use by another device, the devices can automatically
reclaim other addresses until an unused one is found. Reclaim address range is
0-220. In addition, the Adelsystem devices can be assigned a given address
using the J1939-81 Commanded Address Message (PGN 65240) based on the
Broadcast Announce Mode (BAM) of the transport protocol (J1939-21).
The factory-assigned source address is 0 (zero). Any subsequent change in
the source address accomplished
through the mentioned address claiming process or commanded-address message is
immediately applied and stored in
the device non-volatile memory thus preserved across power-cycling.
Per the J1939-81 standard, the J1939 NAME is structured according to the
following table, where the default values for Adelsystem devices are reported:
Arbitrary address capable| Industry group| Vehicle
system instance| Vehicle system| Res.| Function
n| Function instance| ECU instance| Mfr. code|
Identity number
---|---|---|---|---|---|---|---|---|---
Byte 8 1 bit| Byte 8 3 bit| Byte 8 4 bit| Byte 7 7 bit|
Byte 7 1 bit| Byte 6 8 bit| Byte 5 5 bit| Byte 5 3 bit|
Byte 4-3 11 bit| Byte 3-1 21 bit
1| Based on producttype| Assigned| Based on producttype| don’t care| Based on
producttype| Assigned| Assigned| 861| Assigned (the 21 LSBs of the device
uniqueidentifier UID)
| PGN| byte 0..7| byte 8
---|---|---|---
Commanded Address Message| 65240| J1939 NAME, LSB first(byte 0 = identity
number lower part, etc…)| Newsource address
---|---|---|---
Discovering the source address and NAME of any/all devices on bus The NAME field of any device is automatically published by the devices at every source address claiming procedure, but it can also be requested at any time sending the PGN 59904 (Request PGN) as per J1939-81 network management to the destination address of the device whose NAME is being requested or to the broadcast address (0xFF) to discover the NAME and source address of all the devices on the bus and specifying in the data field the PGN 60928 (0xEE00).
| PGN| Purpose| Source Address| Destination Address|
byte 0| byte 1| byte 2..7
---|---|---|---|---|---|---|---
J1939-81Request for Address Claimed|
59904
| To know the NAME and source address of all thedevices on bus| Requesting device’s| 0xFF (broadcast address)|
0x00
|
0xEE
|
0x00
To know the NAME of the device with a knownsource address| Requesting device’s| The known source address of the target device
The targeted device or all the devices on bus will reply with the J1939-81 Address Claimed PGN (PGN 60928) specifying as source address its/their own source address and its/their NAME in the data fields:
| PGN| Source Address| Destination Address| byte 0..7
---|---|---|---|---
J1939-81 Address Claimed| 60928| Device’s own source address| 0xFF(broadcast
address)| NAME
Device unique identifier and restore to factory settings
Each device is assigned an 8-byte unique identifier (UID) at the factory which
is used for device identification. The value is reported by the SAE J1939 PGN
65259 (Component Identification), that can be queried using the standard PGN
59904 (Request PGN). The structure of PGN 65259 follows.
| PGN| byte 0| byte 1| byte 2…9| byte 10| byte
11
---|---|---|---|---|---|---
Component identification| 65259| 0x2A| 0x2A| 8-byte UID, LSB first| 0x2A| 0x2A
Restore to factory settings erases all the user configurations and history
stored in device memory and replaces them
with the default values. This is accomplished using PGN 65491 in order to
write the value 1 to the factory setting SPN (SPN 520358). It is possible only
when the device is in configuration mode. The restored default values are
effective only after power cycling.
| PGN| byte 0| byte 1| byte 2| byte 3| byte 4|
byte 5| byte 6| byte 7
---|---|---|---|---|---|---|---|---|---
Parameter set| 65491| Target source address (SPN 523003)| Parameter SPN to
write (SPN 523004)| Set value (SPN 523005)|
Factory settings (SPN 520358)| 65491| device source address (0x00 is default)|
0xA6| 0xF0| 0x07| 0x00| 0x01| 0x00| don’t care
| LSB| | | MSB|
same as 520358 decimal
Standards and Certification
Electrical Safety:
Assembling device: IEC/EN 62368-1
EMC Standards Immunity:
EN 61000-6-2
EMC Standards Emission:
EN 61000-6-3
Standards Conformity:
The CE mark in According to EMC 2014/30/UE Directive; 2014/35/UE (Low Voltage)
In According to UL 1236 and CSA C22.2 N° 107.2
DIN41773 (Charging cycle)
Rail Mounting:] All modules must have a minimum vertical and horizontal
distance of 5 mm to this power supply in order to guarantee sufficient auto
convection. Depending on the ambient temperature and load of the device, the
temperature of the housing can become very high! Mounting Steps: 1, 2, 3,
4.
Removing Steps: 4, 3, 2, 1.
MOUNTING – REMOVING
**Step 1
Step 2
Step 3
Step 4
**
Technical data
| CB12245A| CB12245AJ
---|---|---
|
Input Data| |
Nominal Input Voltage (2 x Vac)| 115 – 230 – 277| 115 – 230 – 277
Input Voltage range (Vac)| 90 – 305| 90 – 305
Inrush Current (Vn and In Load) I2t| £ 16 A £ 5 msec.| £ 16 A £ 5 msec.
Frequency| 47 – 63 Hz ±6%| 47 – 63 Hz ±6%
Input Current (115 – 270 Vac)| 2.4 – 1.2 A| 2.4 – 1.2 A
Internal Fuse| 4 A| 4 A
External Fuse (recommended)| 10 A (MCB curve B)| 10 A (MCB curve B)
Battery Charger Output 24 Vdc (depend on jumper selection)| |
Fast Charge – Boost Charge (Lead Acid)| 28.8 Vdc| 28.8 Vdc
Fast Charge – Boost Charge (Ni-Cd)| 30 Vdc| 30 Vdc
Recovery Charge| 6 – 18 Vdc| 6 – 18 Vdc
Charging Current Max Ibatt < 40°C(In) Input V. 230Vac| 5 A ± 5%| 5 A ± 5%
Charging Current Max Ibatt < 40°C(In) Input V. 120Vac| 4 A ± 5%| 4 A ± 5%
Charging Current Max Ibatt > 40°C(In)| 3.5 A± 5%| 3.5 A± 5%
Battery Charger Output 12 Vdc (depend on jumper selection)| |
Fast Charge – Boost Charge| 14.4 Vdc| 14.4 Vdc
Fast Charge – Boost Charge (Ni-Cd)| 15 Vdc| 15 Vdc
Recovery Charge| 3 – 8 Vdc| 3 – 8 Vdc
Charging Current Max Ibatt < 40°C (In)| 6 A ± 5%| 6 A ± 5%
Charging Current Max Ibatt > 40°C (In)| 6 A ± 5%| 6 A ± 5%
Battery Tester| |
Short circuit Element Detection| Yes| Yes
Battery Impendency (Life test)| No| No
Reverse polarity protection| Yes| Yes
Battery Disconnected (Protection No Spark)| Yes| Yes
Battery Voltage Wrong| Yes| Yes
End of charge control| Yes| Yes
Generic Output Data| |
Max. time Bust Charge (typ. At In)| 15 h| 15 h
Min. time Bust Charge (typ. At In)| 4 min.| 4 min.
Max.Time Bulk charge (Typ. at IN)| 15 h| 15 h
Min.Time Bulk charge (Typ. at IN)| 4 min.| 4 min.
Float Charge: Depend on Battery typeFloat Charge Ni-Cd: V/cell (Jumper Config
Battery type)| 2.23;2.25;2.27;2.31.4 V| 2.23;2.25;2.27;2.31.4 V
End of charging current (Bulk & Absorption charge)| 6% charging current| 6%
charging current
Charging current limiting Iadj| 20 ÷ 100 % / In| 20 ÷ 100 % / In
Quiescent Current| ≤5mA| ≤5mA
Remote Charge Input Control| Bulk / Float| Bulk / Float
Power Supply function| By Jumper Enabling| By Jumper Enabling
Output Voltage 12 or 24 Vdc Selection| By Jumper Enabling| By Jumper Enabling
Boost charge Enabling| By Jumper Enabling| By Jumper Enabling
Efficiency (50% of In)| 90%| 90%
Dissipation Power load max (W)| 9| 9
Residual Ripple| £ 60 mVpp| £ 60 mVpp
Quiescent Current| £ 5 mA| £ 5 mA
Charging Curve automatic: IuoUo| 4 stage| 4 stage
Detection of element in short circuit| Yes| Yes
Short-circuit protection)| Yes| Yes
Over Load protection| Yes| Yes
Overheating Thermal Protection| Yes| Yes
Over Voltage Output protection| (Typ. 35Vdc)| (Typ. 35Vdc)
Connection and Monitoring| |
Signal Output (free switch contact)| |
Main or Backup Input Power| Yes| Yes
Low Battery| Yes| Yes
Fault Battery| Yes| Yes
Type of Signal Output Contact (free switch contact)| |
Max. current can be switched (EN60947.4.1): Max. DC1: 30 Vdc 1 A; AC1: 60 Vac
1AMin.1mA at 5 Vdc| Resistive load Min. load| Resistive load Min. load
Can (connection)| |
Can Bus J1939| No| Yes
General Data| |
Insulation voltage (In /Out)| 3000 Vac| 3000 Vac
Insulation voltage (In / PE)| 1605 Vac| 1605 Vac
Insulation voltage (Out / PE)| 500 Vac| 500 Vac
Protection Class (EN/IEC 60529)| IP20| IP20
Protection class| I, with PE connected| I, with PE connected
Reliability: MTBF IEC 61709| > 300.000 h| > 300.000 h
Pollution Degree Environment| 2| 2
Connection Terminal Blocks screw Type| 2,5mm(24–14AWG)| 2,5mm(24–14AWG)
Dimensions (w-h-d)| 45x110x105 mm| 45x110x105 mm
Weight| 0.30 Kg approx.| 0.30 Kg approx.
Safety Standard Approval| CE – UL1236| CE
Climatic Data| |
Ambient temperature (operation)| -25 ÷ +70°C| -25 ÷ +70°C
De Rating Ta > 50°C| – 2.5%(In) / °C| – 2.5%(In) / °C
Ambient temperature Storage| -40 ÷ +85°C| -40 ÷ +85°C
Humidity at 25 °C no condensation| 95% to 25°C| 95% to 25°C
Cooling| Auto Convention| Auto Convention
Auto Derating| Yes Up to 50 °C| Yes Up to 50 °C
Accessory| |
ADELView Graphic| |
ADELView System| |