Danfoss VMTD-F-B Direct Heating and Domest User Guide
- June 17, 2024
- Danfoss
Table of Contents
Danfoss VMTD-F-B Direct Heating and Domest
Specifications
The Termix VMTD-F-B is a district heating substation for direct heating and
instantaneous domestic hot water. It is applicable for single and multi-family
houses and decentralized systems.
Functional Description
The substation is prefabricated with a built-in water heater and a
differential pressure controlled heating system. It includes a differential
pressure controller, a fitting piece, sensor pockets for insertion of a heat
meter, strainer, and ball valves.
The heating circuit is designed for direct generation of heat.
The differential pressure control sets the optimum operation conditions for
radiator thermostatic valves, enabling individual temperature control in each
room. Optionally, a zone valve with actuator and a room thermostat can be
included for time-dependent temperature control.
Safety Notes
Special versions of substations are available upon request.
All pipes and components are made of stainless steel and brass for corrosion
protection. The maximum chloride compounds of the flow medium should not
exceed 150 mg/l to prevent equipmentcorrosion. The choice of materials should
always comply with local legislation.
We recommend mounting safety valve(s) in compliance with local regulations.
The substation must be equipped with features that allow it to be separated
from all energy sources, including power supply.
Mounting
To mount the Termix VMTD-F-B:
- Ensure the substation is placed in a suitable location.
- Connect the necessary electrical connections.
- Ensure the substation is equipped with safety valve(s) in compliance with local regulations.
- Connect the substation to the district heating system or other energy sources.
Start-up
To start-up the Termix VMTD-F-B:
- Ensure all electrical connections are properly installed.
- Open the necessary valves to allow flow through the substation.
- Check for any leaks or abnormal operation.
Electrical Connections
The Termix VMTD-F-B requires electrical connections for proper operation.
Follow the provided electrical connection diagram and ensure all connections
are made according to local electrical codes and regulations.
Design
The Termix VMTD-F-B features a compact and efficient design. It is constructed
with high-quality materials for durability and corrosion resistance.
Schematic Diagram
A schematic diagram of the Termix VMTD-F-B is provided for reference. It
illustrates the internal components and their connections.
Declaration
The manufacturer declares that the Termix VMTD-F-B complies with relevant
standards and regulations. A declaration of conformity is provided for
reference.
FAQ
Q: Can the Termix VMTD-F-B be used in both single and multi-family
houses?
A: Yes, the Termix VMTD-F-B is applicable for both single and multi-
family houses.
Q: Can other energy sources be used with the substation?
A: Yes, other energy sources can be used as long as they meet the
operating conditions and are comparable to district heating.
Q: Is it necessary to mount safety valve(s) on the substation?
A: We recommend mounting safety valve(s) in compliance with local
regulations to ensure safe operation.
Q: How should the substation be connected to energy sources?
A: The substation should be equipped with features that allow it to be
separated from all energy sources, including power supply.
Functional description
District heating substation for direct heating and instantaneous domestic hot water.
Application
The Termix VMTD-F-B is a complete solution with built-in water heater and a
differential pressure controlled heatingsystem. Termix VMTD-F-B is applicable
for single and multi-family houses and for decentralized systems.
District heating (DH)
The substation is prefabricated with a differential pressure controller, a
fitting piece and sensor pockets for insertion of a heat meter as well as
strainer and ball valves.
Heating (HE)
The heating circuit is designed for direct generation of heat.
The differential pressure control sets the optimum operation conditions for
radiator thermostatic valves in order to enable individual temperature control
in each room. In order to enable a time-depending temperature control program,
a zone valve with actuator and a room thermostat can be included as an option.
Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger and the temperature
is regulated with a thermostatic control valve. The patented sensor
accelerator accelerates the closing of the Danfoss AVTB valve and protects the
heat exchanger against overheating and lime scale formation. The heat
exchanger cools the DH water very efficiently, thereby creating a very good
operating economy.
The sensor accelerator and AVTB valve also works as a bypass keeping the house
supply line warm. This shortens the waiting periods during summer when the
heating system is in reduced operation. The sensor accelerator helps to ensure
a stable hot water temperature regardless of varying loads, flow temperatures
and differential pressure without the need for readjusting the valve.
Safety notes
Safety Notes – general
The following instructions refer to the standard design of substation. Special
versions of substations are available on request.
This operating manual should be read carefully before installation and start-
up of the substation. The manufacturer accepts no liability for damage or
faults that result from non-compliance with the operating manual. Please read
and follow all the instructions carefully to prevent accidents, injury and
damage to property.
Assembly, start-up and maintenance work must be performed by qualified and
authorized personnel only.
Please comply with the instructions issued by the system manufacturer or
system operator.
Corrosion protection
All pipes and components are made of stainless steel and brass.
The maximum chloride compounds of the flow medium should not be higher than
150 mg/l.
The risk of equipment corrosion increases considerably if the recommended
level of permissible chloride compounds is exceeded.
Energy source
The substation is designed for district heating as the primary source of
energy. However, also other energy sources can be used where the operating
conditions allow it and always are comparable to district heating.
Application
The substation is designed to be connected to the house installation in a
frost-free room, where the temperature does not exceed 50 °C and the humidity
does not exceed 60%. Do not cover or wall up the substation or in any other
way block the entrance to the station.
Choice of material
Choice of materials always in compliance with local legislation.
Safety valve(s)
We recommend mounting of safety valve(s), however, always in compliance with
local regulations.
Connection
The substation must be equipped with features that ensure that the substation
can be separated from all energy sources (also power supply).
Emergency
In case of danger or accidents – fire, leaks or other dangerous circumstances
– interrupt all energy sources to the station if possible, and seek expert
help.
In case of discoloured or bad-smelling domestic hot water, close all shut-off
valves on the substation, inform the operating personnel and call for expert
help immediately.
REACH
All Danfoss A/S products fulfill the requirements in REACH.
One of the obligations in REACH is to inform customers about presence of
Candidate list substances if any, we hereby inform you about one substance on
the candidate list: The product contains brass parts which contains lead (CAS
no: 7439-92-1) in a concentration above 0.1% w/w.
Storage
Any storage of the substation which may be necessary prior to installation
should be in conditions which are dry and heated.
Authorized personnel only
Assembly, start-up and maintenance work must be performed by qualified and
authorized personnel only.
Please observe instructions carefully
To avoid injury to persons and damage to the device, it is absolutely
necessary to read and observe these instructions carefully.
Warning of high pressure and temperature
Be aware of the installation’s permissible system pressure and temperature.
- The maximum temperature of the flow medium in the substation is 120 °C.
- The maximum operating pressure of the substation is 10 bar. PN 16 versions are available on enquiry.
- The risk of persons being injured and equipment damaged increases considerably if the recommended permissible operating parameters are exceeded.
- The substation installation must be equipped with safety valves, however, always in accordance with local regulations.
Warning of hot surface
- The substation has got hot surfaces, which can cause skin burns.
- Please be extremely cautious in close proximity to the substation.
- Power failure can result in the motor valves being stuck in open position. The surfaces of the substation can get hot, which can cause skin burns. The ball valves on district heating supply and return should be closed.
Warning of transport damage
Before substation installation, please make sure that the substation has not
been damaged during transport.
IMPORTANT – Tightening of connections
Due to vibrations during transport all flange connections, screw joints and
electrical clamp and screw connections must be checked and tightened before
water is added to the system. After water has been added to the system and the
system has been put into operation, re-tighten ALL connections.
Mounting
Installation must be in compliance with local standards and regulations.
District heating (DH) – In the following sections, DH refers to the heat
source which supplies the substations. A variety of energy sources, such as
oil, gas or solar power, could be used as the primary supply to Danfoss
substations. For the sake of simplicity,DH can be taken to mean the primary
supply.
Connections:
- Hot water circulation (HWC) (Optional)
- District heating (DH) supply
- District heating (DH) return
- Cold water mains (CWM)
- Domestic cold water (DCW)
- Domestic hot water (DHW)
- Heating (HE) supply
- Heating (HE) return
Connection sizes:
- DH + HE: G ¾” (int. thread)
- CWM + DCW + DHW: G ¾” (int. thread)
Dimensions (mm):
-
Without cover:
H 710 x W 528 x D 150 -
With cover (mount on wall variant):
H 800 x W 540 x D 190 -
With cover (built-in wall variant):
H 915–980 x W 610 x D 150 -
Weight (approx.): 20 kg
Authorized personnel only
Assembly, start-up and maintenance work must be performed by qualified and
authorized personnel only.
The pipe placement can deviate from the shown drawing. Please note the markings on the station.
Installation
Mounting:
-
Adequate space
Please allow adequate space around the substation for mounting and maintenance purposes. -
Orientation
The station must be mounted so that components, keyholes and labels are placed correctly. If you wish to mount the station differently please contact your supplier. -
Drillings
Where substations are to be wall-mounted, drillings are provided in the back mounting plate. Floor mounted units have support. -
Labelling
Each connection on the substation is labelled.
Before installation:
-
Clean and rinse
Prior to installation, all substation pipes and connections should be cleaned and rinsed. -
Tightening
Due to vibration during transport, all substation connections must be checked and tightened before installation. -
Unused connections
Unused connections and shut-off valves must be sealed with a plug. Should the plugs require removal, this must only be done by an authorized service technician.
Installation:
-
Strainer
If a strainer is supplied with the station it must be fitted according to schematic diagram. Please note that the strainer may be supplied loose. -
Connections
Internal installation and district heating pipes connections must be made using threaded, flanged or welded connections.
Keyhole for mounting.
Start-up
Start-up, Direct heating
The shut-off valves should be opened and the unit observed as it enters
service. Visual checking should confirm temperatures, pressures, acceptable
thermal expansion and absence of leakage.
If the heat exchanger operates in accordance with design, it can be put to
regular use.
After water has been added to the system and the system has been put into
operation, re-tighten ALL connections.
Re-thighten connections
After water has been added to the system and the system has been put into
operation, re-tighten ALL connections.
Electrical connections
Before making electrical connections, please note the following:
Safety notes
Please read the relevant parts of the safety notes.
230 V
The substation must be connected to 230 V AC and earth.
Potential bonding
Potential bonding should be carried out according to 60364-4-41:2007 and IEC
60364-5-54:2011.
Bonding point on the mounting plate below right corner marked with earth
symbol.
Disconnection
The substation must be electrically connected so that it can be disconnected
for repairs.
Outdoor temperature sensor
Outdoor sensors should be mounted so as to avoid exposure to direct sunlight.
They should not be placed close to doors, windows or ventilation outlets.
The outdoor sensor must be connected to the station on the terminal block under the electronic control.
-
Authorized electrician
Electrical connections must be made by an authorized electrician only. -
Local standards
Electrical connections must be made in accordance with current regulations and local standards.
Design
Your substation might look different than the substation shown.
Design description
- B Heat exchanger, DHW
- O Termix sensor accelerator
- 7 Thermostatic valve, DHW
- 9 Strainer
- 14 Sensor pocket, energy meter
- 31 Differential pressure controller
- 41A Fitting piece, cold water mains
- 41B Fitting piece, energy meter
Schematic diagram
Your substation might look different than the schematic diagram shown.
Schematic description
- B Heat exchanger, DHW
- 7 Thermostatic valve, DHW
- 9 Strainer
- 14 Sensor pocket, energy meter
- 31 Differential pressure controller
- 41A Fitting piece, cold water mains
- 41B Fitting piece, energy meter
- DHW: Domestic Hot Water
- CWM: Cold Water Mains
- DCW: Domestic Cold Water
- DH Supply: District Heating Supply
- DH Return: District Heating Return
- HE Supply: Heating Supply
- HE Return: Heating Return
Technical parameters
Technical parameters
- Nominal pressure: PN 10 (PN 16 versions are available on enquiry)
- Max. DH supply temperature: 120 °C
- Min. DCW static pressure: 0.5 bar
- Brazing material (HEX): Copper
- Heat exchangers test pressure: 30 bar
- Sound level: N 55 dB
Controls
Heating circuit
Differential pressure controller
The differential pressure controller smooths out the fluctuations in pressure
arriving from the district heating network. The operating pressure in the
substation is thus held steady.
TP7000
TP7000 electronic 7 day programmable room thermostat.
Signals from the room thermostat can be used to control zone valves.
DHW temperature control
There are various types of DHW temperature control used in Danfoss
substations.
DHW temperature should be adjusted to 45-50 °C, as this provides optimal
utilisation of DH water. At DHW temperatures above 55 °C, the possibility of
lime scale deposits increases significantly.
-
AVTB controller (20–60 °)
The temperature setting is as follows:- 1 = 20 °C
- 2 = 35 °C
- 3 = 50 °C
- 4 = 60 °C
- 5 = 70 °C
The values are intended as a guide.
The AVTB operates at its best at DH supply temperatures of up to 90 °C.
Thermostatic control
DHW temperature is adjusted as follows:
To increase temperature, turn the handle on the thermostatic controller to
select a higher number.
To decrease temperature, turn the handle on the thermostatic controller to
select a lower number.
Other
Safety valve
The purpose of the safety valve is to protect the substation from excessive
pressure.
The blow-off pipe from the safety valve must not be closed. The blow-off pipe
outlet should be placed so that it discharges freely and it is possible to
observe any dripping from the safety valve.
It is recommended to check the operation of safety valves at intervals of 6
months. This is done by turning the valve head in direction indicated.
Strainer
Strainers should be cleaned regularly by authorized personnel. The frequency
of cleaning would depend on operating conditions and the manufacturer’s
instructions.
GTU Pressure Equalizer
The GTU Pressure Equalizer absorbs the expansion on the secondary side of the
Termix water heaters and can be used as a substitute to the safety valve.
Furthermore the pressure equalizer absorbs a possible increase in pressure, so
a discharge outlet is omitted.
The GTU Pressure Equalizer may not be applied in systems with hot water
circulation.
Return temperature limiter FJVR (10-80 °C)
The return limiter type FJVR automatically controls the return temperature
from radiators, convectors and under floor heating pipes.
Fitting piece
The substation is equipped with a fitting piece for energy meter.
Assembly of energy meters:
-
Close ball valves
Close the ball valves on DH Supply and DH Return, if there is water on the system. -
Loosen nuts
Loosen the nuts on the fitting piece. -
Remove fitting piece
Remove the fitting piece and replace it with the energy meter. Do not forget the gaskets. -
Tighten connections
After mounting of the energy meter remember to check and tighten all threaded connections.
Sensor pocket, energy meter
The sensors of the energy meter is mounted in the sensor pockets.
Maintenance
The substation requires little monitoring, apart from routine checks. It is
recommended to read the energy meter at regular intervals, and to write down
the meter readings.
Regular inspections of the substation according to this Instruction are
recommended, which should include:
-
Strainers
Cleaning of strainers. -
Meters
Checking of all operating parameters such as meter readings. -
Temperatures
Checking of all temperatures, such as DH supply temperature and DHW temperature. -
Connections
Checking all connections for leakages. -
Safety valves
The operation of the safety valves should be checked by turning the valve head in the indicated direction. -
Venting
Checking that the system is thoroughly vented.
Inspections should be carried out minimum every two years.
Spare parts can be ordered from Danfoss. Please ensure that any enquiry includes the substation serial number.
Authorized personnel only
Assembly, start-up and maintenance work must be performed by qualified and
authorized personnel only.
Troubleshooting
Troubleshooting in general
In the event of operating disturbances, the following basic features should be
checked before carrying out actual troubleshooting:
- the substation is connected to electricity,
- the strainer on the DH supply pipe is clean,
- the supply temperature of the DH is at the normal level (summer, at least 60 °C – winter, at least 70 °C),
- the differential pressure is equal to or higher than the normal (local) differential pressure in the DH network – if in doubt, ask the DH plant supervisor,
- pressure on the system – check the HE pressure gauge.
Authorized personnel only
Assembly, start-up and maintenance work must be performed by qualified and
authorized personnel only.
Troubleshooting DHW
Problem | Possible cause | Solution |
---|---|---|
Too little or no DHW. | Strainer in supply or return line clogged. | Clean |
strainer(s).
DHW circulation pump out of order or with too low setting.| Check circulation
pump.
Defective or clogged non-return valve.| Replace – clean.
No electricity.| Check.
Wrong setting of automatic controls, if any.| To adjust an electronic
controller for DHW, pls. note enclosed instructions for electronic controller.
Scaling of the plate heat exchanger.| Replace – rinse out.
Defective motorized valve.| Check (use manual function) – replace.
Defective temperature sensors.| Check – replace.
Defective controller.| Check – replace.
Hot water in some taps but not in all.| DCW is being mixed with the DHW, e.g.
in a defective thermostatic mixing valve.| Check – replace.
Defective or clogged non-return valve on circulation valve.| Replace – clean.
Tap temperature too high; DHW tap load too high.| Thermostatic valve adjusted
to a too high level.| Check – set.
Temperature drop during tapping.| Scaling of the plate heat exchanger.|
Replace – rinse out.
Larger DHW flow than the substation has been designed for.| Reduce DHW flow.
Thermostatic control valve does not close| Temperature difference between DH
supply and DHW set point too low.| Lower the set point temperature or increase
the DH supply temperature.
Troubleshooting HE
Problem | Possible cause | Solution |
---|---|---|
Too little or no heat. | Strainer clogged in DH or HE circuit (radiator | |
circuit). | Clean gate/strainer(s). | |
The filter in the energy meter on DH circuit clogged. | Clean the filter (after |
consulting the DH plant operator).
Defective or wrongly adjusted differential pressure controller.| Check the
operation of the differential pressure controller – clean the valve seat if
required.
Sensor defective – or possibly dirt in the valve housing.| Check the operation
of the thermostat – clean the valve seat if required.
Automatic controls, if any, wrongly set or defective – possibly power
failure.| Check if the setting of the controller is correct – see separate
instructions.
Check the power supply. Temporary setting of motor to “manual” control – see instructions on automatic controls.
Pump out of operation.| Check if the pump is receiving power and that it
turns. Check if there is air trapped in the pump housing – see pump manual.
The pump is set at too low speed of rotation.| Set the pump at higher speed of
rotation.
Pressure drop – the pressure drop on the radiator circuit shows lower than
recommended operating pressure.| Fill water on the system and check the
functioning of the pressure expansion vessel if required.
Air pockets in the system.| Vent the installation thoroughly.
Limiting of the return temperature adjusted too low.| Adjust according to
instructions.
Defective radiator valves.| Check – replace.
Uneven heat distribution in building because of incorrectly set balancing
valves, or because there are no balancing valves.| Adjust/install balancing
valves.
Diameter of pipe to substation too small or branch pipe too long.| Check pipe
dimensions.
Uneven heat distribution.| Air pockets in the system.| Vent the installation
thoroughly.
DH supply temperature too high.| Wrong setting of thermostat or of automatic
controls, if any.| Adjust automatic controls, – see instructions for automatic
controls.
Defective controller. The controller does not react as it should according to
the instructions.| Call automatic controls manufacturer or replace the
regulator.
Defective sensor on self-acting thermostat.| Replace thermostat – or sensor
only.
DH supply temperature too low.| Wrong setting of automatic controls, if any.|
Adjust automatic controls – see instructions for automatic controls.
Defective controller. The controller does not react as it should according to
the instructions.| Call in automatic controls manufacturer or replace
controller.
Defective sensor on self-acting thermostat.| Replace thermostat – or sensor
only.
Wrong placement/fitting of outdoor temperature sensor.| Adjust location of
outdoor temperature sensor.
Strainer clogged.| Clean gate/strainer.
Too high DH return temperature.| Too small heating surface/too small radiators
compared to the total heating requirement of the building.| Increase total
heating surface.
---|---|---
Poor utilization of existing heating surface. Defective sensor on self-acting
thermostat.| Make sure the heat is distributed evenly across the full heating
surface – open all radiators and keep the radiators in the system from heating
up at the bottom. It is extremely important to keep the supply temperature to
the radiators as low as possible, while maintaining a reasonable level of
comfort.
The system is single pipe loop.| The system should feature electronic controls
as well as return sensors.
Pump pressure too high.| Adjust pump to a lower level.
Air in system.| Vent the system.
Defective or incorrectly set radiator valve(s). Single pipe loop systems
require special one-pipe radiator valves.| Check – set/replace.
Dirt in the motorized valve or in the differential pressure controller.| Check
– clean out.
Defective motorized valve, sensor or automatic controller.| Check – replace.
Electronic controller not adjusted correctly.| Adjust according to
instructions.
Noise in system.| Pump pressure too high.| Adjust pump to a lower level.
Heat load too high.| Defective motorized valve, sensor or electronic
controller.| Check – replace.
Disposal
Disposal note
This symbol on the product indicates that it may not be disposed of as
household waste..
It must be handed over to the applicable take-back scheme for the recycling of
electrical and electronic equipment.
- Dispose of the product through channels provided for this purpose.
- Comply with all local and currently applicable laws and regulations.
Declaration
Declaration of conformity
Category 0 without electrical equipment
Gemina Termix A/S • Member of the Danfoss Group
danfoss.com • +45 9714 1444 •
mail@termix.dk
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, online or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also
applies to products ordered but not delivered provided that such alterations
can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>