Ti SALES FRS202 Installation Guide
- June 4, 2024
- Ti-SALES
Table of Contents
INSTALLATION PROCEDURE – FRS202
Installation Guide
FRS202
Leak and Pipe Confirmation
Confirm the leak location by cleaning and examining the pipe. Check the
diameter of the pipe to make certain you are using the correct size
saddle. Pipe Preparation
Shut off the water supply if possible and remove the Corporation Stop from the
pipe. Scrape the pipe to remove as much dirt and corrosion as possible so the
surface around the leak and the entire saddle contact area are smooth. Saddle Preparation
Install corporation stop into saddle while holding the saddle boss
stationary with another wrench. Back off the nuts on the saddle bolts to the
end of the bolts, but do not remove them. Separate one ide of the saddle by
unhooking the top and bottom pieces, taking note of how the pieces are to be
reassembled. Lubricate the pipe and saddle gasket with soapy water or an
acceptable lubricant to achieve the best results.
Saddle Installation
Slip the saddle around the pipe next to the hole and rehook the top and
bottom. Make certain the gasket is free of foreign material and there is
nothing lodged between the gasket and pipe. Center the saddle over the damaged
section. Hand-tighten the nuts evenly. Torque the nuts evenly with incremental
torque settings to a maximum of 50-60 ft. lbs. Recheck the saddle bolt torque
before backfilling.
PRECAUTIONS:
- Check the diameter of the pipe to make certain you are using the correct size saddle.
- ALWAYS RECHECK TORQUE AND PRESSURE TEST FOR LEAKS BEFORE BACKFILLING.
- Backfill and compact carefully around the saddle, corp stop, and service line according to the pipe manufacturer’s instructions.
36 Hudson Rd
Sudbury MA 01776
800-225-4616
www.tisales.com
References
Read User Manual Online (PDF format)