ONLINE XANTO 2000 UPS Battery User Manual
- June 16, 2024
- ONLINE
Table of Contents
User manual
ONLINE XANTO series
Models 700 – 3000
XANTO 2000 UPS Battery
Germany
ONLINE USV-Systeme AG
Luise-Ullrich-Str. 8
D-82031 Grünwald
Phone +49 (89) 2423990-10
Fax +49 (89) 2423990-20
www.online-usv.de| Italy
ONLINE UPS-Systems S.r.l.
Via Ferruccio Gilera 110
I-20862 Arcore (MB)
Phone +39 (039) 2051444
Fax +39 (039) 2051435
www.online-ups.it| Switzerland
ONLINE USV-Systeme AG
c/o swizzconnexx
Pilatusstrasse 17
CH-5630 Muri
Phone +41 (41) 5002868
Fax +49 (89) 242399020
www.online-usv.ch
---|---|---
Introduction
ONLINE USV-Systeme AG (ONLINE) is one of the leading manufacturers of
uninterruptible power supplies (UPS). Since 1988, the German company has
focussed on the development, production, sale and support of UPS systems.
Based on unit numbers sold,
ONLINE products are the German number one in the UPS market and
internationally recognised because of their top quality and excellent support.
The power supply often fails when you least expect it. There can also be
significant fluctuation in the quality of the power supply. Network problems
can lead to the corruption of critical data, data which is not backed up can
be lost and hardware damaged. This means expensive repairs and downtime.
Models in the XANTO range from ONLINE are the best way of preparing for these
kinds of scenarios. These UPS system offer top class power supply protection
for your delicate electronic systems. They protect against the most common
supply problems such as ower outage, voltage blips, surge voltage and low
voltage, voltage drops, interference, switching and voltage peaks, frequency
deviations and harmonic distortion.
XANTO reliably protects your systems from power supply problems and the
functionality of the devices is retained. As well as first-class performance
and reliability, XANTO has the following unique benefits:
- True double conversion technology (VFI-SS-111)
- Pioneering power factor 1.0
- Pure sinewave output voltage
- Frequency converter operation
- Automatic and manual bypass
- Scalable autonomy time with additional battery packages
- Efficiency >97%
- Rack-tower-versatile models in space-saving 2U size
- Battery deep-discharge-protection
- Cold-start function, starting the UPS system without main power
- Switchable output sockets to increase the backup time for critical loads
- Surge protection for data and telephone wires
- Steplessly controlled fan
- RS-232 and USB interface
- Slot for optional SNMP adapter or AS400-/ dry-contact interface-card
- Emergency-off function (EPO = Emergency Power Off)
- 2 years warranty including battery and 24 hours free exchange in advance
Safety warnings
This manual contains important instructions that you must follow during the
installation and maintenance of the UPS system and the batteries.
Please read all the instructions in the manual before working with the device.
Keep the manual in a safe place.
CAUTION
- The UPS system carries life-threatening voltages. All repair and maintenance work must be carried out by customer service personnel.
- The UPS system has its own energy source (batteries). The output of the UPS system can be live even when the UPS system is not connected to a source of alternating current.
- In order to reduce the risk of fire or electric shock, the UPS system may only be installed in buildings with controlled temperature and air humidity in which there are no conductive contaminants. The ambient temperature must not exceed 40°C. The UPS system must not be operated near water or in extremely high air humidity (>90%).
- Before transporting the UPS system, make sure that it is disconnected from the power supply and switched off.
- Batteries can pose a risk of electric shock or catch fire as a result of high short circuit current. Please take the necessary precautionary measures. Maintenance must be carried out by qualified personnel who are trained in handling batteries and have good knowledge of the necessary precautionary measures (see Chapter Maintenance). keep unauthorised personnel away from batteries
- Batteries must be disposed of properly. Local regulations must be taken into consideration.
- Batteries must not be burnt. There is risk of explosion.
Installation
3.1 Checking the delivery
Keep the transport box and the packaging material for the carrier or sales
point. If parts of the system have been damaged in transit, submit a transport
damage complaint to your supplier within 24 hours. If you only discover damage
after accepting the device, please submit a complaint for concealed damage.
3.2 Unpacking the UPS system
CAUTION
- Unpacking the UPS system at a low ambient temperature can lead to the formation of condensation inside and outside the casing. Only install the UPS system if the inside and outside are completely dry (risk of electric shock).
- The UPS system is very heavy (see Chap. 8 Technical data). Be careful when unpacking and transporting the UPS.
PLEASE NOTE
Move and open the packaged UPS system carefully. Leave the components in their
packaging until they are installed.
To unpack the UPS system and accessories:
- Open the external box and take the accessories packed with the UPS system out.
- Carefully lift the UPS system out of the external box.
- Place the UPS system in a protected, adequately ventilated position which is free of humidity, flammable gasses and corrosion.
3.3 Checking the accessories
*Download from www.online-ups.com
Table 1: Package contents
3.4 Installation as tower, activating battery
The UPS system is delivered fully assembled.
**CAUTION**
The casing is very heavy (see Chap. 8 Technical Data).
-
Position the UPS system on an even, stable surface for its final location.
-
If you install additional battery packs, position them next to the UPS system.
-
In pure tower models (Art.-No. X700 – X3000) the battery is connect
-
JUST RACK-TOWER-VERSATILE MODELS:
If you have purchased a rack-tower-versatile model (Art.-No.X700R – X3000R), for safety reasons, the UPS system is delivered without the batteries connected. To order to activate the battery, remove the front panel. To do this, pull them to the front side of the UPS-system. Now connect the two red battery connectors to one another. Finally, fit the front panel by reversing the sequence. -
You can also install this rack-tower-versatile model as a tower.
To do this, connect the two components to one foot (see Figure 7) and push the UPS system into the two feet from above (see Figure 8). Make sure the distance between the two feet is as great as possible to ensure stability. If you are using additional battery packs, use the extension plates for the foots.
Connecting additional battery packs
-
In order to install additional battery packs, remove the covers of the battery connector on the back of the UPS system and the battery packs, see Chap. 8.6 Rear view. If you are installing multiple battery packs, remove all the covers apart from the “V DC Input” cover on the last battery pack. Keep the covers and the screws.
-
Connect all plug connections between the battery packs and the UPS system. This involves connecting the “VDC Output” output on a battery pack with the “VDC Input” on the upstream battery pack. The battery pack connected directly to the UPS system is
connected to the “VDC Input” on the UPS system. A maximum of seven battery packs can be connected to the UPS system. -
Enter the number of battery packs used in menu no. 7 (see Chapter 4.3 Settings).
-
Continue the getting started process (see Chap. 3.6)
3.5 Installation in a rack, activating the batteries
The UPS system is delivered fully assembled.
CAUTION
The casing is very heavy (see Chap. 8 Technical data).
Optional slide rails (article no. Rack Kit) are available for the rack model.
The slide rails fit 48 cm (19 inch) racks with a depth of 48 to 78 cm.
- Fit the rack kit (separate assembly instructions provided with the rack kit).
- Adjust the display direction for horizontal rack installation. To do this, pull the frontpanel to the frontside of the UPS-system. Push the plastic clips apart and pull the display out of the holder. Push it 90 degrees anticlockwise and insert it back into the front panel.
- For safety reasons, the UPS system is delivered without the batteries connected. To activate the battery connect the two red battery connectors to one another.
- Finally, fit the front panel by reversing the sequence.
- Align the mounting bracket (L = left and R = right) with the screw holes on either side of the UPS system and affix it using the M4 x 8 countersunk screws provided (see Fehler! Verweisquelle konnte nicht gefunden werden.).
- Push the UPS system into the rack.
- Secure the mounting bracket of the UPS system in the rack (see Fehler! Verweisquelle konnte nicht gefunden werden.Fehler! Verweisquelle konnte nicht gefunden werden.).
- Continue the getting started process (see Chapter 3.6).
Connecting additional battery packs
-
In order to install additional battery packs, remove the covers of the battery connector on the back of the UPS system and the battery packs, see Chap. 8.6 Rear view. If you are installing multiple battery packs, remove all the covers apart from the “V DC Input” cover on the last battery pack. Keep the covers and the screws.
-
Connect all plug connections between the battery packs and the UPS system. This involves connecting the “VDC Output” output on a battery pack with the “VDC Input” on the upstream battery pack. The battery pack connected directly to the UPS system is
connected to the “VDC Input” on the UPS system. A maximum of seven battery packs can be connected to the UPS system. -
Enter the number of battery packs used in menu no. 7 (see Chapter 4.3 Settings).
-
Continue the getting started process (see Chap. 3.6)
3.6 Getting started
PLEASE NOTE
Make sure that the overall rated performance of the load connected does not
exceed the capacity of the UPS system. The power consumption of inductive
loads or laser printers can be very high, please take this into consideration
when specifying your UPS system.
- If you install additional battery packs, make sure they are properly connected (see Chap. 3.4, 3.5) and the battery fuse on the back of the battery packs is switched on.
- Connect the load with the UPS system without switching them on. Make sure that the UPS system has two groups of output sockets. The programmable output sockets can be switched independently of the remaining sockets. The programmable output sockets are primarily designed for less critical load which cannot be brought down using software. Critical load should not be connected to the programmable output sockets.
- Connect the power supply cable (supplied with the XANTO 2000 and 3000) for the UPS system into a socket. The display on the UPS system shows “Sb”,
- Hold the “ ” button on the UPS system down until you hear a short beep.
- The UPS system carries out a self-test, after which “OK” appears on the display. The UPS system is now operating in normal mode and supplying the load with reliable power.
- If an additional emergency power off switch has been installed, the emergency stop function needs to be tested.
- Switch the load on one by one.
PLEASE NOTE
The internal batteries charge up to 90% of their full capacity in less than
four hours. ONLINE recommends charging the batteries for 48 hours after
installation or extended periods of non-use.
The batteries start to charge as soon as the UPS system is connected to the
supply network and supplied with power, irrespective of the operating mode.
Starting in battery mode
- Hold the “ ” button on the UPS system down until you hear a beep.
- The UPS system is starting, the display then shows the battery status (see Chap. 4.4 Operating statuses) and supplies the load connected with reliable power.
- If the display is lit, fix all warnings (see Chap. 7.3 Trouble- shooting) and restart the UPS system.
Switching off
-
Hold the “OFF / ” button on the UPS system down for 2 seconds. When the continuous beep ends, the UPS system switches to standby mode.
PLEASE NOTE
If the “OFF / ” button is released after less than 2 seconds, the unit is not switched off. -
Disconnect the mains connection cable of the UPS system from the socket. The display on the UPS system goes out after a short time and the UPS system switches off completely.
Operation
4.1 Control panel
The UPS system has a control panel with three buttons and a graphical display
(see Figure 15).
Button| Function|
---|---|---
| Switch on| In standby mode: Press button for more than 2 seconds
Alarm signal OFF| In battery mode: Press button for more than 2 seconds, not
valid if there are warnings or error messages
Back to top| In configuration mode: In previous menu
Self-test| In normal, frequency converter or Eco mode: Press button for more
than 2 seconds
OFF / | Switch off| In normal mode: Hold the button down for longer than 2
seconds (switch to standby or bypass mode, depending on the menu setting)
Selection| In configuration mode: Press the button to apply the selection
SELECT / ****| Switch over| In normal mode: Switching the display from input
voltage, frequency and
current, battery voltage, current and capacity, UPS internal temperature,
output
voltage, frequency and current, load
Configuration mode| In standby mode: Press button for longer than 2 seconds to
start configuration mode
Down| In configuration mode: Back to menu
ON + SELECT| Manual bypass mode| In normal mode: Press both buttons for longer
than 2 seconds to switch to bypass mode. (Depending on the input voltage). In
order to exit bypass mode
/ switch back to normal mode, press both buttons at once until the permanent
beeping stops. Not available in frequency converter mode.
Exit| In configuration mode: Press both buttons to revert from the sub-menu to
the main menu or, if you are in the main menu, to exit configuration mode
immediately.
Table 2: Descriptions of display
PLEASE NOTE
During the function of battery test, the batteries must be completely charged
and the UPS system must be in normal mode.
4.2 Display and menu
Symbol | Description | Function |
---|---|---|
Input, battery, temperature, out- put, load | Pressing the SELECT button in |
normal mode displays the following measurements:
Input voltage, frequency and current, battery voltage, capacity and current,
UPS internal temperature, output voltage, current and frequency, load in %.
| Autonomy time| Display of remaining autonomy time
| Load display| Displays the current load. Each segment rep-resents 25 %. If
all the segments are lit up, the UPS system is working at 100% load.
| Overload| Indicates that the UPS system is overloaded
P| Programmable output sockets| Indicates actively programmed output
sockets
| Battery display| Indicates the current battery capacity. Each segment
represents 25 %. If all the segments are lit up, the battery is 100% charged.
| Battery empty| Battery symbol underneath battery display: Flashing indicates
the battery capacity is almost empty
| Configuration| Display of configuration menu options. For
further information, see Chap. 4.3 Settings
| Error| Display of error or alarm code. For complete table, see Chap. 7.1
Error codes
| Acoustic alarm| Displays a deactivated acoustic alarm, silent
| Input voltage| The UPS input is connected to the mains volt-age
| Rectifier| Rectifier active, battery charging
| Inverter| Active inverter, the load on the output sockets are UPS-protected
| Output sockets| Active UPS output
| Battery| Battery symbol in DC link: UPS system in bat-
tery mode
| Battery charging| Battery symbol in DC link: Battery in charging
mode
| Bypass mode| Bypass mode, the load is supplied directly by
the supply network without UPS protection
| High-efficiency
mode| The UPS system is working in high-efficiency
mode
CVCF| Frequency converters| The UPS system is working in frequency
converter
mode
PFC| Power factor correction| The power factor correction of the UPS
system
is
active
Table 3: Display
Alarm | Description |
---|---|
Every 10 seconds | UPS system in bypass mode |
Every 5 seconds | UPS system in battery mode |
Every 2 seconds | Battery voltage low |
Every second | Overload |
Continuous tone | Error |
Table 4: Acoustic alarm
Abbreviation | Display | Description |
---|---|---|
AAT | Time in battery mode | |
AC | Active Closed | |
AO | Active Open | |
BF | Battery Fault | |
BL | Battery Low | |
BP | Batterypack | |
BR | Battery Replace | |
BY | Bypass not within tolerance | |
CH | Charger | |
DIS | Disable | |
EAT | Remaining autonomy time | |
EE | EEPROM Error | |
EN | Enable | |
EP | EPO / Emergency Power Off | |
ESC | Escape | |
FU | Bypass frequency not stable | |
NC | Battery not connected | |
OC | Battery overloaded | |
OI | Input voltage too high | |
OK | OK | |
OL | Overload | |
ON | On | |
SB | Standby | |
SD | Shudown | |
SF | Site Fault | |
TP | Temperature |
Table 5: Overview of operating status
4.3 Settings
- Open configuration menu: Switch to standby- or bypass mode and press ****button for 2 seconds.
- Selection of menu options: Press or button until you reach the menu option you want (see Table 6: Configuration menu).
- Select menu option: Press OFF / button.
- Change menu setting: Press or button until you reach the setting you want (see Table 6: Configuration menu).
- Confirm setting: Press OFF / button.
- Exiting configuration menu: go to menu “00” or press and buttons at the same time.
Setting | Available options | Standard |
---|---|---|
Select output voltage: |
[208] = 208V
[220] = 220V
[230] = 230V
[240] = 240V| “230V”
| Frequency converter mode:
Switch frequency converter mode on or off
[ENA] = on (bypass mode not possible)
[DIS] = off| “DIS”
| Output frequency:
If frequency converter mode is possible,
the output frequency is in normal and battery
mode
[50] = 50 Hz
[60] = 60 Hz
No function if menu 2: frequency converter mode = DIS| “50”
| High-efficiency mode:
[ENA] = on
[DIS] = off| “DIS”
| Bypass mode:
If the UPS system is switched off, it is switched to bypass instead of standby
mode.
[ENA] = Enabled
[DIS] = Disabled| “DIS”
| Battery deep discharge protection:
Shutdown of all output sockets after time defined here.
[0 – 999] = Shutdown after 0 to 999 minutes.
[DIS] = Shutdown time dependent on battery capacity.
Attention: If the setting is [0], shutdown is after 10 seconds.| “DIS”
| Number of additional battery packs:
Selection of correct number of additional battery packs| “0”
| Autonomy time
Select from display
[AAT] = Remaining autonomy time
[RAT] = Time in battery mode|
| Emergency power off function:
[AO] = active open, emergency power off is active with emergency power off
contact open
[AC] = active close, emergency power off is active with emergency power off
contact closed| “AO”
| External isolating transformer:
If the function is activated, the switch from standby to UPS normal mode has a
90 degree phase shift and reduce the magnetisation current on the isolating
transformer.
If this function is disabled, the switch is in phase zero crossing.
[ENA] = External isolating transformer allowed on UPS output[DIS] = External
isolating transformer not allowed on UPS output| “DIS”
| Programmable output sockets:
[ENA] = Enabled
[DIS] = Disabled| DIS”
| Shutdown time for programmable output sockets:
[0 – 999] = Shutdown of programmable output sockets in battery mode after time
defined here.
Only available if “Programmable output sockets = active” and UPS system
restarted after setting the time.| “999”
| Charging voltage: Boost voltage
[2.25 – 2.40] = fine adjustment of boost
load voltage from 2.25 to 2.4V / cell| 2.36V / cell
| Charging voltage: Float voltage
[2.20 – 2.30] = fine adjustment of float
load voltage from 2.20 to 2.30V / cell| 2.28V / cell
| Site Wiring Fault Detection (SF):
[ENA] = on
[DIS] = off| «ENA»
| Exit:
Exiting configuration menu|
Table 6: Configuration menu
4.4 Operating statuses
The status of the UPS system is displayed on the control panel.
Normal operating mode In normal mode, “OK” is shown on the display and
the UPS system is fed by the supply network. The UPS system monitors the
batteries and charges them as required. The load connected is supplied with
reliable UPS power.
Battery mode
In battery mode, the following display appears: At the same time, an acoustic
alarm every 5 seconds indicates that the load connected are being supplied
with battery power.
If the battery charge level is low in battery mode, “BL” is shown on the
display starts to flash and the alarm sounds every 2 seconds. The remaining
autonomy time is low. Close all applications, as the UPS is about to shut down
automatically.
If the battery is exhausted, the UPS system shuts itself down. All displays
and the alarm are switched off.
If the supply network is restored after the UPS system has shut down, the UPS
is automatically restarted. The batteries are charged up and the load
connected is supplied with power.
Standby mode
If the UPS system is switched off and the power supply cable is connected, the
UPS system works in standby mode. The following display appears: No power is
available for the load connected. The battery is charged if necessary.
High-efficiency mode
In high-efficiency mode, the load are supplied via the bypass. The inverter is
always ready for use at the same time. If the supply network is outside the
tolerance, there is a smooth transition to normal mode.
The battery is charged in high-efficiency mode. Bypass mode
Bypass mode can be activated in normal mode by pressing the and
buttons together for 2 seconds. To switch back to normal mode, press and
buttons also together until the continuous alarm stops. In the event of an
overload, the UPS system automatically switches into bypass mode. A beep
sounds every 10 seconds. Frequency converter mode
In addition to regular UPS mode, the UPS system can also operate as a
frequency converter. This involves providing the load with a constant output
frequency of either 50 or 60Hz. Bypass is not available in frequency converter
mode. The battery is charged.
Communication and interfaces
5.1 RS 232 and USB interface
In order to establish communication between the UPS system and a computer,
connect the computer using a suitable data cable (cable provided) to the
RS-232 or USB interface on the UPS system (see Chap. 8.6 Rear view).
PLEASE NOTE
**** The RS-232 and USB communication interfaces cannot be used at the same
time.
The UPS system can then exchange data via the DataWatch software (see Chap.
5.5).
The assignment of the cable connection pins for the RS-232 communications
interface is shown in Figure 22, while the functions of the connection pins
can be found in Table 7: Pin assignment for RS-232 interface. Figure 22:
RS-232 interface (DB-9 connector)
Pin | Function |
---|---|
1 | Not used |
2 | Send data (TxD) |
3 | Receive data (RxD) |
4 | Not used |
5 | Mass |
6, 7, 8, 9 | Not used |
Table 7: Pin assignment for RS-232 interface
5.2 Slot for interface cards
The XANTO features a slot (see Chap. 8.6 Rear view) for the following
interface cards:
Product no. | Description |
---|---|
DW7SNMP30 | SNMP adapter Basic |
The SNMP adapter communicates via TCIP/IP with the load attached to the
network.
DW5SNMP30| SNMP adapter Professional
Works like Basic, but with additional interface for temperature sensor and
environment management.
DWAS400DC| AS400 relay card
Combined slot card for optional communication with IBM AS400 servers or
individual use of relay contacts. The following messages/contact outputs
are available: Normal mode, standby mode, battery mode, battery voltage low,
bypass mode, collective error, input for UPS shutdown.
Table 8: Interface cards
PLEASE NOTE
** The interface cards installed in the slot can be used in parallel with
the RS-232 or USB communication.
5.3 Emergency Power Off (EPO) function
The Emergency Power Off (EPO) function is used to remotely shut down the UPS
system and connected loads immediately. This means removing the bridge on the
emergency power off connector (back of UPS system, see Fig. 15) and connecting
an external emergency power off switch.
Cross section of connecting cable = 0.5 – 2.5mm 2 (AWG 13 – 20)
Recommended cross-section of connecting cable = 1.5mm 2(AWG 15)
CAUTION**
- The emergency power off switch must not be connected to circuits which are connected to the supply network. Reinforced insulation from the network is required. The emergency power off switch must be designed for at least 60V DC / 30V AC and 20mA.
- Depending on the programming via the UPS menu (see Chapter 4.3 Settings), either an opener or a closer can be used. The emergency power off function must be active for at least 250ms for proper operation.
- If the emergency power off function is activated, the input voltage of the UPS system also needs to be interrupted.
- The emergency power off function is only used to shut down the UPS voltage on an electronic basis.
PLEASE NOTE
- Leave the plug of the UPS system connected if you do not need the emergency power off function.
- Always test the emergency power off function before connecting a critical load. This avoids the load being switched off accidentally
Figure 23: Emergency power off connector
See Chap. 8.6 Rear view for the position of the emergency power off connector.
5.4 Surge voltage protection for data and telephone lines (DSL / telephone
/ fax / network)
The surge protection filters surge voltage from the data and telephone cables.
This involves connecting the incoming cable to the IN connection on the
reverse of the UPS system.
Connect the OUT connection to the end device. The data connection protection
cable protects networks with a transfer rate of 10 to 1000 Mbit/s.
5.5 DataWatch software
The XANTO range is supplied as standard with DataWatch, a comprehensive
software solution for shutting down and managing the PC or server system and
for monitoring the XANTO and the power supply network.
To ensure you are always working with the latest version of DataWatch, please
download it from the download area of www.online-usv.de.
DataWatch works in the background and is in constant communication with the
XANTO via the RS-232, USB or network protocol. The most famous of all
functions: Automatic data backup including the shutdown of running
applications and the proper shutdown of the whole system by means of a freely
configurable shutdown routine. At the same time, DataWatch has a comprehensive
messaging system, time-controlled test routines and event logging.
DataWatch supports all current operating systems.
As a client/server application, DataWatch works in networks and on local
workstations. Based on optional RCCMD agent (Remote Console Command), multiple
servers connected to a UPS system can be addressed and controlled across the
network without additional hardware.
Overview of functions: | UPS /LCD | DataWatch software |
---|
Display of input voltage. frequency and current. bat- tery voltage. current
and capacity. UPS intemal temperature. output voltage. frequency and current.
load| X| X
Change operation mode of the UPS system (nor- mal-. standby-. bypass-. high
efficiency- and converter-mode)| X| X
Changing the output voltage| X| X
Enable / disable and configure converter mode| X| X
Enable / disable high efficiency mode| X| X
Enable / disable high bypass mode| X| X
Configure and enable/disable the battery deep dis- charge protection| X| X
Configure additional battery packs| X| X
Select the type of autonomy lime (accumulated. re- maining)| X| X
Configure and enable/disable the emergency
power off function (EPO)| X| X
Configure and enable/disable the settings for oper- ation with external
isolation transformer| X| X
Configure and enable/disable the programmable outlet sockets| X| X
Changing the settings for charging voltage (boos. float)| X| X
Manual restart of the UPS system| X| X
Signalling battery failure| X| X
Advanced display of the total battery runtime| | X
Display of the serial number| | X
Local server shutdown via RS-232 / USB-interface| | X
Multi server shutdown via TCP/IP| | X
SNMP-proxy-agent| | X
Send E-Mail. SMS. broadcastmessages| | X
Manual UPS 10s-test| X| X
Manual UPS fulltest| | X
Auto UPS selftest| | X
Enabe/disable alarm for battery operation| X| X
Enable/disable all alarms| | X
Reset UPS system to factory settings| | X
Display alarm-, warning- and error-messages| X| X
Chronological record, display and export (csv) of warning-, alarm- and error-
messages| | X
Record, display and export (csv) of voltage, current, frequency and
temperature (datalog chart)| | X
Customized event configuration| | X
Maintenance
6.1 Care and maintenance
To ensure a long service life of the system, the area around the UPS system
should be kept clean and free of dust. If the area around the system is very
dusty, clean the external surfaces of the system with a vacuum cleaner.
To ensure a long service life for the batteries, the ambient temperature
should not exceed 25°C.
**PLEASE NOTE**
- Before transporting the UPS system, make sure that it is disconnected from the supply network and switched off.
- The service life of a battery varies as a function of how often it is used, intensity of use and ambient temperature. Batteries which are used beyond their expected service life often have reduced autonomy times. Replace the batteries in good time to ensure the system always runs at optimum performance.
6.2 Storage
If you intend to store the UPS system for an extended period, charge the
battery every three months by connecting the UPS system to the supply network
for five hours. The system should be stored in a cool, dry place.
6.3 When to change the batteries
If “BR” is shown on the display and an alarm signal sounds every 2 seconds,
the batteries need to be replaced. Contact your reseller or ONLINE
(www.usvshop24.de) to order new batteries.
6.4 Changing batteries in tower
PLEASE NOTE
Do not replace the batteries while the UPS system is in battery mode.
To replace the batteries, the UPS system must be switched off, disconnected
from the supply network and opened.
Batteries cannot be hot-swapped.
CAUTION
- Maintenance work must be carried out by a qualified technician who is familiar with batteries and the necessary safety measures. Do not allow unauthorised personnel to handle the batteries.
- Batteries pose the risk of an electric shock or injury due to high short circuit current. Take the following safety measures:
- remove watches, jewellery and other metal items
- only use tools with insulated handles
- do not place tools or metal components on the batteries
- The batteries must only be replaced with the same number of batteries of the same type.
- Batteries must be properly disposed of. When disposing of batteries, comply with the statutory regulations applicable in your location.
- Batteries must not be burnt. There is risk of explosion.
- Do not open or damage the battery or batteries. Battery acid can damage the eyes and skin and cause poisoning.
- DANGER OF ELECTRIC SHOCK. Never make changes to the battery cabling or connections. Attempting to change the battery cabling yourself could lead to serious injury.
- The batteries of the UPS system are very heavy. Be careful when handling heavy batteries.
6.5 Changing the batteries in rack
PLEASE NOTE
Do not replace the batteries while the UPS system is in battery mode.
The hot-swap functionality means the batteries can be replaced without
shutting down the UPS system and disconnecting the load.
If you would prefer to disconnect the UPS system before changing the
batteries, read Chapter 3.6 Getting started.
CAUTION
- Maintenance work must be carried out by a qualified technician who is familiar with batteries and the necessary safety measures. Do not allow unauthorised personnel to handle the batteries.
- Batteries pose the risk of an electric shock or injury due to high short circuit current. Take the following safety measures:
- remove watches, jewellery and other metal items
- only use tools with insulated handles
- do not place tools or metal components on the batteries
- The batteries must only be replaced with the same number of batteries of the same type.
- Batteries must be properly disposed of. When disposing of batteries, comply with the statutory regulations applicable in your location.
- Batteries must not be burnt. There is risk of explosion.
- Do not open or damage the battery or batteries. Battery acid can damage the eyes and skin and cause poisoning.
- DANGER OF ELECTRIC SHOCK. Never make changes to the battery cabling or connections. Attempting to change the battery cabling yourself could lead to serious injury.
- The batteries of the UPS system are very heavy. Be careful when handling heavy batteries.
The batteries are behind the front panel of the UPS system. The internal batteries are packed together for ease of handling.
-
Remove the front panel (see Figure 24). To do this pull it to the frontside of the UPS-system. PLEASE NOTE
There is a flat ribbon cable connecting the control panel to the UPS system. Do not pull on the cable or disconnect it. -
Disconnect the battery connector (see Figure 25).
-
Remove the battery cover (see Figure 26).
-
Carefully remove the battery insert using the handle.
-
Replace the batteries in the battery insert.
PLEASE NOTE
• Check that the replacement batteries have the same specifications as the old batteries.
• Read chapter 6.7 Disposing of the old batteries or UPS system for information on proper disposal. -
Reverse the removal procedure to reinsert the battery insert.
CAUTION
A small arc can occur when the batteries are connected to the UPS system. This is normal and represents no risk to personnel. Insert the battery able quickly and firmly into the battery plug connection in the UPS system. -
Continue with Chapter 6.6 Testing the new batteries.
6.6 Testing the new batteries
- To charge the batteries, connect the UPS to the supply network for 48 hours.
- In normal mode, hold the ON / / button for at least 2 seconds to start the self-test.
- If the batteries are faulty, a warning is displayed automatically (see Table 10: Warnings). Press “OK” to acknowledge a successful battery test and to switch the UPS system back into normal mode.
PLEASE NOTE
The UPS system only starts a self-test when the batteries are fully charged
and the UPS system is in normal mode with no active warning messages.
6.7 Disposing of the old batteries or UPS system
Find out from a local recycling centre how the old batteries or the UPS system
should properly be disposed of. Old batteries can also be returned to ONLINE
for disposal free of charge. Please contact Support (see Chap. 7.5)
CAUTION
- Batteries must not be burnt. There is risk of explosion.
- Batteries must be disposed of properly. Find out about the local disposal regulations.
- Do not open or damage the battery or batteries. Battery acid can damage the eyes and skin and cause poisoning.
Troubleshooting
The XANTO is designed for autonomous operation and automatically reports and
problems in the display.
7.1 Error codes
Error code | Event |
---|---|
01 | Error starting the DC link |
02 | DC link voltage too high |
03 | DC link voltage too low |
11 | Error starting inverter |
12 | Inverter voltage too high |
13 | Inverter voltage too low |
14 | Short circuit in inverter output |
27 | Battery voltage too high |
28 | Battery voltage too low |
2A | Short circuit on charger output |
41 | Temperature too high |
43 | Overload |
45 | Charger error |
49 | Input voltage too high |
Table 9: Error codes
If the UPS system indicates one of the error codes listed above, please
contact ONLINE support (see Chap. 7.5).
7.2 Warnings
Event | Symbol | Code | Alarm |
---|---|---|---|
Battery capacity low | Warning sound every 2 seconds | ||
Overload | Warning sound every second | ||
Input current too high | **** | 2 warning sounds every 10seconds | |
Battery not connected | Warning sound every 2 seconds | ||
Battery overload | Warning sound every 2 seconds | ||
UPS input error | Warning sound every 2 seconds | ||
Emergency power offactive | **** | Warning sound every 2 seconds | |
Temperature too high | **** | Warning sound every 2 seconds | |
Charger error | **** | Warning sound every 2 seconds | |
Battery error | **** | Warning sound every 2 seconds | |
Bypass voltage out of tolerance | Warning sound every 2 seconds | ||
Bypass frequency not stable | **** | Warning sound every 2 seconds | |
Replace battery | **** | Warning sound every 2 seconds | |
EEPROM Error | **** | Warning sound every 2 seconds |
Table 10: Warnings
7.3 Troubleshooting
Operating status| Possible cause|
Measure
---|---|---
The UPS system cannot be switched on, althoughthere are no alarms and the
input voltage is normal.| The input cable is not correctly connected to
the input socket.| Check that both connectors are properly inserted
in the sockets.
The input cable has beenaccidentally connected tothe UPS output sockets.|
Connect the input cable
to the UPS input.
The ** and symbols flash and an alarm is
sounded every 2 seconds.| Emergency power off is active.| Check that the
emergency power off connector
is seated firmly and the wire jumpers match the
menu settings in Chapter 4.3 (closed or open, depending on the jumper). Then
ress the OFF
button for 2 seconds and start the UPS system using the ON button.
The , symbols and the waming flash and an alarm is sounded every 2
seconds.| L and N wrong way round on UPS input.| Rotate the mains plug about
180 degrees.
The **, and symbols flash and an alarm is sounded every 2 seconds.| The
internal battery is not connected.| Check that the battery is properly
connected (see Chap. 3.4, 3.5). Then re-start the UPS system using the ON
button.
The ****, and symbols flash and an alarm is sounded every second.| The output
load on the UPS system is too high.| Reduce the load on the UPS output
sockets.
The load on the UPS out- put is too high, load is supplied via the bypass.|
Reduce the load on the UPS output sockets. The UPS is then automatically
switched back to normal mode.
The and symbols and the error code 43 are shown in the display. A permanent alarm sounds.
| If the overload persists, the UPS switches back to bypass mode.| Reduce the
load on the UPS output and then re-start the UPS.
UPS system shutting down because of too fre- quent or too extensive overload
on the UPS out- put.| Reduce the load on the UPS output sockets.
Then press the OFF but-ton for 2 seconds and then start the UPS using the ON
button.
The and symbols and the error code 49 are shown in the display. A
permanent alarm sounds.| The UPS input current entered is too high.| Reduce
the load on the UPS output sockets. The UPS is then automatically switched
back to normal mode.
Error code 14 and contin- uous alarm.| Short circuit in UPS out- put.|
Disconnect all the loads from the UPS output sockets and restart the UPS
system without
load. If the error continues to occur, please contact ONLINE support
(see Chap. 7.5). If the error has been fixed, check the load.
Autonomy time is shorter than expected.
| Battery is not fully charged.| Charge the battery for at least 5 hours. If
the error persists, please contact ONLINE support (see Chap. 7.5).
The battery is worn through age or faulty.| Replace the battery (see Chap.
6.4).
Error code 2A and continuous alarm.| Short circuit on charger output| Check
the external battery packs for wiring errors, it may be necessary to replace
the batteries if they are too old.
The ****and symbols flash and an alarm is sounded
every 2 seconds.| The fan is blocked or not working properly. The
temperature is too high.| Check the fan is working and there is enough space
behind the fan.
Table 11: Troubleshooting
7.4 Muting the alarm
In battery mode, hold the button for at least 2 seconds to mute the alarm.
Once the alarm is successfully muted, appears in the display. Check the status
the warning message has triggered and take appropriate measures to rectify the
situation. If the status of the warning message changes, the alarm is emitted
again. This has priority over the previous muting of the alarm.
PLEASE NOTE
The alarm cannot be muted for alarm and error messages.
7.5 Support
ONLINE USV-Systeme AG (ONLINE) is one of the leading manufacturers of
uninterruptible power supplies (UPS). Since 1988, the German company has
focussed on he development, production, sale and support of UPS systems.
Based on unit numbers sold,
ONLINE products are the German number one in the UPS market and
internationally recognised because of their top quality and excellent
support. As a German provider, ONLINE guarantees direct approachability,
simple processing and short response times. Comprehensive support is a matter
of course – before and after purchase.
ONLINE sets great store by reliable support and service.
-
Free direct advice and support on:
Software hotline: +49 (89) 242 39 90 – 13
Hardware hotline: +49 (89) 242 39 90 – 18 -
Free 24 h advance exchange
-
Interactive UPS configurator online or as app
-
2 years full warranty, optional renewal
-
Unbureaucratic 14 day money-back guarantee
-
Excellent product availability and wide network of distributors.
Further information: www.online-usv.de
Technical data
8.1 List of device types
UPS system| Form factor| UPS item no.| Service| Battery
pack Battery| pack item no.
---|---|---|---|---|---
XANTO 700| Tower| X700| 700VA1 700W| –|
XANTO 1000| Tower| X1000| 1000VA/1000W| XANTO 1000 / 1500 battery pack|
X1000BP
XANTO 1500| Tower| X1500| 1500VA/1500W
XANTO 2000| Tower| X2000| 2000VA/ 2000W| XANTO 2000battery pack| X2000BP
XANTO 3000| Tower| X3000| 3000VA/ 3000W| XANTO 3000battery pack| X3000BP
XANTO 700R| Rack| X700R| 700VA1 700W| –| –
XANTO 1000R| Rack| X1000R| 1000VA/1000W| XANTO battery pack
1000R / 1500R| X1000RBP
XANTO 1500R| Rack| X1500R| 1500VA/ 1500W
XANTO 2000R| Rack| X2000R| 2000VA/ 2000W| XANTO 2000Rbattery pack| X2000RBP
XANTO 3000R| Rack| X3000R| 3000VA/ 3000W| XANTO 3000Rbattery pack| X3000RBP
Table 12: Overview of UPS systems and battery packs
8.2 Dimensions and weight
UPS system | Dimensions (W x H x D) | Weight |
---|---|---|
**Tower models** | ||
XANTO 700 | 158 x 238 x 397 | 12.1kg |
XANTO 1000 | 158 x 238 x 397 | 13.4 kg |
XANTO 1500 | 158 x 238 x 397 | 15.0 kg |
XANTO 2000 | 190 x 335 x 415 | 20.3 kg |
XANTO 3000 | 190 x 335 x 415 | 28.5 kg |
XANTO 1000 / 1500 battery pack | 158 x 238 x 397 | 19.8 kg |
XANTO 2000 battery pack | 190 x 335 x 415 | 30.0 kg |
XANTO 3000 battery pack | 190 x 335 x 415 | 39.0 kg |
**Rack models** | ||
XANTO 700R | 438 x 88 (2U) x 412 | 11.6 kg |
--- | --- | --- |
XANTO 1000R | 438 x 88 (2U) x 412 | 14.1 kg |
XANTO 1500R | 438 x 88 (2U) x 412 | 15.5 kg |
XANTO 2000R | 438 x 88 (2U) x 512 | 19.5 kg |
XANTO 3000R | 438 x 88 (2U) x 632 | 27.5 kg |
XANTO 1000R / 1500R | 438 x 88 (2U) x 412 | 21.5 kg |
XANTO 2000R battery pack | 438 x 88 (2U) x 512 | 29.0 kg |
XANTO 3000R battery pack | 438 x 88 (2U) x 632 | 41.2 kg |
Table 13: Dimensions and weight
PLEASE NOTE
All rack models are just 2 height units (HE) tall.
8.3 Electrical connections
UPS system | Input connection | Output connections |
---|---|---|
XANTO 700 XANTO 700R | IEC320 C14 (10A) | 4x IEC320 C13 (10A) |
8x IEC320 C13 (10A)
XANTO 1000 XANTO 1000R| IEC320 C14 (10A)| 4x IEC320 C13 (10A)
8x IEC320 C13 (10A)
XANTO 1500
XANTO 1500R| IEC320 C14 (10A)| 4x IEC320 C13 (10A)
8x IEC320 C13 (10A)
XANTO 2000 XANTO 2000R| IEC320 C20 (16A)| 8x IEC320 C13 (10A)
XANTO 3000
XANTO 3000R| **** IEC320 C20 (16A)| 8x IEC320 C13 (10A)
1x IEC320 C19 (16A)
6x IEC320 C13 (10A)
1x IEC320 C19 (16A)
Table 14: Electrical connections
8.4 Electrical specifications
Model | XANTO 700/R | XANTO 1000/R | XANTO 1500/R | XANTO 2000/R | XANTO 3000/R |
---|
Electrical characteristics
Rated power (VA / W)| 700 /700| 1000 /1000| 1500 /1500| 2000 /2000| 3000 /3000
Technology| Doubleconversion, classification as per VFI-SS-111
Input voltage and tol- erance, battery opera- tion| 230V (110 – 300V @ 50%
load, 160 – 300V @ 100% load)
Input frequency| 50 / 60Hz (auto sensing)
Input current| 5.3A| 7.7A| 11.0A| 15.3A| 17.6A
Output voltage, toler- ance in battery opera- tion| 230V +/-1%
Output frequency, nor- mal operation| 50 / 60H +/-0,1Hz
Output frequency, bat- tery operation| 50 / 60H +/-3Hz
Output voltage adjust- able to| 208 / 220 / 230 / 240V
Max. output current| 3.5A| 5.0A| 7.5A| 10.0A| 15.0A
Switchover time| 0
Wave form| Sine
Efficiency, Normal operation| >89%| >91%
High-efficiency mode| >97%
Battery mode| >88%| >90%
Overload-compatible, normal mode|
<110%| Alarm
110 – 130%| Alarm, Bypass/Standby after 5 minutes
131 – 140%| Alarm, Bypass/Standby after 30 seconds
140%| Alarm, Bypass/Standby after 1.5s
Battery mode|
<110%| Alarm
110 – 130%| Alarm, Bypass/Standby after 2 minutes
131 – 140%| Alarm, Bypass/Standby after 10 seconds
140%| Alarm, Bypass/Standby after 1.5
Power loss, max.| 119W| 170W| 255W| 340W| 510W
Batteries
Autonomy times| See Table 17
Battery type| See Table 16
Design| Sealed, maintenance-free, valve-controlled, lead/acid, life expectancy 3 to 5 years in accordance with EUROBAT
Load voltage| 27.4V| 41.1V| 41.1V| 54.8V| 82.1V
Charging current| 2 – 12A| 2 – 8A
Communication
USB| Yes
RS-232:| Yes
Modem / Network
Over-voltage protec- tion| Yes
SNMP slot| Yes
EPO| Yes
Operating conditions, standards and approvals
Operating temperature| 0 – 40°C
Rel. air humidity| 20 – 90%
Operating altitude <1000m| Normal operating mode
1000 – 4000m| Performance reduction of 1% per 100m >1000m
Noise level, max.| <50dB
MTBF at 25°C (w/o battery)| >50.000 hours
Safety| EN62040-1
EMC, Performance| EN62040-2
Approval| CE
Protection class| IP20
Table 15: Electrical specifications
8.5 Batteries and autonomy time
UPS system | UPS internal battery | Battery pack |
---|---|---|
**Tower models** | ||
XANTO 700 | 24V (2x 12V / 9Ah) | – |
XANTO 1000 | 36V (3x 12V / 9Ah) | 36V (2x 3x 12V / 9Ah) |
XANTO 1500 | 36V (3x 12V / 9Ah) | 36V (2x 3x 12V / 9Ah) |
XANTO 2000 | 48V (4x 12V / 9Ah) | 48V (2x 4x 12V / 9Ah) |
XANTO 3000 | 72V (4x 12V / 9Ah) | 72V (2x 6x 12V / 9Ah) |
**Rack models** | ||
XANTO 700R | 24V (2x 12V / 9Ah) | – |
XANTO 1000R | 36V (3x 12V / 9Ah) | 36V (2x 3x 12V / 9Ah) |
XANTO 1500R | 36V (3x 12V / 9Ah) | 36V (2x 3x 12V / 9Ah) |
XANTO 2000R | 48V (4x 12V / 9Ah) | 48V (2x 4x 12V / 9Ah) |
XANTO 3000R | 72V (4x 12V / 9Ah) | 72V (2x 6x 12V / 9Ah) |
Table 16: Batteries
UPS sys- tem| Int. batt.| +1 BP| +2 BP| +3
BP| +4 BP| +5 BP| +6 BP| +7 BP
---|---|---|---|---|---|---|---|---
Tower models
XANTO 700| 24 /10| –| –| –| –| –| –| –
XANTO 1000| 27 /11| 103 /47| 190/ 86| 280 /130| 373 /174| 465 /221| 559 /268|
652 /315
XANTO 1500| 15 /6| 61 /28| 114/ 52| 171 /79| 229 /107| 269 /135| 349 /165| 409
/196
XANTO 2000| 16 /6| 65 /28| 121/ 52| 180 /78| 241 /106| 304 /135| 367 /165| 430
/195
XANTO 3000| 17 /6| 67 /29| 125/ 53| 186 /81| 249 /109| 314 /139| 378 /170| 443
/201
Rack models
XANTO 700R| 24 /10| –| –| –| –| –| –| –
XANTO 1000R| 27 /11| 103 /47| 190/ 86| 280 /130| 373 /174| 465 /221| 559 /268|
652 /315
XANTO 1500R| 15 /6| 61 /28| 114/ 52| 171 /79| 229 /107| 269 /135| 349 /165|
409 /196
XANTO 2000R| 16 /6| 65 /28| 121/ 52| 180 /78| 241 /106| 304 /135| 367 /165|
430 /195
XANTO 3000R| 17 /6| 67 /29| 125/ 53| 186 /81| 249 /109| 314 /139| 378 /170|
443 /201
Table 17: Autonomy times (in minutes) at 50 / 100% load, pf=0.7
8.6 Rear view 8.7 CE confirmation
DECLARATION of CONFORMITY
Luise-Ullrich-Strasse 8
82031 Griinwald/Germany
Telefon +49 (89) 2423990-10
Telefax +49 (89) 2423990-20
info@online-usv.de
www.online-usv.de
Warranty
ONLINE USV-Systeme AG (ONLINE) guarantees that this product will be free of
material and production faults for a period of two years from the purchase
date. A warranty of three years is valid for purchase dates March 1 st 2020
on. ONLINE’s obligation in accordance with this guarantee is restricted to the
repair or replacement (at ONLINE’s discretion) of any faulty products. Before
warranty claims can be asserted, a Returned Material Authorization (RMA)
number must be obtained from customer services. Products must be returned with
the postage paid by the sender, a brief description of the problem and
evidence of the place and date of purchase. This warranty does not apply to
devices damaged by accidents, negligence or misuse or those which have
otherwise been altered or modified.
Apart from the above exceptions, ONLINE accepts no explicit or tacit warranty,
including a guarantee of conventional quality or suitability for a specific
purpose. In some jurisdictions, the restriction or exclusion of tacit
guarantees is prohibited, which means that the restrictions or exclusions
above may not apply to the purchaser.
Irrespective of the above exclusions, ONLINE shall under no circumstances
accept liability for direct, indirect, specific, auxiliary or subsequent
damage caused as a result of the use of this product, even if ONLINE was
informed about the possibility of such damage. In particular, ONLINE shall not
be liable for costs of whatsoever nature, such as lost profit or revenue, loss
of equipment, loss of the use of device, loss of software or data, replacement
costs, third-party claims or other costs.
The content is copyright © 2020 by ONLINE USV-Systeme AG. All rights reserved.
Unauthorised reproduction in part or in whole is not permitted without
consent.
X700-3000_usermanual_engl_3_years
warranty_202003.docx
Documents / Resources
|
ONLINE XANTO 2000 UPS
Battery
[pdf] User Manual
XANTO 2000 UPS Battery, XANTO 2000, UPS Battery, Battery
---|---
References
- ONLINE USV-Systeme AG - USV Anlagen XANTO, ZINTO, YUNTO
- ONLINE USV-Systeme AG - USV Anlagen XANTO, ZINTO, YUNTO
- Online Srl - Gruppi di continuità e UPS
- ONLINE USV-Systeme AG - USV Anlagen XANTO, ZINTO, YUNTO
- ONLINE USV-Systeme AG - USV Anlagen XANTO, ZINTO, YUNTO
- ONLINE USV-Systeme AG - USV Anlagen XANTO, ZINTO, YUNTO
- online-usv - online-usv
- online-usv - online-usv
- Manual-Hub.com – Free PDF manuals!
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>