ONLINE USV ATS-30A Automatic Transfer Switch User Manual

June 4, 2024
ONLINE USV

ONLINE USV ATS-30A Automatic Transfer Switch

ONLINE USV ATS-30A Automatic Transfer Switch product AUTOMATIC TRANSFER SWITCH
Model ATS-30A

Introduction

This ATS-30A product is designed with two independent power inlets to supply power to the load from a prima-ry power source. Should primary power source fail, the secondary will automatically back up the connected equipment without any interruption. The transfer time from one line to another is seamless to the connected equipment. After switching to a secondary power source, the ATS can also switch power back to the primary input when power to the primary input is restored.

Package contents:

Product Overview

Front ViewONLINE USV ATS-30A Automatic Transfer Switch fig
1

  1. Power switch for input source A
  2. Power switch for input source B
  3. Circuit breaker for output 2
  4. Circuit breaker for output 3
  5. USB communication port
  6. RS-232 communication port
  7. Communication slot
  8. Operation indicators (please refer to section 4 for the details)

Back ViewONLINE USV ATS-30A Automatic Transfer Switch fig
2

  1. Contact port (please refer to section 7 for the details)
  2. Input source A connector
  3. Input source B connector
  4. Output connector “Output 1” (Grand)
  5. Output receptacles “Output 2” (IEC 16A)
  6. Output receptacles “Output 3” (IEC 10A)

Safety Warnings

Before using the unit, please read all instructions and cautionary markings on the unit, this manual and the batteries.

WARNING

  • The ATS must be connected to earth when in use. In line with current regulations, only use the cables that have been supplied with the machine. The power supply socket must be easily accessible to the operator.
  • The ATS has been designed exclusively to operate indoors. It is advisable to install it in areas where no inflammable liquids or gases, or other harmful or noxious substances, have been stored.

ATTENTION

  • A soft damp cloth may be used to clean the outside of the machine (always with the system disconnected from the mains power supply and users).
  • Do not use any type of solvent as this may damage the external finishing of the machine.
  • The ATS has been designed exclusively for professional use.

PLEASE NOTE
These instructions may be modified by the wiring regulations in force in the country where the ATS is purchased.

Operation Indicators & Status

ONLINE USV ATS-30A Automatic Transfer
Switch fig 3

  1. Source preference selector
  2. Priority setting LEDs
  3. Power source status LEDs
  4. Output source LEDs
  5. Fault indicator
  6. Alarm mute button

ONLINE USV ATS-30A Automatic Transfer Switch fig 4

Installation

PLEASE NOTE
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged.

Mounting the Unit
The unit can be mounted in a standard 19″-rack. Fasten the mounting brackets to the unit using the screws provided. With brackets attached securely, users can mount the unit in a standard 19″-rack as shown below.ONLINE USV ATS-30A
Automatic Transfer Switch fig 5

PLEASE NOTE
If the temperature around the unit will rise above 40°C, ventilation is required.

Connecting the Unit ONLINE USV ATS-30A Automatic Transfer Switch fig
6

  1. Take out the terminal cover by removing four screws.
  2. Fasten the input/output wirings through the cable gland.
  3. Fasten the terminal cover and cable gland to the unit. Then, customer can plug the user load to the output 10A (“Output 3”) or 16A (“Output 2”) sockets depending on user’s requirements.

Operation

Power On/Off
Put the input power switch in “ON” position. The output will then be supplied by the source set as selected.

Setting priority of power source
It is possible to set the power source preference to supply the output by pushing the button of “source preference selector”. The default power source is “Source A”.ONLINE USV ATS-30A Automatic Transfer Switch fig
7

Communication Port

The ATS is supplied with the following communication ports:

  • Serial port is available with RS232 com. port and USB com. port on the front panel.

PLEASE NOTE
the use of one port automatically excludes the other.

  • Contacts port on the rear panel.

Serial Ports: RS-232 & USB connectors
Put the input power switch in “ON” position. The output will then be supplied by the source set as selected.ONLINE USV ATS-30A Automatic Transfer Switch
fig 8

PLEASE NOTE
The utilization of the communication port is optional and it is not necessary for the correct functioning of the ATS.

Contact Ports
The contacts port is formed using six (6) pins numbered from left to right (see fig. 1), which can be connected to an external monitoring system (such as a BMS) in order to monitor the operational status of the ATS. The external equipment must respect the voltage and current characteristics of contacts port.

The contacts port provides the following pins:

  • Pin 1: common contact.

  • Pin 2: “Source B” active contact
    (if the contact between “pin 1” and “pin 2” is closed, output is supplied by “Source B”).

  • Pin 3: “Source A” active contact
    (if the contact between “pin 3” and “pin 1” is closed, output is supplied by “Source A”).

  • Pin 4: “Source A” status OK contact
    (if the contact between “pin 4” and “pin 1” is closed, “Source A” is present and regular).

  • Pin 5: “Source B” status OK contact
    (if the contact between “pin 5” and “pin 1” is closed, “Source B” is present and regular).

  • Pin 6: Status OK contact
    (if the contact between “pin 6” and “pin 1” is closed, ATS functioning status is regular).

The following diagram shows the functioning of the contacts port.

ATTENTION
The pins of the contact port are able to carry maximum current of 8A and maximum voltage of 250Vac.

Trouble Shooting

Use the table below to solve minor problems.ONLINE USV ATS-30A Automatic
Transfer Switch fig 11

If there is any abnormal situations occur, which doesn’t list above, please call the service people immediately for a professional examination.

Specifications

ONLINE USV ATS-30A Automatic Transfer Switch fig
12

Appendix

Input Voltage and Frequency ThresholdsONLINE USV ATS-30A Automatic Transfer
Switch fig 13

Imprint

ONLINE USV-Systeme AG
Luise-Ullrich-Straße 8
82031 Grünwald / Germany
Phone +49 (0)89-242 39 90-10 E-Mail [email protected]
www.online-usv.de

ONLINE USV-Systeme AG c/o swizzconnexx
Pilatusstrasse 17
5630 Muri / Switzerland
Phone +41 (0)41-500 28 68 E-Mail [email protected]
www.online-usv.ch

ONLINE UPS-Systems S.r.l.
Via Ferruccio Gilera 110
20862 Arcore (MB) / Italia
Phone +39 (0)39-205 14 44
E-Mail [email protected]

www.online-ups.it

The content is copyright © 2022 by ONLINE USV-Systeme AG.
All rights reserved. Unauthorised reproduction in part or in whole is not permitted without consent.
ONLINE USV-Systeme AG • Luise-Ullrich-Straße 8 • DE 82031 Grünwald • www .online-ups.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ONLINE USV User Manuals

Related Manuals