PowMr SOLXPOW X2 Series Solar Inverter Charger User Manual
- May 15, 2024
- PowMr
Table of Contents
POW-HVM1K-12V
POW-HVM 1.5K – 24VSOLAR INVERTER CHARGER
User Manual
ABOUT THIS MANUAL
1.1. Purpose
This manual describes the assembly, installation, operation and
troubleshooting of this unit. Please read this manual carefully before
installations and operations. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines as well as information
on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
-
Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
-
CAUTION –To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries.
Other types of batteries may burst, causing personal injury and damage. -
Do not disassemble the unit. Take it to a qualified service center when service or repair is required.
Incorrect re-assembly may result in a risk of electric shock or fire. -
To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning.
Turning off the unit will not reduce this risk. -
CAUTION -— Only qualified personnel can install this device with battery.
-
NEVER charge a frozen battery.
-
For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It’s very important to correctly operate this inverter/charger.
-
Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion. 9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
-
GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
-
NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
-
Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
INTRODUCTION
This is a multi-function inverter/charger, combining functions of inverter,
solar charger and battery charger to offer uninterruptible power support with
portable size. Its comprehensive LCD display offers user-configurable and
easy-accessible button operation such as battery charging current, AC/solar
charger priority, and acceptable input voltage based on different
applications.
3.1 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible to mains voltage or generator power
- Auto restart while AC is recovering
- Overload/ Over temperature/ short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
3.2 Basic System Architecture
The following illustration shows basic application for this inverter/charger.
It also includes following devices to have a complete running system:
- Generator or Utility.
- PV modules
Consult with your system integrator for other possible system architectures
depending on your requirements.
This inverter can power all kinds of appliances in home or office environment,
including motor-type appliances such as tube light, fan, refrigerator and air
conditioner.
3.3 Product Overview
- LCD display
- Status indicator
- Charging indicator
- Fault indicator
- Function buttons
- Power on/off switch
- AC input
- AC output
- PV input
- Battery input
- Circuit breaker
- Output receptacles
INSTALLATION
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. You should have received the following items inside of
package:
The unit x 1
User manual x 1
U-terminal x 2
4.2 Preparation
Before connecting all wirings, please take off bottom cover by removing two
screws as shown below.
4.3. Mountingthe Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It’s recommended to use M4 or MS
screws.
4.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested
to install a separate DC over-current protector or disconnect device between
battery and inverter. It may not be requested to have a disconnect device in
some applications, however, it’s still requested to have over-current
protection installed. Please refer to typical amperage in below table as
required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to
use appropriate cable for battery connection. To reduce risk of injury, please
use the proper recommended cable as below.
Recommended battery cable size:
Model | Wire Size | Cable (mm2) | Torque value (max) |
---|---|---|---|
1.0KW 12V | 1 x 6AWG | 14 | 5 Nm |
1.5KW 24V | 1 x 6AWG | 14 | 5 Nm |
Please follow below steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as below chart.
- Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals.
Recommended tool: #2 Pozi Screwdriver
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in
series.
CAUTION!! Before making the final DC connection or closing DC
breaker/disconnector, be sure positive (+) must be connected to positive (+)
and negative (-) must be connected to negative (-).
4.5 AC Input /OutputConnection
CAUTION!! Before connecting to AC input power source, please install a
separate AC breaker between inverter and AC input power source. This will
ensure the inverter can be securely disconnected during maintenance and fully
protected from over current of AC input. The recommended spec of AC breaker is
20A for 1.0KW and 20A for 1.5KW.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings.
Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to
use appropriate cable for AC input connection. To reduce risk of injury,
please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model | Gauge | Torque Value |
---|---|---|
1.0KW 12V | 14 AWG | 2Nm |
1.5KW 24V | 12AWG | 2Nm |
Please follow below steps to implement AC input/output connection:
-
Before making AC input/output connection, be sure to open DC protector or disconnector first.
-
Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
-
Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor ( **) first.
→ Ground (yellow-green)
L → LINE (brown or black)
N → Neutral (blue) WARNING:**
Be sure that AC power source is disconnected before attempting to hardwire it to the unit. -
Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
L → LINE (brown or black)
N → Neutral (blue) -
Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioner are required at least 2~ 3
minutes to restart because it’ serquired to have enough time to balance
refrigerant gas inside of circuits. If a power shortage occurs and recovers
ina short time, it will cause damage to your connected appliances. To prevent
this kind of damage, please check manufacturer of air conditioner if it’s
equipped with time-delay function before installation. Otherwise. this
inverter/charger will trig overload fault and cut off output to protect your
appliance but sometimes it still causes internal damage to the air
conditioner.
4.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC
circuit breaker between inverter and PV modules.
WARNING! It’s very important for system safety and efficient operation to
use appropriate cable for PV module connection. To reduce risk of injury,
please use the proper recommended cable size as below.
Model | Wire Size | Torque value ( max ) |
---|
1.0KW 12V
1.5KW 24V| 1x12AWG| 2 Nm
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL | 1.0 KW | 1.5 KW |
---|---|---|
Max. PV Array Open Circuit Voltage | 150Vdc | |
PV Array MPPT Voltage Range | 20 ∼ 150Vdc | 30 ∼ 150Vdc |
Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.
Solar Panel Spec. (reference)
– 250Wp
– Vmp: 30.1Vdc
– Imp: 8.3A
– Voc: 37.7Vdc
– Isc: 8.4A
– Cells: 60| SOLAR INPUT| Q’ty of panels| Total input power
---|---|---|---
(Min in serial: 4 pcs, max. in serial: 12 pcs)
2 pcs in serial| 2 pcs| 500W
3 pcs in serial| 3 pcs| 750W
4 pcs in serial| 4 pcs| 1000W
PV Module Wire Connection
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector.
Recommended tool: 4mm blade screwdriver
4.7 Final Assembly
After connecting all wirings, please put bottom cover back by screwing four
screws as shown below.
OPERATION
5.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected
well, simply press On/Off switch (located on the button of the case) to turn
on the unit.
5.2 Operation and Display Panel
The operation and display panel, shown in below chart, is on the front
panel of the inverter. It includes three indicators, four function keys and a
LCD display, indicating the operating status and input/output power
information.
LED Indicator
LED Indicator | Messages |
---|---|
AC/ INV | Green |
Flashing | Output is powered by battery or PV in battery mode. |
CHG | Green |
Flashing | Battery is charging. |
FAULT | Red |
Flashing | Warning condition occurs in the inverter. |
Function Keys
Function Key | Description |
---|---|
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter
setting mode. Press “UP” or “DOWN” button to select setting programs. And
then, press “ENTER” button to confirm the selection or ESC button to exit.
Setting Programs:
Program | Description | Selectable option |
---|---|---|
0 | Exit setting mode | Escape (default) |
1 | Output source priority: To configure load power source priority | Utility |
first (default) | Utility will provide power to the loads as first priority. |
Solar and battery energy will provide power to the loads only when utility
power is not available.
Solar first| Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, utility will
supply power to the loads at the same time.
Battery provides power to the loads only when any one condition happens:
– Solar energy and utility is not available.
– Solar energy is not sufficient and utility is not available.
SBU priority| Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, battery energy
will supply power to the loads at the same time.
Utility provides power to the loads only when battery voltage drops to either
low-level warning voltage or the setting point in program 12.
MKS priority| When solar is available,solar energy and battery energy will
supply power to the loads,the utility only supplies energy to the load as a
backup power.
When solar is not available,utility energy will supply power to the loads,the
battery only supplies energy to the load as a backup power.
2| Maximum charging current: To configure total charging current for solar and
utility chargers.
(Max. charging current = utility charging current + solar charging current)|
10A| 20A
---|---|---|---
30A| 40A (default)
50A| 60A
70A| 80A
3| AC input voltage range| Appliances (default)| If selected, acceptable AC
input voltage range will be within 90-280VAC.
UPS| If selected, acceptable AC input voltage range will be within 170-280VAC.
5| Battery type| AGM (default)| Flooded
User-Defined| If “User-Defined” is selected, battery charge voltage and low DC
cut-off voltage can be set up in program 26, 27 and 29.
6| Auto restart when overload occurs| Restart disable (default)| Restart
enable
7| Auto restart when over temperature occurs| Restart disable (default)|
Restart enable
9| Output frequency| 50Hz (default)| 60Hz
10| Output voltage| 220V| 230V (default)
240V|
11| Maximum utility charging current
Note: If setting value in program 02 is smaller than that in program in 11,
the inverter will apply charging current from program 02 for utility charger.|
2A| 10A
---|---|---|---
20A (default)| 30A
40A|
12| Setting voltage point back to utility source when selecting “MKS priority”
in program 01| 1.5KW 24V default setting:23V
1.0KW 12V default setting:11.5V
Setting range is from 21.0V to 26.2V for 1.5KW model 10.5V to 13.1V for 1.0KW
model Increment of each click is 0.1V
13| Setting voltage point back to battery mode when selecting “MKS priority”
in program 01| 1.5KW 24V default setting:27V| Battery fully charged
1.0KW 12V default setting:13.5V| Battery fully charged
Setting range is from 24.0V to 29.2V for 1.5KW model 12V to 14.6V for 1.0KW
model Increment of each click is 0.1V
14| Maximum battery discharge current when selecting “SBU priority” in program
01| 10A| 20A (default)
30A| 40A
16| Charger source priority: To configure charger source priority| If this
inverter/charger is working in Line, Standby or Fault mode, charger source can
be programmed as below:
---|---|---
Solar first| Solar energy will charge battery as first priority.
Utility will charge battery only when solar energy is not available.
Solar and Utility (default)| Solar energy and utility will charge battery at
the same time.
Only Solar| Solar energy will be the only charger source no matter utility is
available or not.
If this inverter/charger is working in Battery mode or Power saving mode, only
solar energy can charge battery. Solar energy will charge battery if it’s
available and sufficient.
18| Alarm control| Alarm on (default)| Alarm off
19| Auto return to default display screen| Return to default display screen
(default)| If selected, no matter how users switch display screen, it will
automatically return to default display screen (Input voltage /output voltage)
after no button is pressed for 1 minute.
Stay at latest screen| If selected, the display screen will stay at latest
screen user finally switches.
20| Backlight control| Backlight on (default)| Backlight off
22| Beeps while primary source is interrupted| Alarm on (default)| Alarm off
23| Overload bypass:
When enabled, the unit will transfer to line mode if overload occurs in
battery mode.| Bypass disable (default)| Bypass enable
25| Record Fault code| Record enable (default)| Record disable
---|---|---|---
26| Bulk charging voltage (C.V voltage)| 1.0KW 12V default setting:
14.1V
1.5KW 24V default setting: 28.2V
If self-defined is selected in program 5, this program can be set up. Setting
range is from 12V to 15V for 1.0KW 12V model and 24V to 30V for
1.5KW 24V model. Increment of each click is 0.1V.
27| Floating charging voltage| 1.0KW 12V default setting: 13.5V
1.5KW 24V default setting: 27.0V
If self-defined is selected in program 5, this program can be set up. Setting
range is from 12V to15V for 1.0KW 12V model and 24V to 30V for
1.5KW 24V model. Increment of each click is 0.1V.
29| Low DC cut-off voltage| 1.0KW 12V default setting: 10.0V
1.5KW 24V default setting: 20.0 V
If self-defined is selected in program 5, this program can be set up. Setting
range is from 10.0V to12.0V for 1.0KW 12v model and 20.0V to 24.0V for 1.5KW
24V model. Increment of each click is 0.1V. Low DC cut-off voltage will be
fixed to setting value no matter what percentage of load is connected.
30| Battery equalization| Battery equalization| Battery equalization disable
(default)
If “Flooded” or “User-Defined” is selected in program 05, this program can be
set up.
| Battery equalization voltage| tom 12V default setting: 14.6V
---|---|---
1.5KW 24V default setting: 29.2V
Setting range is from 12V to15V for 1.0KW 12v model and 24V to 30V for 1.5KW
24V model. Increment of each click is 0.1V.
33| Battery equalized time| 60min (default)| Setting range is from 5min to
900min. Increment of each click is 5min.
34| Battery equalized timeout| 120min (default)| Setting range is from 5min to
900 min. Increment of each click is 5 min.
35| Equalization interval| 30days (default)| Setting range is from 0 to 90
days. Increment of each click is 1 day
36| Equalization activated immediately| Enable| Disable (default)
If equalization function is enabled in program 30, this program can be set up.
If “Enable” is selected in this program, it’s to activate battery equalization
immediately and LCD main page will shows “ “. If “Disable” is selected, it
will cancel equalization function until next activated equalization time
arrives based on program 35 setting. At this time, “ ” will not be shown in
LCD main page.
5.4 Fault REference Code
Fault Code | Fault Event | Icon on |
---|---|---|
1 | Fan is locked when inverter is off. | |
2 | Over temperature | |
3 | Battery voltage is too high | |
4 | Battery voltage is too low | |
5 | Output short circuited or over temperature is detected by internal | |
converter components. | ||
6 | Output voltage is too high. | |
7 | Overload time out | |
8 | Bus voltage is too high | |
9 | Bus soft start failed | |
51 | Over current or surge | |
52 | Bus voltage is too low | |
53 | Inverter soft start failed | |
55 | Over DC voltage in AC output | |
57 | Current sensor failed | |
58 | Output voltage is too low | |
59 | PV voltage is over limitation |
5.5 Warning Indicator
Warning Code| Warning Event| Audible Alarm| Icon
flashing
---|---|---|---
1| Fan is locked when inverter
is on.| Beep three times every second|
3| Battery is over-charged| Beep once every second|
4| Low battery| Beep once every second|
7| Overload| Beep once every 0.5 second|
10| Output power derating| Beep twice every 3 seconds|
15| PV energy is low.| Beep twice every 3 seconds|
| Battery equalization| None|
CLEARANCE AND MAINTENANCE FOR ANTI -DUST KIT (Optional)
6.1 Overview
Every inverter is already installed with anti-dusk kit from factory. Inverter
will automatically detect this kit and activate internal thermal sensor to
adjust internal temperature. This kit also keeps dusk from your inverter and
increases product reliability in harsh environment.
6.2 Clearance and Maintenance(option)
Step 1: Please remove screws as below.
Step 2: Then, dustproof case can be removed and take out air filter foam as shown in below chart.
Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble
the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL | 1.0KW-12V | 1.5KW-24V |
---|---|---|
Input Voltage Waveform | Sinusoidal (utility or generator) | |
Nominal Input Voltage | 230Vac | |
Low Loss Voltage | 170Vac±1 OV (UPS); |
90Vac±10V(APPliances)
Low Loss Return Voltage| 180Vac±10V(UPS);
100Vac±10V(Appliances)
High Loss Voltage| 280Vac±10V
High Loss Return Voltage| 270Vac±10V
Max AC Input Voltage| 300Vac
Nominal Input Frequency| 50Hz / 60Hz (Auto detection)
Low Loss Frequency| 40±1Hz
Low Loss Return Frequency| 42±1Hz
High Loss Frequency| 65±1Hz
High Loss Return Frequency| 63±1Hz
Output Short Circuit Protection| Circuit Breaker
Efficiency (Line Mode)| >95% ( Rated R load, battery full charged )
Transfer Time| 10ms
Output power derating:
When AC input voltage drops to 170V, the output power will be derated.|
Table 2 Inverter Mode Specifications
INVERTER MODEL | 1.0KW-12V | 1.5KW-24V |
---|---|---|
Rated Output Power | 1000VA/1000W | 1500VA/1500W |
Output Voltage Waveform | Pure Sine Wave | |
Output Voltage Regulation | 230Vac±5% | |
Output Frequency | 50Hz | |
Peak Efficiency | 94% | |
Overload Protection | 3s@ ≥150% load,5s@ 100% ~ 150% load | |
Surge Capacity | 2* rated power for 5 seconds | |
Nominal DC Input Voltage | 12Vdc | 24Vdc |
Cold Start Voltage | 11.5Vdc | 23.0Vdc |
Low DC Warning Voltage
@ lo ad < 50%
@ load ≥50%| 11.25Vdc
11.0Vdc| 22.5Vdc
22Vdc
Low DC Warning Return Voltage
@ load < 50%
@ load≥50%| 11.75Vdc
11.5Vdc| 23.5Vdc
23Vdc
Low DC Cut-off Voltage
@ load < 50%
@ load ≥50%| 10.75Vdc
10.5Vdc| 21.5Vdc
21Vdc
High DC Recovery Voltage| 15.5Vdc| 31Vdc
High DC Cut-off Voltage| 16.0Vdc| 32Vdc
No Load Power Consumption| <28W| <28W
Table 3 Charge Mode Specifications
Utility Charging Mode
INVERTER MODEL| 1.0 KW-12V| 1.5KW-24V
Charging Algorithm| 3-Step
AC Charging Current 1 Max)| 40Amp
(@V / p= 230Vac)| 40Amp
HIV’ p 230Vac)
Bulk Charging Voltage| Flooded Battery| 15.| 29.
AGM i Gel Battery| 14.| 28.
Floating Charging Voltage| 13.5Vdc| 27Vdc
Charging Curve|
MPPT Solar Charging Mode
INVERTER MODEL| 1.OKW-12V| 1.5KW-24V
Max. PV Array Power| 600W| 1200W
PV Array MPPT Voltage Range| 20~150Vdc| 30 ~150Vdc
Max. PV Array Open Circuit Voltage| 150Vdc
Max solar charging current| 40Amp
Max(AC+Solar) Charging current| 80Amp
Table 4 General Specifications
INVERTER MODEL | 1.0KW-12V | 1.5KW-24V |
---|---|---|
Safety Certification |
CE
Operating Temperature Range|
-10ºC to 50 ºC
Storage temperature|
-15 ºC- 60 ºC
Humidity|
5% to 95% Relative Humidity (Non-condensing)
Dimension (D WH) mm|
286X240X91
Net Weight, kg|
3
|
3.5
SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
Tel/Fax: +86 755-28219903
Email: support@powmr.com
Web: www.powmr.com
Add: Henggang Street, Longgang District,
Shenzhen, Guangdong, China
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>