ONLINE USV X10000-PDU-HU Power Distribution Unit User Guide
- June 2, 2024
- ONLINE USV
Table of Contents
ONLINE USV X10000-PDU-HU Power Distribution Unit
Introduction
The product is used as an external power distribution unit in conjunction with UPS systems or large-scale voltage regulators. It supplies connected equipment with continuous power from any protected UPS, generator or mains input power source. It’s perfect to use in conjunction with 6-10K Rack online UPS.
Rack Mount the Unit
The module can be mounted to a 19” enclosure. Please follow the below chart
for rack mount installation.
Product Overview
- UPS input breaker
- Output breaker
- Output receptacles (10A)
- Output receptacles (16A)
- UPS input terminals
Installation and Operation
Inspection
Unpack the package and check the package contents. The shipping package
contains:
- Power distribution unit x 1
- Quick guide x 1
PLEASE NOTE
Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged during transportation. Do not install the unit and notify
the carrier and dealer immediately if there is any damage or lacking of some
parts. Please keep the original package in a safe place for future use.
Initial Setup
The Installation and wiring must be performed in accordance with the local
electric laws/regulations and execute the following instructions by
professional personnel.
-
Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire.
PLEASE NOTE
Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS’s maximum input current. Otherwise, the receptacle may be burned and destroyed. -
Switch off the mains switch in the building before installation.
-
Turn off and shut down the connected UPS.
-
Prepare wires based on the following table:
PLEASE NOTE- The cable for 6K should be able to withstand over 40A current. It is recommended to use 8AWG or thicker wire for safety and efficiency.
- The cable for 10K should be able to withstand over 63A current. It is recommended to use 6AWG or thicker wire for safety and efficiency.
- The selections for color of wires should be followed by the local electrical laws and regulations.
-
Remove the terminal block cover on the rear panel of the module. Then connect the wires according to the following terminal block diagrams:
Connect UPS and Power Distribution Unit
Remove the terminal block cover on the rear panel of the module. Then, connect
input terminals of UPS to input terminals of this module. Refer to blew chart
for wiring connection:
PLEASE NOTE
Make sure that the wires are connected tightly with the terminals. Put the
terminal block cover back to the rear panel.
Imprint
ONLINE USV-Systeme AG
Luise-Ullrich-Straße 8
82031 Grünwald / Germany
Phone +49 (0)89-242 39 90-10
E-Mail info@online-usv.de
ONLINE USV-Systeme AG
c/o swizzconnexx
Pilatusstrasse 17
5630 Muri / Switzerland
Phone +41 (0)41-500 28 68
E-Mail info@online-usv.ch
ONLINE UPS-Systems S.r.l.
Via Ferruccio Gilera 110
20862 Arcore (MB) / Italia
Phone +39 (0)39-205 14 44
E-Mail commerciale@online-ups.it
The content is copyright © 2022 by ONLINE USV-Systeme AG.
All rights reserved. Unauthorised reproduction in part or in whole is not
permitted without consent.
ONLINE USV-Systeme AG • Luise-Ullrich-Straße 8 • DE 82031 Grünwald • www .online-usv.de
References
- Servizi di spedizione, logistica e corriere internazionali | UPS - Italia
- USV – CTA Energy Systems AG
- EFFEKTA – innovating power. | EFFEKTA Regeltechnik GmbH
- ONLINE USV-Systeme AG - USV Anlagen XANTO, ZINTO, YUNTO
- Online Srl - Gruppi di continuità e UPS
- ONLINE USV-Systeme AG - USV Anlagen XANTO, ZINTO, YUNTO
- ONLINE USV-Systeme AG - USV Anlagen XANTO, ZINTO, YUNTO
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>