24-80 Battery Charger
Product Information
Specifications
Manufacturer: Victron Energy
Model: Skylla-TG
Available Models: Skylla-TG 24/80, Skylla-TG 24/100, Skylla-TG
24/100 3-Phase, Skylla-TG 48/50
Description
The Skylla-TG chargers are battery chargers designed and
manufactured by Victron Energy. These chargers are equipped with
protective devices and other technical features to ensure safe and
efficient charging of lead-acid batteries.
Warnings
-
The cover of the battery charger should only be removed by a
qualified technician. Prior to accessing the battery charger, the
mains supply circuit must be disconnected. -
Explosive gases can be produced during the charging of a
lead-acid battery. It is important to prevent flames and sparks and
ensure adequate ventilation during charging. -
The battery charger is not suitable for charging
non-rechargeable batteries. -
A dangerous voltage is present on some internal parts of the
battery charger. Caution should be exercised when handling the
unit. -
The battery charger is not protected against reverse battery
polarity. It is essential to follow the installation procedure to
avoid damage to the charger. The warranty will be void if the
charger becomes defective due to reverse battery polarity.
Product Usage Instructions
1. Installation
To install the Skylla-TG charger, follow these steps:
-
Ensure that the mains supply circuit is disconnected before
proceeding with the installation. -
Select a suitable location for the charger, ensuring proper
ventilation and protection from moisture. -
Connect the charger to the battery using appropriate cables and
connectors. Ensure the correct polarity is maintained. -
Connect the charger to the mains power supply using a suitable
power cable. -
Once all connections are secure, restore the mains supply and
verify that the charger is receiving power.
2. Operation
To operate the Skylla-TG charger, follow these steps:
-
Ensure that the charger is properly installed and connected to
a suitable battery. -
Turn on the charger using the power switch or button, if
available. -
Monitor the charging process and ensure that the charger is
functioning correctly. -
Adjust any settings or parameters as required, following the
instructions provided in the manual. -
Once the battery is fully charged, disconnect the charger from
the mains power supply and remove the connections to the
battery.
3. Maintenance
Regular maintenance of the Skylla-TG charger is important to
ensure optimal performance and longevity. Follow these
guidelines:
-
Inspect the charger regularly for any signs of damage or
wear. -
Clean the charger’s exterior using a soft cloth and mild
detergent, if necessary. -
Ensure that all connections are tight and secure.
-
Check the charger’s cooling system for any obstructions or
buildup of dust or debris. Clean if necessary. -
Refer to the manual for any specific maintenance procedures
recommended by the manufacturer.
FAQ
Q: Can the Skylla-TG charger be used to charge non-rechargeable
batteries?
A: No, the Skylla-TG charger is specifically designed for
charging lead-acid rechargeable batteries and should not be used
with non-rechargeable batteries.
Q: Is the battery charger protected against reverse battery
polarity?
A: No, the battery charger is not protected against reverse
battery polarity. It is important to follow the installation
procedure to avoid damage to the charger. The warranty will be void
if the charger becomes defective due to reverse battery
polarity.
Q: What should I do if I encounter a fault or issue with the
Skylla-TG charger?
A: Refer to the “Fault Tracing” section in the manual for
guidance on troubleshooting common issues. If the problem persists,
contact a qualified technician or the manufacturer for further
assistance.
Victron Energy
USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG
SKYLLA-TG 24/80 SKYLLA-TG 24/100 SKYLLA-TG 24/100 3-Phase SKYLLA-TG 48/50
SECTIONS
English Nederlands Deutsch
Page
3 31 59
Manual Skylla-TG
1
Copyrights 2004 Victron Energy B.V. All Rights Reserved
This publication or parts thereof, may not be reproduced in any form, by any
method, for any purpose.
VICTRON ENERGY B.V. MAKES NO WARRANTY, EITHER EXPESSED OR IMPLIED, INCLUDING
BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE, REGARDING THESE VICTRON ENERGY PRODUCTS AND MAKES SUCH
VICTRON ENERGY PRODUCTS AVAILABLE SOLELY ON AN “AS IS” BASIS.
IN NO EVENT SHALL VICTRON ENERGY B.V. BE LIABLE TO ANYONE FOR SPECIAL,
COLLATERAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES IN CONNECTION WITH OR ARISING
OUT OF PURCHASE OR USE OF THESE VICTRON ENERGY PRODUCTS. THE SOLE AND
EXCLUSIVE LIABILITY TO VICTRON ENERGY B.V., REGARDLESS OF THE FORM OF ACTION,
SHALL NOT EXCEED THE PURCHASE PRICE OF THE VICTRON ENERGY PRODUCTS DESCRIBED
HEREIN.
For conditions of use and permission to use this manual for publication in
other than the English language, contact Victron Energy B.V.
Victron Energy B.V. reserves the right to revise and improve its products as
it sees fit. This publication describes the state of this product at the time
of its publication and may not reflect the product at all times in the future.
2
Victron Energy Manual Skylla-TG
USER MANUAL
SKYLLA-TG 24/80 SKYLLA-TG 24/100 SKYLLA-TG 24/100 3-Phase SKYLLA-TG 48/50
Manual Skylla-TG
3
USER MANUAL SKYLLA-TG CHARGERS
1. INTRODUCTION
5
1.1 Victron Energy
5
1.2 The Skylla-TG chargers
5
1.3 Warnings
5
2. DESCRIPTION
7
2.1 The Skylla-TG battery charger
7
2.2 The battery
8
2.3 Protection
9
3. DIRECTIONS FOR USE
11
3.1 Installation
11
3.2 Operation
15
3.3 Maintenance
16
4. OPTIONS
17
4.1 Permanent boost-charge
17
4.1 Permanent boost-charge
18
4.2 Adjusting the charge voltage
18
4.3 Adjusting the equalize-charging mode time
19
4.4 Diode-splitter charge voltage compensation.
19
4.5 Traction battery compensation
20
4.6 Use as a power-supply
20
4.7 Use of a temperature sensor.
20
4.8 Charging batteries with voltage sensing
21
4.9 Intelligent startup
21
4.10 Connecting the output voltage alarm
22
4.11 Connecting remote panels
22
4.12 Connecting a remote on/off switch
23
4.13 Connecting a remote boost switch
23
4.14 Connecting a voltmeter
24
4.15 Connecting a ampèremeter
24
5. FAULT TRACING
25
6. TECHNICAL SPECIFICATIONS
26
6.1 General
26
6.2 Input
26
6.3 Output
27
6.4 Mechanical
28
4
Manual Skylla-TG
1. INTRODUCTION
1.1 Victron Energy
Victron Energy has established an international reputation as a leading
designer and manufacturer of power systems. Our R&D department is the driving
force behind this reputation. This department is continually seeking new ways
of incorporating the latest technology in our products. A Victron Energy power
system can supply high-quality energy at places where there is no permanent
mains power source available. An automatic stand alone operating energy supply
system can consist of: a Victron Energy inverter, a Victron Energy battery
charger, if required a Victron Energy Mains Manager and batteries with
sufficient capacity. Our equipment can be used in numerous situations, in the
field, on ships and in other places where mobile power is indispensable.
Victron Energy equipment can be used for all kinds of electrical appliances
for household, technical and administrative purposes and instruments
susceptible to interference.
1.2 The Skylla-TG chargers
This manual contains directions for installing the following chargers: Skylla-
TG 24/80, Skylla-TG 24/100, Skylla-TG 24/100 3-Phase and the Skylla-TG 48/50.
It describes the functionality and operation including their protective
devices and other technical features.
1.3 Warnings
The cover of the battery charger may only be removed by a qualified
technician. Before obtaining access to the battery charger the mains supply
circuit must be disconnected.
Explosive gasses can occur during charging a lead-acid battery. Prevent flames
and sparks. Provide adequate ventilation during charging.
The battery charger can not be used to charge non-rechargeable batteries.
There is a dangerous voltage present on some oMf athneuaml eTtaitlapnaprtasge
5 inside the battery charger.
The battery charger is NOT protected against reverse battery polarity. (“+”
connected to “-” and “-” connected to “+”). Follow the installation procedure.
The warranty expires when the battery charger becomes defective due to reverse
battery polarity.
The on/off switch at the front of the cabinet does not switch off the mains
supply.
Disconnect the mains supply before making or breaking the connections to the
battery.
Do not use the voltage sense facility in combination with the diodesplitter
compensation. This will raise the output voltage, which could damage the
battery.
6
Manual Skylla-TG
2. DESCRIPTION
2.1 The Skylla-TG battery charger
The TG battery charger is a fully automatic charger for 24V or 48V batteries
and is powered by a mains voltage of 230Vac, 50Hz. It charges the battery
according to the IUoUo characteristic, which is a 3-stage charging
characteristic. This characteristic is shown in illustration 1. While
charging, the TG continuously measures the battery voltage and current and
bases the charging voltage and current on the measured values.
Illustration 1. The IUoUo charge characteristic.
Type
24V / 80A 24V / 100A 24V / 100A 3-Ph 48V / 50A
Boost voltage
28,5 Vdc 28,5 Vdc 28,5 Vdc 57 Vdc
Float voltage
26,5 Vdc 26,5 Vdc 26,5 Vdc 53 Vdc
Minimal voltage 25 Vdc 25 Vdc 25 Vdc 50 Vdc
Assuming that the battery is discharged, the TG charger starts charging in the boost-charge mode. In this mode the battery is charged until the battery voltage reaches the boost voltage. At this point the battery is charged to approximately 80% of its maximum capacity. This is the end of the boost-charge mode and the TG charger automatically switches to the equalizecharge mode. During the equalize-charge mode the charging voltage stays the same as the boost voltage but the charge current slowly decreases. The duration of this mode is pre-selectable to 4, 8 or 12 hours. The standard time of the equalize- mode is 4 hours. After this time the TG charger automatically switches into the float-charge mode. In the float-charge mode the charge voltage changes into the float voltage and the charge current continues to decrease. This mode lasts for 20 hours. After the float-charge mode the charger returns to the equalize-charge mode for 30 minutes, this is to compensate for the normal leakage or self discharge of the battery.
Manual Skylla-TG
7
The TG charger can remain connected to the battery continuously, without gas formation taking place, caused by overcharging. It is not necessary to disconnect the battery from the charger during long time storage, for example during the winter storage of a ship. The TG charger will keep your battery in optimum condition under all circumstances and will prolong the lifetime of your battery. A parallel load connected to the battery can cause a voltage drop. The TG charger automatically switches into the boost-charge mode when the battery voltage drops below the minimal voltage. The TG charger is equipped with a separate starter-battery connection to charge an extra battery, like a starter-battery. You can use this battery for starting machines, like a boat engine for this application. The TG charger has a stabilised output voltage. Therefore the TG charger can also be used as a DC power supply in applications where no battery is present.
2.2 The battery
The TG charger can charge various batteries. The recommended battery capacity is indicated
in the table below:
Type
Recommended capacity
24/80
300 – 600 Ah
24/100
500 – 1000 Ah
24/100 3-Ph
500 – 1000 Ah
48/50
200 – 400 Ah
The charge voltages of the TG charger are factory set. Most battery manufactures recommend these charging voltages for optimal charging of 24V or 48V lead-acid batteries. It is possible to charge different types of batteries, like traction batteries. To charge these batteries the charging voltages of the charger have to be changed. Contact your Victron Energy dealer or battery dealer for more details about the recommended charging voltages.
8
Manual Skylla-TG
2.3 Protection
The battery charger is safe to use due to its robust design and its internal
electronic protection. This chapter describes the various internal electronic
protective devices.
Maximum charge current protection The battery charger provides a maximum
charge current of 50A for the 50A charger,
80A for the 80A charger, or 100A for the 100A charger. This level is
electronically limited and is factory set. The maximum output current can also
be limited by using an external potentiometerpanel, the Victron Energy COV
panel.
Short circuit protection The charger output is protected against short-
circuits. The short-circuit current is
electronically limited at 50A, 80A or 100A, according to the model. In this
condition the output voltage approaches 0 Volt. The battery charger resumes
normal operation when the short circuit is removed. The short circuit current
can also be reduced by the Victron Energy COV panel.
Input protection The charger mains-input is protected with a fuse. The charger
will not be damaged by using input voltage between 0 and 300 Vac. The charger
will not be damaged by using input voltage frequency between 0 and 65
Hz.
Over voltage protection The charger switches off automatically when the
battery voltage becomes higher than
the over voltage value. The charger switches back on when the battery voltage
becomes less than the raise value. See the table below.
Model 24V 48V
Over voltage value 35,5 Vdc 68,1 Vdc
Raise value 33,5 Vdc 64.1 Vdc
The charger output is protected with a fuse.
Starter battery protection The output current of the starter battery output is
electronically limited at 4A. The starter
battery output is also protected against wrong connections by means of a 10A
fuse.
Manual Skylla-TG
9
Temperature protection The internal temperature of the charger is measured
continuously. However, due to a
high ambient temperature outside the cabinet the temperature within the
battery charger can rise. When the external temperature of the battery charger
becomes higher than 40°C, the output current decreases and the Failure led
flashes. Before the internal temperature becomes too high due to extreme
conditions the charger switches off and the Failure led illuminates
continuously. The charger resumes operation when the internal temperature is
restored within limits.
Voltage sense protection When the voltage sense facility is used the charger
automatically decreases the output
voltage when the voltage loss over the battery cables is more than 2 Volt in
total.
Battery watchdog timer
The charger is equipped with a battery watchdog timer. This timer measures the
duration of the boost mode. The moment the boost mode lasts longer than 10
hours, the charger will switch to float mode. The charging voltage will then
become the float voltage. In this way it is prevented that a defective battery
is needlessly charged with a high charging voltage.
10
Manual Skylla-TG
3. DIRECTIONS FOR USE
3.1 Installation
Find a dry and well-ventilated area to mount the TG charger and battery. Keep
the distance between the charger and the battery less than 6 meters. The
charger may be wall or floor mounted. Mounting on a wall improves the air
circulation within the charger cabinet and will prolong the lifetime of the
battery charger. The holes for the mains cable, the battery connections, the
remote connections and the earth connection are located at the bottom of the
battery charger housing, see illustration 2.
Hole for the remote cable
Hole for the positive battery cable
Illustration 2, Location of the charger connection holes
Hole for the mains cable
M6 Earth Stud
Hole for the starter battery cables
Hole for the negative battery cable
Connecting earth Connect the earth screw to a real earth-point. Connections to
earth have to be according to applicable safety standards. On a ship: Connect
the earth screw to the earth plate or to the hull of the ship. On land:
Connect the earth screw to the earth of the mains. Mobile applications (a
vehicle, a car or a caravan): Connect the earth screw to the frame
of the vehicle. v
Connecting the battery The connections between the TG charger and the battery
are essential for a good operation of the charger. Therefore the battery
connections need tightening well. It is important to use short and thick
battery cables to minimise the voltage losses in the cable. Cable resistance
decreases accordingly as the cables become shorter and thicker. Therefore it
is not recommended to use cables longer than 6 meters. The table below shows
the recommended cable core thickness.
Type 24/80 24/100 24/100 3-Ph 48/50
core diameter of cables until 1,5m 16 mm2 35 mm2 35 mm2 10 mm2
core diameter of cables between 1,5m and 6m 25 mm2 50 mm2 50 mm2 16 mm2
Manual Skylla-TG
11
The battery connection sequence
The Titan is NOT protected against reverse battery polarity. (“+” connected to
“-” and “-” connected to “+”). Follow the installation procedure. The warranty
expires when the Titan becomes defective due to reverse polarity.
Disconnect the mains supply before making or breaking the connections to the battery.
The on/off switch at the front of the cabinet does not switch off the mains supply.
Check if the charger is switched off and if the mains supply is disconnected.
Remove the front of the battery charger to access the battery connections. If
not placed, place the connection tool to the negative battery connection (-)
of the
charger, see illustration 3. Connect the positive battery-cable (+) to the
positive battery connection terminal on the
charger printed circuit board, see illustration 3. Hook the negative battery-
cable (-) to the connection tool, see illustration 3. Check if the green led
illuminates, see illustration 3. If not the positive and negative
battery cables have been reversed. Disconnect the connection tool and connect
the negative battery cable (-).
The battery disconnection sequence Switch off the charger. Disconnect the mains supply. Disconnect the negative battery-cable. Disconnect the positive battery-cable.
– starter battery connection
+ starter battery connection
Green led
Negative battery connection
Output fuses
Illustration 3.
Positive battery connection
Location of the battery
Red led
connections
Connection tool
12
Manual Skylla-TG
Connecting the starter battery The starter battery has to be connected using
wire with a core of at least 1.5 mm2. Connect the positive (+) battery-pole to
the right side of the starter battery connector, see
illustration 3. Connect the negative (-) battery-pole to the left side of the
starter battery connector, see
illustration 3.
Connecting the mains Check if the battery is already connected to the charger.
Remove the front of the battery charger to access the AC input connector.
Connect the mains PE cable (green/yellow) to the AC input connector located on
the
circuit board, see illustration 4. Connect the mains neutral cable (blue) to
the AC input connector. Connect the mains line cable (brown) to the AC input
connector. Plug the mains cable into the mains socket. Make sure that the
mains socket is connected
to earth. The connection to the earth of the mains has to be according to
applicable safety standards.
AC input connector
N L
Illustration 4. Location of the AC input connector.
PE connection neutral connection
line connection
Manual Skylla-TG
13
illustration 4b Connecting the 3phase mains Check if the battery is already
connected to the charger. Remove the front of the battery charger to access
the AC input connector. Connect the mains PE cable (green/yellow) to the AC
input connector located next to the
Magnetic Circuit Breaker, see illustration 4b. Connect the 3 mains line cables
to the Magnetic Circuit Breaker. Plug the mains cable into the mains socket.
Make sure that the mains socket is connected
to earth. The connection to the earth of the mains has to be according to
applicable safety standards.
14
Manual Skylla-TG
3.2 Operation
Located on the front of the TG charger are an on/off switch and three rows of
leds, as shown in illustration 5.
The battery charger can be switched on and off with the on/off switch. The
“output voltage” leds indicate the output voltage value. The “output current”
leds indicate the output current value. The other leds indicates the state of
the charger.
Illustration 5. Example of the battery charger front panel.
The operation sequence:
Explosive gasses can occur during charging a lead-acid battery. Prevent flames
and sparks. Provide adequate ventilation during charging.
Switching the charger on with the on/off switch results in the following: The
“on” led will flash for about 2 seconds. In these first 2 seconds the charger
reads all
input signals and calculates the necessary output voltage. After 2 seconds the
charger will switch on and the “on” led illuminates. According to the
condition of the battery, the charger will start in the boost-charge mode or
at float-charge mode. If the battery is not full the “boost” led illuminates
and the charger will start boost-charging the battery. A dip switch can be
used to set the charger so that it will always start charging in the boost
mode, irrespective of the condition of the battery. When the battery voltage
has reached the boost voltage the charger will change into the equalize-charge
mode and the “equalize” led illuminates. This mode will last for a
preselectable time of 4, 8 or 12 hours. After this time the charger will enter
the float-charge mode and the “float” led will illuminate.
Manual Skylla-TG
15
After the batteries are charged the TG charger does not have to be switched
off and the batteries can stay connected to the battery charger.
3.3 Maintenance
The TG charger does not require any specific maintenance. However an annual
check of the battery connections is recommended. Keep the charger dry, clean
and free of dust. If any problems arise, use the fault finding procedure to
trace the fault, see chapter 5.
16
Manual Skylla-TG
4. OPTIONS
The TG charger is factory set to standard values. Some of these standard
values can be changed by a qualified electrical technician into customised
values. This chapter describes which values can be changed and how to change
them.
The cover of the Titan may only be removed by a qualified technician. Before
obtaining access to the Titan the mains supply circuit must be disconnected.
There is a dangerous voltage present on some of the metal parts inside the
battery charger.
Attention ! The value of the potentiometers I, Vboost and Vfloat may only be
adjusted by a qualified electrician. The remaining potentiometers may not be
adjusted at any case.
Opening of the battery charger cabinet In order to change the standard values
the front of the charger has to be removed. Disconnect the mains from the
charger and wait two minutes. Unscrew the 4 screws on the front of the
cabinet, see illustration 6. Remove the front panel of the battery charger.
Adjustments can be made by means of turning a potentiometer or by changing the
position of a switch on the DIP-switch. See illustration 7 for the location of
the DIP-switch and the potentiometers.
Illustration 6. Removing the front.
DIP switch
I Vboost Vfloat
Illustration 7. Location of the DIP-switch and potentiometers.
Manual Skylla-TG
17
4.1 Permanent boost-charge
In some cases, for example when the battery is almost empty, it is recommended
to permanent boost-charge the battery for 10 hours. Do not permanently boost-
charge sealed lead-acid batteries. Contact your Victron Energy dealer or
battery dealer for more information on charging the battery.
To set the charger into the permanent boost-charge mode : Place the DIP switch
number 8 “R boost” to the left. In this mode the
battery is being charged to the boost voltage. Do not permanent boost-charge
the battery for longer than 10 hours
as this can cause long term gas formation in the battery and will damage the
battery. While a battery is being boost-charged, check the water level of the
battery frequently and if necessary add distilled water to the battery.
4.2 Adjusting the charge voltage
The battery charger has a factory set float and boost voltage. The boost-
voltage is always higher than the float-voltage. These charging voltages are
the recommended values from almost every battery manufacturer. Before
adjusting the charge voltage disconnect the temperature sensor and/or the
voltage sense wires.
To change the float-voltage: Remove all batteries and other users that are
connected to the output of
the battery charger. Plug the AC plug into the mains and switch on the
charger. Place DIP-switches 7 “Eq2” and 6 “Eq1” to the left position, this
will
reduce the equalize time to 0 hours. The charger switches into the float-
charge mode. Place DIP-switch 4 “fine” to the left position in order to
accurately adjust the output voltage. Measure the float-voltage on the charger
output by using a precision voltage meter. Adjust the float-voltage by turning
the “V float” potentiometer until the recommended voltage is reached. Correct
the equalize time by moving DIP-switch 7 “Eq2” and 6 “Eq1”. Place DIP-switch 4
“fine” to the right position. In this position the output voltage is less
sensitive to influence of temperature.
18
Manual Skylla-TG
To change the boost-voltage: Place DIP-switch 7 “Eq2” to the right and place
DIP-switch 8 “R
boost” to the left. The charger switches into the boost-charge mode. Place
DIP-switch 4 “fine” to the left position in order to accurately
adjust the output voltage. Measure the boost-voltage on the charger output by
using a precision
voltage meter. Adjust the boost-voltage by turning the “V boost” potentiometer
until the recommended voltage is reached. Replace DIP-switch 8 “R boost” to
the right. Correct the equalize time by moving DIP-switch 7 “Eq2” and 6 “Eq1”.
Place DIP-switch 4 “fine” to the right position. In this position the output
voltage is less sensitive to influence of temperature.
4.3 Adjusting the equalize-charging mode time
The duration of the equalize-charge mode can be changed to fit the
specifications of the battery. The duration of the equalize-charge mode can be
set to 0, 4, 8 or 12 hours. When selecting 0 hours, the charger will skip the
equalize-charge mode and will directly switch into the float-charge mode. The
standard equalize-time is 4 hours. According to the table below the duration
of the equalize-charge mode can be set by moving the DIP-switches 7 “Eq2” and
6 “Eq1” in the corresponding way:
0 hours 4 hours 8 hours 12 hours
4.4 Diode-splitter charge voltage compensation.
If a diode-splitter (Victron Energy Argo) is connected to the TG charger the
charge voltage have to be raised to compensate for the voltage loss over the
diode-splitter. If the voltage-sense option is used, do not use the diode-
splitter compensation. When both options are used simultaneously the output
voltage will be too high.
To select the diode-splitter option: Place DIP switch 5 “split” to the left.
Manual Skylla-TG
19
4.5 Traction battery compensation
If a Traction-battery is connected to the TG charger the charge voltages have
to be changed. The output voltage has to be raised to correctly charge the
traction-battery. It is possible that the charge voltages are not correct
after activating this compensation. See for adjusting the charge voltages
chapter 4.2.
To set the charger into the traction mode: Place DIP-switch 3 “trac” to the
left.
4.6 Use as a power-supply
The TG charger can be used as a power supply without the obligation to connect
a battery to the charger output.
To use the charger as a power supply: Put the charger into the permanent
boost-charge mode, see chapter 4.1. Adjusted the output voltage to the desired
voltage, see chapter 4.2.
With the above mentioned procedure the output voltage range is limited. When
the full output voltage range is required please contact your Victron Energy
dealer. See chapter 6.3 for details.
4.7 Use of a temperature sensor.
The temperature sensor supplied with the charger can be connected to the
charger by using the 3 meter cable with stripped and tinned cable ends. This
sensor should be mounted on the battery. The temperature sensor adjusts the
charging voltage according to the battery temperature.
To connect the temperature sensor: Disconnect the mains, Connect the – (black
wire) of the temperature sensor
to the “-tmp” connector, see illustration 8. Connect the + (red wire) of the
temperature sensor
to the “+ tmp” connector, see illustration 8. Switch on the mains. If the
temperature sensor is correctly connected the
“TMP OK” on the printed circuit board led illuminates. If this led does not
illuminate or flashes, the sensor is not connected correctly.
Illustration 8. Location of the external connections.
20
Manual Skylla-TG
4.8 Charging batteries with voltage sensing
Do not use the voltage sense facility in combination with the diodesplitter
compensation, as this will raise the output voltage.
When high current runs trough a thin cable between the charger and the battery
there will be a voltage loss in the cables. The charging voltage measured at
the battery poles will be lower than the specified voltage and this will
result in a longer charging time. However, the charger is equipped with a
voltage sense facility. The battery voltage is exactly measured and the
charger increases the output voltage to compensate for the voltage loss across
the cables. The charger can compensate for a maximum of 2V voltage loss over
the cables. When the voltage loss is bigger than 2V the “on” led flashes and
the failure led illuminates. The charge voltage will decrease until the
voltage loss becomes maximum 2 Volt. The “on” led flashes and the failure led
illuminates until the charger is manually switched off. When this occurs the
battery cables have to be replaced because they are too thin or have bad
connections.
To install the voltage sense option: Disconnect the mains. Connect a red 0,75
mm2 wire to the positive battery pole and the “+Vse” connector of
the charger, see illustration 8. Connect a black 0,75 mm2 wire between the
negative pole of the battery and the “-
Vse” connector of the charger, see illustration 8. For properly functioning
both wires have to be connected. Switch on the mains. The “VSE OK” led on the
printed circuit board illuminates when connected correctly.
If this led does not illuminate the voltage sense wires are wrongly connected.
4.9 Intelligent startup
The factory setting of the charger is such that the battery voltage is checked
when the charger is switched on (intelligent startup). In the case of a flat
battery, the charger will start charging in the boost mode. If the battery
voltage is sufficiently high during charger startup, the charger will be
charging in the float mode. In some situations it may be desirable for the
charger not to check the battery voltage upon startup. With this charger this
function is enabled by sliding dip switch 2 “Watch” to the left. When this dip
switch is positioned on the left, the charger will always start charging in
the boost mode. When dip switch 2 “Watch” is positioned on the right, it is
checked upon startup whether the battery voltage is sufficiently high to
enable a start in the float mode. If it is not, the charger is started in the
boost mode as yet.
Manual Skylla-TG
21
4.10 Connecting the output voltage alarm
The charger is equipped with a potential free alarm contact (change over
type). If the battery voltage is in between Vmin and Vmax the contact is
activated. (See figure 8, remote connections: NO, NC, COM).
Model 24V 48V
Vmin 23,8 Vdc 47,6 Vdc
Vmax 33,5 Vdc 67 Vdc
4.11 Connecting remote panels
Victron Energy provides four optional remote panels that can be connected to
the charger. See illustration 8 for the circuit board connector where the
remote panels have to be connected to.
The COV panel: The maximum charging current of 50A, 80A or 100A, according to the model, can be limited with an external panel. This panel, the Victron Energy COV panel, contains an adjustable potentiometer. Limiting the maximum charging current can be useful to meet the batteries specifications, or to make sure the shore fuse does not blow.
To connect the panel: Disconnect the mains. Connect the panel to the “+ pot” and “-pot” connector.
The CMV panel: This panel indicates the charging mode and possible failures.
To connect the panel: Disconnect the mains. Connect the boost led to the ” L_BO” connector. Connect the equalize led to the “L_EQ” connector. Connect the float led to the “L_FL” connector. Connect the failure led to the “L_FA” connector. Connect the ground of the panel to the “GND” connector.
The CSV panel: With the CSV panel the charger can be switched on or off. On the panel a green “on” led is present. To operate the CSV panel you first have to switch the charger on with the on/off switch located on the front panel of the charger.
22
Manual Skylla-TG
To connect the panel: Disconnect the mains Connect the on led to the “L_ON”
connector. Connect the ground of the panel to the “GND” connector. Connect the
“TG switch” to the “REM” connector.
The SKC panel: This panel indicates if the charger is on or off, it indicates
the charging mode and it contains an adjustable potentiometer. Limiting the
maximum charging current can be useful to more accurately charge the batteries
according the manufacturers specifications, or to make sure the shore fuse
does not blow.
To connect the panel: Disconnect the mains. Connect the on led to the “L_ON”
connector. Connect the boost led to the ” L_BO” connector. Connect the float
led to the “L_FL” connector. Connect the ground of the panel to the “GND”
connector. Connect current control to the “+ POT” and “-POT” connector.
4.12 Connecting a remote on/off switch
A remote switch can be connected to the charger so the charger can be switched
on and off from a remote location. To operate the switch, first switch the
charger on with the on/off switch located on the charger.
To connect the remote on/off switch: Disconnect the mains. Connect the switch
in between the “REM” and the “GND” connector.
4.13 Connecting a remote boost switch
A remote switch can be connected to the charger so the charger can be switched
permanently into the boost-charge mode. Due to parallel loads connected to the
battery it is advised to switch the charger into the permanent boost-charging
mode in order not to discharge the battery. If the switch is closed the
charger switches into the permanent boost-charge mode. If the switch is opened
again the charger will automatically go to the float-charge mode. This in
order not to overcharge a battery with charging it to long with higher
charging voltage.
To connect the boost switch: Disconnect the mains. Connect one pole of the
switch to the “RBOO” connector. Connect the other pole of the switch to the
“GND” connector.
Manual Skylla-TG
23
4.14 Connecting a voltmeter
The remote-connector offers a possibility to connect a voltmeter. It is
possible to connect a digital as well as an analogue voltmeter. This output
can only be used when the voltagesense is connected. The voltage at this
output is equal to the voltage measured at the point where the voltage sense
wires are connected.
Connecting a voltmeter Disconnect the mains voltage. Make sure that the
voltage sense wires are connected, see chapter 4.8. Connect a black wire
between the “-” connection of the voltmeter and “-VM” at the
remote connector. Connect a red wire between the “+” connection of the
voltmeter and “+VM” at the
remote connector. Connect the mains voltage.
4.15 Connecting a ampèremeter
The remote connector offers a possibility to connect an ampèremeter, which
indicates the output current of the charger. For the 50A charger an
ampèremeter, which indicates 50A at 60mV input voltage is required. For the
80A charger an ampèremeter, which indicates 80A at 60mV input voltage is
required, likewise for the 100A charger an ampèremeter, which indicates 100A
at 60mV input voltage is required.
Connecting an ampèremeter Disconnect the mains voltage. Connect a black wire
between the “-” connection of the ampèremeter and “-AM” at
the remote connector. Connect a red wire between the “+” connection of the
ampèremeter and “+AM” at the
remote connector. Connect the mains voltage.
24
Manual Skylla-TG
5. FAULT TRACING
When a fault occurs in the battery charger, the following table can be used in order to find the
fault. Before the TG is being checked, make sure that all the devices connected to the battery
charger are removed. If the fault can not be solved contact your Victron Energy dealer.
Problem
Possible cause
Solution
The charger does not The mains voltage has to be in between Measure the mains voltage and make sure it is in
operate
185Vac and 265 Vac.
between 185Vac and 265Vac.
A broken input fuse.
Return the charger to your dealer.
The battery is not The equalize-charge mode is set to being fully charged a too short period.
Set the equalize-charge mode to a longer time.
A bad battery connection.
Check the battery connections.
The boost charge voltage is set to a wrong value.
Adjust the boost charge voltage to the right value.
The float charge voltage is
Adjust the float charge voltage to the right
set to a wrong value.
value.
The capacity of the battery is too large. Connect a battery with a smaller capacity or
install a larger charger.
The output fuses are broken.
Replace the output fuses.
The battery is being overcharged
The failure led illuminates The failure led flashes The failure led flashes in
a code1 The failure led illuminates in combination with a blinking on/off led
The battery charger is set into the permanent boost-charge mode.
Deselect the permanent boost DIP-switch (Rboost).
The boost charge voltage is set to a wrong value. The float charge voltage is set to a wrong value. A bad battery. The battery is located in a warm place
Adjust the boost charge voltage to the right value. Adjust the float charge
voltage to right value.
Check the battery. Connect a temperature sensor
The battery is too small.
Reduce the charge current.
The charger is switched off as a result of a high ambient temperature.
The charger is reducing the output current as a result of a high ambient
temperature. The output fuses are broken.
Place the charger in a cooler, or better ventilated place. Place the charger
in a cooler, or better ventilated place.
Replace the output fuses.
There is a voltage drop higher than 2V Turn the charger off, replace battery cables and
across the battery cables.
connect them well.
A qualified technician may only remove the cover of the Titan. Before obtaining access to the Titan the mains supply circuit must be disconnected.
1Flashing code sequence is two times on in one second and then one second off.
Manual Skylla-TG
25
6. TECHNICAL SPECIFICATIONS
6.1 General
Switch on behaviour Efficiency 24/80
24/100 48/50 Temperature range
EMC Emission
Immunity Vibration Safety
Charger can switch on under every load 85 % at 230Vac and 30Vdc 80A 85 % at 230Vac and 30Vdc 100A 85 % at 230Vac and 60Vdc 50A 0 °C until +40 °C, decreasing output power if temperature > +40ºC According Council Directive 89/336 EEG EN 55014 (1993) EN 61000-3-2 (1995) EN 61000-3-3 (1995) EN 55104 (1995) IEC 68-2-6 (1982) EN 60335-2-29 (1991)
6.2 Input
Input voltage range
Input voltage range 3-Ph
Frequency range
Maximum Input current
model:
24/80
24/100
24/100 3-Ph
48/50
Input fuse
model:
24/80
24/100,48/50
24/100 3-Ph
Cos phi / power factor
185 – 265 Vac,
full output power available
320 – 460 Vac 3-Ph, full output power available
45 – 65 Hz,
full output power available
At 230V ac input voltage :
12A at 30V / 80A
16A at 30V / 100A
3x 6A at 30V / 100A
16A at 60V / 50A
250Vac/8A and 12A fast 6,3x32mm, or equivalent 2 x 250Vac /12A fast 6,3x32mm, or equivalent 2 x 250Vac /12A fast 6,3x32mm, or equivalent and 3-Ph MCB 6A B 1,0
26
Manual Skylla-TG
6.3 Output
Model
TG 24/80
Boost charge voltage Float charge voltage Output voltage range Output voltage range supply mode2 Charge characteristic Voltage compensation for diode- splitter, via DIP-switch
28,50 Vdc 26,50 Vdc 24-33Vdc 0-33Vdc
IUoUo + 0,6 V
TG 24/100 TG 24/100 3-Ph
TG 48/50
28,50 Vdc 26,50 Vdc 24-33Vdc 0-33Vdc
57 Vdc 53 Vdc 48-66Vdc 0-66Vdc
IUoUo + 0,6 V
IUoUo + 0,6 V
Model
TG 24/80
Current/voltage stability
± 1 %
Boost charge voltage
compensation for traction
+ 2,0 V
battery, via DIP-switch
Maximum output current
80A
Output current range
0-80A
Output voltage ripple
measured with a 50A, 80A or <100mVtt
100A resistive load
Maximum output power
2250W
Short circuit current
80A
Maximum starter battery
4A
current
Low battery alarm relay
23,8 Vdc
±0,8Vdc
High battery alarm relay
33.5Vdc
± 0,8Vdc
Output fuse (flat car fuse)
6 x 20A
Leakage current from battery
when the battery charger is 6,4 mA
turned off
- 6,3mm x 32mm fuse 30A slow
TG 24/100 TG 48/50
± 1 %
± 1 %
+ 2,0 V
+ 4,0 V
100A 0-100A
50A 0-50A
<100mVtt <200mVtt
3000W 100A 4A
3000W 50A n/a
23,8 Vdc ±0,8Vdc 33.5Vdc ± 0,8Vdc 8 x 20A
47,6 Vdc ±1,6Vdc 67 Vdc ± 1,6Vdc other *
6,4 mA 6,4 mA
2 Contact your Victron Energy dealer for this option.
Manual Skylla-TG
27
6.4 Mechanical
TG 24/80 TG24/100 TG48/50
TG 24/100 3-Ph
Cabinet Protection Colour Dimensions Dimensions including box Weight Weight including box Input 230Vac connection Battery connection Earth connection Temperature sensor connection Starter battery connection Cooling Noise Relative humidity
Aluminium sea water resistant IP 21 Blue (RAL5012), epoxy coated 368 x 250 x 257mm 438 x 320 x 330mm
Aluminium sea water resistant IP 21 Blue (RAL5012), epoxy coated 515 x 260 x 265mm 645 x 370 x 375mm
9.8 Kg 10.5 Kg
23 Kg 24,3 Kg
Connection block, suitable for wires up to 4 mm² M8 bolts
Connection block, suitable for wires up to 10 mm² M8 bolts
M6 Studs at bottom of the cabinet M6 Stud at bottom of the cabinet
Connection block
Connection block
Connection block, suitable for wires Connection block, suitable for wires
up to 1,5mm²
up to 1,5mm²
Forced air cooling
Forced air cooling
< 45dB(A)
< 45dB(A)
95% (maximal)
95% (maximal)
28
Manual Skylla-TG
250
25
200
250
7
309
365
23
Ø 6 220
25
200
Ø 8
All measurements in mm. © victron energy b.v.
Skylla-TG 24/80, 24/100 and Titan 48/50 dimensions
drawing no.: TI020000 date: 220703
revision.: 01
Manual Skylla-TG
29
258
29
200
250
7
515 459
2 3 Ø 6 220
2 5
2 0 0
All measurements in © victron energy b.v.
30
Ø 8 Skylla-TG 24/100 3-Phase dimensions
Manual Skylla-TG
drawing no.: TI030000 date: 130504 revision.: 00