vacon ® 100 x ac drives
installation manual
VACON 100 X AC Drives
SAFETY
This manual contains clearly marked warning information which is intended for
your personal safety and to avoid any unintentional damage to the product or
connected appliances. Please read the warning information carefully. VACON ®
100 X is a drive designed to control asynchronous AC motors and permanent
magnet motors. The product is intended to be installed in a restricted access
location and for a general purpose use.
Only trained and qualified personnel authorized by the manufacturer are
allowed to install, operate and maintain the drive.
1.1 Signs
The cautions and warnings are marked as follows:
Table 1. Warning signs.
__
| = DANGEROUS VOLTAGE!
---|---
__
| = HOT SURFACE
__
| = WARNING or CAUTION
1.2 Units
The dimensions used in this manual conform to International Metric System
units, otherwise known as SI (Systeme International dunnite’s) units. For the
purpose of the equipment’s UL certification, some of these dimensions are
accompanied by their imperial equivalents.
Table 2. Unit conversion table.
Physical dimension| SI value| US value| Conversion
factor| US designation
---|---|---|---|---
length| 1 mm| 0.0394 inch| 25.4| inch
Weight| 1 kg| 2.205 lb| 0.4536| pound
Speed| 1 min-1| 1 rpm| 1| revolution per minute
Temperature| 1 °C (T1)| 33.8 °F (T2)| T2 = T1 x 9/5 + 32| Fahrenheit
Torque| 1 Nm| 8.851 lbf in| 0.113| pound-force inches
Power| 1 kW| 1.341 HP| 0.7457| horsepower
1.3 Danger
| The components of the power unit of VACON ® 100 X drives are live when the
drive is connected to mains potential. Coming into contact with this voltage
is extremely dangerous and may cause death or severe injury.
---|---
| The motor terminals (U, V, W), the brake resistor terminals and the DC-
terminals are live when VACON ® 100 X Drive is connected to the mains, even if
the motor is not running.
| After disconnecting the AC drive from the mains, wait until the indicators
on the keypad go out (if no keypad is connected, see the indicators on the
cover). Wait an additional 30 seconds before doing any work on the
connections of VACON ® 100 X Drive. Do not open the unit before this time has
expired. After expiration of this time, use measuring equipment to absolutely
ensure that no voltage is present. Always ensure absence of voltage before
starting any electrical work!
| The control I/O-terminals are isolated from the mains potential. However,
the relay outputs and other I/O-terminals may have a dangerous control voltage
present even when VACON ® 100 X drive is disconnected from the mains.
| Before connecting the AC drive to mains make sure that the powerhead of
VACON ® 100 X Drive is mounted firmly on the terminal box.
| During a coast stop (see the Application Manual), the motor is still
generating voltage to the drive. Therefore, do not touch the components of the
AC drive before the motor has completely stopped and wait until the
indicators on the keypad go out (if no keypad is connected, see the indicators
on the cover). Wait an additional 30 seconds before starting any work on the
drive.
| The terminals are live when the VACON® 100X Drive is connected to a
photovoltaic system. Photovoltaic cells generate DC voltage even at low
intensity of sunlight.
1.4 Warnings
| VACON® 100 X AC drive is meant for fixed installations (on the motor or on
the wall) only.
---|---
| Only DVC A circuits (Decisive Voltage Class A, according to IEC 61800-5-1)
are allowed to be connected to the control unit. This advice aims to protect
both the drive and the client application. The manufacturer is not responsible
for direct or consequential damages resulting from unsafe connections of
external circuits to the drive. See paragraph 1.6 for more details.
| Do not perform any measurements when the AC drive is connected to the mains.
| The touch current of VACON® 100 X AC drives exceeds 3.5mA AC. According to
standard EN61800-5-1, a reinforced protective ground connection must be
ensured. See paragraph 1.5 for more details.
| If the AC drive is used as a part of a machine, the machine manufacturer is
responsible for providing the machine with a supply disconnecting device (EN
0204-1). See paragraph 4.1 for more details.
| Only spare parts delivered by the manufacturer can be used.
| At power-up or fault reset, the motor will start immediately if the start
signal is active, (unless the pulse control for Start/Stop logic has been
selected) and the STO inputs are ready to be used (normal operation). The I/O
functionalities (including start inputs) may change if parameters,
applications or software are changed. Disconnect, therefore, the motor if an
unexpected start can cause danger. This is valid only if STO inputs are
energized. For prevention on unexpected restart, use appropriate safety relay
connected to the STO inputs.
| The motor starts automatically after automatic fault reset if the autorepeat
function is activated. See the Application Manual for more detailed
information. This is valid only if STO inputs are energized. For prevention
on unexpected restart, use appropriate safety relay connected to the STO
inputs.
| Before performing any measurement on the motor or on the motor cable,
disconnect the motor cable from the AC drive.
| Do not perform any voltage withstand test on any part of VACON ® 100 X. The
tests must be performed according to a specific procedure. Ignoring this
procedure may damage the product.
| Do not touch the components on the circuit boards. Static voltage discharge
may damage the components.
| Check that the EMC level of the AC drive corresponds to the requirements of
your supply network. See paragraph 6.2 for more details.
| In a domestic environment, this product may cause radio interference in
which case supplementary mitigation measures may be required.
| Optional keypad is IP66/Type 4X outdoor rated. Strong exposure to direct
sunlight or to heavy temperatures might cause the degradation of display LCD.
| Do not remove the EMC screws in the solar pump application. IT (impedance-
grounded) AC supply network is not allowed in the solar pump application.
| If a service switch is used on the motor output, parameter P3.1.2.6 Motor
Switch must be enabled. Otherwise turning the service switch on while the
drive is modulating can cause damage to the equipment. Notice also that the
parameter Motor Switch is designed for a service switch or similar, not for
repeated daily use.
1.5 Grounding and earth fault protection
The VACON® 100 X AC drive must always be earthed with a grounding conductor
connected to the grounding terminal marked with .
See Table 16 and Table 17 for the required cross-section of phase conductor
and protective grounding conductor (both made of copper).
Since the touch current exceeds 3.5 mA AC, according to EN61800-5-1, the MM4
and MM5 must have a fixed connection and provision of an additional terminal
for a second protective grounding conductor of the same cross-sectional area
as the original protective grounding conductor. MM6 must have a fixed
installation and a cross-section of the protective grounding conductor of at
least 10 mm 2 Cu.
On the terminal-box, three screws (for MM4 and MM5) and two screws (for
MM6)are provided for ORIGINAL and MOTOR protective grounding conductors: the
customer can choose the screw for each one.
The cross-sectional area of every protective grounding conductor which does
not form a part of the supply cable or cable enclosure must, in any case, be
not less than:
- 2.5 mm² if mechanical protection is provided or
- 4 mm² if mechanical protection is not provided. For cord-connected equipment, provisions must be made so that the protective grounding conductor in the cord is, in the case of failure of the strain-relief mechanism, the last conductor to be interrupted.
The power-head is earthed through metal aglets, located on the terminal-box, which fit into spring baskets on the powerhead. See Figure 1, Figure 2 and Figure 3 for the location of the screws (three for MM4 and MM5, two for MM6) and the metal aglets (one for MM4 and MM5, two for MM6). Please, pay attention not to damage or remove these aglets.![Danfoss VACON 100 X AC Drives
- metal aglet](https://manuals.plus/wp-content/uploads/2024/01/Danfoss- VACON-100-X-AC-Drives-metal-aglet.png)
However, always follow the local regulations for the minimum size of the
protective grounding conductor.
NOTE: Due to the high capacitive currents present in the AC drive, fault
current protective switches may not function properly.
1.6 Insulation system
Please, consider carefully the insulation system depicted in Figure 4 before
connecting any circuit to the unit.
A distinction has to be made for the following three groups of terminals,
according the insulation system of VACON ® 100 X:
- Mains and motor connections (L1, L2, L3, U, V, W)
- Relays (R01, R02) (*)
- Thermistor-input
- Control terminals (I/Oes, RS485, Ethernet, STO)
The Control terminals (I/Os, RS485, Ethernet, STO) are isolated from the Mains
(the insulation is reinforced, according to IEC 61800-5-1) and the GND
terminals are referred to PE.
This is important when you need to connect other circuits to the drive and
test the complete assembly.
Should you have any doubt or question, please contact your local
distributor.
(*) The relays may be used also with DVC A circuits. This is possible only if both relays are used with DVC A circuit: to mix Mains and DVC A is not allowed.
1.7 Compatibility with RCDs
This product can cause a d.c. current in the protective grounding conductor.
Where a residual current-operated protective (RCD) or monitoring (RCM) device
is used for protection in case of direct or indirect contact, only an RCD or
RCM of Type B is allowed on the supply side of this product.
1.8 Extended temperature range
VACON® 100 X has an integrated cooling system, independent from the motor
fan. Under maxi- mum operating conditions, the ambient temperature cannot
exceed 40 °C. See Table and Table 31 for the output rated current. Higher
temperatures are allowed only with derating of the output current. With
derating the unit can operate up to 60°C. See the Figure 5.
NOTE: the maximum allowed switching frequency above 50°C is 1.5 kHz.
The AC drive is cooled down by air-ventilation. Therefore, make sure that
enough free space is left around the AC drive to ensure sufficient air
circulation (see for more details the mounting instructions on chapter 3).
1.9 Electro-magnetic compatibility (EMC)
The VACON® 100 X complies with IEC 61000-3-12, provided that the short circuit
ratio (RSCE) is greater than or equal to 120 at the interface point between
the user’s supply and the public system. It is the responsibility of the
installer or user of the equipment to ensure, by consultation with the
distribution network operator if necessary, that the equipment is connected
only to a supply with a short-circuit ratio RSCE greater than or equal to 120.
1.10 Marine environment
For installation, safety and EMC requirements in a marine environment download
and read the Marine Installation Guide.
NOTE! You can download the English and French product manuals with
applicable safety, warning and caution information from
https://www.danfoss.com/en/service-and-support/.
RECEIVING THE DELIVERY
Check the correctness of delivery by comparing your order data to the drive information found on the package label. If the delivery does not correspond to your order, contact the supplier immediately. See chapter 2.4.
2.1 Type designation code
VACON® type designation code is formed of a nine-segment code and optional
+codes. Each segment of the type designation code uniquely corresponds to the
product and options you have ordered. The code is of the following format:
VACON0100-3L-0061-4-X +xxxx +yyyy
VACON
This segment is common for all products.
0100
Product range:
0100 = VACON® 100 Product family
3L
Input/Function: 3L = Three-phase input
0061
Drive rating in ampere; e.g. 0061 = 61 A See Table 30, Table 31 and Table 32
for all the drive ratings.
4 Supply voltage:
2 = 208-240 V
4 = 380-480 V
5 = 380-500 V
X
-IP66/ Type 4X
-EMC-level C2
-Two relay outputs
-One thermistor input
-STO function
-GP software package installed| R02
+EMC4
+LS60
+LSUS
+QGLC
+xxxx +yyyy
Additional codes (Several options possible).
Examples of additional codes:
+HMGR
Graphical keypad IP66
+SRBT
Integrated battery for real time clock
+FBIE
Onboard fieldbus protocols activated
(Ether Net/IP and PROFINET IO)
+A1181
Solar pump application
---|---
2.2 order codes
The order codes for VACON ® 100 X drive family are shown in the following
table:
Table 3. Order codes of VACON ® 100 X. See chapter 7 for more details.
Enclosure size Order code Description
Supply voltage 3AC 208-240V
__
MM4
| VACON0100-3L-0006-2-X| 1.1 kW – 1.5 HP drive
VACON0100-3L-0008-2-X| 1.5 kW – 2.0 HP drive
VACON0100-3L-0011-2-X| 2.2 kW – 3.0 HP drive
VACON0100-3L-0012-2-X| 3.0 kW – 4.0 HP drive
MM5| VACON0100-3L-0018-2-X| 4.0 kW – 5.0 HP drive
VACON0100-3L-0024-2-X| 5.5 kW – 7.5 HP drive
VACON0100-3L-0031-2-X| 7.5 kW – 10.0 HP drive
MM6| VACON0100-3L-0048-2-X| 11.0 kW – 15.0 HP drive
VACON0100-3L-0062-2-X| 15.0 kW – 20.0 HP drive
Supply voltage 3AC 380-480V
__
__
__
MM4
| VACON0100-3L-0003-4-X| 1.1 kW – 1.5 HP drive
VACON0100-3L-0004-4-X| 1.5 kW – 2.0 HP drive
VACON0100-3L-0005-4-X| 2.2 kW – 3.0 HP drive
VACON0100-3L-0008-4-X| 3.0 kW – 4.0 HP drive
VACON0100-3L-0009-4-X| 4.0 kW – 5.0 HP drive
VACON0100-3L-0012-4-X| 5.5 kW – 7.5 HP drive
__
MM5
| VACON0100-3L-0016-4-X| 7.5 kW – 10.0 HP drive
VACON0100-3L-0023-4-X| 11.0 kW – 15.0 HP drive
VACON0100-3L-0031-4-X| 15.0 kW – 20.0 HP drive
__
MM6
| VACON0100-3L-0038-4-X| 18.5 kW – 25.0 HP drive
VACON0100-3L-0046-4-X| 22.0 kW – 30.0 HP drive
VACON0100-3L-0061-4-X| 30.0 kW – 40.0 HP drive
VACON0100-3L-0072-4-X| 37.0 kW – 50.0 HP drive
Supply voltage 3AC 380-500V
__
__
__
MM4
| VACON0100-3L-0003-5-X| 1.1 kW – 1.5 HP drive
VACON0100-3L-0004-5-X| 1.5 kW – 2.0 HP drive
VACON0100-3L-0005-5-X| 2.2 kW – 3.0 HP drive
VACON0100-3L-0008-5-X| 3.0 kW – 4.0 HP drive
VACON0100-3L-0009-5-X| 4.0 kW – 5.0 HP drive
VACON0100-3L-0012-5-X| 5.5 kW – 7.5 HP drive
__
MM5
| VACON0100-3L-0016-5-X| 7.5 kW – 10.0 HP drive
VACON0100-3L-0023-5-X| 11.0 kW – 15.0 HP drive
VACON0100-3L-0031-5-X| 15.0 kW – 20.0 HP drive
__
MM6
| VACON0100-3L-0038-5-X| 18.5 kW – 25.0 HP drive
VACON0100-3L-0046-5-X| 22.0 kW – 30.0 HP drive
VACON0100-3L-0061-5-X| 30.0 kW – 40.0 HP drive
VACON0100-3L-0072-5-X| 37.0 kW – 50.0 HP drive
2.3 Unpacking and lifting the AC drive
The weights of the AC drives vary according to enclosure size. You may need to
use a piece of special lifting equipment to move the drive from its package.
Note the weights of each individual enclosure size in Table below.
Table 4. Enclosure weights.
Enclosure size | Weight |
---|---|
[kg] | [lb] |
MM4 | 8.8 |
MM5 | 14.9 |
MM6 | 31.5 |
VACON® 100 X drives have undergone scrupulous tests and quality checks at the
factory before they are delivered to the customer. However, after unpacking
the product, check that no signs of transport damage are to be found on the
product and that the delivery is complete.
Should the drive have been damaged during shipping, please contact the cargo
insurance company or the carrier in the first instance.
2.4 Accessories
After having opened the transport package and lifted the drive out, check
immediately that these various accessories were included in the delivery. The
contents of the accessories bag differ by drive size:
2.4.1 Enclosure MM4
Table 5. Content of accessory bag, MM4.
Item | Quantity | Purpose |
---|---|---|
STO terminal connector | 1 | Six pin black connector (see Figure 7) to use STO |
function
M4 x 12 DIN6900-3-Combi-Delta-Tx screw| 10| Screws for control cable clamps
M1-3 Cable clamp| 5| Clamping control cables
M4 x 12 DIN6900-3-Combi-Delta-Tx screw| 6| Screws for power cable clamps
M25 Cable clamp| 3| Clamping power cables
‘Product modified’ sticker| 1| Information about modifications
HMI cap*| 1| Closing cap for the HMI connector
*. Provided only if the drive is delivered with the keypad.
2.4.2 Enclosure MM5
Table 6. Content of accessory bag, MM5.
Item | Quantity | Purpose |
---|---|---|
STO terminal connector | 1 | Six pin black connector (see Figure 7) to use STO |
function
M4 x 12 DIN6900-3-Combi-Delta-Tx screw| 10| Screws for control cable clamps
M1-3 Cable clamp| 5| Clamping control cables
M4 x 12 DIN6900-3-Combi-Delta-Tx screw| 6| Screws for power cable clamps
M32 Cable clamp| 3| Clamping power cables
‘Product modified’ sticker| 1| Information about modifications
HMI cap*| 1| Closing cap for the HMI connector
*. Provided only if the drive is delivered with the keypad.
2.4.3 Enclosure MM6
Table 7. Content of accessory bag, MM6.
Item | Quantity | Purpose |
---|---|---|
STO terminal connector | 1 | Six pin black connector (see Figure 7) to use STO |
function
M4 x 12 DIN6900-3-Combi-Delta-Tx screw| 10| Screws for control cable clamps
M1-3 Cable clamp| 5| Clamping control cables
M4 x 25 DIN6900-3-Combi-Delta-Tx screw| 6| Screws for power cable clamps
M40 Cable clamp| 3| Clamping power cables
‘Product modified’ sticker| 1| Information about modifications
HMI cap*| 1| Closing cap for the HMI connector
*. Provided only if the drive is delivered with the keypad mounted.
2.4.4 STO terminal connector
2.4.5 ‘Product modified’ sticker
In the small plastic bag included in the delivery you will find a silver
Product modified sticker. The purpose of the sticker is to notify the service
personnel about the modifications made in the AC drive. Attach the sticker on
the side of the AC drive to avoid losing it. Should the AC drive be later
modified, mark the change on the sticker.
2.4.6 Disposal
When the device reaches the end of its operating life do not dispose of it as
a part of standard household garbage. Main components of the product can be
recycled, but some need to be fragmented to separate different types of
materials and components that need to be treated as special waste from
electrical and electronic components. To ensure environmentally sound and safe
recycling treatment, the product can be taken to appropriate recycling center
or returned to the manufacturer.
Observe local and other applicable laws as they may mandate special treatment
for specific components or special treatment may be ecologically sensible.
MOUNTING
VACON® 100 X is the ideal solution for a decentralized installation. It is
conceived to be mounted on a wall or directly on the motor, saving space and
reducing the cabling complexity. In both cases, it must be ensured that the
mounting plane is even.
3.1 Dimensions MM4
Enclosure size | Dimensions W x H x D |
---|---|
[mm] | [in] |
MM4 | 190.7 x 315.3 x 196.4 |
MM4 +HMGR | 190.7 x 315.3 x 213.8 |
3.2 Dimensions MM5
Enclosure size | Dimensions W x H x D |
---|---|
[mm] | [in] |
MM5 | 232.6 x 367.4 x 213.5 |
MM5 +HMGR | 232.6 x 367.4 x 230.8 |
3.3 Dimensions MM6
Enclosure size | Dimensions W x H x D |
---|---|
[mm] | [in] |
MM6 | 349.5 x 499.8 x 235.4 |
MM6 +HMGR | 349.5 x 499.8 x 254.2 |
3.4 Introduction of modules
The mechanical concept of VACON® 100 X drive is based on two segregated parts,
power and control, connected to each other by pluggable terminals. The power
unit, called powerhead, includes all the power electronics such as the EMC-
filter, IGBTs, capacitors, choke or power boards while the control board and
the control terminals are located in the terminal box.
3.5 Mounting
The drive consists of two main elements:
- The terminal box that includes the power terminals and control board with the control terminals and
- The powerhead containing all the power electronics.
To install the drive, both parts need to be separated. The terminal box must be fixed first and all cabling done. After this, the powerhead will be plugged on the terminal box and fixed with 4 (MM4 and MM6) or 6 (MM5) dedicated screws located on top side of the powerhead (see Figure 13.). In order to guarantee specified IP protection, recommended fastening torque is 2-3 Nm. The screws must be tightened crosswise.
3.5.1 Wall-mounting
The drive can be mounted in vertical or horizontal position on the wall or any
other relatively even mounting plane or machine frame and fixed with the
screws recommended in Table 8. Recommended screw or bolt size for MM4 is M5,
for MM5 M6 and MM6 is M8.
Table 8. Screws for wall mounting.
Enclosure size | Screw number | Screw size |
---|---|---|
MM4 | 4 | M5 |
MM5 | 4 | M6 |
MM6 | 4 | M8 |
3.5.2 Motor-mounting
The drive can also be mounted on a motor (on top or on any side of the motor).
The drive is equipped with a cooling system independent of the motor. Motor-
mounting requires special adapting components.
Contact your local distributor for additional information.
3.5.3 Segregated modules
In order to ease replacements in case of failure, the power and the control
sub-systems are enclosed in two segregated parts, connected together through
pluggable terminals:
- Power-head: heat-sink enclosing all power electronics
- Terminal-box: block containing unit control and power terminals
Firstly, the terminal-box has to be fixed and the cabling has to be done.
Secondly, the power-head has to be plugged and fixed to the terminal-box with
dedicated screws (see Table 9). In order to preserve the specified IP
protection class, the recommended fastening torque is 2-3 Nm.
Table 9. Screws for fixing the powerhead to the terminal box.
Enclosure size | Screw number | Screw size |
---|---|---|
MM4 | 4 | M5 |
MM5 | 6 | M5 |
MM6 | 4 | M6 |
3.6 Cooling
The AC drive produces heat in operation and is cooled down by air circulated
by a fan. The cooling concept is independent of the motor fan.
Enough free space must be left around the AC drive to ensure sufficient air
circulation and cooling.
Different acts of maintenance may also require a certain amount of free space.
The minimum clearances given in Table 10 must not be exceeded. It is also
important to ensure that the temperature of the cooling air does not exceed
the maximum ambient temperature of the drive.
Contact local distributor for more information on required clearances in
different installations.
Min clearance [mm]
Type| A| B| C
All types| 80| 160| 60
Table 10. Min. clearances around AC drive.
A = Clearance left and right from the drive
B = Clearance above the drive
C = Clearance underneath the AC drive
Table 11. Required cooling air.
Type | Cooling air required [m 3/h] |
---|---|
MM4 | 140 |
MM5 | 140 |
MM6 | 280 |
Should you need further details on the cooling system of the VACON ® 100 X, please contact your local distributor.
POWER CABLING
The mains cables are connected to terminals L1, L2 and L3 and the motor cables to terminals marked with U, V and W. See principal connection diagram in Figure 15. See also Table 12 for the cable recommendations for different EMC levels.
Use cables with heat resistance in accordance with the application
requirements. The cables and the fuses must be dimensioned according to the AC
drive nominal OUTPUT current which you can find on the rating plate.
Table 12. Cable types required to meet standards.
| EMC levels
---|---
Cable type| 1 st environment| 2 nd
environment
Category C2| Category C3| Category C4
Mains cable| 1| 1| 1
Motor cable| 3*| 2| 2
Control cable| 4| 4| 4
1 = Power cable intended for fixed installation and the specific mains
voltage. Shielded cable not required. (MCMK or similar recommended).
2 = Symmetrical power cable equipped with concentric protection wire and
intended for the specific mains voltage. (MCMK or similar recommended). See
Figure 16.
3 = Symmetrical power cable equipped with compact low-impedance shield and
intended for the specific mains voltage. [MCCMK, EMCMK or similar recommended.
See Figure 16. *360º grounding of the shield with cable glands in motor end
needed for EMC level C2.
4 = Screened cable equipped with compact low-impedance shield (JAMAK,
SAB/ÖZCuY-O or similar).
NOTE: The EMC requirements are fulfilled at factory defaults of switching
frequencies (all frames).
NOTE: If safety switch is connected, the EMC protection must be
continuous over the whole cable installation.
4.1 Circuit breaker
Please disconnect the drive via an external circuit breaker. You have to
provide a switching device between supply and main connection terminals.
When connecting the input terminals to the power supply using a circuit
breaker, observe that this is of type B or type C and ensure it has a capacity
of 1.5 to 2 times of the inverter’s rated current (see Table and Table 31).
NOTE: circuit breaker is not allowed in installations where C-UL is
required. Only fuses are recommended.
4.2 UL standards on cabling
To meet the UL (Underwriters Laboratories) regulations, use a UL-approved
copper cable with a minimum heat-resistance of +75°C. Use Class 1 wire only.
The units are suitable for use on a circuit capable of delivering not more
than 100,000 rams symmetrical amperes, 500V AC maximum, when protected by T or
J class fuses.
Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the
National Electrical Code and any additional local codes.
4.3 Description of the terminals
The following pictures describe the power terminals and the typical
connections in VACON ® 100 X drives.
Table 13. Terminal description.
Terminal | Description |
---|---|
L1 L2 L3 | These terminals are the input connections for the power supply. |
DC-DC+/R+ R- | DC bus terminals (DC- DC+) and Brake resistor terminals (R+ R-) |
U/T1 V/T2 W/T3 | These terminals are for motor connections. |
Table 14. Terminal description.
Terminal | Description |
---|---|
L1 L2 L3 | These terminals are the input connections for the power supply. |
DC- DC+/R+ R- | DC bus terminals (DC- DC+) and Brake resistor terminals (R+ R-) |
U/T1 V/T2 W/T3 | These terminals are for motor connections. |
Table 15. Terminal description.
Terminal | Description |
---|---|
L1 L2 L3 | These terminals are the input connections for the power supply. |
DC- DC+/R+ R- | DC bus terminals (DC- DC+) and Brake resistor terminals (R+ R-) |
U/T1 V/T2 W/T3 | These terminals are for motor connections. |
4.4 Cable dimensioning and selection
Table 16 and Table 17 show the minimum dimensions of the Cu-cables and the
corresponding fuse sizes.
These instructions apply only to cases with one motor and one cable connection
from the AC drive to the motor. In any other case, ask the factory for more
information.
4.4.1 Cable and fuse sizes, enclosures MM4 to MM6
The recommended fuse type is gG/gL (IEC 60269-1). The fuse voltage rating must
be selected according to the supply network. The final selection must be made
according to local regulations, cable installation conditions and cable
specification. Bigger fuses than those recommended below must not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time
depends on used fuse type and impedance of the supply circuit. Consult the
factory about faster fuses. The manufacturer also recommends high speed gS
(IEC 60269-4) fuse ranges.
Table 16. Cable and fuse sizes for VACON ® 100 X.
Enclosure size| Type| Input [A]| __
Fuse (gG/gL) [A]
| Mains, *motor and brake resistor cable Cu [mm 2] | Terminal
cable size
---|---|---|---|---|---
Main terminal [mm2]| Earth terminal [mm2]**
| 0003 4 – 0004 4
0003 5 – 0004 5| 3.4 – 4.6| 6| 31.5+1.5| 0.5—10 solid
0.5—6 stranded| M4 ring terminal or 1—6
MM4| 0006 2 – 0008 2
0005 4 – 0008 4
0005 5 – 0008 5| 6.0 – 7.2
5.4 – 8.1| 10| 31.5+1.5| 0.5—10 solid
0.5—6 stranded| M4 ring terminal or 1—6
| 0011 2 – 0012 2
0009 4 – 0012 4
0009 5 – 0012 5| 9.7 – 10.9
9.3 – 11.3| 16| 32.5+2.5| 0.5—10 solid
0.5—6 stranded| M4 ring terminal or 1—6
| 0018 2
0016 4
0016 5| 16.1
15.4| 20| 36+6| 0.5—16 solid or stranded| M5 ring terminal or 1—10
MM5| 0024 2
0023 4
0023 5| 21.7
21.3| 25| 36+6| 0.5—16 solid or stranded| M5 ring terminal or 1—10
| 0031 2
0031 4
0031 5| 27.7
28.4| 32| 310+10| 0.5—16 solid or stranded| M5 ring terminal or 1—10
| 0038 4
0038 5| 36.7| 40| 310+10| M6 ring terminal| M6 ring terminal
MM6| 0048 2
0046 4
0046 5| 43.8
43.6| 50| 316+16| M6 ring terminal| M6 ring terminal
0062 2
0061 4
0061 5| 57.0
58.2| 63| 325+16| M6 ring terminal| M6 ring terminal
| 0072 4
0072 5| 67.5| 80| 335+16| M6 ring terminal| M6 ring terminal
The terminal sizes are intended for 1 conductor. For MM6, the max. diameter of
the ring terminal is 14 mm.
The cable dimensioning is based on the criteria of the International Standard
IEC60364-5-52: Cables must be PVC-isolated; Max number of parallel cables is
9.
When using cables in parallel, NOTE HOWEVER that the requirements of both the
cross-sectional area and the max number of cables must be observed.
For important information on the requirements of the grounding conductor, see
chapter Grounding and earth fault protection of the standard.
For the correction factors for each temperature, see International Standard
IEC60364-5-52.
4.4.2 Cable and fuse sizes, enclosures MM4 to MM6, North America
The recommended fuse type is class T (UL & CSA). The fuse voltage rating must
be selected according to the supply network. The final selection must be made
according to local regulations, cable installation conditions and cable
specification. Bigger fuses than those recommended below must not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time
depends on used fuse type and impedance of the supply circuit. Consult the
factory about faster fuses. The manufacturer also recommends high speed J (UL
& CSA) fuse ranges. Table 17. Cable and fuse sizes for VACON ® 100 X.
Enclosure size| Type| Input **[A]| Fuse (class T) [A]| Mains and motor cable Cu**|
Terminal cable size
---|---|---|---|---|---
Main terminal| Earth terminal
MM4| 0003 4 – 0004 4
0003 5 – 0004 5| 3.4 – 4.6| 6| AWG14| AWG24-AWG10| AWG17-AWG10
M4 ring terminal
0006 2 – 0008 2
0005 4 – 0008 4
0005 5 – 0008 5| 6.0 – 7.2
5.4 – 8.1| 10| AWG14| AWG24-AWG10| AWG17-AWG10
M4 ring terminal
0011 2
0009 4
0009 5| 9.7
9.3| 15| AWG14| AWG24-AWG10| AWG17-AWG10
M4 ring terminal
0012 2
0012 4
0012 5| 10.9
11.3| 20| AWG14| AWG24-AWG10| AWG17-AWG10
M4 ring terminal
MM5| 0018 2
0016 4
0016 5| 16.1
15.4| 25| AWG10| AWG20-AWG5| AWG17-AWG8
M5 ring terminal
0024 2
0023 4
0023 5| 21.7
21.3| 30| AWG10| AWG20-AWG5| AWG17-AWG8
M5 ring terminal
0031 2
0031 4
0031 5| 27.7
28.4| 40| AWG8| AWG20-AWG5| AWG17-AWG8
M5 ring terminal
Enclosure size| __
Type
| I input [A]| Fuse (class T) [A]| Mains and
motor cable Cu| Terminal cable size
---|---|---|---|---|---
Main terminal| Earth terminal
MM6| 0038 4
0038 5| 36.7| 50| AWG4| AWG13-AWG0
M6 ring terminal| AWG13-AWG2
M6 ring terminal
0048 2
0046 4
0046 5*| 43.8
43.6| 60| __
AWG4
| AWG13-AWG0
M6 ring terminal| AWG13-AWG2
M6 ring terminal
0062 2
0061 4
0061 5| 57.0
58.2| 80| AWG4| AWG13-AWG0
M6 ring terminal| AWG13-AWG2
M6 ring terminal
0072 4
0072 5**| 67.5| 100| AWG2| AWG9-AWG2/0
M6 ring terminal| AWG9-AWG2/0
M6 ring terminal
-
With the optional mains switch, the mains cable must be rated AWG6 (minimum 75ºC, Cu). The motor cable must be rated AWG4 (minimum 75ºC, Cu).
The optional mains switch cannot be used with these models, unless current derating is applied. The input current cannot exceed 52 A at 30°C ambient temperature and 45 A at 40°C ambient temperature. With the optional main switch, use a maximum 60 A fuse.
The cable dimensioning is based on the criteria of the Underwriters’ Laboratories UL508C:Cables must be PVC-isolated; Max ambient temperature +40 °C (104 °F), max temperature of cable surface +75 °C (167 °F); Use only cables with concentric copper shield; Max number of parallel cables is 9.
When using cables in parallel, NOTE HOWEVER that the requirements of both the cross-sectional area and the max number of cables must be observed.
For important information on the requirements of the grounding conductor, see standard Underwriters’ Laboratories UL508C.
For the correction factors for each temperature, see the instructions of standard Underwriters’ Laboratories UL508C.
4.4.3 Brake resistor cables
VACON ® 100 X AC drives are equipped with terminals for an optional external brake resistor. These terminals are marked with DC+/R+ and R-. See Table 33 and Table 34 for the resistor ratings and Table 16 for cable sizing.
4.4.4 Control cables
For information on control cables see chapter Control unit.
4.5 Cable installation**- Before starting, check that none of the components of the AC drive is live. Read carefully the warnings in chapter 1.
- Place the motor cables sufficiently far from other cables.
- Avoid placing the motor cables in long parallel lines with other cables.
- If the motor cables run in parallel with other cables note the minimum distances between the motor cables and other cables given in table below.
Distance between cables, [m] | Shielded cable, [m] |
---|---|
0.3 | ≤ 50 |
1 | ≤ 200 |
- The given distances also apply between the motor cables and signal cables of other systems.
- The maximum lengths of motor cables (shielded) are 100 m (MM4) and 150 m (MM5 and MM6).
- The motor cables should cross other cables at an angle of 90 degrees.
- If cable insulation checks are needed, see chapter Cable and motor insulation checks.
Start the cable installation according to the instructions below:
- Strip the motor and mains cables as recommended below.
Table 18. Cables stripping lengths [mm].
Enclosure size| A1| B1| C1| D1| C2| D2|
E
---|---|---|---|---|---|---|---
MM4| 15| 70| 10| 30| 7| 30| as short as possible
MM5| 20| 70| 10| 40| 10| 40
MM6| 20| 90| 15| 60| 15| 60
IEC installation:
2| • Remove the cable entry plate. The cable entry system is a
combination of a cable entry plate (see the figure below) and cable glands. In
the cable entry plate there are several openings available for the cables
with ISO metric thread.
• Open only the inlet holes where you need to run the cables.
---|---
3| • Choose the correct cable glands according to drive and cable size
as shown in the following pictures.
4| • Cable glands must be made of plastic materials. They are used for
sealing cables passing through cable entries to ensure the characteristics of
the enclosure.
---|---
Plastic cable glands are recommend. If metal cable glands are needed, all insulation system requirements and all protective grounding requirements have to be fulfilled in accordance with the national electrical regulations and IEC 61800- 5-1.
5| • Screw the cable glands on the cable entry holes using the proper
tightening torque as shown in Table 19.
---|---
Tightening torques of cable glands:
Table 19. Tightening torque and dimension of cable glands.
Enclosure size| Gland screw type [metric]|
Tightening torque [Nm]/[lb- in.]
---|---|---
[Nm]| lb-in.
MM4| M16| 1.0| 8.9
M25| 4.0| 35.5
__
MM5
| M16| 1.0| 8.9
M25| 4.0| 35.5
M32| 7.0| 62.1
__
MM6
| M16| 1.0| 8.9
M25| 4.0| 35.5
M40| 10.0| 88.7
UL installation:
6| • To connect NPT pipes to VACON ® 100 X, use the optional metal
cable entry plate (included in -R02 option) to meet UL installation rules.
• One metal conduit plate with accessories (screws and gasket) is delivered
in a separate bag together with the drive. See the following figures for more
details.
---|---
7| • All the (3) terminal box openings are closed with the standard
plastic plates with the metric threads.
---|---
8| • The metal cable entry plate for UL installation has to be
installed in place of one of standard plastic cable entries provided with the
default package. The tightening torque of cable entry plate screws: 1.5 -2.0
Nm (13.2-17.7 lb-in). The metal cable entry plate has three not-threaded
openings: input line, motor and I/Os and can be mounted only on left or right-
hand side of the drive.
9| • Flexible or rigid cable conduit can be used.
• Use proper fittings to join and terminate rigid conduit tubing, and
protect it from damage too.
• The proper selection of electrical conduit materials, fittings, and
installation are important for safe electrical wiring.
10| • Setscrew fittings are commonly used with conduit; they provide
weather tight joints that are firm to keep the IP degree of the drive.
Cable installation:
11| • Pass the cables (supply cable, motor cable, brake cable and I/O
cables) through the conduits (UL connections) or through the cable glands (IEC
connections) and cable entries.
---|---
12| • Detach the cable clamps and the grounding clamps.
13
| Connect the stripped cables:
• Expose the shield of both cables in order to make a 360-degree connection
with the cable clamp (reverse the shield over the plastic cover of the cable
and fix all together).
• Connect the phase conductors of the supply and motor cables into their
respective terminals.
• Form the rest of the cable shield of both cables into “pigtails” and make
a grounding connection with the clamp. Make the pigtails just long enough to
reach and be fixed to the terminal – no longer.
Tightening torques of cable terminals:
Table 20. Tightening torques of terminals.
__
Enclosure size
| __
Type
| Tightening torque [Nm]/[lb-in.] Power and motor terminals|
Tightening torque [Nm]/[lb-in.] EMC grounding clamps|
Tightening torque, [Nm]/[lb-in.] Grounding terminals
---|---|---|---|---
[Nm]| lb-in.| [Nm]| lb-in.| [Nm]| lb-in.
MM4| 0006 2 – 0012 2
0003 4 – 0012 4
0003 5 – 0012 5| 1.2—1.5| 10.6—13.3| 1.5| 13.3| 2.0| 17.7
MM5| 0018 2 – 0031 2
0016 4 – 0031 4
0016 5 – 0031 5| 1.2—1.5| 10.6—13.3| 1.5| 13.3| 2.0| 17.7
MM6| 0048 2 – 0062 2
0038 4 – 0072 4
0038 5 – 0072 5| 4—5| 35.4—44.3| 1.5| 13.3| 2.0| 17.7
14| • Check the connection of the earth cable to the motor and the AC
drive terminals marked with .
---|---
CONTROL UNIT
Remove the powerhead of the drive to reveal the terminal box with the control
terminals.
The control unit of the AC drive consists of the control board and additional
boards (option boards) connected to the slot connectors of the control board.
The locations of boards, terminals and switches are presented in Figure 28
below.
Table 21. Locations of components in control unit.
Number | Meaning |
---|---|
1 | Control terminals 1-11 (see chapter 5.1.2) |
2 | Control terminals 12-30, A-B (see chapter 5.1.2) |
3 | Relay terminals (see chapter 5.1.2) |
4 | Thermistor input (see chapter 5.1.2) |
5 | STO terminals |
6 | DIP switches |
7 | Ethernet terminal (see chapter 5.2.1) |
8 | Option boards |
When delivered from the factory, the control unit of the AC drive contains the
standard controlling interface – the control and relay terminals of the
control unit – unless otherwise specifically ordered. On the next pages you
will find the arrangement of the control I/O and the relay terminals, the
general wiring diagram and the control signal descriptions.
The control board can be powered externally (+24VDC, max. 1000mA, ±10%) by
connecting the external power source to terminal #30, see chapter 5.1.2. This
voltage is sufficient for parameter setting and for keeping the control unit
active. Note however that the measurements of the main circuit (e.g. DC-link
voltage, unit temperature) are not available when the mains is not connected.
5.1 Control unit cabling
The principal terminal block placement is presented in Figure 29 below. The
control board is equipped with 22 fixed control I/O terminals and the relay
board with 6+2. Additionally, the terminals for the Safe Torque Off (STO)
function (see chapter 9.) can be seen in the picture below. All signal
descriptions are also given in Table 23.
5.1.1 Control cable sizing
The control cables shall be at least 0.5 mm 2 screened multicore cables, see
Table 22. The maxi- mum terminal wire size is 2.5 mm 2 for the relay terminals
and 1.5 mm 2 for other terminals. Find the tightening torques of the control
and relay board terminals in Table 22.
Table 22. Control cable tightening torques.
Terminal screw | Tightening torque |
---|---|
Nm | lb-in. |
I/O terminals and STO terminals (screw M2) | 0.22-0.25 |
Relay terminals (screw M3) | 0.22-0.25 |
5.1.2 Standard I/O terminals
The terminals of the Standard I/Os and the Relays are described below. For
more information on the connections, see chapter 7.
The terminals shown on shadowed background are assigned for signals with
optional functions selectable with DIP switches. See more information in
chapter 5.1.5 and in chapter 5.1.6.
5.1.3 Relay and thermistor input terminals
Table 24. I/O terminal signals for relay and thermistor terminals and
connection example.
5.1.4 Safe Torque off (STO) terminals
For more information on the functionalities of the Safe Torque Off (STO), see
chapter 9.
Table 25. I/O terminal signals for the STO functions.
Safe Torque Off terminals
Terminal| Signal
S1| Isolated digital input 1 (inter- changeable polarity); +24V ±20% 10…15mA
G1
S2| Isolated digital input 2 (inter- changeable polarity); +24V ±20% 10…15mA
G2
F+| Isolated feedback (CAUTION! Polarity to be respected); +24V ±20%
F-| Isolated feedback (CAUTION! Polarity to be respected); GND
5.1.5 Selection of terminal functions with DIP switches ®
The VACON 100 X drive embodies five so-called DIP switches that allow for
three functional se- lections each. The shadowed terminals in Table 23 can be
functionally modified with the DIP switches. The switches have three
positions: C, 0 and V. The switch in the position “C” means that the input or
the output has been set in current mode. The switch in the position “V” means
voltage mode.The middle position “0” is for Test mode. See Figure 30 to locate
the switches and make appropriate selections for your requirements. Factory
defaults are: AI1 = V; AI2 = C, AO = C.
5.1.6 Isolating digital inputs from ground
The digital inputs (terminals 8-10 and 14-16) on the standard I/O board can be
isolated from ground by setting the DIP switch to position ‘0’. The switch in
the position “1” means that the common of digital input has been connected to
24 V (negative logic). The switch in the position “2” means that the common
of digital inputs has been connected to ground (positive logic). See Figure
31. Locate the switch and set it in desired position. Factory default is
2.
5.1.7 Bus termination of the RS485 connection
This DIP switch is related to the RS485 connection. It is used for bus
termination. The bus termination must be set to the first and to the last
device on the network. This switch in position “0” means that a termination
resistor of 120 ohm is connected and the termination of the bus has been set.
This switch in the position “1” means that a pull-up and a pull-down resistors
of 10 kOhm have been connected for biasing purpose. The switch in the position
“2” means no termination and no biasing resistors have been connected. Factory
default is 2. See Figure 32.
In case other termination or biasing values are needed, use the advanced
connector. Biasing resistors (for example 390 ohm) can be connected between
terminals 1 (+5V) to 2 (RS485_A) and 3 (RS485_B) to 4(GND). Termination
resistor (for example 220 ohm) can be connected between terminals 2 (RS485_A)
to 3 (RS485_B). When the advanced connector is used, the DIP switch must be
set to “2”.
5.2 I/O cabling and fieldbus connection
The AC drive can be connected to fieldbus either through RS485 or Ethernet.
The connection for RS485 is on the standard I/O terminals (A and B) and the
connection for Ethernet is left to the control terminals. See Figure
33.
5.2.1 Prepare for use through Ethernet
1| Connect the Ethernet cable (see specification on page 51) to its
terminal and run the cable through the conduit plate.
---|---
2| Remount the powerhead. NOTE: When planning the cable runs, remember
to keep the distance between the Ethernet cable and the motor cable at a
minimum of 30 cm.
For more detailed information, see the user’s manual of the fieldbus you are
using.
5.2.1.1 Ethernet cable data
Table 26. Ethernet cable data.
Connector | Shielded RJ45 connector. Note: max length of the connector 40 mm. |
---|---|
Cable type | CAT5e STP |
Cable length | Max. 100m |
5.2.2 Prepare for use through RS485
1| Strip about 15 mm of the RS485 cable (see specification on page 53)
and cut off the grey cable shield. Remember to do this for both bus cables
(except for the last device).
Leave no more than 10 mm of the cable outside the terminal block and strip the
cables at about 5 mm to fit in the terminals. See picture below. Also strip
the cable now at such a distance from the terminal that you can fix it to the
frame with the grounding clamp. Strip the cable at a maximum length of 15 mm.
Do not strip the aluminum cable shield!
---|---
| |
2| Then connect the cable to its appropriate terminals on VACON ® 100
X AC drive standard terminal block, terminals A and B (A = negative, B =
positive). See Figure 33.
---|---
3| Using the cable clamp included in the delivery of the drive, ground
the shield of the RS485 cable to the frame of the AC drive.
---|---
4| If VACON ® 100 X AC drive is the last device on the bus ,
the bus termination must be set. Locate the DIP switches to the top of the
control unit (see Figure 32) and turn the right most switch to position “0”.
This setting creates a 120 ohm termination. In case something else is needed
and/or biasing is needed, use the advanced connector to add external resistors
(see Figure 32). See also step 6.
5| NOTE: When planning the cable runs, remember to keep the distance
between the fieldbus cable and the motor cable at a minimum of 30 cm.
6| The bus termination must be set for the first and the last device of the
fieldbus line. See picture below and step 4. We recommend that the first
device on the bus and, thus, terminated, was the Master device.
---|---
5.2.3 RS485 cable data
Table 27. RS485 cable data.
Connector | 2.5 mm 2 |
---|---|
Cable type | STP (Shielded Twisted Pair), type Belden 9841 or similar |
Cable length | Depends on the used fieldbus. See respective bus manual. |
5.3 Battery installation for Real Time Clock (RTC)
Enabling the functions of the Real Time Clock (RTC) requires that an optional
battery is installed in the VACON ® 100 X drive.
Detailed information on the functions of the Real Time Clock (RTC) can be
found in the Application Manual. See the following figures to install the
battery on the control box of VACON ® 100 X AC drive.
1 | Remove the three screws on the control box as shown in Figure 34. |
---|
2 | Rotate and open the cover of the control box as shown in Figure 35. |
---|
3| Install the battery in the correct place and connect it to the
control box. See Figure 36 for battery location and connector.
---|---
COMMISSIONING
Before commissioning, note the following directions and warnings:
| Internal components and circuit boards of VACON ® 100 X drive (except for
the galvanically isolated I/O terminals) are live when it is connected to the
mains potential. Coming into contact with this voltage is extremely dangerous
and may cause death or severe injury.
---|---
| The motor terminals U, V, W and the brake resistor terminals R-/R+ are live
when VACON ® 100 X drive is connected to the mains, even if the motor is not
running.
| The control I/O-terminals are isolated from the mains potential. However,
the relay outputs and other I/O-terminals may have a dangerous control
voltage present even when VACON ® 100 X drive is disconnected from the mains.
| Do not make any connections to or from the AC drive when it is connected to
the mains.
| After disconnecting the AC drive from the mains, wait until the fan stops
and the indicators on the powerhead go out. Wait an additional 30 seconds
before doing any work on the connections of VACON ® 100 X Drive. Do not open
the unit before this time has expired. After expiration of this time, use a
measuring equipment to absolutely ensure that no voltage is present. Always
ensure absence of voltage before starting any electrical work!
| Before connecting the AC drive to mains make sure that the powerhead VACON ®
100 X Drive is mounted firmly on the terminal box.
6.1 Commissioning of the drive
Read carefully the safety instructions in Chapter 1 and above and follow them.
After the installation:
| Check that both the AC drive and the motor are grounded.
---|---
| Check that the mains and motor cables comply with the requirements given in
chapter 5.
| Check that the control cables are located as far as possible from the power
cables.
| Check that the shields of the shielded cables are connected to protective
earth marked with .
| Check the tightening torques of all terminals.
| Check that the wires do not touch the electrical components of the drive.
| Check that the common inputs of digital input groups are connected to +24V
or ground of the I/O terminal.
| Check the quality and quantity of cooling air.
| Check the inside of the AC drive for condensation.
| Check that all Start/Stop switches connected to the I/O terminals are in the
Stop- position.
| Before connecting the AC drive to mains: Check mounting and condition of all
fus- es and other protective devices.
| Run the Startup Wizard (see the Application Manual).
6.2 Changing EMC protection class
If your supply network is an IT (impedance-grounded) system but your AC drive
is EMC-protected according to class C1 or C2 you need to modify the EMC
protection of the AC drive to EMC-level T (C4). This is done by removing the
EMC screws as described below:
| Warning! Do not perform any modifications on the AC drive when it is
connected to mains.
---|---
| Do not remove the EMC screws in the solar pump application. IT (impedance-
grounded) AC supply network is not allowed in the solar pump application.
1| Separate the powerhead and the terminal box. Turn the powerhead
upside down and remove the two screws marked in Figure 37 (for MM4), Figure 38
(for MM5) and in Figure 40(for MM6).
---|---
2| CAUTION! Before connecting the AC drive to mains make sure that
the EMC protection class settings of the drive are appropriately made.
---|---
3| NOTE! After having performed the change write ‘EMC level
modified’ on the sticker included in the VACON ® 100 X delivery (see below)
and note the date. Unless already done, attach the sticker close to the name
plate of the AC drive.
---|---
6.3 Running the motor
MOTOR RUN CHECK LIST
| Before starting the motor, check that the motor is mounted properly and
ensure that the machine connected to the motor allows the motor to be started.
---|---
| Set the maximum motor speed (frequency) according to the motor and the
machine connected to it.
| Before reversing the motor make sure that this can be done safely.
| Make sure that no power correction capacitors are connected to the motor
cable.
| Make sure that the motor terminals are not connected to mains potential.
6.3.1 Cable and motor insulation checks
-
Motor cable insulation checks
Disconnect the motor cable from terminals U, V and W of the AC drive and from the motor. Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1MΩ at ambient temperature of 20°C. -
Mains cable insulation checks
Disconnect the mains cable from terminals L1, L2 and L3 of the AC drive and from the mains. Measure the insulation resistance of the mains cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1MΩ at ambient temperature of 20°C. -
Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the motor connection box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at least the motor nominal voltage but not exceed 1000 V. The insulation resistance must be >1MΩ at ambient temperature of 20°C.
6.3.2 Motor overload protection
On VACON® 100 X, the motor temperature can be measured with sensors in the
motor or be calculated by the electronic motor overload protection. The AC
drive provides an input for an external temperature sensor, which must be
embedded in the motor. This is a standard feature of VACON® 100 X. The
electronic motor overload protection is based on a temperature model and
algorithms to estimate the motor temperature from the operating conditions.
The internal electronic motor overload protection implemented in VACON® 100 X
has thermal memory retention and speed sensitivity.
According to EN 61800-5-1:2007/A1:2017, the electronic motor overload
protection shall comply with Table 28.
Table 28. Multiplier values for current settings
Multiplier | Maximum trip time |
---|---|
7.2 (trip at a lower overload could occur) | 20 s |
1.5 | 8 min |
1.2 | 2 h |
To guarantee a thermal protection in accordance with the standard, set the
following parameters for VACON® 100 X.
Table 29. Parameter settings
Index | Parameter | Description | Value |
---|---|---|---|
P3.9.2.6 | MotorThermMemoryAdjust | The estimated temperature rise is added to a |
motor ambient
temperature set by the parameter P3.9.2.2 MotAmbientTemp.
0 = Disabled
1 = Constant 2 = Last value
3 = Real time clock| 100
P3.9.2.4| Motor Thermal Time Const| The time constant is the time within which
the calculated
thermal stage has reached 63% of its final value| 3
For more parameters related to the motor overload protection, see the Application Manual.
| Internal motor overload protection operates at 105% of the motor full load
current.
---|---
| Instruct the AC drives with nominal motor current (full load current
according to the motor technical label) in order to use the protection
properly.
| Parameters other than those previously described may not be changed. If
further parameters related to the motor overload protection are changed, the
protection
function of the motor model can no longer be guaranteed.
| The thermal model cannot protect the motor in the event of incorrect
installation or parameter assignment. Follow the instructions for installation
and commissioning.
6.4 Maintenance
In normal conditions, the AC drive is maintenance-free. However, regular
maintenance is recommended to ensure trouble-free operation and longevity of
the drive. We recommend the table below is followed for maintenance intervals.
NOTE: Because of capacitor type (thin film capacitors), reforming of
capacitors is not necessary.
Maintenance interval | Maintenance action |
---|---|
Regularly and according to general maintenance interval | • Check the |
tightening torques of terminals.
6…24 months (depending on environment)| • Check the input and output
terminals and the control I/O terminals.
• Check the operation of the cooling fan.
• Clean the fan and the fan housing if necessary.
• Check the heatsink for dust, and clean it if necessary.
6…20 years| • Change the main fan.
10 years| • Replace the battery of the RTC.
TECHNICAL DATA
7.1 AC drive power ratings
7.1.1 Mains voltage 3AC 208-240V
Table 30. Power ratings of VACON ® 100 X, supply voltage 3AC 208-240V.
| Mains voltage 3AC 208-240V, 50/60 Hz
---|---
AC drive type| Input current [A]| Loanability| Motor shaft power
230V supply
Rated continuous current IN [A]| 50% overload current[A]| Max current IS|
[kW]| [HP]
MM4| 0006| 6.0| 6.6| 9.9| 13.2| 1.1| 1.5
0008| 7.2| 8.0| 12.0| 16.0| 1.5| 2.0
0011| 9.7| 11.0| 16.5| 22.0| 2.2| 3.0
0012| 10.9| 12.5| 18.8| 25.0| 3.0| 4.0
MM5| 0018| 16.1| 18.0| 27.0| 36.0| 4.0| 5.0
0024| 21.7| 24.2| 36.3| 48.4| 5.5| 7.5
0031| 27.7| 31.0| 46.5| 62.0| 7.5| 10.0
MM6| 0048| 43.8| 48.0| 72.0| 96.0| 11.0| 15.0
0062| 57.0| 62.0| 93.0| 124.0| 15.0| 20.0
NOTE: The rated currents in given ambient temperatures (in Table 30) are
achieved only when the switching frequency is equal to or less than the
factory default.
7.1.2 Mains voltage 3AC 380-480/500V
Table 31. Power ratings of VACON® 100 X, supply voltage 3AC 380-480/500V, high
overload.
| Mains voltage 3AC 380-480/500V, 50/60 Hz
---|---
AC drive type| Input current [A]| Loanability| Motor shaft power
400V| 480V
Rated continuous current IN[A]| 50% overload current[A]| Max current IS| [kW]|
[HP]
MM4| 0003| 3.4| 3.4| 5.1| 6.8| 1.1| 1.5
0004| 4.6| 4.8| 7.2| 9.6| 1.5| 2.0
0005| 5.4| 5.6| 8.4| 11.2| 2.2| 3.0
0008| 8.1| 8.0| 12.0| 16.0| 3.0| 5.0
0009| 9.3| 9.6| 14.4| 19.2| 4.0| 5.0
0012| 11.3| 12.0| 18.0| 24.0| 5.5| 7.5
MM5| 0016| 15.4| 16.0| 24.0| 32.0| 7.5| 10.0
0023| 21.3| 23.0| 34.5| 46.0| 11.0| 15.0
0031| 28.4| 31.0| 46.5| 62.0| 15.0| 20.0
MM6| 0038| 36.7| 38.0| 57.0| 76.0| 18.5| 25.0
0046| 43.6| 46.0| 69.0| 92.0| 22.0| 30.0
0061| 58,2| 61.0| 91.5| 122.0| 30.0| 40.0
Table 32. Power ratings of VACON ® 100 X, supply voltage 3AC 380-480/500V, low overload.
| Mains voltage 3AC 380-480/500V, 50/60 Hz
---|---
AC drive type| Input current [A]| Loanability| Motor shaft power
400V| 480V
Rated continuous current IN [A]| 10% overload current[A]| Max current IS|
[kW]| [HP]
MM6| 0072| 67.5| 72.0| 80.0| 108.0| 37.0| 50.0
NOTE: The rated currents in given ambient temperatures (in Table 31 and
Table 32) are achieved only when the switching frequency is equal to or less
than the factory default.
7.1.3 Definitions of overloadability
High overload= Following continuous operation at rated output current IN , the
drive supplies 150% * IN for 1 min, followed by a period of at least 9 min at
IN or below.
Example: If the duty cycle requires 150% rated current for 1 min in every 10
min, the remaining 9 min must be at rated current IN or less.
Low overload= Following continuous operation at rated output current IN ,
the drive supplies 110% * IN for 1 min, followed by a period of at least 9 min
at IN or below.
Example: If the duty cycle requires 110% rated current for 1 min in every
10 min, the remaining 9 min must be at rated current IN or less.
NOTE! For more information, refer to IEC61800-2 (IEC:1998) Standard.
7.2 Brake resistor ratings
Make sure that the resistance is higher than the minimum resistance defined.
The power handling capacity must be sufficient for the application.
Recommended minimum brake resistor values for VACON ® 100 X AC drives:
Table 33. Brake resistor ratings, 208-240V.
Mains Voltage 3AC 208-240V, 50/60 Hz
Enclosure size| Type| Minimum Resistance recommended
[ohm]| Brake power @405 VDC [kW]
MM4| 0006| 25| 6.6
0008| 25| 6.6
0011| 25| 6.6
0012| 25| 6.6
MM5| 0018| 15| 10.9
0024| 15| 10.9
0031| 10| 16.4
MM6| 0048| 8| 20.5
0062| 8| 20.5
__Table 34. Brake resistor ratings, 380-480/500V.
Mains Voltage 3AC 380-480/500V, 50/60 Hz
Enclosure size| Type| Minimum Resistance recommended
[ohm]| Brake power @845 VDC [kW]
MM4| 0003| 50| 14.3
0004| 50| 14.3
0005| 50| 14.3
0008| 50| 14.3
0009| 50| 14.3
0012| 50| 14.3
MM5| 0016| 30| 23.8
0023| 30| 23.8
0031| 20| 35.7
MM6| 0038| 15| 47.6
0046| 15| 47.6
0061| 15| 47.6
0072| 15| 47.6
7.1 VACON ® 100 X – technical data
Table 35. VACON ® 100 X technical data.
Mains connection| Input voltage Uin| 3 AC 208…240 V
3 AC 380…480 V
3 AC 380…500 V
---|---|---
Input voltage tolerance| -15%…+10%
Input frequency| 50/60 Hz
Protection class| I
Input frequency tolerance| 47.5…66 Hz
Connection to mains| Once per minute or less
Starting delay| <7 s
Supply network| TN- and IT-network (cannot be used with corner earthed
network)
Short-circuit current| Max. short-circuit current has to be < 100 kA (with
optional mains switch < 5 kA)
DC connection| Input Voltage UDC:| 234 … 400 VDC
436 … 800 VDC
Input voltage tolerance: No tolerance permissible, 0%
Motor connection| Output voltage| 3 AC 0… Uin
Rated output current| IN: Ambient temperature max. +40°C. See Table 30, Table
31 and Table 32.
Overload output current| 1.5 x IN (1 min/10 min);
1.1 x IN (1 min/10 min) only for MM6 0072. See Table 30, Table 31 and Table
32.
Starting output current| IS for 2 s every 20 s.
See Table 30, Table 31 and Table 32.
Output frequency| 0…320 Hz (standard)
Frequency resolution| 0.01 Hz
Protection class| I
Motor characteristics| AC squirrel cage motors
Permanent magnet motors Synchronous Reluctance Motors
Cable type| Screened motor cable
Cable maximum length (full EMC compliance)| C2: 5 m
Control characteristics| Switching frequency| Programmable 1.5…16 kHz;
Default: 6 kHz (MM4 and MM5); 4 kHz (MM6) Automatic switching frequency
derating in case of overheating
---|---|---
Frequency reference Analogue input Panel reference| Resolution 0.1%
(10-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point| 8…320 Hz
Acceleration time| 0.1…3000 s
Deceleration time| 0.1…3000 s
Braking| Brake chopper standard in all frames External brake resistor optional
Control connections| See chapter 5.
Communication interface| Fieldbus| Standard: Serial communication (RS485/Mod-
bus); Ethernet/IP, PROFINET IO, Modbus TCP, BACnet IP
Optional: CAN Open; PROFIBUS DP, Divicine, Lon Works, AS-interface
Status indicators| Drive status indicators (LED) on top side (POWER, RUN,
FAULT, READY)
Ambient conditions| Ambient operating temperature| -10°C …+40°C
Extended temperature range| up to 60°C with current derating (see chapter 1.8)
Storage temperature| -40°C…+70°C
Relative humidity| 0 to 100% RH
Pollution degree| PD2 used for PCB design.
However the drives are suitable for outdoor use because of dust-tight
enclosure to numeral 6 [acc. to IEC 60529].
Altitude| 100% load capacity (no derating) up to 1,000m; derating 1%/100m at
1,000…3,000m
Stationary vibration: sinusoidal| 3 Hz £ f £ 8.72 Hz: 10 mm
8.72 Hz £ f £ 200 Hz: 3g [3M7 acc. to IEC 60721-3-3]
Shock/Bump| 25g / 6 ms [3M7 acc. to IEC 60721-3-3]
Degree of protection| IP66/Type 4X
Noise Level| Average noise level (min-max) in dB (A)| The sound pressure
depends on the cooling fan speed, which is controlled in accordance with the
drive temperature.
MM4: 45-56
MM5: 57-65
MM6: 63-72
Directives| EMC| 2014/30/EU
---|---|---
Low Voltage Directive| 2014/35/EU
RoHS| 2011/65/EU, amended 2015/863/EU
WEEE| 2012/19/EU
Standards| Immunity| EN61800-3, 1st and 2 nd environment
Emissions| EN61800-3, Category C2
The drive can be modified for IT-networks.
THD| EN61000-3-12 (see chapter 1.9)
Safety| EN 61800-5-1
| ISO 9001
Approvals| Functional Safety| TÜV – Tested
Electrical Safety| TÜV – Tested
EMC| TÜV – Tested
USA, Canada| cULus approval, file number E171278
Declaration of Conformity| Korea| KC mark
Australia| RCM Declaration of Conformity Registration number E2204
Europe| EC Declaration of Conformity
Protections| Under voltage trip limit| Depends on supply voltage
(0.8775*supply volt-age):
Supply voltage 240 V: Trip limit 211 V Supply voltage 400 V: Trip limit
351 V Supply voltage 480 V: Trip limit 421 V
Overvoltage fault protection| Yes
Earth fault protection| Yes
Mains supervision| Yes
Motor phase supervision| Yes
Overcurrent protection| Yes
Unit overtemperature protection| Yes
Motor overload protection| Yes. These devices provide motor overload
protection at 105% of full load amperes.
Motor stall protection| Yes
Motor underload protection| Yes
Short-circuit protection of +24V and +10V reference voltages| Yes
Thermal motor protection| Yes (by PTC)
DC-link absolute maxi- mum voltage| Supply voltage 240 V: absolute maximum 450
VDC Supply voltage 400 V: 900 VDC
7.3.1 Technical information on control connections
Table 36. Technical information on standard I/O terminals.
Standard I/O
Terminal| Signal| Technical information
1| Reference output| +10V, +3%; Maximum current 10 mA
2| Analogue input, voltage or current| Analogue input channel 1 0-20 mA
(Ri =250 L)
0-10 V (Ri=200kL)
Resolution 0.1%, accuracy ±1%
Selection V/mA with DIP switches (see chapter 5). Default 0-10V
Short-circuited protected.
3| Analogue input common| Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
4| Analogue input, voltage or current| Analogue input channel 2 0-20 mA
(Ri =250 L) 0-10 V (Ri=200kL)
Resolution 0.1%, accuracy ±1%
Selection V/mA with DIP switches (see chapter 5). Default 0-20mA
Short-circuited protected.
5| Analogue input common| Differential input if not connected to ground;
Allows 20V differential mode voltage to GND
6| 24V aux. voltage| +24V, ±10%, max volt. ripple < 100mVrms; max. 250mA
Short-circuit protected
7| I/O ground| Ground for reference and controls (connected internally
to frame earth through 1ML)
8| Digital input 1| Positive or negative logic Ri = min. 5kL
18…30V = “1”
0…5V = “0”
9| Digital input 2
10| Digital input 3
11| Common A for DIN1-DIN6.| Digital inputs can be isolated from ground,
see chapter 5. Default: connected to ground.
12| 24V aux. voltage| Same as terminal 6.
13| I/O ground| Ground for reference and controls (connected internally
to frame earth through 1ML)
14| Digital input 4| Positive or negative logic Ri = min. 5kL
18…30V = “1”
0…5V = “0”
15| Digital input 5
16| Digital input 6
17| Common A for DIN1-DIN6.| Digital inputs can be isolated from ground,
see chapter 5. Default: connected to ground.
18| Analogue output, voltage or current| Analogue output channel 1 0-20
mA (RL<500 L)
0-10 V (RL>1kL)
Resolution 0.1%, accuracy ±2%
Selection V/mA with DIP switches (see chapter 5). Default 0-20mA
Short-circuited protected.
19| Analogue output common
30| 24V auxiliary input voltage| Can be used with an external power
supply (with a current limiter or fuse protected) to supply the control unit
and fieldbus for backup purposes. Dimensioning: max. 1000mA/control unit.
Table 36. Technical information on standard I/O terminals.
Standard I/O
Terminal| Signal| Technical information
A| RS485| Differential receiver/transmitter
Set bus termination with DIP switches (see page 49). Default: but termination
disconnected.
B| RS485
Table 37. Technical information on Relay and thermistor terminals.
Relays Terminal| Relays with two change-over contact (SPDT) and a
PTC thermistor input. 5.5 mm isolation between channels.
---|---
Signal| Technical information
21| Relay output 1| Switching capacity 24VDC/8A 250VAC/8A 125VDC/0.4A
Min.switching load 5V/10mA
22
23
24| Relay output 2| Switching capacity 24VDC/8A 250VAC/8A 125VDC/0.4A
Min.switching load 5V/10mA
25
26
28| Thermistor input| Ntrip = 4.7 kL (PTC); Measuring voltage 3.5V
29
- If 230VAC is used as control voltage from the output relays, the control circuitry must be powered with a separate isolation transformer to limit short circuit current and overvoltage spikes. This is to prevent welding on the relay contacts. Refer to standard EN 60204-1, section 7.2.9
OPTIONS
The options available for VACON ® 100 X are described below.
8.1 Mains switch
The mains switch can be used for service or urgency stop. The purpose of the
mains switch is to disconnect the VACON ® 100 X from the mains when, for
example, service actions are needed. The mains switch color is red/yellow. The
mains switch is available as option and it can be integrated in the drive. The
mains switch can be mounted on either side of the drive. See Figure 43.
Figure 43. The mains switch mounted on either side of the drive, MM4 example
NOTE! If the cULus mark is required, the use of the optional mains switch
is not allowed with the models 0062-2, 0061-4, 0061-5, 0072-4, and 0072-5,
unless current derating is applied. The input current cannot exceed 52 A at
30°C ambient temperature and 45 A at 40°C ambient temperature.
NOTE! Mains switch only for AC voltage. Do not use for DC voltage.
NOTE! Braided cable types recommended for mains switch cabling.
Table 38. Order codes for VACON ® 100 X Mains Switch
Order code | Description | Option type |
---|---|---|
POW-QDSS-MM04 | VACON ® 100 X MM4 Mains Switch Option | Loose Option |
POW-QDSS-MM05 | VACON ® 100 X MM5 Mains Switch Option | Loose Option |
POW-QDSS-MM06 | VACON ® 100 X MM6 Mains Switch Option | Loose Option |
8.1.1 Installation
1| • Remove the cable entry plate from the drive on the left-hand-side
if the mains switch must be mounted on this side. Otherwise remove the cable
entry plate from the right-hand-side. See the Figure 44.
---|---
2| • Remove the cable entry plate from the bottom side of the terminal
box by loosing the six screws. Cables pass through this inlet hole.
---|---
3| • Remove the powerhead from the terminal box by loosing the screws
on the top side of the drive.
---|---
4| • Connect the supply cable to the Mains switch passing through the
cable entry plate of the bottom side (use the cable gland for sealing the
cable to the gland plate) and then through the terminal box as shown in the
figure below.
---|---
5| • Connect the cables from the Mains switch to the terminal box. The
cables have to be connected to the terminals L1, L2 and L3.
---|---
6| • Place the Mains switch plate with the cables in the groove and
fix it with its screws.
7| • Place the cable entry plate with the other cables (motor cable,
brake cable, I/O cables) in the groove on the bottom side of the drive and fix
it with its screws.
8| • Mount the powerhead on the terminal box with its screws: the
installation process has been completed. See Figure 49.
---|---
8.2 Control Keypad
The control keypad is the interface between the VACON® 100 X AC drive and the
user. With the control keypad it is possible to control the speed of a motor,
to supervise the state of the equipment and to set the AC drive’s parameters.
The keypad is an option and can be delivered separately. The option includes
the keypad, the keypad holder and three screws. You can use one screw to fix
the keypad holder to the drive or three screws to fix the keypad holder to an
enclosure/cabinet or any special housing for the drive in which you want to
have a remote keypad control available.
Table 39. Keypad order codes
Order code | Description | Type of option |
---|---|---|
PAN-HMWM-MK02 | Keypad Wall mounting Kit | Loose Option |
CAB-HMI2M-MC05-X | MC05 HMI cable l=2m for -X keypads Option | Loose Option |
CAB-HMI5M-MC05-X | MC05 HMI cable l=5m for -X keypads Option | Loose Option |
8.2.1 Mounting onto the drive
8.2.2 Installation
1 | • Remove the HMI cap from the drive as shown in the Figure 51. |
---|
2| • Install the keypad holder with a screw as shown in the Figure 52.
The metal sheets of the keypad holder have to be mounted under the fan holder
as shown in the following figures.
---|---
3| • Connect the keypad to the drive and plug the cable on the HMI
connector as shown in the Figure 53 and in the Figure 54.
---|---
8.2.3 Wall-mounting
The keypad can be mounted on the wall in a convenient location by using the
same keypad holder and three screws provided with the keypad option kit.
1 | • Fix the keypad holder with three screws to the wall. |
---|
2| • Connect and fix the cable to the enclosure of the drive and
hold the keypad to the wall.
---|---
8.2.4 Graphical and Text keypad
There are two keypad types you can choose for your user interface: keypad with
graphical display and keypad with text segment display (text keypad).
The button section of the keypad is identical for both keypad types.
8.2.5 VACON® keypad with graphical display
The graphical keypad features an LCD display and 9 buttons.
8.2.5.1 Keypad display
The keypad display indicates the status of the motor and the drive and any
irregularities in motor or drive functions. On the display, the user sees
information about his present location in the menu structure and the item
displayed.
8.2.5.2 Main menu
The data on the control keypad are arranged in menus and submenus. Use the Up
and Down arrows to move between the menus. Enter the group/item by pressing
the OK button and return to the former level by pressing the Back/Reset
button.
The Location field indicates your current location. The Status field gives
information about the present status of the drive. See Figure 59.
8.2.5.3 Using the graphical keypad
Editing values
The selectable values can be accessed and edited in two different ways on the
graphical keypad.
Parameters with one valid value
Typically, one parameter is set one value. The value is selected either from a
list of values (see example below) or the parameter is given a numerical value
from a defined range (e.g. 0.00…50.00 Hz). Change value of a parameter
following
the procedure below:
- Locate the parameter.
- Enter the Edit mode.
- Set new value with the arrow buttons up/down. You can also move from digit to digit with the arrow buttons left/right if the value is numerical and then change the value with the arrow buttons up/down.
- Confirm change with OK button or ignore change by returning to previous level with Back/Reset button.
Parameters with checkbox selection
Some parameters allow selecting several values. Make a checkbox selection at
each value you wish to activate as instructed below.
Resetting fault
Instructions for how to reset a fault can be found in chapter 8.2.7.
Function button
The FUNCT button is used for four functions:
- to quickly access the Control page,
- to easily change between the Local (Keypad) and Remote control places,
- to change the rotation direction and
- to quickly edit a parameter value.
Control places
The control place is the source of control where the drive can be started and
stopped. Every control place has its own parameter for selecting the frequency
reference source. The Local control place is always the keypad. The Remote
control place is determined by parameter P3.2.1 (I/O or Fieldbus). The
selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and
Fieldbus have the lowest priority and can be chosen with parameter P3.2.1 (Rem
Control Place). I/O B, again, can bypass the remote control place selected
with parameter P3.2.1 using a digital input. The digital input is selected
with parameter P3.5.1.7 (I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control
has higher priority than remote control. Therefore, if, for example, bypassed
by parameter P3.5.1.7 through digital input while in Remote, the control place
will still switch to Keypad if Local is selected. Switching between Local and
Remote Control can be done by pressing the FUNCT-button on the keypad or by
using the “Local/Remote” (ID211) parameter.
Changing control places
Change of control place from Remote to Local (keypad).
- Anywhere in the menu structure, push the FUNCT button.
- Push the Arrow up or the Arrow down button to select Local/Remote and confirm with the OK button.
- On the next display, select Local or Remote and again confirm with the OK button.
- The display will return to the same location as it was when the FUNCT button was pushed. However, if the Remote control place was changed to Local (Keypad) you will be prompted for keypad reference.
Accessing the control page
The Control page is meant for easy operation and monitoring of the most
essential values.
- Anywhere in the menu structure, push the FUNCT button.
- Push the Arrow up or the Arrow down button to select Control page and confirm with the OK button.
- The control page appears
If keypad control place and keypad reference are selected to be used you can set the Keypad Reference after having pressed the OK button. If other control places or reference values are used the display will show Frequency reference which is not editable. The other values on the page are Multimonitoring values. You can choose which values appear here for monitoring.
Changing direction
Rotation direction of the motor can quickly be changed by applying the FUNCT
button. NOTE! Changing direction command is not visible in the menu unless the
selected control place is Local.
- Anywhere in the menu structure, push the Func button.
- Push the Arrow up or the Arrow down button to select Change direction and confirm with the OK button.
- Then choose the direction you wish to run the motor to. The actual rotation direction is blinking. Confirm with the OK button.
- The rotation direction changes immediately and the arrow indication in the status field changes.
Quick edit
Through the Quick edit functionality you can quickly access the desired
parameter by entering the parameter’s ID number.
- Anywhere in the menu structure, push the FUNCT button.
- Push the Arrow up or the Arrow down buttons to select Quick Edit and confirm with the OK button.
- Then enter the ID number of parameter or monitoring value you wish to access. Press OK button to confirm.
- Requested Parameter/Monitoring value appears on the display (in editing/monitoring mode.)
Copying parameters
NOTE: This feature is available with graphical keypad only.
The parameter copy function can be used to copy parameters from one drive to
another.
The parameters are first saved to the keypad, then the keypad is detached and
connected to another drive. Finally the parameters are downloaded to the new
drive restoring them from the keypad. Before any parameters can successfully
be copied from one drive to another the drive has to be stopped when the
parameters are downloaded.
- First go into User settings menu and locate the Parameter backup submenu. In the Parameter backup submenu, there are three possible functions to be selected:
- Restore factory defaults will re-establish the parameter settings originally made at the factory.
- By selecting Save to keypad you can copy all parameters to the keypad.
- Restore from keypad will copy all parameters from keypad to a drive.
NOTE: If the keypad is changed between drives of different sizes, the
copied values of these parameters will not be used:
Motor nominal current (P3.1.1.4)
Motor nominal voltage (P3.1.1.1)
Motor nominal speed (P3.1.1.3)
Motor nominal power (P3.1.1.6)
Motor nominal frequency (P3.1.1.2)
Motor cos phi (P3.1.1.5)
Switching frequency (P3.1.2.3)
Motor current limit (P3.1.3.1)
Stall current limit (P3.9.3.2)
Stall time limit (P3.9.3.3)
Stall frequency (P3.9.3.4)
Maximum frequency (P3.3.1.2)
Help texts
The graphical keypad features instant help and information displays for
various items.
All parameters offer an instant help display. Select Help and press the OK
button.
Text information is also available for faults, alarms and the startup
wizard.
Adding item to favourites
You might need to refer to certain parameter values or other items often.
Instead of locating them one by one in the menu structure, you may want to add
them to a folder called Favorites where they can easily be reached.
To add an item to the Favorites.
8.2.6 VACON® keypad with text segment display
You can also choose a Keypad with text segment display (Text keypad) for your
user interface. It has mainly the same functionalities as the keypad with
graphical display although some of these are somewhat limited.
8.2.6.1 Keypad display
The keypad display indicates the status of the motor and the drive and any
irregularities in motor or drive functions. On the display, the user sees
information about his present location in the menu structure and the item
displayed. If the text on the text line is too long to fit in the display,
the text will scroll from left to right to reveal the whole text string.
8.2.6.2 Main menu
The data on the control keypad are arranged in menus and submenus. Use the Up
and Down arrows to move between the menus. Enter the group/item by pressing
the OK button and return to the former level by pressing the Back/Reset
button.
8.2.6.3 Using the keypad
Editing values
Change value of a parameter following the procedure below:
- Locate the parameter.
- Enter the Edit mode by pressing OK.
- Set new value with the arrow buttons up/down. You can also move from digit to digit with the arrow buttons left/right if the value is numerical and change then the value with the arrow buttons up/down.
- Confirm change with OK button or ignore change by returning to previous level with Back/ Reset button.
Resetting fault
Instructions for how to reset a fault can be found in chapter 8.2.7.
Function button
The FUNCT button is used for four functions:
- to quickly access the Control page,
- to easily change between the Local (Keypad) and Remote control places,
- to change the rotation direction and
- to quickly edit a parameter value.
Control places
The control place is the source of control where the drive can be started and
stopped. Every control place has its own parameter for selecting the frequency
reference source. The Local control place is always the keypad. The Remote
control place is determined by parameter P3.2.1 (I/O or Fieldbus). The
selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and
Fieldbus have the lowest priority and can be chosen with parameter P3.2.1 (Rem
Control Place). I/O B, again, can bypass the remote control place selected
with parameter P3.2.1 using a digital input. The digital input is selected
with parameter P3.5.1.7 (I/O B Ctrl Force).
Local control
Keypad is always used as control place while in local control. Local control
has higher priority than remote control. Therefore, if, for example, bypassed
by parameter P3.5.1.7 through digital input while in Remote, the control place
will still switch to Keypad if Local is selected. Switching between Local and
Remote Control can be done by pressing the FUNCT-button on the keypad or by
using the “Local/Remote” (ID211) parameter.
Changing control places
Change of control place from Remote to Local (keypad).
- Anywhere in the menu structure, push the FUNCT button.
- Using the arrow buttons, select Local/Remote and confirm with the OK button.
- On the next display, select Local or Remote and again confirm with the OK button.
- The display will return to the same location as it was when the FUNCT button was pushed. However, if the Remote control place was changed to Local (Keypad) you will be prompted for keypad reference.
Accessing the control page
The Control page is meant for easy operation and monitoring of the most
essential values.
- Anywhere in the menu structure, push the FUNCT button.
- Push the Arrow up or the Arrow down button to select Control page and confirm with the OK button.
- The control page appears
If keypad control place and keypad reference are selected to be used you can set the Keypad Reference after having pressed the OK button. If other control places or reference values are used the display will show Frequency reference which is not editable.
Changing direction
Rotation direction of the motor can quickly be changed by applying the FUNCT
button. NOTE! Changing direction command is not visible in the menu unless the
selected control place is Local.
-
Anywhere in the menu structure, push the Funct button.
-
Push the Arrow up or the Arrow down button to select Change direction and confirm with the OK button.
-
Then choose the direction you wish to run the motor to. The actual rotation direction is blinking.
Confirm with the OK button. -
The rotation direction changes immediately and the arrow indication in the status field changes.
Quick edit
Through the Quick edit functionality you can quickly access the desired
parameter by entering the parameter’s ID number.
- Anywhere in the menu structure, push the FUNCT button.
- Push the Arrow up or the Arrow down buttons to select Quick Edit and confirm with the OK button.
- Then enter the ID number of parameter or monitoring value you wish to access. Press OK button to confirm.
- Requested Parameter/Monitoring value appears on the display (in editing/monitoring mode.)
8.2.7 Fault Tracing
When an unusual operating condition is detected by the AC drive control
diagnostics, the drive initiates a notification visible, for example, on the
keypad. The keypad will show the code, the name and a short description of the
fault or alarm. The notifications vary in consequence and required action.
Faults make the drive stop and require reset of the drive. Alarms inform of
unusual operating conditions but the drive will continue running. Info may
require resetting but do not affect the functioning of the drive.
For some faults you can program different responses in the application. See
parameter group Protections. The fault can be reset with the Reset button on
the control keypad or via the I/O terminal. The faults are stored in the Fault
history menu which can be browsed. The different fault codes you will find in
the table below.
NOTE: When contacting distributor or factory because of a fault
condition, always write down all texts and codes on the keypad display.
Fault appears
When a fault appears and the drive stops, examine the cause of fault, perform
the actions advised here and reset the fault as instructed below.
- With a long (1 s) press on the Reset button on the keypad or
- By entering the Diagnostics Menu (M4), entering Reset faults (M4.2) and selecting Reset faults parameter.
- For keypad with LCD display only: By selecting value Yes for the parameter and clicking OK.
8.2.7.1 Fault History
In menu M4.3 Fault history you find the maximum number of 40 occurred faults.
On each fault in the memory you will also find additional information, see
below.
Table 40. Fault codes and descriptions.
Fault code| Fault ID| Fault name| Possible cause|
Remedy
---|---|---|---|---
1| 1| Overcurrent (hardware fault)| AC drive has detected too high a cur- rent
(>4*IH) in the motor cable:
• sudden heavy load increase
• short circuit in motor cables
• unsuitable motor| Check loading. Check motor.
Check cables and connections. Make identification run. Check ramp times.
2| Overcurrent (software fault)
2| 10| Overvoltage (hardware fault)| The DC-link voltage has exceeded the
limits defined.
• too short a deceleration time
• brake chopper is disabled
• high overvoltage spikes in supply
• Start/Stop sequence too fast| Make deceleration time longer. Use brake
chopper or brake resistor (available as options). Activate overvoltage
controller. Check input voltage.
11| Overvoltage (soft- ware fault)
3| 20| Earth fault (hard- ware fault)| Current measurement has detected that
the sum of motor phase current is not zero.
• insulation failure in cables or motor| Check motor cables and motor.
21| Earth fault (soft- ware fault)
5| 40| Charging switch| The charging switch is open, when the START command
has been given.
• faulty operation
• component failure| Reset the fault and restart. Should the fault re-occur,
con- tact the distributor near to you.
7| 60| Saturation| Various causes:
• defective component
• brake resistor short-circuit or overload| Cannot be reset from keypad.
Switch off power.
DO NOT RE-CONNECT POWER!
Contact factory.
If this fault appears simultane- ously with F1, check motor cables and motor.
Fault code| Fault ID| Fault name| Possible cause|
Remedy
---|---|---|---|---
8| 600| System fault| Communication between control board and power unit has
failed.| Reset the fault and restart. Should the fault re-occur, con- tact the
distributor near to you.
601| Communication between control board and power unit has interference, but
it is still working.
602| Watchdog has reset the CPU
603| Voltage of auxiliary power in power unit is too low.
604| Phase fault: Voltage of an output phase does not follow the reference
605| CPLD has faulted but there is no detailed information about the fault
606| Control and power unit software are incompatible| Update software. Should
the fault re-occur, contact the dis- tributor near to you.
607| Software version cannot be read. There is no software in power unit.|
Update power unit software. Should the fault re-occur, con- tact the
distributor near to you.
608| CPU overload. Some part of the soft- ware (for example application) has
caused an overload situation. The source of fault has been suspended| Reset
the fault and restart. Should the fault re-occur, con- tact the distributor
near to you.
609| Memory access has failed. For exam- ple, retain variables could not be
restored.
610| Necessary device properties cannot be read.
614| Configuration error.
647| Software error| Update software. Should the fault re-occur, contact the
dis- tributor near to you.
648| Invalid function block used in applica- tion. System software and
application are not compatible.
649| Resource overload.
Error when loading parameter initial values.
Error when restoring parameters. Error when saving parameters.
9| 80| Undervoltage (fault)| DC-link voltage is under the voltage limits
defined.
• most probable cause: too low a supply voltage
• AC drive internal fault
• defect input fuse
• external charge switch not closed
NOTE! This fault is activated only if the drive is in Run state.| In case of
temporary supply voltage break reset the fault and restart the AC drive. Check
the supply voltage. If it is ade- quate, an internal failure has occurred.
Contact the distributor near to you.
81| Undervoltage (alarm)
10| 91| Input phase| Input line phase is missing.| Check supply voltage, fuses
and cable.
Fault code| Fault ID| Fault name| Possible cause|
Remedy
---|---|---|---|---
11| 100| Output phase supervision| Current measurement has detected that there
is no current in one motor phase.| Check motor cable and motor.
12| 110| Brake chopper supervision
(hardware fault)| No brake resistor installed. Brake resistor is broken.
Brake chopper failure.| Check brake resistor and cabling.
If these are ok, the chopper is faulty. Contact the distributor near to you.
111| Brake chopper saturation alarm
13| 120| AC drive undertempera- ture (fault)| Too low temperature measured in
power unit’s heatsink or board. Heat- sink temperature is under -10°C.| Check
the ambient tempera- ture
14| 130| AC drive overtemperature (fault, heatsink)| Too high temperature
measured in power unit’s heatsink or board. Heat- sink temperature is over
100°C.| Check the correct amount and flow of cooling air.
Check the heatsink for dust. Check the ambient tempera- ture.
Make sure that the switching frequency is not too high in relation to ambient
tempera- ture and motor load.
131| AC drive overtemperature (alarm, heatsink)
132| AC drive overtemperature (fault, board)
133| AC drive overtemperature (alarm, board)
15| 140| Motor stalled| Motor is stalled.| Check motor and load.
16| 150| Motor overtemperature| Motor is overloaded.| Decrease motor load.
If no motor overload exists, check the temperature model parameters.
17| 160| Motor underload| Motor is underloaded.| Check load.
19| 180| Power overload (short-time supervision)| Drive power is too high.|
Decrease load.
181| Power overload (long-time supervision)
__
25
| 240| Motor control fault| Start angle identification has failed.| Reset the
fault and restart. Should the fault re-occur, con- tact the distributor near
to you.
241| Generic motor control fault.
26| 250| Start-up prevented| Start-up of the drive has been pre- vented. Run
request is ON when a new software (firmware or application), parameter setting
or any other file, which has affects the operation of the drive, has been
loaded to drive.| Reset the fault and stop the AC drive.
Load the software and start the AC drive.
Fault code| Fault ID| Fault name| Possible cause|
Remedy
---|---|---|---|---
30| 290| Safe off| Unstable STO input A (spurious pulses detected).| Check the
Safety switch and cabling.
Reset the fault and restart. Should the fault re-occur, con- tact the distributor near to you.
291| Safe off| Unstable STO input B (spurious pulses detected).| Check the
Safety switch and cabling.
Reset the fault and restart. Should the fault re-occur, con- tact the
distributor near to you.
520| Safe diagnostic| Diagnostic failure (STO inputs are in different state).|
Check the Safety switch and cabling.
Reset the fault and restart the drive.
Should the fault re-occur, con- tact the distributor near to you.
530| STO fault| STO function demanded. Drive is in safe state.| Wait for STO
inputs deactiva- tion.
Reset the fault and restart.
32| 312| Fan cooling| Fan life time is up.| Change fan and reset fan life time
counter.
33| 320| Fire mode enabled| Fire mode of the drive is enabled. The drive’s
protections are not in use.| Check the parameter settings
37| 360| Device changed (same type)| Option board changed for one previ- ously
inserted in the same slot. The board’s parameter settings are saved.| Device
is ready for use. Old parameter settings will be used.
38| 370| Device changed (same type)| Option board added. The option board was
previously inserted in the same slot. The board’s parameter settings are
saved.| Device is ready for use. Old parameter settings will be used.
39| 380| Device removed| Option board removed from slot.| Device no longer
available.
40| 390| Device unknown| Unknown device connected (power unit/option board)|
Device no longer available.
41| 400| IGBT temperature| IGBT temperature (unit temperature + I2T) is too
high.| Check loading. Check motor size.
Make identification run.
44| 430| Device changed (different type)| Option board changed or Power unit
changed. No parameter settings are saved.| Set the option board parame- ters
again if option board was changed. Set drive parameters again if power unit
was changed.
45| 440| Device changed (different type)| Option board added. The option board
was not previously present in the same slot. No parameter settings are saved.|
Set the option board parame- ters again.
46| 662| Real Time Clock| RTC battery voltage level is low and the battery
should be changed.| Replace the battery.
47| 663| Software updated| Software of the drive has been updated (either the
whole software package or application).| No actions needed.
Fault code| Fault ID| Fault name| Possible cause|
Remedy
---|---|---|---|---
50| 1050| AI low fault| At least one of the available analogue input signals
has gone below 50% of the defined minimum signal range.
Control cable is broken or loose. Signal source has failed.| Change the failed
parts. Check the analog input circuit.
Check that parameter AI1 sig- nal range is set correctly.
51| 1051| External Fault| Fault activated by digital input.| Check the digital
input or the device connected to it.
Check the parameter settings.
__
52
| 1052
1352| Keypad communication fault| The connection between the control keypad
and AC drive is broken| Check keypad connection and possible keypad cable
53| 1053| Fieldbus communication fault| The data connection between the field-
bus master and fieldbus board is bro- ken| Check installation and fieldbus
master.
54| 1654| Slot D fault| Defective option board or slot| Check board and slot.
1754| Slot E fault
57| 1057| Identification| Identification run has failed.| Check that motor is
connected to the drive.
Ensure that there is no load on the motor shaft.
Ensure that the start command will not be removed before completion of
identification run.
58| 1058| Mechanical brake| Actual status of mechanical brake remains
different from the control sig- nal for longer than what is defined.| Check
the status and connec- tions of the mechanical brake.
61| 1061| Waiting restart time| The drive is counting the delay time before a
new attempt to start, after it stopped because of low power/voltage available
from DC supply.| The delay can be skipped by turning off and on again the
external Start command. Delay timing can be set with parame- ters from
P3.22.1.2 to P3.22.1.4.
63| 1063| Quick Stop fault| The Quick stop function is activated| Find the
cause for the quick stop activation. After you find it, correct it. Reset the
fault and restart the drive. Once found and corrective actions taken, reset
the fault and restart the drive.
1367| Quick Stop alarm
65| 1065| PC communication fault| The data connection between the PC and AC
drive is broken|
66| 1066| Thermistor fault| The thermistor input has detected an increase of
motor temperature| Check motor cooling and load. Check thermistor connection
(If thermistor input is not in use it has to be short circuited)
Fault code| Fault ID| Fault name| Possible cause|
Remedy
---|---|---|---|---
68| 1301| Maintenance counter 1 alarm| Maintenance counter has reached the
alarm limit.| Carry out the needed mainte- nance and reset counter.
1302| Maintenance counter 2 alarm| Maintenance counter has reached the alarm
limit.| Carry out the needed mainte- nance and reset counter.
1303| Maintenance counter 3 alarm| Maintenance counter has reached the alarm
limit.| Carry out the needed mainte- nance and reset counter.
1304| Maintenance counter 4 alarm| Maintenance counter has reached the alarm
limit.| Carry out the needed mainte- nance and reset counter.
69| 1310| Fieldbus mapping error| Non-existing ID number is used for mapping
values to Fieldbus Process Data Out.| Check parameters in Fieldbus Data
Mapping menu.
1311| Not possible to convert one or more values for Fieldbus Process Data
Out.| The value being mapped may be of undefined type. Check parameters in
Fieldbus Data Mapping menu.
1312| Overflow when mapping and converting values for Fieldbus Process Data
Out (16-bit).|
76| 1076| Start prevented| Start command is active and was blocked in order to
prevent uninten- tional rotation of the motor during the first power-up.|
Reset drive to restore the nor- mal operation. The need of restart depends on
the parame- ter settings.
77| 1077| >5 connections| Maximum number of 5 simultaneous active fieldbus or
PC tool connections supported by the application exceeded.| Remove excessive
active con- nections.
100| 1100| Soft fill time-out| The Soft fill function in the PID control- ler
has timed out. The wanted process value was not achieved within time.| Reason
might be a pipe burst.
101| 1101| Process supervision fault (PID1)| PID controller: Feedback value
outside of supervision limits (and the delay if set).| Check settings.
105| 1105| Process supervision fault (PID2)| PID controller: Feedback value
outside of supervision limits (and the delay if set).| Check settings.
109| 1109| Input pressure supervision| Input pressure supervision signal has
gone below the alarm limit.| Check the process. Check the parameters
Check the input pressure sen- sor and connections.
1409| Input pressure supervision signal has gone below the fault limit.
111| 1315| Temperature fault 1| At least one of the selected tempera- ture
input signals has reached the alarm limit.| Find the cause of temperature
raise.
Check the temperature sensor and connections.
Check that the temperature input is hard wired if no sensor is connected.See
option board manual for further
information.
1316| At least one of the selected tempera- ture input signals has reached the
fault limit.
112| 1317| Temperature fault 2| At least one of the selected tempera- ture
input signals has reached the fault limit.
1318| At least one of the selected tempera- ture input signals has reached the
fault limit.
Fault code| Fault ID| Fault name| Possible cause|
Remedy
---|---|---|---|---
113| 1113| Pump running time| In the Multimap system, 1 or more of the pump
runtime counters is above a user-specified alarm limit.| Do the necessary
maintenance actions, reset the runtime counter and reset the alarm. See Pump
running time count- ers.
1313| In the Multimap system, 1 or more of the pump runtime counters is above
a user-specified Fault limit
300| 700| Unsupported| The application is not compatible (it is unsupported).|
Replace the application.
701| The option board or the slot is not com-partible (it is unsupported).|
Remove the option board.
8.30 Heater (arctic option)
8.3.1 Safety
This manual contains clearly marked cautions and warnings which are intended
for your personal safety and to avoid any unintentional damage to the product
or connected appliances.
Please read the information included in dangers carefully.
The optional heater allows the drive to operate in low temperature conditions
down to -40°C. This option is intended to be installed inside the drive.
Only trained and qualified personnel authorized by the manufacturer are
allowed to install and maintain this component.
8.3.2 Dangers
| The components of the optional heater are live when the element is
connected to mains potential. Coming into contact with this voltage is
extremely dangerous and may cause death or severe injury.
---|---
|
The heater can be used only inside the drive and in combination with only the
VACON® 100 X. Before connecting the heater to mains, make sure that the ®
VACON 100 X drive is closed firmly.
Table 41. Dangers
8.3.3 Technical data
The optional heater has to be supplied with single-phase 230V. The thermal
element is always supplied and if the drive is connected at -40°C the drive
will be heated up until the temperature of -10°C is exceeded. The heating is
temperature controlled and an internal fan ensures that the air is equally
distributed inside the enclosure.
The integrated relay output (switching capacity: 24VDC / 3A, 277VAC / 3A) can
be used to control the power-up of the drive. The contact is closed when the
internal temperature is higher than the minimum allowed value for the power-up
(~ -10°C). This can be included and managed in the logic of the entire system.
A bi-color LED (on the enclosure of this option), shows the status of the
drive, ready or not-ready.
Table 42. Technical information on input and relay terminals.
Heater connections
Terminal| Signal| Technical information
L1| Line| Supply voltage input terminals: 1AC 230V 50Hz 60 Hz 900 mA
Tolerance: 208V -15%…250V +10%
External fuse needed:
• class T (UL& CSA) min. 300V
• class J (UL& CSA) min. 300V
N| Neutral
X1| Feedback relay output| Switching capacity: 24VDC / 3A 250VAC /3A
8.3.4 Fuses
The recommended fuse types for the heater supply voltage are shown in the
table below.
Table 43. Fuses ratings.
Fuses for heater supply voltage input – 230VAC
gG/gL (IEC 60269-1) 500V| class T (UL & CSA) **300V| class
J (UL & CSA) **300V
1A| 1A| 1A
Table 44. Order codes for VACON® 100 X Heater
Order code | Description | Option type |
---|---|---|
ENC-QAFH-MM04 | VACON ® 100 X MM4 Auxiliary Frame Heater option | Loose Option |
ENC-QAFH-MM05 | VACON ® 100 X MM5 Auxiliary Frame Heater option | Loose Option |
ENC-QAFH-MM06 | VACON ® 100 X MM6 Auxiliary Frame Heater option | Loose Option |
8.3.5 Mounting instructions: MM4 Example
8.4 Option
boards
VACON® 100 X drive family embodies a wide selection of expander boards with
which the available ® I/O of VACON 100 X AC drive can be increased and its
versatility improved.
There are two board slots (labelled D and E) on the VACON® 100 X control
board. To locate the slot, see chapter 5. Usually, when the AC drive is
delivered from the factory, the control unit does not include any option board
in the board slots.
The following option boards are supported:
Table 45. Option boards supported in VACON® 100 X.
Code| Description|
Note
---|---|---
OPTB1| Option board with six birdie-tonal terminals.| With jumper blocks it is
possible to use each terminal as digital input or as digital output.
OPTB2| I/O expander board with a thermistor input and two relay outputs.|
OPTB4| I/O expander board with one galvanically isolated analogue input and
two galvanically isolated analogue outputs (standard signals 0(4)…20mA).|
OPTB5| I/O expander board with three relay outputs|
OPTB9| I/O expander board with five 42…240 VAC digital inputs and one relay
output.|
OPTBF| I/O expander board with ana-logue output, digital output and relay
output.| On the OPTBF board, there is one jumper block for selecting the ana-
logue output mode (mA/V).
OPTBH| Temperature measurement board with three individual channels.|
Supported sensors: PT100, PT1000, NI1000, KTY84-130, KTY84-150, KTY84-131
OPTBK| AS-interface option board|
OPTC4| LonWorks option board| Pluggable connector with screw ter- minals
OPTE2| Modbus RTU and N2| Screw terminals
OPTE3| PROFIBUS DP option board| Pluggable connector with screw ter- minals
OPTE5| PROFIBUS DP option board| 9-pin Sub-D terminal
OPTE6| CANopen option board|
OPTE7| DeviceNet option board|
OPTE8| Modbus RTU and N2| Sub-D9 connector
OPTE9| Dualport Ethernet option board|
OPTEC| EtherCAT option board|
8.5 Flange adapter
VACON® 100 X is an IP66/Type 4X outdoor drive, designed to be installed as
close as possible to the motor, minimizing the use of electrical rooms,
integrating the drive as part of the machine, without the use of cabinets.
VACON® 100 X drives are products than can be mounted directly onto the motor,
machine or wher-ever the most efficient location for the drive is. This
solution allows the machine designer, to use the available space in and around
the machine, optimally. A decentralized solution provides a more flexible
solution as an OEM manufacturer can deliver its machine in one piece, and
there is no need to install the drives in a separate location. See the MM4
flange adapter in Figure 81.
These flange adapters can be used, for example, with the following motor types:
- B3 – Foot mounting
- B34 – Foot – B14 face mounting
- B35 – Foot – B5 flange mounting
Compared to a traditional solution, with the AC drives located in an
electrical room, a decentralized solution offers significant savings potential
in cabling and installation costs. By locating the drive near the machine or
onto the motor, the length of the motor cable will be minimized. ENC-QMMF-MM04
flange adapter can be used with 5 different motor sizes while both ENC-
QMMFMM05 and ENC-QMMF-MM06 flange adapters can be connected only to 3
different motor sizes. See Table 46 for further details.
Table 46 shows the corresponding flange adapters for different motor sizes.
See also the relations with the inverter enclosure sizes.
Table 46. Correspondences between flange adapters, motors and inverter sizes.
Flange adapter type code| Motor size| Power at 1500 rpm [kW]| Rated current at
1500 rpm [A]| A [mm]| B [mm]| Inverter enclosure size
---|---|---|---|---|---|---
ENC-QMMF-MM04| 90S| 1.1| 2.89| 140| 100| MM4
90L| 1.5| 3.67| 140| 125
100L| 2.2/3| 5.16/6.8| 160| 140
112M| 4| 8.8| 190| 140
132S| 5.5| 11.8| 216| 140
ENC-QMMF-MM05| 132M| 7.5| 15.6| 216| 178| MM5
160M| 11| 22.6| 254| 210
160L| 15| 30.1| 254| 254
ENC-QMMF-MM06| 180M| 18.5| 36.1| 279| 241| MM6
180L| 22| 42.5| 279| 279
200L| 30| 57.4| 318| 305
8.5.1 Mounting instructions: MM4 Example
SAFE TORQUE OFF
This chapter describes the Safe Torque Off (STO) function which is a
functional safety feature present into VACON ® 100 X drive products as
standard.
9.1 General description
The STO function brings the motor in no-torque-state as defined by 4.2.2.2 of
the IEC 61800-5-2: “Power that can cause rotation (or motion in the case of a
linear motor) is not applied to the motor. The Power Drive System (Safety
Related) will not provide energy to the motor which can generate torque (or
force in the case of a linear motor).”
Therefore, the STO function is suitable for applications that rely on the
immediate removal of power to the actuator, resulting in an uncontrolled coast
to stop (activated by an STO demand). Additional protective measures need to
be applied when an application requires a different stop method.
9.2 Warnings
| Designing of safety-related systems requires specialist knowledge and
skills. Only qualified people are permitted to install and set up the STO
function. The use of STO does not itself ensure safety. An overall risk
evaluation is required for ensuring that the commissioned system is safe.
Safety devices must be correctly incorporated into the entire system which
must be designed in compliance with all relevant standards within the field of
industry.
---|---
| The information in this manual provides guidance on the use of the STO
function. This information is in compliance with accepted practice and
regulations at the time of writing. However, the end product/system designer
is responsible for ensuring that the end-system is safe and in compliance with
relevant regulations.
| When a permanent magnet motor is used and in case of a multiple IGBT power
semiconductor failure, when the STO option energizes the drive outputs to
the off state, the drive system may still provide an alignment torque which
maximally rotates the motor shaft by 180°/p (where p is the number of poles of
the motor) before the torque production ceases.
| Electronic means and contactors are not adequate for protection against
electric shock. The Safe Torque Off function does not disconnect the voltage
or the mains
from the drive. Therefore hazardous voltages may still be present on the
motor. If electrical or maintenance work has to be carried out on electrical
parts of the drive or the motor, the drive has to be completely isolated from
the main supply, e.g. using an external supply disconnecting switch (see
EN60204-1).
| This safety function corresponds to an uncontrolled stop in accordance with
stop category 0 of IEC 60204-1. The STO function does not comply with
Emergency
Switching Off according to IEC 60204-1 (no galvanic insulation from the Mains
in case the motor is stopped).
| The STO function is not a prevention of unexpected start-up. To fulfill
those requirements, additional external components are required according to
appropriate
standards and application requirements.
| In circumstances where external influences (e.g. falling of suspended loads)
are present additional measures (e.g. mechanical brakes) may be necessary to
prevent any hazard.
| STO must not be used as a control for starting or stopping the drive.
9.3 Standards
The STO function has been designed for use in accordance with the following
standards:
Table 47. Safety Standards.
Standards
IEC 61508, Parts 1-7
EN 61800-5-2
EN 62061
ISO 13849-1
IEC 60204-1
The STO function has to be applied correctly to achieve the desired level of
operational safety. Four different levels are allowed, depending on the use of
the STO signals (see the following table).
*Table 48. Four different STO levels. () see 9.5.1**
STO inputs| STO feedback| Cat.| PL|
SIL
---|---|---|---|---
Both dynamically used(*)| Used| 4| e| 3
Both statically used| Used| 3| e| 3
Connected in parallel| Used| 2| d| 2
Connected in parallel| Not used| 1| c| 1
The same values are calculated for SIL and SIL CL. According to EN 60204-1,
the emergency stop category is 0.
The SIL value for the safety related system, operating in high
demand/continuous mode, is related to the probability of dangerous failure per
hour (PFH), reported in the following table.
*Table 49. SIL values. () see 9.5.1.**
STO inputs| STO feedback| PFH| PFDav| MTTFd (years)|
DCavg
---|---|---|---|---|---
Both dynamically used(*)| Used| 1.2 E-09 1/h| 1.0 E-04| >4274 y| HIGH
Both statically used| Used| 1.2 E-09 1/h| 1.1 E-04| >4274 y| MEDIUM
Connected in parallel| Used| 1.2 E-09 1/h| 1.1 E-04| >4274 y| MEDIUM
Connected in parallel| Not used| 1.5 E-09 1/h| 1.3 E-04| >4274 y| NONE
The STO inputs must always be supplied by a safety device.
The power supply of the safety device may be external or taken from the drive
(as long as this is compliant with the rating specified for terminal 6). See
Chapter 5.1.2 for the standard I/O terminal description.
9.4 The principle of STO
The STO functionality, such as the technical principles and data (wiring
examples and commissioning) will be described in this chapter. ® In VACON 100
X, the STO function is realized by preventing the propagation of the control
signals
to the inverter circuit. The inverter power stage is disabled through
redundant disabling paths which start from the two separated and galvanically
isolated STO inputs (S1-G1, S2-G2 in Figure 89). In addition, an isolated
output feedback is generated to improve the diagnostics of the STO function
and to achieve a better safety capability (F+, F- terminals). The values
assumed by the STO output feedback are indicated in the following table:
Table 50. Values of the STO output feedback (and torque on the motor). (*)
Only one channel is preventing the motor from moving.
STO inputs| Operating conditions| STO feedback output|
Torque at the motor shaft
---|---|---|---
Both inputs energized with 24V DC| Normal operation| The feedback must be 0V|
present (motor on)
Power removed from both inputs| STO demand| The feedback must be 24V| disabled
(motor de-energized)
The STO inputs have different values| Failure in demand or due to internal
fault| The feedback must be 0V| disabled (motor de-energized)(*)
The diagram below is a conceptual schematic diagram and is presented to illustrate the safety function with relevant safety components only shown.
9.4.1 Technical details
The STO inputs are digital inputs intended for a nominal 24V d.c. input,
positive logic (e.g. enabled when high).
Table 51. Electrical data.
Technical information:|
Technical values
---|---
Maximum voltage| 30 V
Typical input current at 24V| 10…15 mA
Logic threshold| according to IEC 61131-2 15V 30V = “1” 0V 5V = “0”
Response time at nominal voltage:|
Reaction time| <20ms
The reaction time of the STO function is the amount of time which passes from
the moment in which the STO is activated until the system is in the Safe
State. For VACON ® 100 X, the reaction time is 20 ms maximum.
9.5 Connections
To make the STO function available and ready to be used, both the STO jumpers
have to be removed. They are located in front of the STO inputs to
mechanically prevent the insertion of the STO connector. For the correct
configuration,
see the following table and the Figure 90.
Table 52. STO connector and data signals.
Signal | Terminal | Technical information | Data |
---|---|---|---|
STO1 | S1 | Insulated digital input 1 (interchangeable polarity) | 24V ±20% 10…15 |
mA
G1
STO2| S2| Insulated digital input 2 (interchangeable polarity)| 24V ±20% 10…15
mA
G2
STO feed- back| __
F+
| Insulated digital output for STO feedback (CAUTION! Polarity must be
respected)| 24V ±20% 15 mA max.
F-| GND
| Make sure that the AC drive is switched off before cabling.
---|---
| Disconnect both the STO jumpers to allow the cabling of the terminals.
| When the STO function is used, the IP-class of the drive may not be reduced
below IP54. The IP-class of drive is IP66. It can be reduced by the wrong use
of the cable entry plates or the cable glands.
The following examples show the basic principles for wiring the STO inputs and
the STO output feedback. Local standards and regulations must be always
followed in the final design.
9.5.1 Safety Capability Cat. 4 / PL e / SIL 3
For this safety capability, an external safety device must be installed. This
must be used to dynamically activate the STO inputs and to monitor the STO
output feedback.
The STO inputs are dynamically used when they do not commute together (static
use), but according to the following picture (where the inputs are released
with delay in turn). The dynamic use of the STO inputs allows detecting faults
that may otherwise accumulate.
| An emergency push button connected to the STO inputs does not assure the
same quality, because no fault detection is performed at a sufficient
frequency (once a day is recommended).
---|---
| The external safety device, which forces the STO inputs and evaluates the
STO output feedback, has to be a safe device and it has to fulfill the
requirements of the specific application.
| A simple switch cannot be used in this case!
The picture below shows an example of connection for the STO function. The external device has to be connected with 6 wires to the drive.
The external device has to monitor the STO function in accordance with
theTable 50. The device has to periodically de-energize the STO inputs and it
has to verify that the STO output feedback assumes the expected value.
Any difference between the expected and the real value has to be considered as
a failure and has to drive the system into a Safe State. In case of failure,
check the wiring. If the fault recognized by the external safety device
persists, the drive will have to be replaced/repaired.
9.5.2 Safety Capability Cat. 3 / PL e / SIL 3
The safety capability is reduced to Cat. 3 / PL e / SIL 3 if the STO inputs
are statically used (which means they are forced to commute together).
Both STO inputs and the STO feedback have to be used. The same warnings and
cabling instruction as 9.5.1 apply, except that the proof test interval has to
be at least once every three months.
9.5.3 Safety Capability Cat. 2 / PL d / SIL 2
The safety capability is reduced to Cat. 2 / PL d / SIL 2 if the STO inputs
are connected in parallel (no redundancy of the STO inputs).
The STO feedback has to be used. The same warnings as in 9.5.1 apply, except
the proof test interval has to be at least once a year. The picture below
shows an example of connection for the STO function. The external device has
to be connected with 4 wires to the drive.
9.5.4 Safety Capability Cat. 1 / PL c / SIL 1
Without any automatic monitoring of STO output feedback, the safety capability
is reduced to Cat. 1 / PL c / SIL 1. The STO inputs (which can be connected in
parallel) must be supplied by a safety push button or a safety relay.
| The choice of using the STO inputs (without the automatic monitoring of the
output feedback) does not allow other safety capabilities to be achieved.
---|---
| The standards for functional safety require that functional proof tests are
performed on the equipment at user-defined intervals. Therefore, this safety
capability can be achieved, as long as the STO function is manually monitored
at the frequency determined by the specific application (once a
year can be acceptable).
| This safety capability can be achieved by connecting in parallel the STO
inputs externally and by ignoring the use of the STO output feedback.
The picture below shows an example of connection for the STO function. A switch (a safety push button or a safety relay) may be connected with 2 wires to the drive. When the contacts of the switch are opened, the STO is demanded, the drive indicates F30 (=”Safe Torque Off”) and the motor stops by coasting.
9.6
Commissioning
9.6.1 General wiring instructions
Protect the STO cabling with a shielding or an enclosure to exclude external
damage.
Wires ferrules are highly recommended for all STO signals (inputs and
feedback).
The wiring must be done according to the general wiring instructions for the
specific product. A shielded cable is required. In addition, the voltage drop
from the supply point to the load must not exceed 5% [EN 60204-1 part 12.5].
The following table indicates examples of cables to be used.
Table 53. Cable types required to meet the standards. (*) Additional wires are
needed for restarting the drive after each STO demand.
STO feedback | Cable size |
---|---|
STO feedback automatically monitored by an external safetydevice | 3 x (2 + 1) |
x 0.5 mm 2 (*)
STO feedback ignored, simply safety device (switch) used| 2 x (2 + 1) x 0.5 mm
2
9.6.2 Checklist for commissioning
Follow the checklist shown in the table below for the steps required to use
the STO function.
Table 54. Checklist for commissioning of STO.
| Carry out a risk assessment of the system to ensure that the use of the
STO function is safe and according to the local regulations.
---|---
| Include in the assessment an examination of whether the use of external
devices, such as a mechanical brake, are required.
| Check if the switch (if used) has been chosen according to the required
safety perfor- mance target (SIL/PL/Category) set during the risk evaluation.
| Check if the external device for automatic monitoring of the STO output
feedback (if used) has been chosen in accordance with the specific
application.
| Check if the reset function with the STO function (if used) is edge
sensitive.
| The shaft of a permanent magnet motor might, in an IGBT fault situation,
still provide energy before the torque production ceases. This may result in a
jerk of max. 180° elec- trically. Ensure that the system is designed in such a
way that this can be accepted.
| Check if the degree of protection of the enclosure is at least IP54. See
paragraph 9.5.
| Check if the recommendations on EMC for cables have been followed.
| Check if the system has been designed in such a way that enabling of the
drive through STO inputs will not lead to an unexpected start of the drive.
| Check if only approved units and parts have been used.
__| Set up a routine to ensure that the functionality of the STO function is
being checked at regular intervals.
9.7 Parameters and fault tracing
There are no parameters for the STO function itself.
| Before testing the STO function, make sure that the checklist (Table 54) is
inspected and completed.
---|---
| When STO function activates, the drive always generates a fault (“F30”) and
the motor stops by coasting.c
| In the application the STO state can be indicated using a digital output.
To re-enable motor operation, after the STO state, it is necessary to perform the following steps:
- Release the switch or the external device (“F30” is displayed even after this has been released).
- Reset the fault (through a digital input or from the keypad).
- It is possible that a new start command is required for the restart (depending on the application nd your parameter settings).
9.8 Maintenance and diagnostics
If any service or repair is to be conducted on the drive installed, inspect
the checklist given in Table 54.
During maintenance breaks, or in case of service/repair, ALWAYS make sure that
the STO function is available and fully functional by testing it.
The STO function or the STO input/output terminals do not need any
maintenance.
The following table shows faults that may be generated by the software that
monitors the hardware related to the STO safety function. If you detect any
failure in safety functions, including STO, contact your local supplier.
Table 55. Fault related to the STO function.
Fault Code| Fault| Cause|
Correction
---|---|---|---
30| Safe Torque Off| STO inputs in a differ- ent state or both de- energized|
Check cabling
NOTE! See Table 40 for detailed fault code descriptions.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
www.danfoss.com