AZ 17-02ZRI B6R Safety Switch With Separate Actuator

Product Information

Specifications

  • Product Name: Safety switch with separate actuator AZ 17-02ZRI
    B6R

  • Ordering Code: [insert ordering code]

  • Special Versions: [insert special versions]

  • Purpose: The safety switchgear is developed to execute
    safety-related functions as part of an entire plant or
    machine.

  • Warning about Misuse: It is important to use the safety
    switchgear only in accordance with the versions listed below or for
    the applications authorized by the manufacturer. Detailed
    information regarding the range of applications can be found in the
    chapter Product description.

  • Exclusion of Liability: The information contained in this
    operating instructions manual is provided without liability and is
    subject to technical modifications.

  • Technical Data: [insert technical data]

Mounting

General Mounting Instructions

Before mounting the safety switch with separate actuator, please
ensure that you have read and understood the operating instructions
manual. The mounting process should only be carried out by
authorized qualified personnel.

Mounting of the Actuator

Follow the steps below to mount the actuator:

  1. [Step 1]
  2. [Step 2]
  3. [Step 3]

Dimensions

The dimensions of the safety switch with separate actuator are
as follows:

  • [Dimension 1]
  • [Dimension 2]
  • [Dimension 3]

Electrical Connection

General Information for Electrical Connection

When connecting the safety switch to the electrical system, it
is important to follow these general guidelines:

  • [Guideline 1]
  • [Guideline 2]
  • [Guideline 3]

Contact Options

The safety switch with separate actuator offers multiple contact
options for electrical connections. Please refer to the operating
instructions manual for detailed information on each contact
option.

Set-up and Maintenance

To ensure the safe operation and disassembly of the switchgear,
follow the set-up and maintenance instructions provided in the
operating instructions manual.

Disassembly and Disposal

Disassembly

When disassembling the safety switch with separate actuator,
carefully follow the steps outlined in the operating instructions
manual to avoid any damage or injury.

Disposal

Properly dispose of the safety switch and its components
according to local regulations and guidelines. Contact your local
waste management facility for proper disposal methods.

Frequently Asked Questions (FAQ)

Q: Who should carry out the operations described in the

operating instructions manual?

A: All operations described in the operating instructions manual
must be carried out by trained specialist personnel, authorized by
the plant operator only.

Q: Can the Schmersal range of products be used by private

consumers?

A: No, the Schmersal range of products is not intended for
private consumers.

Q: Where can I find further technical information about

Schmersal products?

A: You can find further technical information in the Schmersal
catalogues or in the online catalogue on the Internet at
products.schmersal.com.

Safety switch with separate actuator AZ 17-02ZRI B6R
Table of Contents
1 About this document 1.1 Function 1.2 Target group of the operating instructions: authorised qualified personnel 1.3 Explanation of the symbols used 1.4 Appropriate use 1.5 General safety instructions
2 Product description 2.1 Ordering code 2.2 Special versions 2.3 Purpose 2.4 Warning about misuse 2.5 Exclusion of liability 2.6 Technical Data
3 Mounting 3.1 General mounting instructions 3.2 Mounting of the actuator 3.3 Dimensions
4 Electrical connection 4.1 General information for electrical connection 4.2 Contact Options
5 Set-up and maintenance 6 Disassembly and disposal
6.1 Disassembly 6.2 Disposal
1 About this document
1.1 Function
This document provides all the information you need for the mounting, set-up and commissioning to ensure the safe operation and disassembly of the switchgear. The operating instructions enclosed with the device must always be kept in a legible condition and accessible.
1.2 Target group of the operating instructions: authorised qualified personnel
All operations described in the operating instructions manual must be carried out by trained specialist personnel, authorised by the plant operator only.
Please make sure that you have read and understood these operating instructions and that you know all applicable legislations regarding occupational safety and accident prevention prior to installation and putting the component
1-11

into operation.
The machine builder must carefully select the harmonised standards to be complied with as well as other technical specifications for the selection, mounting and integration of the components.
The information contained in this operating instructions manual is provided without liability and is subject to technical modifications.

1.3 Explanation of the symbols used

F

Information, hint, note: This symbol is used for identifying useful additional information.

2 Caution:Failure to comply with this warning notice could lead to failures or malfunctions. Warning:Failure to comply with this warning notice could lead to physical injury and/or damage to the machine.

1.4 Appropriate use
The Schmersal range of products is not intended for private consumers.
The products described in these operating instructions are developed to execute safety-related functions as part of an entire plant or machine. It is the responsibility of the manufacturer of a machine or plant to ensure the correct functionality of the entire machine or plant.
The safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer. Detailed information regarding the range of applications can be found in the chapter “Product description”.

1.5 General safety instructions

The user must observe the safety instructions in this operating instructions manual, the country specific installation standards as well as all prevailing safety regulations and accident prevention rules.

F

Further technical information can be found in the Schmersal catalogues or in the online catalogue on the Internet:

products.schmersal.com.

2 Product description

2.1 Ordering code

: AZ 17-(1)Z(2)I-(3)-(4)-(5)
(1)

2-11

11 02
(2) R
(3) ST
(4) B1 B5 B6L B6R
(5) 1637

1 NO /1 NC 2 NC
5N 30N
M16 M12
B1 B5 B6L B6R

2.2 Special versions
For special versions, which are not listed in the ordering code, these specifications apply accordingly, provided that they correspond to the standard version.

2.3 Purpose
The safety switches with separate actuator are suitable for sliding, hinged and removable safety guards, which need to be closed in order to ensure the necessary operational safety. The safety switches are used for applications, in which the hazardous situation is terminated without delay when the safety guard is opened.
When the safety guard is opened, the NC contacts are positively opened and the NO contacts are closed.

F

The safety switchgear units are classified as type 2 interlocking devices in accordance with EN ISO 14119 and are rated as highly coded.

2

The user must evaluate and design the safety chain in accordance with the relevant standards and the required safety level.

3-11

2

The entire concept of the control system, in which the safety component is integrated, must be validated to the relevant standards.

2.4 Warning about misuse

2

In case of improper use or manipulation of the safety switchgear, personal hazards or damages to machinery or plant components cannot be excluded. There are no residual risks, provided that the safety instructions as well as the instructions regarding mounting, commissioning, operation and maintenance are observed.

2.5 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from defective mounting or failure to comply with the operating instructions manual. The manufacturer shall accept no liability for damages resulting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary repairs, conversions and modifications to the device are strictly forbidden, the manufacturer shall accept no liability for damages resulting from such invasive work, arbitrary repairs, conversions and/or modifications to the device.

2.6 Technical Data

EN ISO 14119

EN ISO 13849-1 EN ISO 14119 EN IEC 60947-5-1 115 g
2 2 1
EN ISO 13849-1 EN IEC 60947-5-1

4-11

EN ISO 13849 B10D Normally-closed contact (NC) Note

c 1 2,000,000 Electrical life on request. 20

EN ISO 13849 Note

1 d 3 for 2-channel use and with suitable logic unit. 20

Positive break force per NC contact, minimum Tightening torque of the fastening screws for the housing cover, minimum Tightening torque of the fastening screws for the housing cover, maximum Note

1,000,000 30 N 11 mm 17 N 34 N 2 m/s 2x M5 0.7 Nm
1 Nm
Torx T10

Mechanical data – Connection technique

Allowed type of cable

M 16 x 1.5 0.75 mm² 1 mm² flexible

30 mm

5-11

30 mm 85 mm

Ambient temperature
Ambient conditions – Insulation values

IP67 -30 … +80 °C -30 °C +85 °C 2,000 m

IEC 60664-1

250 VAC 4 kV III 3

EN 60947-5-1

10 A 1,000 A NC 2,000 /h

AC-15 AC-15 DC-13 DC-13

230 VAC 4 A 24 VDC 4 A

Note about the safety classification

Basically suitable up to Cat. 1 / PL c. With 2-channel usage with fault exclusion mechanism (if a fault exclusion to the 1-channel mechanics is authorised) and suitable logic applicable up to Cat. 3 / PL d

6-11

(Determined values can vary depending on the application-specific parameters hop, dop and tcycle as well as the load.)
If multiple safety components are wired in series, the Performance Level to EN ISO 13849-1 will be reduced due to the restricted error detection under certain circumstances.

3 Mounting

3.1 General mounting instructions

2

Please observe the remarks of the standards EN ISO 12100, EN ISO 14119 and EN ISO 14120.

The mounting position however must be chosen so that the ingress of dirt and soiling in the used opening is avoided. Use the supplied base plate for the fixing. The tightening torque of the fixing screws must not exceed 150 Ncm. The enclosure must not be used as an end stop. Any position is possible. The mounting position however must be chosen so that the ingress of dirt and soiling in the used opening is avoided. The unused opening must be sealed by means of slot sealing plugs.
3.2 Mounting of the actuator

2

The marks on the used actuator opening of the solenoid interlock and on the actuator must be opposite.

7-11

2

The actuator must be permanently fitted to the safety guards and protected against displacement by suitable measures (tamperproof screws, gluing, drilling of the screw heads).

Please observe that, when fixing the switch e.g. by means of rivetting or welding, the insertion depth of the actuator is not modified. Different actuator forms are available. The actuators B1 and B5 are preferably used for sliding and removable safety guards. For hinged guards, the B6R and B6L actuators.
Actuator B6L / B6R
When the switch is fitted on a hinged safety guard, please ensure that the point of rotation is located within the range of the upper surface of the safety switch, in which the actuator hook is inserted (refer to table).

Actuating radii [mm]

over the small edge of the actuator

over the wide edge of the actuator

Rmin

d

Rmin

d

B6L

50

11

50

11

B6R

50

11

50

11

The axis of the hinge must be d mm above and in a parallel plane to the top surface of the safety switch. The basis setting provides a minimum radius of Rmin.
The B6L or B6R actuators are set to the smallest radius in factory. To increase the radius, the setting screws a + b must be turned by means of a hexagonal key A/F 2.0 mm.

3.3 Dimensions
8-11

All measurements in mm. AZ 17 safety switch

Actuator
Straight actuator B1
Flexible actuator B6L

Angled actuator B5 Flexible actuator B6R

4 Electrical connection
4.1 General information for electrical connection
9-11

2

The electrical connection may only be carried out by authorised personnel in a de-energised condition.

The contact labelling can be found in the wiring compartment of the switch. Appropriate cable glands with a suitable degree of protection are to be used.
IDC method of termination The IDC method of termination (cut clamp technology) enables connecting flexible wires with cable section 0.75 … 1 mm² without using conductor ferrules. To this effect, strip the wire for 17 … 20 mm and insert it into the cable gland, close the cable gland, push the conductors in the groove of the cover (refer to wiring example) and screw the cover back. Alternatingly tighten the cover screws uniformly. Tightening force for the Torx T10 cover screws 0.7 … 1 Nm.

4.2 Contact Options
B Contacts are shown with safety guard closed. All NC contacts have positive break .

AZ 17-11Z.I

AZ 17-02Z.I

with connector, A-coding
AZ 17-11Z.I-ST

AZ 17-02Z.I-ST

Key

B

Automatic opener, NC contact

Normally-open contact Normally-closed contact

10-11

5 Set-up and maintenance
The safety function of the safety components must be tested. In the case of correct installation and adequate use, the safety switchgear features maintenance-free functionality. A regular visual inspection and functional test, including the following steps, is recommended:

1. Check for correct installation of the actuator and the switch 2. Check the integrity of the cable entry and connections 3. Check the switch enclosure for damages 4. Remove particles of dust and soiling

2

Adequate measures must be taken to ensure protection against tampering either to prevent tampering of the safety guard, for instance by means of replacement actuators.

2

Damaged or defective components must be replaced.

6 Disassembly and disposal

6.1 Disassembly
The safety switchgear must be disassembled in a de-energised condition only.

6.2 Disposal

£

The safety switchgear must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations.

11-11