AAON EcoFit WH Series Horizontal Water Source Heat Pump Units Instruction Manual
- June 16, 2024
- AAON
Table of Contents
- AAON EcoFit WH Series Horizontal Water Source Heat Pump Units
- Product Information
- Features and Options
- Safety Precautions
- Specifications
- Product Usage Instructions
- Operation
- Maintenance
- FAQ
- AAON EcoFit Features and Options Introduction
- MODEL OPTIONS
- General Information
- OPEN LOOP APPLICATIONS
- Additional Sequence of Operations
- 1 Simple Green Simple Green is available from AAON Parts and Supply (Part
- 2 Water Flush This procedure can be used when the only material to cause the
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
AAON EcoFit WH Series Horizontal Water Source Heat Pump Units
Product Information
Product Name: EcoFit WH Series Horizontal
Water-Source Heat Pump Units
Model Number: V01010
Revision: A
Date of Manufacture: 220913
Features and Options
The AAON EcoFit WH Series Horizontal Water-Source Heat Pump Units offer the following features and options:
- High efficiency scroll compressors
- Factory-installed electric heat options
- Direct drive ECM fan motor
- Microchannel condenser coil
- Refrigerant-to-water heat exchanger
- Aluminum corrosion inhibitor for coil cleaning
- PVC and CPVC piping system compatibility
Safety Precautions
Please pay attention to the following safety statements:
- NOTE: Notes are provided to clarify the unit installation, operation, and maintenance.
- CAUTION: Caution statements are given to prevent actions that may result in equipment damage, property damage, or personal injury.
- WARNING: Warning statements are given to prevent actions that could result in equipment damage, property damage, personal injury, or death.
Specifications
- Compressor Rotation: Must be checked for proper operation by a qualified service technician at startup. Reverse rotation can cause compressor damage.
- Cleaning Chemicals: Do not use acidic chemical coil cleaners. For alkaline chemical coil cleaners, use a pH value less than or equal to 8.5 and include an aluminum corrosion inhibitor in the cleaning solution.
- Cooling Tower and Water Loop Cleaning: Avoid using harsh chemicals such as hydrochloric acid or chlorine, as they can damage the refrigerant-to-water heat exchanger. Prevent chemicals from entering the heat exchanger.
- PVC and CPVC Piping System: Polyolester (POE) oils used with refrigerants like R-410A can cause stress cracking and complete failure of PVC and CPVC piping systems.
- Refrigerant-to-Water Heat Exchanger Corrosion: Chemical corrosion resulting in heat exchanger failure is not covered under warranties.
- Chemical Coil Cleaning Compounds: Follow the manufacturer’s usage instructions for caustic or toxic coil cleaning compounds to avoid equipment damage, injury, or death.
- Working in Closed Areas: Avoid working in closed areas where refrigerant or nitrogen gases may be leaking, as they can cause injury or death.
Product Usage Instructions
Installation
- Ensure that the unit is installed by a qualified installer to prevent property damage, personal injury, or loss of life.
- Follow the installation instructions provided in the manual for proper unit setup.
- Refer to the unit power connection for any necessary alterations.
Operation
- Startup and service must be performed by a Factory Trained Service Technician.
- Follow the operation instructions provided in the manual for efficient and safe operation of the unit.
- Check the compressor rotation and fan motor rotation for proper operation.
Maintenance
- Keep a copy of the Installation, Operation & Maintenance (IOM) manual with the unit.
- Regularly clean the unit’s cooling tower or water loop, but avoid using harsh chemicals that can damage the heat exchanger.
- Use appropriate coil cleaners with a pH value less than or equal to 8.5 and include an aluminum corrosion inhibitor.
- Do not use acidic chemical coil cleaners to prevent damage to the unit.
FAQ
Q: Can I use acidic chemical coil cleaners?
A: No, acidic chemical coil cleaners should not be used to prevent damage
to the unit.
Q: What pH value should alkaline chemical coil cleaners have?
A: Alkaline chemical coil cleaners should have a pH value less than or
equal to 8.5.
Q: Can I clean the cooling tower or water loop with harsh chemicals?
A: No, avoid using harsh chemicals such as hydrochloric acid or chlorine,
as they can damage the refrigerant-to-water heat exchanger.
Q: Can I use PVC or CPVC piping systems with this unit?
A: Yes, PVC and CPVC piping systems are compatible with this unit. However,
avoid using Polyolester (POE) oils used with refrigerants like R-410A in PVC
or CPVC piping systems, as they can cause stress cracking and complete
failure.
Q: Do I need to check the compressor and fan motor rotation?
A: Yes, it is essential to check the compressor and fan motor rotation for
proper operation. Reverse rotation can cause compressor damage, and
alterations must only be made at the unit power connection.
Q: Can I work in a closed area where refrigerant or nitrogen gases may
be leaking?
A: No, avoid working in closed areas where refrigerant or nitrogen gases
may be leaking, as they can cause injury or death due to the presence of
sufficient vapors.
EcoFit
WH Series
Horizontal Water-Source Heat Pump Units
Installation, Operation & Maintenance
WARNING
If the information in this manual is not followed exactly, a fire may result
causing property damage, personal injury, or loss of life.
WARNING
QUALIFIED INSTALLER
Improper installation, adjustment, alteration, service, or maintenance can
cause property damage, personal injury or loss of life. Startup and service
must be performed by a Factory Trained Service Technician. Keep a copy of this
IOM with the unit.
AAON EcoFit Features and Options Introduction
Energy Efficiency · Direct Drive Supply Fan · Scroll or Rotary Compressor ·
Waterside Economizer with 3-Way
Motorized Valve · Electronically Commutated Motors
(ECM) or Permanent Split Capacitor Motors (PSC) · Copper or Cupronickel
Coaxial Refrigerant-to-Water-Heat Exchanger · Microchannel Air Coils · AHRI
Certified Performance
Indoor Air Quality · Multiple High Efficiency Filters up to
MERV 14 Rating · Stainless Steel Drain Pan
Humidity Control · ECM Fan Speed Dehumidification · Hot Gas Reheat
Dehumidification
Controls · 5 Wire Thermostat Control
Installation and Maintenance · Color-Coded Wiring and Wiring
Diagram · Non-Fused Service Disconnect
System Integration · Waterside Economizer · Hot Gas Reheat Humidity Control ·
Geothermal
Environmentally Friendly · R-410A Refrigerant
Extended Life · Induction Brazing · Galvanized Steel Cabinet · Stainless Steel
Drain Pan · Cupronickel Coaxial Refrigerant-to-
Water Heat Exchanger · Microchannel Aluminum Air Coil · 5 Year Parts Warranty
Reduced Sound · Sound Absorbing Fiberglass Cabinet
Insulation · Compressors Mounted with Rubber-in-
Shear Isolators on an Isolation Plate with Rubber-in-Shear Isolation to the
Cabinet · Floating Water Connections · Low Sound Package with Mass Loaded
Vinyl Available under Standard Unit Insulation and Sound Absorbing Blower
Insulation
5
Safety
Attention must be paid to the following statements:
NOTE – Notes are intended to clarify the unit installation, operation and
maintenance.
CAUTION – Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING – Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
CAUTION
Rotation must be checked on all COMPRESSORS AND MOTORS of 3 phase units at
startup by a qualified service technician.
Scroll compressors are directional and can be damaged if rotated in the wrong
direction. Compressor rotation must be checked for proper operation, without
using external refrigerant pressure gauges. Often, a compressor running in
reverse rotation will be much louder than a normal compressor, and will not
develop much of a temperature differential between the suction and discharge
lines.
Fan motor rotation must also be checked for proper operation. Alterations must
only be made at the unit power connection.
CAUTION
To prevent damage to the unit, do not use acidic chemical coil cleaners. Do
not use alkaline chemical coil cleaners with a pH value greater than 8.5,
after mixing, without first using an aluminum corrosion inhibitor in the
cleaning solution.
CAUTION
Cleaning the cooling tower or the water loop with harsh chemicals, such as
hydrochloric acid (muriatic acid) or chlorine, can damage the refrigerantto-
water heat exchanger. Care must be taken to avoid allowing chemicals to enter
the refrigerant-to-water heat exchanger. See Appendix A – Heat Exchanger
Corrosion Resistance for more information.
6
CAUTION
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain chemicals. Polyolester (POE) oils used with
R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping
system will result in stress cracking of the piping and fittings and complete
piping system failure.
WARNING
OPEN LOOP APPLICATIONS
Failure of the refrigerant-to-water heat exchanger as a result of chemical
corrosion is excluded from coverage under AAON Inc. warranties and the heat
exchanger manufacturer’s warranties.
WARNING
Some chemical coil cleaning compounds are caustic or toxic. Use these
substances only in accordance with the manufacturer’s usage instructions.
Failure to follow instructions may result in equipment damage, injury or
death.
WARNING
Do not work in a closed area where refrigerant or nitrogen gases may be
leaking. A sufficient quantity of vapors may be present and cause injury or
death.
WARNING
UNIT HANDLING
To prevent injury or death lifting equipment capacity must exceed unit weight
by an adequate safety factor. Always test-lift unit not more than 24 inches
high to verify proper center of gravity lift point to avoid unit damage,
injury or death.
WARNING
ELECTRIC SHOCK AND FIRE HAZARD
Failure to follow safety warnings exactly could result in dangerous operation,
serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death,
or property damage.
Before servicing, disconnect all electrical power to the unit to avoid shock
hazard or injury from rotating parts. Follow proper Lockout-Tagout procedures.
When servicing controls, label all wires prior to disconnecting. Reconnect
wires correctly.
Verify proper operation after servicing. Secure all service panels.
7
WARNING
GROUNDING REQUIRED
All field installed wiring must be completed by qualified personnel. Field
installed wiring must comply with NEC/CEC, local and state electrical code
requirements. Failure to follow code requirements could result in serious
injury or death. Provide proper unit ground in accordance with these code
requirements.
WARNING
During installation, testing, servicing and troubleshooting of the equipment
it may be necessary to work with live electrical components. Only a qualified
licensed electrician or individual properly trained in handling live
electrical components must perform these tasks.
Standard NFPA-70E, an OSHA regulation requiring an Arc Flash Boundary to be
field established and marked for identification of where appropriate Personal
Protective Equipment (PPE) be worn, must be followed.
WARNING
ROTATING COMPONENTS
Unit contains fans with moving parts that can cause serious injury. Do not
remove panel containing fans until the power to the unit has been disconnected
and fan has stopped rotating.
WARNING
WATER FREEZING
Failure of the refrigerant-to-water heat exchanger due to freezing will allow
water to enter the refrigerant circuit and will cause extensive damage to the
refrigerant circuit components. Any damage to the equipment as a result of
water freezing is excluded from coverage under AAON warranties and the heat
exchanger manufacturer warranties.
WARNING
WATER PRESSURE
Prior to connection of condensing water supply, verify water pressure is less
than maximum pressure shown on unit nameplate. To prevent injury or death due
to instantaneous release of high pressure water, relief valves must be field
supplied on system water piping.
8
1. READ THE ENTIRE INSTALLATION, OPERATION AND MAINTENANCE MANUAL. OTHER
IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL.
2. Startup and service must be performed by a Factory Trained Service
Technician.
3. The unit is for indoor use only. See General Information section for more
unit information.
4. Every unit has a unique equipment nameplate with electrical, operational,
and unit clearance specifications. Always refer to the unit nameplate for
specific ratings unique to the model you have purchased.
9
WSHP Series Feature String Nomenclature
Unit Configuration
:
Accessory Options
Gen Major Rev
Size Series Minor Rev Voltage Eff. Level Comp Style Loop Type Coil Type Heat
Type Heat Staging
1 2 3 A 3 B 4 5 6 A 6 B 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6
WH A – 024 – C – A – 3 – 2 – 0 0 0 – 0 0 : 0 B – A A – 0 0 – A 0 – G 0 0 0 0 – 0 0 0 0 0
MODEL OPTIONS
Generation and Orientation WH = Horizontal Water-Source Heat Pump
Major Revision A = EcoFit
Unit Size 006 = 6,000 Btu/hr = ½ ton 009 = 9,000 Btu/hr = ¾ ton 012 = 12,000
Btu/hr = 1 ton 015 = 15,000 Btu/hr = 1 ¼ ton 018 = 18,000 Btu/hr = 1 ½ ton 024
= 24,000 Btu/hr = 2 ton 030 = 30,000 Btu/hr = 2 ½ ton 036 = 36, 000 Btu/hr = 3
ton 042 = 42,000 Btu/hr = 3 ½ ton 048 = 48,000 Btu/hr = 4 ton 060 = 60,000
Btu/hr = 5 ton 072 = 72,000 Btu/hr = 6 ton 096 = 96,000 Btu/hr = 8 ton 120 =
120,000 Btu/hr = 10 ton 150 = 150,000 Btu/hr = 12 ½ ton
Series A = A Cabinet (006, 009 & 012) B = B Cabinet (015 & 018) C = C Cabinet
(024 & 030) D = D Cabinet (036 & 042) E = E Cabinet (048 & 060) F = F Cabinet
(072 & 096) G = G Cabinet (120 & 150)
Minor Revision A = Minor Revision A
Voltage 3 = 460V/3/60Hz 4 = 575V/3/60Hz A = 265V/1/60Hz B = 115V/1/60Hz C =
208-230V/1/60Hz D = 208-230V/3/60Hz
Efficiency Level 1 = Std Efficiency Compact Box with PSC Motor 2 = Std
Efficiency Compact Box with ECM Motor 4 = Std Efficiency Compact Box with Two-
Step
Compressor & ECM Motor
Compressor Style 0 = R-410A On/Off Compressor – Heat Pump A = R-410A Two-Step
Compressor – Heat Pump
Loop Type 0 = Water Loop (Cooling Tower Only, EWT 60°F) A = Ground Loop
Application B = Ground Water Application
Coil Type 0 = Copper Coaxial Refrigerant-to-Water Heat
Exchanger + Microchannel Air Coil A = Copper Coaxial Refrigerant-to-Water Heat
Exchanger + Polymer E-Coated Microchannel Air Coil B = Cupronickel Coaxial
Refrigerant-to-Water Heat Exchanger + Microchannel Air Coil C = Cupronickel
Coaxial Refrigerant-to-Water Heat Exchanger + Polymer E-Coated Microchannel
Air Coil
Heat Type 0 = No Heating
Heating Staging 0 = No Heating
1: Unit Orientation 0 = Right Hand Return + Left Hand Supply A = Right Hand
Return + End Supply B = Left Hand Return + Right Hand Supply C = Left Hand
Return + End Supply
2: Supply Fan 0 = Standard Fan + PSC Motor B = Standard Fan + ECM Motor
10
WSHP Series Feature String Nomenclature
Unit Configuration
:
Accessory Options
Gen Major Rev
Size Series Minor Rev Voltage Eff. Level Comp Style Loop Type Coil Type Heat
Type Heat Staging
1 2 3 A 3 B
4 5 6 A 6 B 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6
WH A – 024 – C – A – 3 – 2 – 0 0 0 – 0 0 : 0 B – A A – 0 0 – A 0 – G 0 0 0 0 – 0 0 0 0 0
3A: Filter Rack* 0 = Open Return Slide-Out Filter Rack D = 4-Sided 2″ Filter
Rack – Return Duct Flange and
Access Panel E = 4-Sided 2″ Filter Rack + High MERV Filter Seal
– Return Duct Flange and Access Panel F = 4-Sided 4″ Filter Rack + High MERV
Filter Seal
– Return Duct Flange and Access Panel J = 4-Sided 1″ Filter Rack + Access
Panel – Return
Duct Flange and Access Panel K = 4-Sided 1″ Filter Rack + High MERV Filter
Seal
– Return Duct Flange and Access Panel
- 1″ Filter Rack for A Cabinet Only 2″ and 4″ Filter Rack for C Cabinet and Larger
3B: Filters A = 2″ MERV 8 Filter B = 4″ MERV 11 Filter C = 4″ MERV 13 Filter D = 4″ MERV 14 Filter E = 1″ MERV 8 Filter F = 1″ MERV 11 Filter G = 1″ MERV 13 Filter
4: Refrigeration and Dehumidification Options 0 = Standard A = ECM Fan Speed Dehumidification B = On/Off Hot Gas Reheat Dehumidification F = Modulating Hot Gas Reheat Dehumidification
5: Service Disconnect 0 = Standard – 5 kAIC A = Non-Fused Service Disconnect – 30 Amp B = Non-Fused Service Disconnect – 60 Amp F = 100 kAIC Fusing w/ Fused Disconnect – 30 Amp G = 100 kAIC Fusing w/ Fused Disconnect – 60 Amp
6B: Control Options 0 = Standard – No Communication
7: Cabinet Options G = 1/2″ Fiberglass Cabinet Insulation + Stainless
Steel Drain Pan H = 1/2″ Fiberglass Cabinet Insulation + Stainless
Steel Drain Pan + Low Sound Package + MLV
8: WSE 0 = Standard – None B = Waterside Economizer + 3-Way Motorized
Valve
9 & 10: Blank 00 = Standard – None
11: Code Options 0 = Standard – ETL USA Listing B = ETL USA + Canada Listing
12: Shipping Options 0 = Standard
13: Cabinet Access A = Standard
14 & 15: Blank 00 = Standard – None
16: Cabinet 0 = Galvanized Steel Cabinet Construction
6A: Control Sequence 0 = Terminal Block for Thermostat + Pioneer Silver
Controller A = Terminal Block for Thermostat + Pioneer Silver
Controller + Expansion Board B = Pioneer Gold Controller
11
General Information
AAON WH Series Water-Source Heat Pump units (WSHP) are designed for indoor
installation only. Units are assembled, wired, charged and run-tested at the
factory.
WARNING
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury or loss of life. Startup and service
must be performed by a Factory Trained Service Technician. A copy of this IOM
must be kept with the unit.
CAUTION
These units must not be used as a “construction heater” at anytime during any
phase of construction. Very low return air temperatures, harmful vapors, and
misplacement of the filters can damage the unit and its efficiency.
Certification of Cooling Models a. Certified as a commercial central air
conditioner with electrically operated compressors. b. Certified for indoor
installation only. c. Certified with refrigerant R-410A coils.
Codes and Ordinances WSHP Series units have been tested and certified, by ETL,
in accordance with UL Safety Standard 1995/CSA C22.2 No. 236.
System must be sized in accordance with the American Society of Heating,
Refrigeration and Air Conditioning Engineers Handbook.
Installation of units must conform to the ICC standards of the International
Mechanical Code, the International Building Code, Installation of Air
Conditioning and Ventilating Systems Standard, NFPA 90A, and local building,
plumbing and waste water codes. All appliances must be electrically grounded
in accordance with local codes, or in the absence of local codes, the current
National Electric Code, ANSI/NFPA 70 or the current Canadian Electrical Code
CSA C22.1.
CAUTION
The Clean Air Act of 1990 bans the intentional venting of refrigerant as of
July 1, 1992. Approved methods of recovery, recycling, or reclaiming must be
followed.
WARNING
Coils and sheet metal surfaces present sharp edges and care must be taken when
working with equipment.
12
WARNING
Failure to observe the following instructions will result in premature failure
of your system and possible voiding of the warranty.
Receiving Unit When received, check the unit for damage that might have
occurred in transit. If damage is found note on the carrier’s Freight Bill. A
request for inspection by carrier’s agent must be made in writing at once.
All units are shrink-wrapped in blue wrap. If a unit shows up with any other
color wrap, the unit has been opened. Check unit thoroughly for damage that
necessitated rewrapping.
Check nameplate to ensure the correct model sizes and voltages have been
received to match the job requirements.
If repairs must be made to damaged goods, notify the factory before any repair
action is taken in order to protect the warranty. Certain equipment
alteration, repair, and manipulation of equipment without the manufacturer’s
consent may void the product warranty. Contact the AAON Warranty Department
for assistance with handling damaged goods, repairs, and freight claims:
918-382-6450.
Note: Upon receipt check shipment for items that ship loose. Consult order and
shipment documentation to identify potential looseshipped items.
Figure 1 – Access Panels
Storage If installation will not occur immediately following delivery, store
equipment in a dry protected area away from construction traffic and in the
proper orientation as marked on the packaging with all internal packaging in
place. Secure all loose-shipped items.
Direct Expansion (DX) Systems All systems are factory assembled, leak tested,
charged with R-410A refrigerant, and run tested.
All systems include air coil, reversing valve, liquid line filter dryer,
thermal expansion valve (TXV), and compressor.
Always control the unit from the thermostat, or control panel, never at the
main power supply, except for emergency or complete shutdown of the unit.
13
During the cooling season, if the airflow is reduced due to dirty air filters
or any other reason, the cooling coils can get too cold which can cause
excessive liquid to return to the compressor. As the liquid concentration
builds up, oil is washed out of the compressor, leaving it starved for
lubrication.
The compressor life will be seriously shortened by reduced lubrication and the
pumping of excessive amounts of liquid oil and refrigerant.
Wiring Diagrams Unit specific wiring diagrams are affixed inside the control
compartment panel.
Installation
AAON equipment has been designed for quick and easy installation.
Before startup of the unit, check the supply blower and remove the foam
shipping block that may be included to support the blower assembly before
installation, or damage may occur.
duct can be mounted directly to the duct connection flanges. Use a properly
sized duct transition to connect supply duct to unit supply air opening.
Return duct flanges are only included on units with the optional 4sided filter
rack. Use flexible gasket material to seal the duct to the unit.
Verify ceiling, floor, or foundation can support the total unit weight,
including accessory weights.
To properly support the horizontal WSHP unit and reduce sound and vibration,
it must be mounted level in both horizontal directions. These units are
designed to be suspended via threaded rod (field provided) through all four
hanger brackets using the four (4) vibration grommets (factory provided) and
3/8″ washers (field provided) and as shown in Figure 3.
Vibration Grommet
Threaded Rod (Field Provided)
3/8″ Washer (Field Provided)
Nut (Field Provided)
Figure 2 – Foam Shipping Block
Locating the Unit Placement of the unit relative to ductwork, electrical and
plumbing must be carefully considered. Supply and return air plenum or
14
Figure 3 – Mounting Horizontal Units
Vibration grommets are factory provided and must be field installed on units 6
tons and larger.
Verify the top of the vibration grommet is inserted into (or through) the hole provided in the hanger bracket, as pointed out in Figure 4.
Figure 4 – Vibration Grommet Installation
The threaded rod and nut must be adequately sized to support the total unit
weight. Avoid installing units directly above or adjacent to sound-sensitive
areas.
Note: Ductwork must be supported independently from the unit. The unit must
not support supply and/or return ductwork.
Allow adequate service clearances as shown on the unit nameplate and unit
drawing. Consult your local building codes for additional service clearance
requirements.
Allow adequate space for piping access and panel removal. Water piping is on
the compressor end and condensate drain connections are located on the
opposite end.
Condensate Drain Figure 5 – Condensate Drain Piping
CAUTION
Emergency drain pan is recommended for all applications where a risk of water
damage to surrounding structure or furnishings. Refer to local codes.
Floor Mounted Units Make sure the unit is level and mounted on a field
supplied platform with a minimum height to allow for proper depth of the
condensate line p-trap. Other installation provisions may be necessary
according to job specifications.
It is recommended that a vibration isolation pad be used when floor mounting a
unit
Condensate Drain Piping A p-trap and drain line must be installed on
horizontal units, with the p-trap not to exceed 6″ from the drain connection.
Use the same pipe size or larger as/than the drain connection and pitch
downward toward drain. Use an air break in long runs of condensate lines.
Note: All horizontal units require a field installed p-trap.
15
CAUTION
Unit must not be operated without ptraps. Failure to install a p-trap may
result in overflow of condensate water.
Draw-through cooling coils will have a negative static pressure in the drain
pan area. This will cause an un-trapped drain to back up due to air being
pulled up through the condensate drain piping.
Condensate drain trapping and piping must conform to all applicable governing
codes.
Note: The drain pan connection on sizes 006060 is a threaded 7/8″ stainless
steel pipe stub. The drain pan connection on sizes 072150 is a threaded 3/4″
stainless steel pipe stub.
Figure 6 – Drain Trap
The total height from the trap inlet to the top of the bottom bend of the trap
must be 2″ minimum.
The height from top of the bottom bend of the trap to the bottom of the
leaving pipe must be at least equal to 1″. This ensures that enough water is
stored in the trap to prevent losing the drain seal during unit startup.
16
Table 1 – WSHP WH Series Clearances
Minimum Clearances Required (inches)
Capacity
Front/Control Panel
Back
Air Intake
006, 009, 012
24
015, 018
024, 030
036, 042
20
048, 060
6 20
072, 096
120, 150
Water Connections
Straight Discharge
Air Intake (Filters)
End Discharge (Optional)
End Discharge
Air Intake (Filters)
Straight Discharge
Figure 7 – Horizontal Unit Orientation (Right Return Unit Shown)
17
Blower Assembly Removal Side Access 1) Using a 516″ socket, remove the
shipping
screw on the outside of the right or discharge side of the unit as shown in
the figure below.
Figure 8 – Blower Assembly with Captive Panel
- Remove the side blower access panel using the panel handle and lift the panel upwards about ½” or until it clears the captive panel at the bottom of the blower panel.
- Pull the bottom of the blower panel out about 10 degrees then down and away from the unit
- Grip the blower assembly with both hands and lift it about ½” or until it clears the captive panel at the assembly.
Figure 9 – Blower Assembly, Shown Pulled Away From Blower Panel
5) Pull the lower half of the blower mount, away from the blower panel about
10 degrees.
18
-
Once the blower assembly is clear of the blower panel, turn the blower assembly, 90 degrees, counter clockwise.
Caution: At any time, DO NOT rest blower assembly on bottom access panel, as damage may occur to the unit -
Firmly grip the blower panel and lift it approximately ½” or until the bottom of the blower panel clears the WSHP unit.
-
Pull the blower assembly out of the unit.
-
Pull the bottom of the blower panel out about 10 degrees then down and away from the unit.
-
Remove the side access panel.
Discharge Modification The AAON WSHP discharge direction can be selected in
ECat and is also designed so that the discharge direction can be field
modified if needed.
Note: DO NOT perform this action while unit is hanging. It MUST be done on a
solid working surface. Otherwise, serious unit damage may occur.
For WH-006 1) Use a 516″ socket to remove the four (4) screws holding the
blower panel in place.
- Swap and install the two panels keeping note of which side is up.
Note: Installing blower panel upside down will result in damage to the unit.
19
For A Cabinet (009 & 012) Remove the blower assembly as outlined in the “Blower Assembly Removal Side Access” section before modifying the discharge. Once complete, proceed to the following:
- Use a 516″ socket to remove the four (4) screws holding the blower panel in place.
- Firmly grip the blower panel and lift it approximately ½” or until the bottom of the blower panel clears the WSHP unit.
- Pull the bottom of the blower panel out about 10 degrees then down and away from the unit.
blower panel upside down will result in damage to the unit.)
Ensure both the blower panel and side access panels are installed correctly as
outlined in the “Blower Assembly Removal Side Access” section.
Lifting and Handling the Unit Before lifting unit, be sure that all shipping
material has been removed from unit. Unit may be lifted with a pallet jack.
WARNING
UNIT HANDLING Incorrect lifting can cause damage to the unit, injury or death.
Lifting equipment capacity must exceed unit weight by an adequate safety
factor. Always test lift unit not more than 24 inches high to verify proper
center of gravity lift point.
- Remove the side access panel as shown in the “Blower Assembly Removal – Side Access” section, step 2.
- Swap the two panels keeping note of which side is up. (Note: Installing
20
Blower Motor and Fan Access To access the blower motor and fan, first remove
the blower assembly as outlined in the appropriate “Blower Assembly Removal”
for your unit.
Once the blower assembly is on a working surface:
- Remove the five (5) screws that secure the blower motor to the blower assembly.
- Pull the motor and blower up and out of the blower assembly.
- Separate the motor from the blower sub assembly, place the sub assembly (motor side down) and remove the set screw as shown below.
- The blower can now be separated from the motor.
Refrigerant-to-Water Heat Exchanger Water Piping
Open Loop Applications This product contains refrigerant-to-water heat
exchanger made of cupronickel or copper and is subject to severe corrosion and
failure when exposed to chlorides.
WARNING
OPEN LOOP APPLICATIONS
Failure of the refrigerant-to-water heat exchanger as a result of chemical
corrosion is excluded from coverage under AAON Inc. warranties and the heat
exchanger manufacturer’s warranties.
Do not allow water containing any form of chlorides to enter this heat
exchanger.
Common forms of chlorides include:
1. Seawater mist entering an open cooling tower system.
2. Contaminated make-up water containing salt water.
3. Water loop systems that have been disinfected.
Chlorides will result in a premature failure of the refrigerant-to-water heat
exchanger.
Failure of the refrigerant-to-water heat exchanger as a result of chemical
corrosion is excluded from coverage under AAON warranties and the heat
exchanger manufacturer warranties.
Failure of the refrigerant-to-water heat exchanger may allow water to enter
the refrigerant circuit and may cause extensive damage to the refrigerant
circuit components.
21
Any damage to the equipment as a result of refrigerant-to-water heat exchanger
failure from chemical corrosion due to the fluid in the refrigerant-to-water
heat exchanger is excluded from coverage under AAON warranties and the heat
exchanger manufacturer warranties.
WARNING
OPEN LOOP APPLICATIONS
Cupronickel refrigerant-to-water heat exchangers must be used with all open
loop applications. Failure to use a Cupronickel heat exchanger may result in
premature failure of your system and possible voiding of the warranty.
CAUTION
Cleaning the cooling tower or water loop with harsh chemicals such as
hydrochloric acid (muriatic acid), chlorine or other chlorides, can damage the
refrigerant-to-water heat exchanger. Care must be taken to avoid allowing
chemicals to enter the refrigerant-to-water heat exchanger. See Appendix A –
Heat Exchanger Corrosion Resistance for more information.
Freezing Water in the Heat Exchanger This product contains one refrigerant-
towater heat exchanger. A refrigerant-to-water heat exchanger contains
refrigerant in one passage and water in another passage. Water is subject to
freezing at 32°F. When water freezes in a heat exchanger significant forces
are exerted on the components of the heat exchanger where the water is
confined.
22
Failure of the refrigerant-to-water heat exchanger due to freezing will allow
water to enter the refrigerant circuit and will cause extensive damage to the
refrigerant circuit components. Any damage to the equipment as a result of
water freezing in the refrigerantto-water heat exchanger is excluded from
coverage under AAON warranties and the heat exchanger manufacturer warranties.
Unit is capable of operating with Entering Water Temperatures (EWT) as low as
57°F during cooling mode without the need for an automatic flow regulating
water valve. If the EWT is expected to be lower than 57°F or more stable
operation is desired, an automatic flow regulating water valve must be
installed.
WARNING
WATER FREEZING
Failure of the refrigerant-to-water heat exchanger due to freezing will allow
water to enter the refrigerant circuit and will cause extensive damage to the
refrigerant circuit components. Any damage to the equipment as a result of
water freezing is excluded from coverage under AAON warranties and the heat
exchanger manufacturer warranties.
Glycol solutions are required if ambient temperatures are expected to fall
below freezing or if the loop water temperature is below 50°F while operating
in the heating mode with the design minimum flow rate. Adding glycol causes an
increase in pressure drop resulting in a decrease in unit performance. A
minimum concentration of 20% glycol solution is required. The unit controller
contains dip switches to set the loop glycol percentage. Set the glycol
percentage to the closest option available, rounding down if needed.
The option selected will reset the Leaving Water Temperature safety for the unit. AAON will not be responsible for frozen coaxial coils due to improper selection of glycol percentage. See Leaving Water Temperature Alarm section for more details.
Table 2 – Glycol Concentration
Freezing Points
% Glycol Ethylene Propylene
Glycol
Glycol
0
32°F
32°F
20
18°F
19°F
30
7°F
9°F
Water loop piping runs through unheated areas or outside the building must be insulated.
Never operate the unit in heat pump mode with a saturated suction temperature below 35°F for pure water systems or below the freezing point +3°F of the aqueous solution of water and glycol.
Water Piping
WARNING
WATER PRESSURE Prior to connection of the water supply, verify water pressure is less than maximum pressure shown on unit nameplate. To prevent injury or death due to instantaneous release of high pressure water, drain valves must be field supplied on water piping. Supply water connection may require a backflow preventer to prevent supply makeup water from backing up into the public water system.
CAUTION
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain chemicals. Polyolester (POE) oils used with
R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping
system will result in stress cracking of the piping and fittings and complete
piping system failure.
Only use approved water pipe material. Do not use galvanized material for water lines/fittings.
Table 3 – Water Connections
Supply and
Model (WHA-)
Return Connection Size
(in. FPT)
006, 009, 012, 015, 018, 024
1/2″
030, 036, 042, & 048
3/4″
060
1″
072
1 ¼”
096 & 120
1 ½”
150
2″
Water pump must be field sized and installed between the cooling tower or geothermal wellfield and self-contained unit. System must be sized in accordance with the ASHRAE Handbook. Use engineering guidelines to maintain equal distances for supply and return piping and limit bend radii to maintain balance in the system. Balancing valves, permanent thermometers and gauges may be required.
23
CAUTION
Installing contractor is responsible for properly sizing and installing water
system components. Improper fluid flow due to valves, piping, or improper pump
operation may result in unacceptable unit operation and void warranty.
CAUTION
WATER PIPING
Follow national and local codes when installing water piping. Incorporate
vibration eliminators on connections to the unit to reduce noise and vibration
and shutoff valves to facilitate servicing. Supply and return water piping
must be at least as large as the unit connections and larger depending on
length of runs, rise and bends.
Before connection to the unit, the water system must be flushed to remove
foreign material that could cause fouling. Install a screen strainer with a
minimum of 20 Mesh ahead of the inlet to prevent fouling and internal tube
damage. Mineral content of the water must be controlled. All make-up water has
minerals in it and as the water is evaporated in the cooling tower, these
minerals remain. As the mineral content of the water increases, the
conductivity of the water increases. A bleed-off (drain valve) must be
provided for the water loop.
Field provided and installed water treatment program must be compatible with
stainless steel, copper, aluminum, ABS plastic, and PVC. Batch feed processes
must never be used as concentrated chemicals can cause corrosion. Never use
hydrochloric acid (muriatic acid) or chlorine as it will corrode stainless
steel.
Water loop piping runs through unheated areas or outside the building must be
insulated.
NOTE: Ball valves must be installed in the water supply and return lines for
unit isolation and water flow balancing. All manual flow valves must be of the
ball valve design. Globe or gate valves must not be used due to high pressure
drops and poor throttling characteristics.
Pressure and temperature ports are recommended in water supply and return
lines for system balancing. These openings must be 5 to 10 pipe diameters from
the unit water connections. To allow for mixing and temperature stabilization,
wells in the water piping must extend at least ½ pipe diameter into the pipe.
Piping systems must not exceed 10 ft/sec fluid velocity to ensure tube wall
integrity and reduce noise.
Electrical Verify the unit nameplate agrees with power supply. WSHP Series
units are provided with single point power wiring connections. A complete set
of unit specific wiring diagrams, showing factory and field wiring are located
inside the controls compartment panel.
24
Table 4 – Nameplate Voltage Markings & Tolerances
Hz
Nameplate Voltage
Nominal System Voltage
Operating Voltage Range 1
Min
Max
Acceptable Performance Range2
Min
Max
115
120
104
127
108
126
208/230
208/240
187
254
187
252
208
208
187
228
187
228
60
230
240
208
254
216
252
265
277
240
293
249
291
460
480
416
508
432
504
575
600
520
635
540
630
50
230 400
230
198
254
208
254
400
344
440
360
440
Notes:
1. Operating voltage is the min and max voltage for which the unit can function. Never
operate outside of this min and max voltage.
2. The Acceptable Performance Range is the min and max voltage for which the unit
performance is designed and rated to give acceptable performance
3. Note: All units are factory wired for either 115V, 208V/230V, 265V, 460V, or 575V.
The transformer configuration must be checked by a qualified technician prior to service, especially if unit is to be connected to a 208V or 230V supply. Note: All our units are default wired to 208V for the 208V/230V option. To utilize 230V service, interchange the yellow and red wire terminals from the transformer.
All units require field supplied electrical overcurrent and short circuit
protection. Device must not be sized larger than the Maximum Overcurrent
Protection (MOP) shown on the unit nameplate.
Codes may require a disconnect switch be within sight of the unit.
Red-Black for 208V Yellow-Black for 230V
WARNING
A unit-mounted disconnect switch is available as an option. It is important to note that this is a method for convenient maintenance of the unit, but does not provide unit protection or isolation.
Disconnect all electrical power sources before servicing the unit. More than one power source may be provided. Failure to do so may result in injury or death from electrical shock or entanglement in moving parts.
Electrical supply can enter through the side of the controls compartment where knockouts and/or capped pre-cut holes have been provided. Horizontal units have been provided with both high and low voltage holes at the top and bottom of the unit. Entry must be made into one each of these locations.
25
A single point connection to a definite purpose contactor is provided on the
control panel, or to the unit-mounted disconnect switch (if installed) on the
corner panel. High voltage conductors must enter the control panel in a
separate opening and separate conduit than 24V low voltage conductors. High
voltage and low voltage openings are nominally sized at 1-1/8″ and 7/8″
respectively.
Note: Alternate locations for field cut electrical entries must be approved by
AAON factory.
CAUTION
Installing Contractor is responsible for proper sealing of the electrical
entries into the unit. Failure to seal the entries may result in damage to the
unit and property.
Size supply conductors based on the unit Minimum Current Ampacity (MCA)
rating. Supply conductors must be rated a minimum of 75°C.
Protect the branch circuit in accordance with code requirements. The unit must
be electrically grounded in accordance with local codes, or in the absence of
local codes, the current National Electric Code, ANSI/NFPA 70 or the current
Canadian Electrical Code CSA C22.1.
Wire power leads to the unit’s contactor or main disconnect. All wiring beyond
this point has been completed by AAON and cannot be modified without effecting
the unit’s agency/safety certification.
Supply voltage must be within the min/max range shown on the unit nameplate.
Available short circuit current must not exceed the short
26
circuit current rating (SCCR) shown on the unit nameplate.
CAUTION
Three phase voltage imbalance will cause motor overheating and premature
failure.
Voltage imbalance is defined as 100 times the maximum deviation from the
average voltage divided by the average voltage. The maximum allowable
imbalance is 2%.
Example: (221V+230V+227V)/3 = 226V, then 100*(226V-221V)/226V = 2.2%, which
exceeds the allowable imbalance.
Check voltage imbalance at the unit disconnect switch and at the compressor
terminal. Contact your local power company for line voltage corrections.
Installing contractor must check for proper motor rotation and check blower
motor amperage listed on the motor nameplate is not exceeded.
CAUTION
Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units.
Supply fan motors must all be checked by a qualified service technician at
startup and any wiring alteration must only be made at the unit power
connection.
Wire control signals to the unit’s low voltage thermostat connections on the
control board, located in the controls compartment. Consult unit wiring
diagram for more detailed
instructions on control signal wiring connections.
If any factory installed wiring must be replaced, use a minimum 105°C type AWM
insulated conductors.
CAUTION
Scroll compressors are directional
and can be damaged if rotated in the
wrong direction. Compressor rotation
must be checked for proper operation,
without using external refrigerant
pressure gauges.
Often, a
compressor running in reverse
rotation will be much louder than a
normal compressor, and will not
develop much of a temperature
differential between the suction and
discharge lines.
WARNING
Disconnect all electrical power sources before servicing the unit. More than
one power source may be provided. Failure to do so may result in injury or
death from electrical shock or entanglement in moving parts/
on the button, and pull back to remove from rotary switch. The button to
release the terminal block:
Figure 10 – Release Button 3) Connect power to terminals of the
disconnect switch. Connecting the field wires (copper conductors only) to
terminals L1, L2, and L3 of the disconnect switch using the screw terminal
connections.
How to Connect to WH Series Disconnect
30 Amp Disconnect
- Remove compressor panel
Electrical knock-outs are available next to the switch to run the wire through. - Reach behind the Disconnect Switch, grasp the terminal block and press down
Figure 11 – Disconnect Terminals 4) Put terminal block back by snapping
back into place behind disconnect switch.
27
60 Amp Disconnect
- Remove compressor panel
Electrical knock-outs are available next to the switch to run the wire through. 2) Remove the faceplate from the bottom with a flathead screwdriver.
terminal connections. Tighten terminals to 18 in-lbs.
Figure 12 – Disconnect Faceplate 3) Remove the four screws behind the
faceplate with a Phillips head screwdriver to release the switch terminal
block
Figure 13 – Screws to Release Switch 4) Connect power to the terminals of the
disconnect switch. Connecting the field wires (copper conductors only) to
terminals L1, L2, and L3 of the disconnect switch using the screw 28
Figure 14 – Disconnect Terminals
- Put terminal block back by screwing back into place front of the switch. Replace faceplate.
Thermostat Control Wiring If a thermostat is used for unit control, locate thermostat on an inside wall 4-5 feet above the floor where it will not be subjected to drafts, sun exposure, or heat from electrical fixtures or appliances. Control wiring must deliver adequate voltage to components to assure proper operation. Control voltage returning from controller circuit must be a minimum of 21 VAC. To assure proper wiring use the following chart to determine the allowable wiring distances.
Table 5 – Control Wiring
Wire
Size Total Wire Distance
(Stranded) – Copper Allowable
Conductors Only
20 AWG
200 ft
18 AWG
350 ft
16 AWG
500 ft
14 AWG
750 ft
12 AWG
1250 ft
Total Wire Distance Allowable =
(Quantity of Control Wires) x
(Control Wire Distance)
Take the total wire distance allowable and divide by the number of wires to be
connected. This indicates the distance allowable for that size wire. The
wiring to the unit must not exceed the total wire distance allowable. If the
voltage at the connectors is less than 21 VAC, isolation relays must be
installed. If under external control 21 VAC must be field verified.
All external devices must be powered via a separate external power supply.
Example: A total of 5 wires must be pulled 75ft to a control the unit. What
size wire must be used?
According to Table 5, 18 AWG allows for 70ft (350 ft. /5 wires) and 16 AWG
allows for 100ft (500 ft. /5 wires). Thus, 16 AWG must be used.
Filter Pull Setup Do not operate the unit without filters in place. Each unit
has a filter pull located in the filter section of the unit. The filter pull
must be setup prior to installing or changing the filters.
If side access to the filters is desired, then no further action is required.
If bottom access to the filters is desired, then the filter pull must be
removed.
If unit includes 4-sided filter rack, clips must be opened to remove filters
and filter pull.
Figure 16 – Filter Rack Open with Clip
Figure 15 – Filter Rack Closed with Clip
Figure 17 – Filter Pull
1. The filter pull is located in the filter area as shown in Figure 18. If
necessary,
29
from the SIDE filter access open the filter access door.
Figure 18 – Using the Filter Pull
2. The filter pull is now accessible. Grasp the filter pull and lift it
approximately ¼” and with moderate force, pull it out and away from the unit.
Note: Use caution that filters are clear of access holes so that filter damage
does not occur. See Figure 19.
3. Because the filter pull may be longer than available room, it may be
necessary to roll, bend or cut the slide to be completely removed.
4. Reinstall the filters, taking note of correct orientation with regard to
airflow.
5. If necessary, close the filter access door and press the fastener clip
firmly until locked into position.
Duct Connection Attach duct to flanges provided on the unit. Use a properly
sized duct transition to connect supply duct to unit supply air opening. The
installer is responsible for sealing ducts to the flanges to prevent air
leaks.
Intake air enters the side of the WH/WV Series units, where the air filters
are located.
30
The left or right hand return depends on feature selected when ordering the
units. Ductwork must be sized in accordance with the ASHRAE Handbook. Ductwork
must be installed in accordance with NFPA Standard 90A.
When attaching duct to the unit, use a flexible/compressible material rated
for duct connections. A three inch flexible connector for both return and
supply duct connections is recommended.
Waterside Economizer An optional cooling and pre-cooling waterside economizer
coil is factory installed upstream of the evaporator coil. Field installed
water piping kit includes an on/off waterside economizer valve.
The waterside economizer circuit operates in either “WSE” or “Mechanical
Cooling” only modes.
During waterside economizer only mode of operation water is 100% diverted
through the waterside economizer coil via a 3-way valve.
During mechanical cooling only mode of operation water flows around the
waterside economizer coil with the waterside economizer valve fully closed.
The water passes only through the refrigerant-to-water heat exchanger.
Waterside economizer coil condensate drains into unit drain pan. See the
previous section on condensate drain piping.
Mineral content of the water must be controlled. All make-up water has
minerals in it and as the water is evaporated in the cooling tower, these
minerals remain. As the mineral content of the water increases, the
conductivity of the water increases.
Field provided and installed water treatment program must be compatible with
stainless steel, copper, aluminum, ABS plastic, and PVC. Batch feed processes
must never be used as concentrated chemicals can cause corrosion. Never use
hydrochloric acid (muriatic acid) or chlorine as it will corrode stainless
steel.
Units with a waterside economizer coil require the Pioneer Expansion Board or
the Pioneer Gold controller. The entering water temperature is monitored by
the control board. Changeover temperature to activate waterside economizer
operation is configurable between 45-60°F (all 1° increments) via dip switches
(Pioneer Expansion Board) or programming menus (Pioneer Gold).
Startup
(See back of the manual for startup form)
Operation Limits
Cooling Heating
Min. Entering Air
65°F 55°F
Max Entering Air
100°F 80°F
Min. Entering Water
68°F 50°F
Max Entering Water
104°F 86°F
Min. GPM/Ton
1.5
Max GPM/Ton
4
Min. CFM/Ton
300
WARNING
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury or loss of life. Startup and service
must be performed by a Factory Trained Service Technician. Keep a copy of this
IOM with the unit.
WARNING
Electric shock hazard. Shut off all electrical power to the unit to avoid
shock hazard or injury from rotating parts.
During startup, it is necessary to perform routine checks on the performance
of the unit. This includes checking of the air flow, the air filters, and
water flow. Due to the chargecritical nature of these units, refrigerant
pressure gauges must only be hooked up to the unit if there is suspicion of an
issue within the circuit.
Supply Fans WSHP Series units are equipped with direct drive forward curved or
backward curved plenum supply fan assemblies that deliver the air volume
specified according to unit size and job requirements.
Figure 19 – WSHP Series Supply Fan
Fan Air Flow Adjustment A specific air volume is delivered by the PSC or
Electronically Commutated Motor (ECM) fans. Field airflow adjustment may be
required at startup.
Standard PSC and ECM motor options have limited RPM Adjustment to adjust
airflow. Each motor type has three speed taps to select from: High, Medium,
and Low. Adjustment for the PSC speed must be made by altering the motor power
connected to the motor.
31
Adjustment for the ECM speed is made by adjusting the call wire to the corresponding 1/4″ speed terminal directly on the motor body (WH015 – 060).
Filters Do not operate the unit without filters in place. Unit must be checked
for correct filter placement during startup. Operation of the equipment
without filters will result in a clogged air coil.
CAUTION
Before completing startup and leaving the unit a complete operating cycle must
be observed to verify that all components are functioning properly.
Adjustment for the A cabinet units (WH006012) is made by adjusting the DC voltage signal to the motor from the Pioneer Expansion board or the Pioneer Gold board. Low fan speed is achieved by connecting the compressor Y call from the thermostat to Y1 on the control board. The higher fan speed is achieved by connecting Y from the thermostat to Y2 on the control board.
Motor Tap RPMs
Fan Speed High Med Low
RPM
1200 950 800
PSC Tap
Black Blue Red
ECM Tap
3 2 1
Note: RPMs are approximate, and will vary slightly depending on TSP across the blower assembly
For unit operation at ISO 13256-1 rating conditions, PSC blower motors must
use “High” Speed and 8. B through E cabinet unit (WH015-060) ECM blower motors
must use speed tap 4. WH ½ – 1 ton units may also require specific dip-switch
settings. Please consult factory for details.
32
Adjusting Refrigerant Charge Unit must be operating in the cooling mode to
adjust the refrigerant charge.
CAUTION
Due to the charge-critical nature of these units, charge must only be adjusted
if absolutely necessary.
Adjusting the charge of a system in the field must be based on determination
of liquid subcooling and evaporator superheat. On a system with a TXV liquid
sub-cooling is more representative of the charge than evaporator superheat but
both measurements must be taken.
Before Charging Unit being charged must be at or near full load conditions
before adjusting the charge.
Units equipped with hot gas reheat must be charged with the hot gas reheat
valves closed while the unit is in cooling mode to get the proper charge.
After charging, operate the unit in reheat (dehumidification) mode to check
for correct operation.
After adding or removing charge the system must be allowed to stabilize,
typically 10-15 minutes, before making any other adjustments.
The type of unit and options determine the ranges for liquid sub-cooling and
evaporator superheat. Refer to the tables below when determining the proper
sub-cooling.
Checking Liquid Sub-Cooling Measure the temperature of the liquid line as it
leaves the refrigerant-to-water heat exchanger.
Read the gauge pressure at the liquid line close to the point where the
temperature was taken.
Convert the pressure obtained to a saturated temperature using the appropriate
refrigerant temperature-pressure chart.
Subtract the measured liquid line temperature from the saturated temperature
to determine the liquid sub-cooling. Compare calculated sub-cooling to the
table below for the appropriate unit type and options.
Checking Evaporator Superheat Measure the temperature of the suction line
close to the compressor.
Read gauge pressure at the suction line close to the compressor.
Convert the pressure obtained to a saturated temperature using the appropriate
refrigerant temperature-pressure chart.
Subtract the saturated temperature from the measured suction line temperature
to determine the evaporator superheat.
Compare calculated superheat to the table below for the appropriate unit type
and options.
CAUTION
DO NOT OVERCHARGE! Refrigerant overcharging leads to excess refrigerant in the
refrigerantto-water heat exchanger coils resulting in elevated compressor
discharge pressure.
Table 6 – Acceptable Refrigeration Circuit
Values at AHRI ISO 13256 WLHP
Conditions
Water-Source Heat Pump
Sub-Cooling
4-8°F
Superheat
8-15°F
CAUTION
Thermal expansion valve must be adjusted to approximately 8-15°F of suction
superheat. Failure to have sufficient superheat will damage the compressor and
void the warranty.
Adjusting Sub-Cooling and Superheat Temperatures The system is overcharged if the sub-cooling temperature is too high and the evaporator is fully loaded (low loads on the evaporator result in increased sub-cooling) and the evaporator superheat is within the temperature range as shown in the table above (high superheat results in increased sub-cooling).
33
Correct an overcharged system by reducing the amount of refrigerant in the
system to lower the sub-cooling. The system is undercharged if the superheat
is too high and the sub-cooling is too low Correct an undercharged system by
adding refrigerant to the system to reduce superheat and raise sub-cooling. If
the sub-cooling is correct and the superheat is too high, the TXV may need
adjustment to correct the superheat.
34
Table 7 – R-410A Refrigerant Temperature-Pressure Chart
°F PSIG °F PSIG °F PSIG °F PSIG °F PSIG 20 78.3 47 134.7 74 213.7 101 321.0
128 463.2 21 80.0 48 137.2 75 217.1 102 325.6 129 469.3 22 81.8 49 139.7 76
220.6 103 330.2 130 475.4 23 83.6 50 142.2 77 224.1 104 334.9 131 481.6 24
85.4 51 144.8 78 227.7 105 339.6 132 487.8 25 87.2 52 147.4 79 231.3 106 344.4
133 494.1 26 89.1 53 150.1 80 234.9 107 349.3 134 500.5 27 91.0 54 152.8 81
238.6 108 354.2 135 506.9 28 92.9 55 155.5 82 242.3 109 359.1 136 513.4 29
94.9 56 158.2 83 246.0 110 364.1 137 520.0 30 96.8 57 161.0 84 249.8 111 369.1
138 526.6 31 98.8 58 163.8 85 253.7 112 374.2 139 533.3 32 100.9 59 166.7 86
257.5 113 379.4 140 540.1 33 102.9 60 169.6 87 261.4 114 384.6 141 547.0 34
105.0 61 172.5 88 265.4 115 389.9 142 553.9 35 107.1 62 175.4 89 269.4 116
395.2 143 560.9 36 109.2 63 178.4 90 273.5 117 400.5 144 567.9 37 111.4 64
181.5 91 277.6 118 405.9 145 575.1 38 113.6 65 184.5 92 281.7 119 411.4 146
582.3 39 115.8 66 187.6 93 285.9 120 416.9 147 589.6 40 118.1 67 190.7 94
290.1 121 422.5 148 596.9 41 120.3 68 193.9 95 294.4 122 428.2 149 604.4 42
122.7 69 197.1 96 298.7 123 433.9 150 611.9 43 125.0 70 200.4 97 303.0 124
439.6 44 127.4 71 203.6 98 307.5 125 445.4 45 129.8 72 207.0 99 311.9 126
451.3 46 132.2 73 210.3 100 316.4 127 457.3
35
Operation
Unit operations must be controlled with thermostat and unit controller, never
at the main power supply, except for emergency or complete shutdown of the
unit.
AAON WSHP Pioneer Silver Controller Part Number: V67470
Description The Water-Source Heat Pump Pioneer Silver Controller contains all
the functionality required to operate the basic configuration of AAON WH
Series units. The controller requires commands from a standard heat pump room
thermostat and has outputs to control a supply fan, compressor, and reversing
valve. The control also contains a port for communication to the Water-Source
Heat Pump Pioneer Silver Expansion Board for additional functionality.
NOTE: If the application currently uses an obsolete mercury bulb type
thermostat, it must be upgraded to an electronic thermostat. The unit will not
function properly when controlled via a mercury bulb thermostat.
General Specifications Electrical Supply Voltage 24VAC (+25%/-15%), Class 2
Supply Power 15VA
Outputs Relay Outputs: 1A maximum per output.
Input Requirements Resistive Inputs: require 10K Type 3 Thermistor 24VAC
Inputs: Inputs provide 4.7k Load
Environmental Operating Temperature 32 to 158°F (0 to 70°C)
Storage Temperature -4 to 158°F (-20 to 70°C)
Humidity (Storage and Operating) 0 to 95% RH non-condensing
Mounting & Dimensions Mounting Board is mounted via four shoulder eyelets
located on the corners of the circuit board.
Dimensions 5.5″ x 4.0″
Inputs and Outputs Pluggable Screw Terminal Block H2 AL1 = Dry, normally open
contact with terminal AL2. Contact closes when controller is in alarm. AL2 =
Dry, normally open contact with terminal AL1. Contact closes when controller
is in alarm. COM = 24VAC Common. ESD = Emergency shutdown Input. 24VAC or
common must be used as input for unit operation. Jumper to COM is factory
installed. NS = Night setback mode enable. 24VAC or common may be used as
inputs. NO = Dry, normally open contact with terminal IN. Contact closes when
compressor is active. IN = Common input for terminals NO and NC. NC = Dry,
normally closed contact with terminal IN. Contact opens when compressor is
active.
36
Pluggable Screw Terminal Block H5 24V = 24VAC power output for thermostat.
NS_OV = Night setback override input. Input requires 24VAC to activate. O =
Thermostat input for reversing valve operation. Input requires 24VAC to
activate. COM = 24VAC common for thermostat power. G = Thermostat input for
fan operation. Input requires 24VAC to activate. NS_TH = Night setback
compressor enable. Input requires 24VAC to activate. Y = Thermostat input for
compressor operation. Input requires 24VAC to activate. AL = 24VAC wet alarm
output.
Pluggable Screw Terminal Block H1 + = Network terminal used for communication
with the expansion board. – = Network terminal used for communication with the
expansion board. S = Shield
Quick Disconnect Terminals P1 – AUX = Auxiliary alarm terminal. Dry contact
with AUX IN enables alarm. P2 – AUX IN = Auxiliary alarm terminal. Dry contact
with AUX enables alarm. P3 – TEST = Delay override terminal. Dry contact with
TEST IN enables the delay override function. P4 – TEST IN = Delay override
terminal. Dry contact with TEST enables the delay override function.
Wiring Harness H3 PURPLE = Evaporator coil temperature sensor. To be used with
10k Type III thermistors. WHITE = Evaporator coil temperature sensor. To be
used with 10k Type III thermistors. TAN = Refrigerant temperature sensor. To
be used with 10k Type III thermistors. GRAY = Refrigerant temperature sensor.
To be used with 10k Type III thermistors.
PINK = Not used BROWN = Condensate drain pan sensor input. GREEN = Low
pressure switch. Input requires a normally closed switch. ORANGE = Low
pressure switch. Input requires a normally closed switch. BLACK = High
pressure switch. Input requires a normally closed switch. YELLOW = High
pressure switch. Input requires a normally closed switch. RED = 24VAC power.
BLUE = 24VAC common.
Wiring Harness H6 BLACK = Reversing valve 24VAC output. RED = Reversing valve
common wire. BLUE = Fan 24VAC output. BROWN = Fan common wire. GREEN =
Compressor contactor 24VAC output. WHITE = Compressor contactor common wire.
Alarm Status LED D5 See Table 8 for flash codes.
Relay Status LEDs COMP = Compressor Relay ALARM = Alarm Relay FAN = Fan Relay
RV = Reversing Valve Relay
Dip Switch SW1 See Table 9 – Glycol Percentage Setpoints
37
Figure 20 – Pioneer Silver Controller Layout
Sequences of Operation
Supply Fan Operation Supply fan will enable upon receiving a 24VAC input on
the “G” terminal or a call for compressor operation unless an alarm prevents
the fan from operating. There is a 30 second minimum off timer for the fan.
The supply fan is enabled for 15 seconds after the last stage of cooling,
heating, or dehumidification stages off. Not all alarms will prevent supply
fan operation. The Alarms that disable the fan are:
- Emergency Shutdown 2) Condensate Overflow 3) Low Voltage 4) High Voltage
Compressor Operation The compressor will enable upon receiving a 24VAC input
on the “Y” terminal or a 24VAC input on the “TH_NS” terminal if in night
setback mode unless an alarm is active. If the supply fan was not enabled
prior to the compressor call, then the supply fan will enable for 5 seconds
before the compressor is started.
The compressor has a minimum on time of 3 minutes and a minimum off time of 2
minutes to prevent short cycling. These delays can be shortened to 5 seconds
if the controller is in test mode. If the unit goes into an alarm then the
minimum on time will be ignored and the compressor will disable. All alarms
will disable the compressor.
38
Reversing Valve Operation The reversing valve will enable if the controller
receives a 24VAC input on the “O” terminal and the compressor has been
operational for a minimum of 5 seconds.
The default reversing valve position is for heating operation, no 24VAC input
on the “O” terminal. Therefore, in compressor cooling operation 24VAC must be
applied to the “O” terminal.
Random Start Delay The controller will enter a random start delay in these
situations:
- The unit powers up 2) Recovery from emergency shutdown
alarm 3) Recovery from high voltage alarm 4) Recovery from low voltage alarm - Night setback mode is disabled
The random start delay will be between 3 and 60 seconds. The fan and compressor will not be operational during this time. The random start delay will be ignored if the unit is in test mode.
Building Occupancy Status Occupied Mode The controller will operate according to the thermostat inputs.
Night Setback Mode Night setback mode is enabled upon receiving a 24VAC or a 24VAC common input on the “NS” terminal. While in night setback mode the controller will ignore the normal thermostat signals. Instead the controller will use the “NS_TH” input as the fan and compressor enable signal operating at full compressor capacity. When the unit is taken out of night setback mode the controller will execute a random start delay.
The night setback mode can be overridden with a 24VAC input to the night setback
override terminal “NS_OV”. Once the override signal is received, night setback
will be overridden for 2 hours even if the signal is removed. While night
setback is overridden the controller will respond to the normal thermostat
signals.
Test Mode Test mode is enabled by connecting the two quick disconnect
terminals “TEST” and “TEST IN” together. The controller will remain in “Test
Mode” as long as the terminals are connected to each other. The controller
will exit “Test Mode” immediately upon removal of the jumper. While in “Test
Mode” there will be no random start delay, and the compressor minimum on and
minimum off times are reduced to 5 seconds each. The 5 second delay between
compressor and reversing valve operation is still present as well as the 5
second delay between the supply fan and compressor.
Alarms LED Fault Codes The controller provides a status LED (D5) in the center
of the board to indicate the unit status. A green status light indicates that
the unit is powered up and that the controller is not detecting any fault
conditions. A flashing red status light indicates that the controller has
detected a fault condition and is now in alarm mode. The number of flashes
indicates what alarm is present. Table 8 describes the meaning of the flash
codes.
39
Table 8 – LED Diagnostic Codes
Number Fault
of LED
Flashes
1
High Discharge Pressure
2
Emergency Shutdown
3
Auxiliary Alarm
4
High Condensate Level Alarm
5
Low Control Voltage Alarm
6
High Control Voltage Alarm
7
Low Suction Pressure
8
Leaving Water Temperature
Alarm
9
Air Coil Low Temperature
Alarm
10
Entering Water Temperature
Alarm
Automatic Reset Alarms The following alarms will automatically reset themselves once the fault condition clears.
Low Control Voltage Alarm The low voltage alarm will activate when the 24VAC control voltage drops to 20VAC +/5%. Below this voltage the onboard normally open relays are not guaranteed to close. The low voltage alarm will release when the voltage rises above 22VAC +/-5%. Once the fault is cleared the controller will activate a random start delay. This alarm will disable the compressor, the supply fan, and the reversing valve.
High Control Voltage Alarm The high voltage alarm will activate when the 24VAC control voltage increases to 32VAC +/-5%. Any voltage higher than this risks damaging components on the control board. The alarm will release when the control
voltage decreases to 30VAC +/-5%. Once the fault is cleared the controller
will activate a random start delay. This alarm will disable the compressor,
the supply fan, and the reversing valve.
Leaving Water Temperature Alarm To prevent freezing of the liquid heat
exchanger, the leaving water temperature alarm will activate and turn the
compressor off if the refrigerant saturated suction temperature during heating
drops below the freeze protection temperature setpoints in Table 9 – Glycol
Percentage Setpoints, based on the glycol percentage that is input into the
controller. The alarm will deactivate (allowing the compressor to run again)
after ten minutes have expired and the refrigerant saturated suction
temperature rises 5°F above the freeze protection temperature. If the alarm is
activated again within two hours, the refrigerant saturated suction
temperature must rise 5°F above the freeze protection temperature and the unit
power must be cycled off and on or the compressor activation call from the
thermostat must be removed and then restarted.
The glycol percentage DIP switch “SW1” is used to set the glycol percentage
that is used in the system for freeze protection. This switch is located in
the center of the control board. The freeze protection setpoints change based
on the glycol percentage that is input to the controller. It is critical that
this setting matches the actual glycol percentage used in the system to
prevent damage caused from freezing. Inputting a glycol percentage that is
higher than actually used in the system can cause extensive damage from
freezing.
40
Table 9 – Glycol Percentage Setpoints
Leaving Water Leaving Water
Switch 1
Switch 2
Glycol
Temperature
Temperature
Position
Position
Percentage
Alarm
Alarm
Activation
Deactivation
Off
Off
0%
35°F
40°F
Off
On
10%*
30°F
35°F
On
Off
20%
23°F
28°F
On
On
30%
15°F
20°F
*Setting not recommended. 20% or more glycol solution is required if ambient temperatures are expected
to fall below freezing or if the loop water temperature is below 50°F while operating in the heating mode.
Air Coil Temperature Alarm The air coil low temperature alarm will trigger if
the air coil temperature drops below 30°F. The alarm will release when the
coil temperature increases to 35°F. This alarm will disable the compressor but
allow operation of the supply fan.
Entering Water Temperature Alarm The entering water temperature alarm is used
to prevent freezing in the waterside economizer coil. Entering water
temperature is only monitored if a unit is ordered with a waterside economizer
coil. This temperature sensor is wired to the Pioneer Silver Expansion Board.
If the entering water temperature falls to 35°F, the waterside economizer coil
will be deactivated until the entering water temperature rises above 40°F. The
supply fan and the compressor are allowed to operate when this alarm is
activated.
Emergency Shutdown Alarm The emergency shutdown input requires a constant
connection to either 24VAC or 24VAC common for normal operation. If the 24VAC
or 24VAC common signal is removed, then the controller will enter emergency
shutdown mode. This alarm will disable the compressor and the supply fan. This
alarm will release when the 24 VAC input is restored.
Lock Out Alarms The following alarms will not automatically reset themselves
on the fault condition clears.
For these alarms to clear one of the following two conditions must be met:
- Controller is power cycled 2) Fault condition is corrected and the
compressor call is removed
Auxiliary Input Alarm The auxiliary alarm will enable if the compressor has been operational for at least 2 minutes and a dry contact has been made between the “AUX” and “AUX IN” quick disconnect terminals for 10 seconds. This alarm will disable the compressor but allow the supply fan to operate. If a secondary drain pan is to be used, the secondary drain pan overflow switch must be wired into the Auxiliary Input Alarm.
High Condensate Level Alarm The high condensate level alarm will enable if the resistance between the condensate level sensor and 24VAC common is less than 100k for more than 30 seconds. This alarm will disable both the compressor and the supply fan.
41
High Discharge Pressure Alarm The high discharge pressure alarm will enable if
the high pressure switch opens. This alarm will disable the compressor but
allow the supply fan to operate. Low Suction Pressure Alarm The low suction
pressure alarm will activate and turn the compressor off if the low suction
pressure switch is open for 10 seconds. The alarm will deactivate if 15
minutes has expired and the low pressure switch has closed. If the alarm is
activated again within two hours, the unit power must be cycled off and on.
42
AAON WSHP Pioneer Silver Expansion Board Part Number: V75410
Description The Water-Source Heat Pump Pioneer Silver Expansion Board is used
in conjunction with the Water-Source Heat Pump Pioneer Silver Controller. The
expansion board contains a port for communications to the main controller.
NOTE: When the expansion board is connected, the H5 terminals on the main
controller will not be used. The H4 terminals on the expansion board must be
used to connect to the thermostat.
General Specifications Electrical Supply Voltage 24VAC (+25%/-15%), Class 2
Supply Power 10VA
Outputs Relay Outputs: 1A maximum per output.
Input Requirements Resistive Inputs: require 10K Type 3 Thermistor 24VAC
Inputs: Inputs provide 4.7k Load
Environmental Operating Temperature 32 to 158°F (0 to 70°C)
Storage Temperature -4 to 158°F (-20 to 70°C)
Humidity (Storage and Operating) 0-95% RH non-condensing
Mounting & Dimensions Mounting Board is mounted via four shoulder eyelets
located on the corners of the circuit board.
Dimensions 6.5″ x 4.0″
Inputs and Outputs Pluggable Screw Terminal Block H4 G = Thermostat input for
fan operation. Input requires 24VAC to activate. Y1 = Thermostat input for
compressor stage 1 operation. Input requires 24VAC to activate. Y2 =
Thermostat input for compressor stage 2 operation. Input requires 24VAC to
activate. O = Thermostat input for reversing valve operation. Input requires
24VAC to activate. DH = Dehumidistat input for dehumidification operation.
Input requires 24VAC to activate. W1 = Thermostat input for Auxiliary Heat 1
operation. W2 = Thermostat input for Auxiliary Heat 2 operation. AL = 24VAC
wet alarm output R = 24VAC power output for thermostat. NS_TH = Night Setback
compressor enable. Input requires 24VAC to activate. NS_OV = Night Setback
override input. Input requires 24VAC to activate. C = 24VAC common for
thermostat power.
Pluggable Screw Terminal Block H1 + = Network terminal used for communication
with the expansion board. – = Network terminal used for communication with the
expansion board. S = Shield
43
Quick Disconnect Terminals P1 – Not Used P2 – 24VAC = 24VAC Power P3 – COM = 24VAC Common P4 – HEAT 2 Enable = 24VAC output P5 – COM = Heat 2 Common P6 – HEAT 1 Enable = 24VAC output P7 – COM = Heat 1 Common P8 – Water Temp Input = Water output temperature sensor (Entering Water Temp). To be used with 10k Type III thermistors. P9 – Water Temp Input = Water output temperature sensor (Entering Water Temp). To be used with 10k Type III thermistors. P10 – Not Used P11 – Not Used
P12 – AO1 = EC Supply Speed (+VDC), 0-10VDC P13 – COM = EC Supply Speed (-VDC) P14 – FAN HIGH = 24VAC Fan High Speed output P15 – WTR ECON = 24V Waterside Economizer output P16 – COM = Fan High Common P17 – COM = WTR ECON Common P18 – COMP2 = 24VAC Compressor Stage 2 output P19 – COM = Compressor Stage 2 Common P20 – REHEAT = 24VAC Reheat output P21 – COM = Common
Figure 21 – Pioneer Silver Expansion Board Layout 44
Dip Switch SW1
Fan-Speed Dehumidification Selections
Fan-Speed Dehum Disabled Fan-Speed Dehum Enabled
Pos 9 OFF ON
POS 1 through 8 are not currently used.
Dip Switch SW2
1. Waterside Economizer Enable
WSE Disabled WSE Enabled
Pos 1 OFF ON
2. Waterside Economizer Temperature Enable Setpoint Selection
Pos 2
Pos 3
45°F
OFF
OFF
46°F
OFF
OFF
47°F
OFF
OFF
48°F
OFF
OFF
49°F
OFF
ON
50°F
OFF
ON
51°F
OFF
ON
52°F
OFF
ON
53°F
ON
OFF
54°F
ON
OFF
55°F
ON
OFF
56°F
ON
OFF
57°F
ON
ON
58°F
ON
ON
59°F
ON
ON
60°F
ON
ON
Relay Status LEDs FAN HIGH = Fan High Speed Relay COMP2 = Compressor Stage 2 Relay ALARM = Alarm Relay WTR ECON = Waterside Economizer Relay REHEAT – Reheat Relay
Pos 4 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON
Pos 5 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON
45
Additional Sequence of Operations
Supply Fan Operation The supply fan will enable upon receiving a 24VAC input
on the “G” terminal or upon a call for compressor operation, unless an alarm
prevents the fan from operating. There is a 30 second minimum off timer for
the fan. The supply fan is enabled for 15 seconds after the last stage of
cooling, heating, or dehumidification stages off.
Two Speed Electronically Commutated Motor (ECM) if equipped with 1) EC motor
and 2) Fan-Speed Dehumidification or Hot Gas Reheat With a two speed ECM, the
supply fan will have two speed operations, “low speed” and “high speed”. The
supply fan speeds will correspond to the below listed operating functions.
· Supply Fan “G” call only – Low Speed · Compressor low capacity “Y1” – Low
Speed · Compressor full capacity “Y2” – High
Speed · Supplementary Heating – High Speed · Dehumidification – Low Speed ·
Waterside Economizer – High Speed
With a “Y1” enable, the supply fan will run at low speed, and with a “Y2”
enable, the supply fan will run at high speed. If there is only one compressor
capacity, the “Y1” call from the thermostat must be wired to the “Y2” terminal
input on the unit control board.
Compressor Operation Unless an alarm is active, the compressor will enable
upon receiving a 24VAC input on the “Y1” or “Y2” terminals, or upon receiving
a 24VAC input on the “TH_NS” terminal if in night setback mode. If the supply
fan was not enabled prior to the compressor call, then the supply fan will
enable for 5 seconds before the compressor is started.
46
The compressor has a minimum on time and a minimum off time of 180 sec and 120
sec respectively to prevent short cycling. These delays are shortened to 5 sec
if the controller is in test mode. If the unit goes into an alarm, the minimum
on time will be ignored and the compressor will disable. Controller includes
built-in compressor inter-stage delays.
All alarms will disable the compressor.
Auxiliary Heating Operation Staged Heating The heating stages will enable
according to thermostat inputs.
Dehumidification Operation
Fan Speed Dehumidification (requires EC Motor) For Fan Speed Dehumidification,
switch 1, position 9 must be set to “ON”.
Fan Speed Dehumidification Mode is enabled based on a 24VAC input to the “DH”
terminal and a 24VAC input to the “Y1” or “Y2” terminals.
Unit operates according to the cooling sequence of operation, with the
exception that the supply fan low speed output is enabled in lieu of high
speed during cooling mode. Compressor operates at full capacity during
dehumidification.
If a waterside economizer is included and the entering water temperature falls
below the Entering Water Temperature setpoint, the waterside economizer coil
will be enabled and operate as described in the Waterside Economizer Operation
section.
Hot Gas Reheat Dehumidification For Hot Gas Reheat Dehumidification, switch 1,
position 9 must be set to “OFF”.
Hot Gas Reheat Dehumidification Mode is enabled based on a 24VAC input to the
“DH” terminal.
Cooling and heating modes are always priority over dehumidification. Hot Gas
Reheat Dehumidification is only available when the cooling and heating demands
are satisfied.
The compressor is enabled at full capacity “Y2” when dehumidification mode is
enabled. The supply fan low speed (if EC motor) and reheat valve “RH” 24VAC
outputs are enabled. If the unit is equipped with waterside economizer, the
Entering Water Temperature setpoint will be ignored, and freeze protection
will be monitored.
On/Off Waterside Economizer (WSE) Coil Operation As the entering water
temperature drops below the Entering Water Temperature setpoint, if the
compressor is enabled, the call for the compressor will be removed once the
minimum on time has been satisfied, and the WSE 24VAC output will be enabled,
sending the cold loop water through the air coil to utilize “free cooling”.
The WSE will act as the unit’s only stage of cooling. If the cooling call has
not been satisfied within 10 minutes of operation, the WSE valve will disable.
Following a delay, the unit will resume normal compressor cooling operation
until the cooling input is removed. When this happens, the Pioneer Silver
controller green LED will flash, signifying the WSE was unable to satisfy the
cooling call.
If the entering water temperature rises above the Entering Water Temperature
setpoint plus
the deadband, the WSE will be disabled, and compressor cooling will be
utilized.
Maintenance
See back of the manual for maintenance log.
At least once each year, a qualified service technician must check out the
unit. Supply fans, evaporator coils and air filters must be inspected monthly.
WARNING
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury or loss of life. Installation and
service must be performed by a qualified installer. Keep a copy of this IOM
with the unit.
See Startup section for information on air flow adjustment.
DX Cooling Set unit controls to cooling mode of operation with supply fans on.
Check the fans for correct operating direction, amperage and voltage. Check
compressor operation, rotation, amperage and voltage to the unit nameplate
(check the amperage on the load side of the compressor contactor). Check for
24V signal across the reversing valve terminals.
Condensate Drain Pans Drain pans will have moisture present and require
periodic cleaning to prevent microbial growth. Cleaning of the drain pans will
also prevent any possible plugging of the drain lines and overflow of the pan
itself. Cleaning of the drain pans and inside of the unit must be done only by
qualified personnel.
47
Supply Fans
CAUTION
Blower wheels must be inspected for excessive dust build up periodically and
cleaned if required. Excessive dust build up on blower wheels may cause an
unbalanced state; leading to vibration and/or component failure. Damages due
to excessive dust build up will not be covered under factory warranty.
WARNING
Electric shock hazard. Shut off all electrical power to the unit to avoid
shock hazard or injury from rotating parts.
Supply Fan Lubrication Supply fan motors are permanently lubricated and
require no oiling.
Microchannel Coil Cleaning
WSHP units include microchannel coils.
Cleaning microchannel coils is necessary in all locations. In some locations
it may be necessary to clean the coils more or less often than recommended. In
general, a WSHP coil must be cleaned at a minimum of once a year. In locations
where there is commonly debris or a condition that causes dirt/grease build
up, it may be necessary to clean the coils more often. Proper procedure must
be followed at every cleaning interval. Using improper cleaning technique or
incorrect chemicals may result in coil damage, system performance fall off,
and potentially leaks requiring coil replacement.
Field applied coil coatings are not recommended with microchannel coils.
Allowed Chemical Cleaners and Procedures AAON recommends certain chemicals
that can be used to remove buildup of grime and debris on the surface of
microchannel coils. These chemicals have been tested for performance and
safety and are the only chemicals that AAON will warrant as correct for
cleaning microchannel coils.
There are two procedures that are outlined below that will clean the coils
effectively without damage to the coils. Use of any other procedure or
chemical may void the warranty to the unit where the coil is installed. With
all procedures make sure the unit is off before starting.
WARNING
Electric shock hazard. Shut off all electrical power to the unit to avoid
shock hazard or injury from rotating parts.
The water pressure used to clean must not exceed 140 psi, from no closer than
6 inches from the coils, and with the water aimed perpendicular to the coils.
1 Simple Green Simple Green is available from AAON Parts and Supply (Part
T10701) and is biodegradable with a neutral 6.5 pH. Recommendation is to use
it at a 4 to 1 mix. Use the following procedure.
1. Rinse the coil completely with water. Use a hard spray but be careful not
to bend or damage the fins. A spray that is too hard will bend the fins. Spray
from the fan side of the coil.
48
2. With a pump sprayer filled with a mix of 4 parts water to 1 part Simple
Green, spray the air inlet face of the coil. Be sure to cover all areas of the
face of the coil.
3. Allow the coil to soak for 10-15 minutes. 4. Rinse the coil with water as
in step one. 5. Repeat as necessary.
2 Water Flush This procedure can be used when the only material to cause the
coil to need cleaning is debris from plant material that has impinged the coil
face.
1. Rinse the coil completely with water. Use a hard spray but be careful not
to bend or damage the fins. A spray that is too hard will bend the fins. Spray
from the fan side of the coil.
2. Spray and rinse the coil from the face.
Caution
Use pressurized clean water, with pressure not to exceed 140 psi. Nozzle must
be 6″ and perpendicular to the coil face. Failure to do so could result in
coil damage.
Application Examples The two procedures can be used to clean microchannel
coils.
Generally the best and broadest based procedure is #1. The grease cutting
effect of the Simple Green is good for restaurant applications.
Other Coil Cleaners There are many cleaners on the market for coils. Before
using any cleaner that is not covered in this section, you must get written
approval from the AAON warranty and service department. Use of unapproved
chemicals will void the warranty.
AAON testing has determined that unless a chemical has a neutral pH (6-8) it
must not be used.
Beware of any product that claims to be a foaming cleaner. The foam that is
generated is caused by a chemical reaction to the aluminum fin material on
tube and fin coils and with the fin, tube, and coating material on
microchannel coils.
Microchannel coils are robust in many ways, but like any component they must
be treated correctly. This includes cleaning the coils correctly to give
optimal performance over many years.
Filter Replacement Monthly filter inspection is required to maintain optimum
unit efficiency. It is strongly recommended that filter media be replaced
monthly.
WARNING
Electric shock hazard. Shut off all electrical power to the unit to avoid
shock hazard or injury from rotating parts.
See Filter Information section for reference to the correct size and quantity
of filters.
49
Replacement Parts Parts for AAON equipment may be obtained by contacting your
local AAON representative. When ordering parts, reference the unit serial
number and part number located on the external or internal nameplate of the
unit.
Note: Warranty end date can be found on the unit nameplate.
AAON Warranty, Service, and Parts Department 2425 S. Yukon Ave. Tulsa, OK
74107 Ph: 918-382-6450
techsupport@aaon.com www.AAON.com
Note: Before calling, have the model and serial number of the unit available
to help answer questions regarding the unit.
Filter Information
Table 10 – 006-012 WH Unit Series Filters (A Cabinet)
Feature 3B
Quantity/Size (W x H x D)
Type
E
Pleated, MERV 8
F
(1) 24″ x 10″ x 1″
Pleated, MERV 11
G
Pleated, MERV 13
Table 11 – 015-030 WH Series Unit Filters (B & C Cabinet)
Feature 3B
Quantity/Size (W x H x D)
Type
A
(2) 16″ x 16″ x 2″
Pleated, MERV 8
B
Pleated, MERV 11
C
(2) 16″ x 16″ x 4″
Pleated, MERV 13
D
Pleated, MERV 14
50
Table 12 – 036 & 042 WH Series Unit Filters (D Cabinet)
Feature 3B
Quantity/Size (W x H x D)
Type
A
(2) 20″ x 20″ x 2″
Pleated, MERV 8
B
Pleated, MERV 11
C
(2) 20″ x 20″ x 4″
Pleated, MERV 13
D
Pleated, MERV 14
Table 13 – 048 & 060 WH Series Unit Filters (E Cabinet)
Feature 3B
Quantity/Size (W x H x D)
Type
A
(3) 16″ x 20″ x 2″
Pleated, MERV 8
B
Pleated, MERV 11
C
(3) 16″ x 20″ x 4″
Pleated, MERV 13
D
Pleated, MERV 14
Table 14 – 072 & 096 WH Series Unit Filters (F Cabinet)
Feature 3B
Quantity/Size (W x H x D)
Type
A
(3) 24″ x 18″ x 2″
Pleated, MERV 8
B
Pleated, MERV 11
C
(3) 24″ x 18″ x 4″
Pleated, MERV 13
D
Pleated, MERV 14
Table 15 – 120 & 150 WH Series Unit Filters (G Cabinet)
Feature 3B
Quantity/Size (W x H x D)
Type
A
(4) 18″ x 24″ x 2″
Pleated, MERV 8
B
Pleated, MERV 11
C
(4) 18″ x 24″ x 4″
Pleated, MERV 13
D
Pleated, MERV 14
51
Appendix A – Heat Exchanger Corrosion Resistance
Potential Problem
Chemical(s) or Condition
Range for Copper Heat Exchangers
Range for Cupro-Nickel Heat Exchangers
Scaling
Calcium & Magnesium Carbonate
Less than 350 ppm
Less than 350 ppm
pH Range
7-9
5-9
Total Dissolved Solids
Less than 1000 ppm
Less than 1500 ppm
Ammonia, Ammonium Hydroxide
Less than 0.5 ppm
Less than 0.5 ppm
Corrosion
Ammonium Chloride, Ammonium Nitrate
Less than 0.5 ppm
Less than 0.5 ppm
Calcium Chloride/ Sodium Chloride
Less than 125 ppm
Less than 125 ppm Note 4
Chlorine
Less than 0.5 ppm
Less than 0.5 ppm
Hydrogen Sulfide
None Allowed
None Allowed
Biological
Iron Bacteria
None Allowed
None Allowed
Growth
Iron Oxide
Less than 1 ppm
Less than 1 ppm
Erosion
Suspended Solids Water Velocity
Less than 10 ppm Less than 8ft/s
Less than 10 ppm Less than 12 ft/s
Notes:
1. Harness in ppm is equivalent to harness in mg/l
2. Grains/gallon = ppm divided by 17.1
3. Copper and cupronickel heat exchangers are not recommended for pool applications for water outside the
range of the table.
4. Saltwater applications (approx. 25,000 ppm) require secondary heat exchangers due to copper piping
between the heat exchanger and the unit fittings.
52
WH Series Startup Form
Job Name:____ Date:____
Address:____
Model Number:____ Serial Number: Tag:____ Startup Contractor:____ Address:____ Phone:____
Pre Startup Checklist Installing contractor must verify the following items.
1. Is there any visible shipping damage? 2. Is the unit level? 3. Are the
unit clearances adequate for service and operation?
4. Have all electrical connections been tested for tightness? 5. Does the
electrical service correspond to the unit nameplate? 6. On 208/230V units, has
transformer tap been checked? 7. Has overcurrent protection been installed to
match the unit nameplate
requirement? 8. Have all set screws on the fans been tightened? 9. Does the
fan rotate freely? 10. Does the field water piping to the unit appear to be
correct per design
parameters? 11. Is all copper tubing isolated so that it does not rub? 12. Are
air filters installed with proper orientation? 13. Have condensate drain and
p-trap been connected?
Yes No Yes No Yes No Yes No Yes No Yes No
Yes No Yes No Yes No
Yes No Yes No Yes No Yes No
Ambient Temperature Ambient Dry Bulb Temperature ____°F Ambient Wet Bulb Temperature ____°F
Supply Fan Assembly
Alignment
Number
hp
1
Check Rotation L1
Nameplate Amps____
L2
L3
Compressors/DX Cooling Only connect gauges for troubleshooting
Check Rotation
Number
L1
L2
1 Full Capacity 1 Reduced Capacity
Head
Suction
L3
Pressure
Pressure
PSIG
PSIG
Refrigeration System 1 Full Capacity – Cooling Mode
Due to the charge-critical nature of these units, charge must only be adjusted if absolutely
necessary
Pressure
Saturated Temperature
Line Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Refrigeration System 1 Reduced Capacity – Cooling Mode
Pressure
Saturated
Line
Temperature Temperature
Discharge
Suction
Liquid
Sub-cooling
N/A N/A
Superheat N/A
N/A
Refrigeration System 1 Full Capacity – Heating Mode (Heat Pump Only)
Pressure
Saturated Temperature
Line Temperature
Sub-cooling
Discharge
N/A
Suction
N/A
Liquid
Superheat N/A
N/A
54
Refrigeration System 1 Reduced Capacity – Heating Mode (Heat Pump Only)
Pressure
Saturated Temperature
Line Temperature
Sub-cooling
Superheat
Discharge
N/A
N/A
Suction
N/A
Liquid
N/A
Unit Configuration No Water Leaks Water Flow ____ gpm
Water Inlet Temperature ____°F
Water Outlet Temperature ____°F
Water/Glycol System 1. Has the entire system been flushed and pressure
checked? 2. Has the entire system been filled with fluid? 3. Has air been bled
from the heat exchangers and piping? 4. Is the glycol the proper type and
concentration (N/A if water)? 5. Is there a minimum load of 50% of the design
load? 6. If geothermal, does water piping include insulation?
7. What is the freeze point of the glycol (N/A if water)?
Yes No Yes No Yes No Yes No Yes No Yes No
Maintenance Log This log must be kept with the unit. It is the responsibility of the owner and/or maintenance/service contractor to document any service, repair or adjustments. AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts. The responsibility for proper startup, maintenance, and servicing of the equipment falls to the owner and qualified licensed technician.
Entry Date
Action Taken
Name/Tel.
56
Literature Change History September 2022 First Version
58
AAON 2425 South Yukon Ave. Tulsa, OK 74107-2728
www.AAON.com
EcoFit WH Series Installation, Operation &
Maintenance V01010 Rev. A 220913
Factory Technical Support: 918-382-6450
Note: Before calling Technical Support, please have the model and serial
number of the unit available. Parts: For replacement parts please contact your
local AAON Representative.
It is the intent of AAON to provide accurate and current product information.
However, in the interest of product improvement, AAON reserves the right to
change pricing, specifications, and/or design of its product without notice,
obligation, or liability.
Copyright © AAON, all rights reserved throughout the world. AAON® and
AAONAIRE® are registered trademarks of AAON, Inc., Tulsa, OK.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>