LEDVANCE T4 Compact Fluorescent
Programmed Rapid Start Ballast
120-277 Volt High Efficiency
Normal Ballast Factor
LTP CF UNV Models Lamp/Ballast Guide
2 Lamp T4 CF Ballast 120-277V PSN Dual Mount
Primary lamps: CF 26W DD/E, DT/E
Also operates: CF 32W DT/E, 42W DT/E
Scan or click QR code to access Ballast Compatibility Listing
Application Information
This LEDVANCE Professional Ballast is ideally suited for:
- Commercial and retail
- Hospitality and institutional
- New construction
- Wall scones and recessed downlights
Ordering Information
Item
Number| Description| # of
Lamps| Primary
Lamp (W)| Lamp family| Line
Voltage| Starting
Method| Dual
Mount| Case
Size| Packaging
---|---|---|---|---|---|---|---|---|---
75867| LTP2X26CFUNVDM| 2| 26| CF= T4 CF| UNV| PS| DM| Small| 20/CS 1/SKU
Electrical Specifications at 120-277V
Item
Number| Description| Input
Current(AMPS)| Lamp Type| Rated
Lumens
(lm)| No. of
Lamps| Ballast
Factor
(BF)| System
Lumens
(lm)| Mean
Lumens(lm)| Input
Power
(W)| System
Efficacy
(lm/W)| B EF*
---|---|---|---|---|---|---|---|---|---|---|---
75867| LTP2X26CFUNVDM| 0.30| 26W DD/E T/E| 1800| 2| 1| 1800| 1550| 50| 67|
1.88
0.16| 26W DD/E T/E| 1800| 1| 0.96| 3600| 3095| 27| 64| 3.570
- Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power 277V 60Hz data
ECS309R1 9-23
Wiring Diagram
Note: For one lamp applications, cap all unused leads Insulate to 400 volts.
Dimensions:
Overall: 5.05″L x 2.42″W x 0.9″H (128.27mm L x 61.47mm W x 22.86mm H)
Mounting: 4.66″ (118.36mm)
Weight: 0.48 lbs. each (approx.)
Packaging:
Quantity: 20 per case /1 per SKU
Wiring:
DUAL (side and bottom) wire-trap connectors, for quick and easy installation
Ordering Guide
Specification Data
Type……………………………..
Catalog #……………………….
Project………………………….
Comments…………………….
Prepared by…………………..
Performance Guide
Data based on fluorescent lamps shown. LTP Programmed Rapid Start based on fluorescent lamps shown. LTP Programmed Rapid Start ballasts are also compatible with other lamps manufacturers equivalent lamps types that meet ANSI specifications.
Specifications
Starting Method: Programmed Rapid Start
Ballast Factor: 2 lamp @ 277V 0.97, 1 lamp @ 277V 0.82, 2 lamp @ 120V 0.88; 1
lamp @ 120V 0.81
Circuit Type: Series
Lamp Frequency: >42kHz
Input Frequency: 50/60 Hz
Low THD: <10%
Power Factor: >98% @120V >97% @277V
Voltage Range: ±10% rated input
Operating Temperatures 1
Starting Temperature: -5°F (-20°C)
Case Temp: 194°F (90°C) Max
Max Ambient Temp.: 131°F (55°C)
Product Ratings
UL Listed Class P, Type 1, Outdoor
FCC Part 18 Non-Consumer
Class A Sound Rating
ANSI C62.41 Cat. A Transient Protection
RoHS Compliant 2
No PCBs, Type CC
1 Operation below 50°F (10°C) may affect light output or lamp operation.
2 Complies with European Union Restriction of Hazardous Substances (Directive
2002/95/EC)
Installation Notes
- Ground ballast case
- Install in accordance with the National Electrical Code
- Remote Mounting: 18ft. max lead length 18AWG
System Life/Warranty
LEDVANCE ballasts carry a five-year warranty from date of manufacture. For additional details, check out the latest Warranty Bulletin on our website, ledvanceUS.com.
SCAN OR CLICK QR CODE TO ACCESS WARRANTY.
LEDVANCE LLC
181 Ballardvale Street, Suite 203
Wilmington, MA 01887 USA
Phone 1-800-LIGHTBULB (1-800-544-4828)
www.ledvanceUS.com
LEDVANCE is a registered trademark. All other trademarks are those of their
respective owners. Specifications subject to change without notice.
SCAN TO FOLLOW US ON SOCIAL MEDIA
https://www.ledvanceus.com/Pages/Follow-Us-On-Social-Media.aspx
© 2023 LEDVANCE LLC
Documents / Resources
|
LEDVANCE T4 Compact Fluorescent Programmed Rapid Start
Ballast
[pdf] Instructions
T4, T4 Compact Fluorescent Programmed Rapid Start Ballast, Compact Fluorescent
Programmed Rapid Start Ballast, Fluorescent Programmed Rapid Start Ballast,
Programmed Rapid Start Ballast, Rapid Start Ballast, Start Ballast, Ballast
---|---
References
- LEDVANCE US and Canada | SYLVANIA General Lighting | Home Page
- LEDVANCE US and Canada | SYLVANIA General Lighting | Home Page
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>