Fronius 2141 Three Phase Inverters Ohmpilot Instruction Manual

June 16, 2024
Fronius

Fronius 2141 Three Phase Inverters Ohmpilot

Fronius-2141-Three-Phase-Inverters-Ohmpilot

Product Information: Fronius Ohmpilot

Specifications

  • Power Range: 0 – 9 kW
  • Phase 1 Power Range: 0 – 3 kW (continuously adjustable)
  • Phase 2 Power Range: 3 kW (fixed)
  • Phase 3 Power Range: 3 kW (fixed)

Operating Instructions

Safety Precautions
Ensure to follow the safety precautions listed below to avoid
any accidents or injuries:

  • DANGER! Indicates an immediate danger. Failure to avoid may result in death or serious injuries.
  • WARNING! Indicates a potential danger. Failure to avoid may result in injuries or damage to the product.
  • CAUTION! Indicates important information. Failure to follow may result in malfunction or damage to the product.

General Information

It is important to prioritize your safety while using the Fronius Ohmpilot.

Environmental Conditions
Ensure that the Fronius Ohmpilot is used within the specified environmental conditions.

Qualified Personnel
Only qualified personnel should handle the installation and operation of the Fronius Ohmpilot.

Data Security
Data security is a priority. Take necessary measures to protect your data.

The copyright of this user manual belongs to the manufacturer.

The Fronius Ohmpilot works in conjunction with the following products:

  • Fronius Symo / Galvo / Eco or Primo (from Fronius Datamanager 2.0 Software-Version 3.8.1-x) or Fronius Symo Hybrid (from Fronius Hybridmanager Software-Version V1.8.1.x)
  • Fronius Primo / Symo GEN24
  • Fronius Smart Meter
  • Fronius Ohmpilot
  • Ohmic consumer (e.g., boiler with heating rod)

Integration of Fronius Smart Meter
For integration of the Fronius Smart Meter, the power ranges are as follows:

  • Phase 1: 0 – 3 kW (continuously adjustable)
  • Phase 2: 3 kW (fixed)
  • Phase 3: 3 kW (fixed)

System Design Considerations

NOTE: Only one Ohmpilot can be used per Fronius Datamanager / Hybridmanager.

NOTE: Starting from software version 3.13.1-  of Fronius Datamanager or 1.11.1-x of Hybridmanager, the Ohmpilot can be used together with the dynamic power limitation from 0-100%.

Installation and Operation Instructions

Location Selection and Mounting Position
Choose an appropriate location for mounting the Fronius Ohmpilot.

General Location Selection
Follow the general guidelines for selecting the location of the Fronius Ohmpilot.

Wall Mounting
Ensure proper wall mounting of the Ohmpilot for safe and secure installation.

Safety

Take necessary safety precautions while installing and operating the Fronius Ohmpilot.

Screw Recommendation
Use the recommended screws for mounting the Fronius Ohmpilot on the wall.

Installation

Follow the installation instructions provided in the user manual
for proper installation of the Fronius Ohmpilot.

Electrical Connection

Follow the instructions for electrical connection based on the type of heating rod:

  • 1-phase heating rod up to 3 kW
  • 3-phase heating rod 900 W up to 9 kW

Status and Settings

Data Connection Setup
Follow the steps to establish a data connection with the Fronius Ohmpilot.

Coupling with Fronius Inverter
Learn how to couple the Fronius Ohmpilot with a Fronius Inverter.

Boost Mode
Understand and utilize the Boost Mode functionality of the Fronius Ohmpilot.

Status Display on Web Interface
Learn how to view status information on the web interface of the Fronius Ohmpilot.

Optional Settings
Make manual settings for HEATING 1, activate legionella protection, adjust daily schedule, and set temperature limits.

Appendix

Status Messages
Refer to the list of status messages provided in the user manual for troubleshooting purposes.

Technical Specifications
Refer to the technical specifications section for detailed information on input data, interfaces, and general data.

Warranty and Disposal
Understand the warranty conditions and proper disposal methods for the Fronius Ohmpilot.

FAQ (Frequently Asked Questions)

  • Q: Can multiple Ohmpilots be used with one Fronius Datamanager/ Hybridmanager?
  • A: No, only one Ohmpilot can be used per Fronius Datamanager / Hybridmanager.
  • Q: Can the Ohmpilot be used together with dynamic power limitation?
  • A: Yes, starting from software version 3.13.1-x of Fronius Datamanager or 1.11.1-x of Hybridmanager, the Ohmpilot can be used together with the dynamic power limitation from 0-100%.

Safety rules

Explanation of safety notices

DANGER!
Indicates immediate danger.
If not avoided, death or serious injury will result.

WARNING!
Indicates a potentially hazardous situation.
If not avoided, death or serious injury may result.

CAUTION!
Indicates a situation where damage or injury could occur.
If not avoided, minor injury and/or damage to property may result.

NOTE! Indicates a risk of flawed results and possible damage to the equipment.

General

The device has been manufactured in line with the state of the art and according to recognized safety standards. If used incorrectly or misused, however, it can cause: – Injury or death to the operator or a third party – Damage to the device and other material assets belonging to the operating
company.
All personnel involved in commissioning, maintenance, and servicing of the device must: – Be suitably qualified – Have knowledge of and experience in dealing with electrical installations and – Have fully read and precisely followed these Operating Instructions
The Operating Instructions must always be at hand wherever the device is being used. In addition to the Operating Instructions, attention must also be paid to any generally applicable and local regulations regarding accident prevention and environmental protection.
All safety and danger notices on the device: – Must be kept in a legible state – Must not be damaged – Must not be removed – Must not be covered, pasted or painted over
The terminals can reach high temperatures.
Only operate the device when all protection devices are fully functional. If the protection devices are not fully functional, there is a danger of: – Injury or death to the operator or a third party – Damage to the device and other material assets belonging to the operating
company

71

Any safety devices that are not fully functional must be repaired by an authorised specialist before the device is switched on.
Never bypass or disable protection devices.
For the location of the safety and danger notices on the device, refer to the section headed “General remarks” in the Operating Instructions for the device.
Any equipment malfunctions which might impair safety must be remedied before the device is turned on.
This is for your personal safety!

Environmental conditions

Operation or storage of the device outside the stipulated area will be deemed as not in accordance with the intended purpose. The manufacturer accepts no liability for any damage resulting from improper use.

Qualified personnel

The servicing information contained in these operating instructions is intended only for the use of qualified service engineers. An electric shock can be fatal. Do not carry out any actions other than those described in the documentation. This also applies to qualified personnel.
All cables and leads must be secured, undamaged, insulated and adequately dimensioned. Loose connections, scorched, damaged or inadequately dimensioned cables and leads must be immediately repaired by authorised personnel.
Maintenance and repair work must only be carried out by an authorised specialist.
It is impossible to guarantee that bought-in parts are designed and manufactured to meet the demands made on them, or that they satisfy safety requirements. Use only original spare parts (also applies to standard parts).
Do not carry out any alterations, installations, or modifications to the device without first obtaining the manufacturer’s permission.
Components that are not in perfect condition must be changed immediately.

Noise emission values

The maximum sound power level of the inverter is specified in the Technical Data.
The device is cooled as quietly as possible with the aid of an electronic temperature control system; this depends on the amount of converted power, the ambient temperature, the level of soiling of the device, etc.
It is not possible to provide a workplace-related emission value for this device because the actual sound pressure level is heavily influenced by the installation situation, the power quality, the surrounding walls and the properties of the room in general.

EMC measures

In certain cases, even though a device complies with the standard limit values for emissions, it may affect the application area for which it was designed (e.g., when there is equipment that is susceptible to interference at the same location, or if the site where the device is installed is close to either radio or television receivers). If this is the case, then the operator is obliged to take action to rectify the situation.

Data protection

The user is responsible for the safekeeping of any changes made to the factory settings. The manufacturer accepts no liability for any deleted personal settings.

Copyright

Copyright of these operating instructions remains with the manufacturer.
The text and illustrations are all technically correct at the time of printing. We reserve the right to make changes. The contents of the operating instructions shall not provide the basis for any claims whatsoever on the part of the purchaser. If you have any suggestions for improvement, or can point out any mistakes that you have found in the instructions, we will be most grateful for your comments.

General information

General

Intended use

With its “24 hours of sun” vision, Fronius is aiming to offer its customers solutions for generating, storing, distributing and using energy in an intelligent and cost efficient manner. The use of surplus energy for hot water preparation constitutes a simple option, with low investment costs, for storing electricity in the form of heat and using it at a time of the customer’s choosing.
The Fronius Ohmpilot, which carries out precisely this task, is therefore an ideal addition to the Fronius product portfolio in the area of energy management and a further step towards “24 hours of sun”.

Components of the solution as a whole

The solution as a whole consists of the following components: – Fronius SnapInverter or GEN24 series inverters
– Fronius Symo / Galvo / Eco or Primo (from Fronius Datamanager 2.0 software version 3.8.1-x or higher) or Fronius Symo Hybrid (from Fronius Hybridmanager software version V1.8.1.x onwards)
– Fronius Primo / Symo GEN24 – Fronius Smart Meter – Fronius Ohmpilot – Resistive load (e.g. boiler with heating element)

Integrating the Fronius Smart Meter

A Fronius Smart Meter is required to operate the Ohmpilot so that the surplus energy can be measured. On the user interface of the inverter, it must be set whether the Fronius Smart Meter is installed at the feed-in point or in the consumption branch.

Description of the device

The Ohmpilot is a separate device that can control the surplus power from the PV system in a continuously variable manner using pulse width modulation for a phase between 0 and 100% (or 0 and 3 kW). In addition, the Ohmpilot has 2 additional outputs for switching further phases. This means that heating elements with an output of 300 W to 9 kW can be controlled in a continuously variable manner.
A heating element with up to 3 kW output can be controlled in a continuously variable manner using one phase.
For a heating element with 9 kW output, the surplus power of 0 – 3 kW is controlled in a continuously variable manner in phase 1. If even more power is available, the Ohmpilot also activates phase 2 and phase 1 can again control the surplus in a continuously variable manner between 3 ­ 6 kW. If the available power is higher than 6 kW, the Ohmpilot also activates phase 3 and phase 1 can again control the surplus in a continuously variable manner between 6 and 9 kW.

Power range 0 – 3 kW
3 – 6 kW

Phase 1
0 – 3 kW continuously variable
0 – 3 kW continuously variable

Phase 2 –
3 kW fixed

Phase 3 –

77

6 – 9 kW

0 – 3 kW continuously variable

3 kW fixed

3 kW fixed

Other resistive loads such as infrared heaters, towel dryers, etc. can also be controlled.

To be considered when designing the system

NOTE!
Ohmpilot phase control The Ohmpilot controls to the sum of all phases. The Ohmpilot is not suitable for the rare case of phase-accurate billing.

NOTE!
Ohmpilot and Fronius Datamanager / Hybridmanager Only one Ohmpilot can be used per Fronius Datamanager / Hybridmanager.

NOTE!
Ohmpilot and dynamic power reduction From software version 3.13.1-x and onwards on the Fronius Datamanager or 1.11.1-x onwards on the Fronius Hybridmanager, the Ohmpilot can be used together with the dynamic power reduction of 0-100%.

NOTE!
Use of other generation sources With the Fronius Datamanager Box 2.0, any other generation source (CHP, thirdparty inverter, etc.) can also be used. However, since information about the power produced and the consumption is missing, this cannot be displayed in Fronius Solar.web.

NOTE!
Due to high heat outputs, the Ohmpilot cannot be operated in backup power situations. It is therefore recommended to install the Ohmpilot outside of the backup power branch. If the Ohmpilot is installed in the backup power branch, the existing automatic circuit breaker of the Ohmpilot must be switched off in the event of a power failure. Alternatively, the heating element measurement must be changed to manual, and the minimum temperature and legionella prevention must be deactivated. (See chapter “Optional settings” on page 2). The power level required for these functions exceeds the power limits in backup power mode. Since these functions are blocked when backup power mode starts, these settings cannot be changed during a power failure.

CAUTION!
Danger from connecting an incorrect load (e.g. fan heater). The result is destruction of the load.
Connect only purely resistive loads.

78

EN

CAUTION!
Danger from connecting an electronic thermostat. The result is destruction of the Ohmpilot or load.
Use mechanical temperature switches.
NOTE!
If the water is hard, the heating element may become calcified, especially if the minimum temperature is set above 60 °C. An annual inspection of the heating element is recommended.
To do this, remove the heating element from the energy storage device and remove the limescale.
Do not scratch the surface of the heating element while doing so.

Warning notices on the device

Warning notices and safety symbols are affixed to the left side of the Ohmpilot. These warning notices and safety symbols must not be removed or painted over. They warn against incorrect operation, as this may result in serious injury and damage.

Safety symbols: Danger of serious injury and damage due to incorrect operation Do not use the functions described here until you have fully read and understood the following documents: – These Operating Instructions – All the Operating Instructions for the system components of the photovoltaic system, especially the safety rules Dangerous electrical voltage Before opening the machine, wait for the capacitors to discharge!
Hot surface
Text of the warning notices:
79

WARNING! An electric shock can be fatal. Before opening the device, it must be disconnected at the input and output. Wait for the capacitors to discharge (15 seconds). WARNING! The device must not be covered and nothing may be hung over the device or the cables.
80

EN

Control elements and connections

Indicators/ controls on the device

Press 1x Press 2x Press 3x Press again

1x WPS 2x ACCESS POINT 3x BOOSTMODE
WPS (Wi-Fi Protected Setup) opens for 2 minutes or until successful pairing with the router. Pressing the WPS button on the router sends the WLAN password to the Ohmpilot.
WLAN access point is activated for 30 minutes so that settings can be implemented on the Ohmpilot via the Fronius Solar.web App.
Boost Mode – dimmer level is activated for 4 hours at 100%, L2 and L3 are switched through. This may result in electricity being sourced from the grid.
Ohmpilot is returned to standard operating mode, Boost Mode, access point or WPS are deactivated.

Heating indica- Dark

tor

Green flashing

Green 2x flashing
Steady green

LAN / WLAN connection indicator

Dark
Blue 1x flashing
Blue 2x flashing
Steady blue

No power supply to the Ohmpilot. The faster the flashing frequency, the greater the heat output. At 0 W heat output, the LED flashes slowly, at full output fast. It measures the output of the heating element and detects whether a 1- or 3-phase heater is connected. Minimum temperature undercut or legionella prevention active (full heat output).
No connection WPS (Wi-Fi Protected Setup) open
WLAN Access Point open
Connection to network

81

Connection area

Error indicator Dark

No error

Red 1x flashing No connection to the inverter Red 2x flashing Temperature measurement faulty Red 3x flashing Heating element faulty Red 4x flashing Ohmpilot faulty Red 5x flashing Minimum temperature not reached A detailed description of the error is provided in Fronius Solar.web.

1 23

4

5

6

7

8

9

10

11

12

(1) (2) (3) (4) (5)
(6)
(7)
(8)
(9)
(10)

Green LED
Blue LED
Red LED
Button
Ethernet RJ45 At least CAT5, screened
Modbus RTU (default address 40) Spring balancer 0.2 – 1.5 mm2, max. 1000 m, screened and twisted
Temperature sensor terminal connection PT 1000, spring balancer 0.2 – 1.5 mm2
INPUT – grid supply 1x 230 V, or 3x 230 V, spring balancer 1.5 – 2.5 mm2
OUTPUT – L3 heating element Spring balancer 1.5 – 2.5 mm2
OUTPUT – L2 heating element Spring balancer 1.5 – 2.5 mm2

82

EN

(11) Multi-function relay output, (see application examples) Variable max. 13 A resistive load, spring balancer 1.5 – 2.5 mm2 WARNING!
Dangerous voltages. A wire detaches and makes contact with dangerous voltages.
If signal cables are connected, the individual wires must be tied together with a cable tie directly upstream of the terminal. (12) OUTPUT – heating element
Continuously variable up to 3 kW
83

Selection of heater

1-phase heater

Controlled in a continuously variable manner from 0 to 3 kW – 0.3 to 3 kW – Purely resistive load (no electronic temperature limiters, fans, etc.)

3-phase heater:

Controlled in a continuously variable manner from 0 to 9 kW. – 0.9 to 9 kW – Equal load distribution on all 3 phases (e.g. 3 x 3 kW). – If a mechanical temperature switch is being used, it must switch all 3 phases
simultaneously. – Purely resistive load (no electronic temperature limiters, fans, etc.) – Neutral conductor must be implemented (this can generally also be retrofit-
ted)
Temperature limitation A mechanical temperature switch simplifies commissioning and use. If a mechanical temperature switch is not available, a temperature sensor can also be connected to the Ohmpilot to limit the maximum temperature. (See chapter “Temperature limitation” on page 2.4)

N

L1 L2 L3

Example for calculation of charging time

500-litre boiler, heater can be fitted at the very bottom of the boiler, temperature spread 45 – 60 °C = 15 °C; 4.5 kW heater
Possible stored energy = 500l x 1.16 kWh x 15 °C = 8.7 kWh. If the heater is fully activated, the heating up takes approx. 2 hours (8.7 kWh / 4.5 kW)

NOTE!
Power adjustment So that optimal use can be made of the surplus power and the hot water is reheated quickly, the heater output should be adapted to the output of the photovoltaic system, e.g. 5 kWp => 4.5 kW heater.

84

Installation and commissioning
85

86

EN

Choice of location and installation position

Choosing location – general remarks

Please note the following criteria when choosing a location for the Ohmpilot:

Install only on a solid surface.

Max. ambient temperatures: 0 °C / +40 °C
Relative humidity: 0 – 99%
The airflow within the Ohmpilot is from the bottom to the top.

If the Ohmpilot is installed in an enclosed space, then forced-air ventilation must be provided to ensure adequate heat dissipation.
IMPORTANT! The maximum cable length from the output of the Ohmpilot to the load (heating element) must not exceed 5 m.

Choice of location

The Ohmpilot is suitable for installation indoors.

Do not install the Ohmpilot outdoors.
The housing complies with protection class IP 54 and is protected against spray water from all sides.
In order to minimise the heating up of the Ohmpilot, do not expose it to direct insolation. Mount the Ohmpilot in a protected position. The Ohmpilot must only be mounted and operated at an ambient temperature of 0-40 °C.

IMPORTANT! The Ohmpilot must not be installed or used at altitudes above 2000 m.

87

Explanation of symbols – installation position

Do not install the Ohmpilot in: – Areas where ammoniac, corrosive vapours, acids or salts are
present (e.g. fertiliser stores, ventilation openings from cattle sheds, chemical plants, tanneries, etc.)
Do not install the Ohmpilot in: – Places where there is an increased risk of damage from
farm animals (horses, cattle, sheep, pigs, etc.) – Stables or adjoining areas – Storage areas for hay, straw, chaff, animal feed, fertilisers,
etc. The Ohmpilot is designed to be dustproof. However, in areas with a heavy build-up of dust, the thermal efficiency may still be impaired by dust forming on the cooling surfaces. Regular cleaning is necessary in such situations. We therefore recommend not installing the device in areas and environments with high dust accumulation. Do not install the Ohmpilot in: – Greenhouses – Storage or processing areas for fruit, vegetables or viticul-
ture products – Areas used in the preparation of grain, green fodder or ani-
mal feeds
The Ohmpilot is designed to be installed vertically on a vertical wall.

Do not install the Ohmpilot horizontally. Do not install the Ohmpilot on a sloping surface. Do not install the Ohmpilot on a sloping surface with its connection sockets facing upwards.
88

EN

Do not install the Ohmpilot at an angle on a vertical wall. Do not install the Ohmpilot horizontally on a vertical wall. Do not install the Ohmpilot such that it overhangs with its connection sockets facing upwards.
Do not install the Ohmpilot such that it overhangs with its connection sockets facing upwards. Do not install the Ohmpilot such that it overhangs with its connection sockets facing downwards. Do not install the Ohmpilot on the ceiling.
89

Wall mounting

Safety

WARNING!
Danger due to residual voltage from capacitors. An electric shock can be fatal!
Before opening the device, wait for the capacitors to discharge (15 seconds).
WARNING!
Risk of burns from the heat sink when open. This can result in personal injury.
Wear suitable protective equipment. Allow heat sink to cool. Do not touch the hot heat sink.
IMPORTANT! The IP 54 protection class only applies if the cover is firmly screwed to the back.

Selecting wall plugs and screws

IMPORTANT! Different fixings may be required to fit the Ohmpilot depending on the type of surface. Fixings are therefore not included in the scope of supply. The installer is responsible for selecting the correct fixings. It must be ensured that the screws are tight and that the wall is stable.

Recommended screws

To install the Ohmpilot, Fronius recommends the use of steel screws with a diameter of 4 – 6 mm.
CAUTION!
Risk of contamination or water on the terminals or electronics This may result in damage to the Ohmpilot.
When drilling, ensure that terminals and electronics do not become dirty or wet.

90

EN

Mounting the

1

2

Ohmpilot on the

wall

3

4

91

Installation
Stripping lengths

Stripping length of terminals on power stage set (L1, L2, etc.)
Stripping length of terminals on control board (D+, D-, – and PT1000)

Electrical connection

WARNING!
Danger from inadequate ground conductor connection. This can result in severe personal injury or damage to property.
Adequately dimension the ground conductor connection.
IMPORTANT! Electrical connection work may only be carried out by a specialist.
IMPORTANT! The ground conductor connection must be perfectly installed and reliably connected.
IMPORTANT! The Ohmpilot must be equipped with an overvoltage protection device of maximum B16 A and a residual-current circuit breaker on the grid side.
IMPORTANT! On the output side, it must be ensured that only purely resistive loads are connected.
IMPORTANT! The maximum cable length from the output of the Ohmpilot to the load (heating element) must not exceed 5 m due to electromagnetic compatibility.
IMPORTANT! The Ohmpilot must be protected against overvoltage from the grid.
IMPORTANT! When connecting a heating element, check the grounding of the boiler/buffer and the heating system. Also check the maximum permissible inlet water and hot water temperature when setting the temperature on the heating element.
IMPORTANT! The RS485 lead should be designed as a data cable in order to prevent any mix-up with the mains lead when connecting.

92

EN

1-phase heating element up to 3 kW
Application example 1
(1) INPUT – grid supply 1x 230V network, spring-loaded terminal 1.5 – 2.5 mm²
(2) OUTPUT up to 3 kW variable, max. 13 A resistive load, spring-loaded terminal 1.5 – 2.5 mm²
(3) Hot water boiler (4) Temperature sensor PT1000 (5) External source (e.g. gas-fired heating) (6) Heating element (max. 3 kW) (7) Residual-current circuit breaker
93

(8) Automatic circuit breaker max. B16A (9) Ferrite (included in scope of supply) IMPORTANT! Plug & Play – no further settings are required for this application after successful connection to the inverter. The Fronius Smart Meter records the current power at the feed-in point and transfers the data to the inverter. By controlling the Ohmpilot, the inverter adjusts any surplus energy that is available to zero. In detail, this takes place by continuously adjusting the heating element connected to the Ohmpilot. Surplus energy is consumed using the heating element in a continuously variable manner. If no temperature sensor is fitted, an external source (e.g. gas-fired heating) must be used to ensure the minimum temperature is met. As an alternative, the Ohmpilot can ensure the minimum temperature. To do this, a temperature sensor must be connected so that the Ohmpilot can measure the temperature. This may result in electricity being sourced from the grid. The maximum temperature must be set on the heating element thermostat. If the heating element does not have a thermostat, the Ohmpilot can also carry out this task as an alternative (see chapter Optional settings on page 122).
94

EN

3-phase heating element 900 W up to 9 kW
Application example 2
(1) INPUT- grid supply 3x 230 V network, spring-loaded terminal 1.5 – 2.5 mm²
(2) OUTPUT – L3 heating element (3) OUTPUT – L2 heating element (4) OUTPUT up to 3 kW variable, max. 13 A resistive load, spring-loaded ter-
minal 1.5 – 2.5 mm² (5) Hot water boiler (6) Temperature sensor PT1000 (7) External source (e.g. gas boiler) (8) Heating element (max. 9 kW) (9) Residual-current circuit breaker
95

(10) Automatic circuit breaker max. B16A (11) Ferrite (included in scope of supply) IMPORTANT! Plug & Play – no further settings are required for this application after successful connection to the inverter. The Fronius Smart Meter records the current power at the feed-in point and transfers the data to the inverter. By controlling the Ohmpilot, the inverter adjusts any surplus energy that is available to zero. In detail, this takes place by continuously adjusting the heating element connected to the Ohmpilot. This means that the surplus energy is consumed in a continuously variable manner with the heating element. Depending on the surplus power, the individual phases are switched on or off and the remaining power is consumed at L1. As a result, the heating element output is divided by three. If no temperature sensor is fitted, an external source (e.g. gas boiler) must be used to ensure the minimum temperature is met. As an alternative, the Ohmpilot can ensure the minimum temperature. To do this, a temperature sensor must be connected so that the Ohmpilot can measure the temperature. This may result in electricity being sourced from the grid. The maximum temperature must be set on the heating element thermostat. If the heating element does not have a thermostat, the Ohmpilot can also carry out this task as an alternative (see chapter Optional settings on page 122). IMPORTANT! A heating element with a neutral conductor is required.
96

EN

1-phase heating element up to 3 kW with heat pump control
Application example 3
97

(1) INPUT – grid supply 1x 230 V network, spring-loaded terminal 1.5 – 2.5 mm²
WARNING!
Short circuit If current-carrying stripped wires touch each other, a short circuit is triggered.
Carry out all connection work in accordance with the applicable electrotechnical guidelines and regulations.
Observe the maximum stripping length of 10 mm. When connecting the phases, tie together the individual wires with a cable tie
directly in front of the terminal.
(2) Multifunctional relay output (3) OUTPUT up to 3 kW variable, max. 13 A resistive load, spring-loaded ter-
minal 1.5 – 2.5 mm² (4) Hot water boiler (5) Temperature sensor PT1000 (6) Heat pump with SG Ready control input
NOTE! Relay contacts can oxidise. The voltage must be at least 15 V and the current at least 2 mA, so that the relay contacts do not oxidise.
(7) Heating element (max. 3 kW) (8) Residual-current circuit breaker (9) Automatic circuit breaker max. B16A (10) Ferrite (included in scope of supply)
The Fronius Smart Meter records the current power at the feed-in point and transfers the data to the inverter. By controlling the Ohmpilot, the inverter adjusts any surplus energy that is available to zero. In detail, this takes place by continuously adjusting the heating element connected to the Ohmpilot and by targeted switching on of the heat pump.
For activation, the heat pump must have a control input (e.g. SG Ready or grid operator release). For example, the heat pump can be switched from operating state 2 (normal operation) to operating state 3 (increased operation) as a result of activation of heat pump input 2 by the relay. The heat pump can also be switched from operating state 1 (blocked time set by grid operator) to operating state 2 (normal operation) as a result of activation of heat pump input 1 by the relay.
A description and list of SG Ready heat pumps can be found at: http:// www.waermepumpe.de/normen-technik/sg-ready/sg-ready-datenbank/
Relatively small surpluses are consumed by the heating element in a continuously variable manner. From a certain excess power, it makes sense to activate the heat pump, as it has a higher efficiency. The average COP (coefficient of performance) for water heating up to 53 °C is 2.5. Thus, with 1 KW of electrical energy, 2.5 KW of thermal energy can be generated.
The optimal switching thresholds depend on:
98

EN

– Heat pump COP. The higher the temperature to which the hot water is heated, the lower the COP.
– The electrical heat pump output. – The feed-in tariff and the costs for purchasing energy. – Reduction of the heat pump’s start-up cycles = increase in service life of the
heat pump. – Thermal losses from the heat pump and the pipes. If no temperature sensor is fitted, the heat pump must be used to ensure the minimum temperature is met. As an alternative, the Ohmpilot can also ensure the minimum temperature by activating the heat pump. This may result in electricity being sourced from the grid. The maximum temperature must be set on the heating element thermostat and on the heat pump. If the heating element does not have a thermostat, the Ohmpilot can also carry out this task as an alternative (see chapter Optional settings on page 122). This function can also be combined with a 3-phase heating element.
Settings in the menu area
General settings, symbolic representation
1 Open the Ohmpilot user interface Chapter Establishing the data connection on page 113 describes how you can access the Ohmpilot user interface.
2 Under HEATER 2 for consumer, select “SG Ready heat pump” 3 Select “Feed-in” under Starting threshold and enter the desired output in
watts at which the heat pump is to be switched on. 4 Under Switch-off threshold, select “Consume” or “Feed-in” and enter the
desired output in watts at which the heat pump is to be switched off. Example 1: If “Consume” has been selected under the switch-off threshold and a power of 500 W has been entered, the heat pump will be switched off as soon as the power being drawn from the grid exceeds 500 W.
99

Example 2: If “Feed-in” has been selected under the switch-off threshold and a power of 500 W has been entered, the heat pump will be switched off as soon as the power being fed in is less than 500 W.
NOTE! The heat pump must be connected to the same Fronius Smart Meter. Between the switch-on and switch-off thresholds, the self-consumption of the heat pump must also be taken into consideration. For example, if the heat pump consumes 3000 watts of electricity and a hysteresis of 500 watts must be taken into account, the switch-on threshold can be set to feed-in 3000 watts and the switch-off threshold to purchase 500 watts.
100

EN

1-phase heating element up to 3 kW and external source
Application example 4
101

(1) INPUT – grid supply 1x 230 V network, spring-loaded terminal 1.5 – 2.5 mm2
WARNING! Short circuit If current-carrying stripped wires touch each other, a short circuit is triggered.
Carry out all connection work in accordance with the applicable electrotechnical guidelines and regulations.
Observe the maximum stripping length of 10 mm. When connecting the phases, tie together the individual wires with a cable tie
directly in front of the terminal. (2) Multifunctional relay output (3) OUTPUT up to 3 kW variable, max. 13 A resistive load, spring-loaded ter-
minal 1.5 – 2.5 mm2 (4) Hot water boiler (5) Temperature sensor PT1000 (6) External source (e.g. gas boiler)
NOTE! Relay contacts can oxidise. The voltage must be at least 15 V and the current at least 2 mA, so that the relay contacts do not oxidise. (7) Heating element (max. 3 kW) (8) Residual-current circuit breaker (9) Automatic circuit breaker max. B16A (10) Ferrite (included in scope of supply)
The Fronius Smart Meter records the current power at the feed-in point and transfers the data to the inverter. By controlling the Ohmpilot, the inverter adjusts any surplus energy that is available to zero. In detail, this takes place by continuously adjusting the heating element connected to the Ohmpilot. Surplus energy is consumed using the heating element in a continuously variable manner.
The temperature is measured by the Ohmpilot. If the temperature falls below the minimum, then an external source (e.g. gas boiler) will be activated until the minimum temperature is reached again, so that the Ohmpilot only uses surplus energy and does not draw any energy from the grid.
The maximum temperature must be set on the heating element thermostat. If the heating element does not have a thermostat, the Ohmpilot can also carry out this task as an alternative (see chapter Optional settings on page 122).
The heating element is used for the legionella prevention program.
This function can also be combined with a 3-phase heating element.
102

EN

Settings in the menu area

General settings, symbolic representation
1 Open the Ohmpilot user interface Chapter Establishing the data connection on page 113 describes how you can access the Ohmpilot user interface.
2 Activate the “Temperature sensor present” field 3 Activate the “Adapt day curve” field 4 Adjust settings under “Time from”, “Time to” and “Minimum temperature” as
desired More information can be found in chapter Adapting the day curve on page 123 5 Under HEATER 2 for Consumer, select “Activate external source”
103

Two heating elements – 3-phase and 1-phase
Application example 5
(1) INPUT – grid supply 3x 230 V network, spring-loaded terminal 1.5 – 2.5 mm2
(2) OUTPUT – L3 heating element (3) OUTPUT – L2 heating element (4) Multifunctional relay output (5) OUTPUT up to 3 kW variable, max. 13 A resistive load, spring-loaded ter-
minal 1.5 – 2.5 mm2 (6) Hot water boiler (7) Temperature sensor PT1000 (8) External source (e.g. gas boiler) 104

EN

(9) Heating element 1 (max. 3 kW) (10) Buffer (11) Heating element 2 (max. 9 kW) (12) Residual-current circuit breaker (13) Automatic circuit breaker max. B16A (14) Ferrite (included in scope of supply)
Many heating systems consist of a boiler and a buffer, whereby the central heating supplies the buffer, and a control system feeds the hot water boiler via a pump. As with thermal photovoltaic systems, the Ohmpilot is also capable of heating the hot water boiler first and then the buffer, so that the maximum amount of photovoltaic surplus energy can be stored.
The Fronius Smart Meter records the current power at the feed-in point and transfers the data to the inverter. By controlling the Ohmpilot, the inverter adjusts any surplus energy that is available to zero. In detail, this takes place by continuously adjusting the heating element connected to the Ohmpilot.
For this application, two heating elements are installed, with preference being given to activation of the first heating element (9). Only once the maximum temperature in the boiler (6) has been reached is the second heating element activated in a continuously variable manner, so that the remaining energy can, for example, be stored in a buffer.
If no temperature sensor is connected to the Ohmpilot, after 30 minutes the Ohmpilot attempts to output energy via the first heating element once again. If a temperature sensor is present, the device switches back to the first heating element as soon as a temperature difference of 8°C is reached (compared to the temperature measured prior to switch-over).
This switching can also be used for layering in a boiler/buffer, so that the maximum temperature is reached in the top part of the boiler using minimal energy and the remaining energy is stored in the lower part of the boiler. By using layering in a storage tank, it is also possible to store significantly more energy, as a minimum temperature is normally maintained in the top part of the boiler. This means that the temperature difference and thus the amount of energy is rather small. In the lower part of the boiler, a high temperature difference of, for example, 50 °C can be used.
Both the first and the second heating element can be 1-phase or 3-phase. For two 3-phase heating elements, see Application example 6. If no temperature sensor is fitted, an external source (e.g. gas boiler) must be used to ensure the minimum temperature is met.
Alternatively, the Ohmpilot can also ensure the minimum temperature. This may result in electricity being sourced from the grid. The maximum temperature must be set on the heating element thermostat. If heating element 1 (9) does not have a thermostat, the Ohmpilot can also carry out this task as an alternative (see chapter Optional settings on page 122). However, heating element 2 (11) must have a thermostat.
NOTE!
Heating at the same time. At no point can both heating elements be heated simultaneously.
105

Settings in the menu area
General settings, symbolic representation
1 Open the Ohmpilot user interface Chapter Establishing the data connection on page 113 describes how you can access the Ohmpilot user interface.
2 Under HEATER 1, select “Manual” and “Single-phase or Three-phase”. 3 Under HEATER 2, select “Single-phase or Three-phase” and enter the output
of the load.
106

EN

Two 3-phase heating elements up to 9 kW
Application example 6
(1) INPUT – grid supply 3x 230 V network, spring-loaded terminal 1.5 – 2.5 mm2
(2) OUTPUT – L3 heating element (3) OUTPUT – L2 heating element (4) Multifunctional relay output (5) OUTPUT up to 3 kW variable, max. 13 A resistive load, spring-loaded ter-
minal 1.5 – 2.5 mm2 (6) Contactor switching (7) Hot water boiler (8) Temperature sensor PT1000 (9) External source (e.g. gas-fired heating) (10) Heating element 1 (max. 9 kW) (11) Buffer (12) Heating element 2 (max. 9 kW) (13) Residual-current circuit breaker
107

(14) Automatic circuit breaker max. B16A (15) Ferrite (included in scope of supply)
Many heating systems consist of a boiler and a buffer, whereby the central heating supplies the buffer, and a control system feeds the hot water boiler via a pump. As with thermal photovoltaic systems, the Ohmpilot is also capable of heating the hot water boiler first and then the buffer, so that the maximum amount of photovoltaic surplus energy can be stored.
The Fronius Smart Meter records the current power at the feed-in point and transfers the data to the inverter. By controlling the Ohmpilot, the inverter adjusts any surplus energy that is available to zero. In detail, this takes place by continuously adjusting the heating element connected to the Ohmpilot.
For this application, two heating elements are installed, with preference being given to activation of the first heating element (10). Only once the maximum temperature in the boiler (7) has been reached is the second heating element (12) activated in a continuously variable manner, so that the remaining energy can, for example, be stored in a buffer.
If no temperature sensor is connected to the Ohmpilot, after 30 minutes the Ohmpilot attempts to output energy via the first heating element once again. If a temperature sensor is present, the device switches back to the first heating element as soon as a temperature difference of 8 °C is reached (compared to the temperature measured prior to switch-over).
This switching can also be used for layering in a boiler/buffer, so that the maximum temperature is reached in the top part of the boiler using minimal energy and the remaining energy is stored in the lower part of the boiler. By using layering in a storage tank, it is also possible to store significantly more energy, as a minimum temperature is normally maintained in the top part of the boiler. This means that the temperature difference and therefore the amount of energy is rather small. In the lower part of the boiler, a high temperature difference of, for example, 50 °C can be used.
The switching must be realised by an external contactor. If no temperature sensor is fitted, an external source (e.g. gas-fired heating) must be used to ensure the minimum temperature is met.
Alternatively, the Ohmpilot can also ensure the minimum temperature. This may result in electricity being sourced from the grid.
The maximum temperature must be set on the heating element thermostat. If heating element 1 (10) does not have a thermostat, the Ohmpilot can also carry out this task as an alternative (see chapter Optional settings on page 122). However, heating element 2 (12) must have a thermostat.
NOTE! Heating at the same time. At no point can both heating elements be heated simultaneously.
108

EN

Settings in the menu area
General settings, symbolic representation
1 Open the Ohmpilot user interface Chapter Establishing the data connection on page 113 describes how you can access the Ohmpilot user interface.
2 Under HEATER 2, select “Three-phase” and enter the output of the load
109

1-phase heating element up to 3 KW and circulating pump
Application example 7
110

EN

(1) INPUT – grid supply 1x 230 V network, spring-loaded terminal 1.5 – 2.5 mm2
WARNING! Short circuit If current-carrying stripped wires touch each other, a short circuit is triggered.
Carry out all connection work in accordance with the applicable electrotechnical guidelines and regulations.
Observe the maximum stripping length of 10 mm. When connecting the phases, tie together the individual wires with a cable tie
directly in front of the terminal. (2) Multifunctional relay output (3) OUTPUT up to 3 kW variable, max. 13 A resistive load, spring-loaded ter-
minal 1.5 – 2.5 mm2 (4) Hot water boiler (5) Temperature sensor PT1000 (6) Circulating pump auxiliary relay
NOTE! Relay contacts can oxidise. The voltage must be at least 15 V and the current at least 2 mA, so that the relay contacts do not oxidise. (7) Heating element (max. 3 kW) (8) Residual-current circuit breaker (9) Automatic circuit breaker max. B16A (10) Ferrite (included in scope of supply)
Via the floating contact of the device control, the Ohmpilot can also control a circulating pump in a heating system in parallel to a heating element. This is possible with all circulating pumps that have an auxiliary relay.
The designation of the floating contact on the Ohmpilot is NC W NO. The switching rocker (W) switches from the “normally open” (NO) position to “normally closed” (NC) when activated.
In heating mode, this contact is activated and the circulating pump runs as “Heater 2” in parallel to the heating element, which is operated via the “Heater 1” output.
To prevent the auxiliary relay of the circulating pump from switching on and off continuously in case of low or fluctuating PV power, the Ohmpilot is equipped with a delay. This has a positive effect on the wear and service life of the relay and the pump.
111

Settings in the menu area
General settings, symbolic representation
1 Open the Ohmpilot user interface Chapter Establishing the data connection on page 113 describes how you can access the Ohmpilot user interface.
2 Under HEATER 1, select “Automatic” 3 Under HEATER 2, select “Circulating pump” IMPORTANT! If the “Circulating pump” option is selected, no other heater can be controlled by the Ohmpilot. The “HEATER 1” output controls the heating element which, in combination with the circulating pump, heats a hot water tank.
112

EN

Establishing the data connection

Possible communication channels

The data connection is required for communication between the inverter and the Ohmpilot. The inverter mainly sends default values to the Ohmpilot. For some applications, it is necessary to make settings via the Ohmpilot user interface.

Ethernet / WiFi or Modbus RTU

Ethernet / WiFi

There are 3 possible communication channels: – Modbus RTU (via RS 485) – LAN (Ethernet) – WLAN
NOTE!
Compatible software versions An inverter from the SnapInverter series (Datamanager 2.0) must have at least software version 3.8.1-x.

Connecting the inverter to the Ohmpilot

Each inverter with a Fronius Smart Meter automatically connects itself to the Ohmpilot. However, if there is more than one inverter with a Fronius Smart Meter in the network, the wrong inverter can be connected. In this case, the Ohmpilot can be manually connected under System Information on the user interface of the inverter to be connected.
Information on how to access the user interface of the inverter can be found in the “Fronius Datamanager 2.0” Operating Instructions.

113

Establishing a connection via Modbus RTU

1 Connect the bus cabling (B) to the Ohmpilot. (The bus cabling is carried out in parallel via the TX+, TX- and GND cables with the Fronius Smart Meter and the Fronius inverter or Datamanager 2.0).
2 Terminate the bus cabling with a resistor on the first and last device. The resistor can be activated on the Ohmpilot using DIP switch number 5. See (A).
3 Set Modbus address using numbers 1-3. Default address: 40 (for future applications, the Modbus address can be changed using the DIP switches on the Ohmpilot).
(A) DIP switches
DIP 1-3 = Modbus address BCD DIP 4 = reserve DIP 5 = terminating resistor (120 Ohm)
NOTE!
Avoid confusion of cables. Use a data cable that is clearly distinguishable from the mains cable, so that there is no confusion, and injury and damage to property are avoided.
NOTE!
Faulty cabling. This is indicated by the red LED indicator flashing 1x.

120

Fronius Smart Meter

Smart Meter Rx Smart Meter TS M+

Tx GND M- GND

120

Fronius Inverter

SnapINverter D+

D-

GEN24

M1+ M1- GND

OFF

Fronius Ohmpilot D+ D- –
12345

In order to implement various settings, the WLAN connection must briefly be opened:
1 Press the button on the Ohmpilot 2x. The blue LED flashes (twice) as long as the WLAN access point is active (30 minutes). Before the access point is opened, it searches for available WLAN networks.
2 Activate the “Ohmpilot” WLAN network on your smart device or PC.
3 In the browser, enter the address http://192.168.250.181 or http://ohmpilotW.local.

114

EN

NOTE!
Accessing the Ohmpilot via the network. In networks with a DNS suffix, the Ohmpilot can be accessed at http://ohmpilotW., e.g. http://ohmpilotW.fronius.com
4 Implement the settings.

Establishing a connection via LAN

As standard, the Ohmpilot obtains its IP address automatically from the DHCP server, meaning that no settings are generally necessary.
The inverter automatically searches for the Ohmpilot, and the search process may take up to 5 minutes. If the red LED is not lit and the green LED is flashing, the Ohmpilot is working correctly.
A static IP address can be assigned to the Ohmpilot via the user interface.

Set Up Network, symbolic representation
1 In the web browser, open the address http://ohmpilotL.local. Alternatively, the IP address assigned by the DHCP server can also be read out. Almost every router displays its connected devices (clients) on its user interface. Apps such as Fing can help you find the automatically assigned IP address. Alternatively, the Ohmpilot can also be searched on the network using the Fronius Solar.web App.
NOTE! Accessing the Ohmpilot via the network. In networks with a DNS suffix, the Ohmpilot can be accessed at http://ohmpilotL., e.g. http://ohmpilotL.fronius.com
To set the IP address manually, the “Static” option must be selected. Then enter the desired IP address. The Ohmpilot can then be reached at http://ohmpilotL.local or at the fixed IP address assigned.
115

Establishing a connection via WLAN

There are two options for connecting the Ohmpilot to an existing WLAN network:
Connecting via WPS (WiFi Protected Setup)
1 Press the button on the Ohmpilot 1x. The blue LED flashes (once) as long as WPS is active.
2 Press the WPS button on the router within 2 minutes. If the blue LED on the Ohmpilot lights up permanently, the connection to the network was successful. The inverter automatically searches for the Ohmpilot, and the search process can take up to 5 minutes. If the red LED is not lit and the green LED is flashing, the Ohmpilot is working correctly.

Set Up Navigation, symbolic representation
Connecting via access point and manual configuration of the WLAN settings 1 Press the button on the Ohmpilot 2x.
The blue LED flashes (twice) as long as the WLAN access point is active (30 minutes). Before the access point is opened, it searches for available WLAN networks. 2 Activate the “Ohmpilot” WLAN network on your smart device or PC. 3 In the browser, enter the address http://192.168.250.181 or http://ohmpilotW.local. Alternatively, the Ohmpilot can also be searched on the network using the Fronius Solar.web App. 4 Select the desired network in the WLAN network tab.
NOTE!
Desired network not listed. If the desired WLAN network is not listed, end access point mode by pressing the button again and repeat the process.
5 Click on “Save & Connect”, enter WLAN password. If the blue LED on the Ohmpilot lights up permanently, the connection to the network was successful. The inverter automatically searches for the Ohmpilot, and the search process can take up to 5 minutes. If the red LED is not lit and the green LED is flashing, the Ohmpilot is working correctly.
116

EN

NOTE! WLAN network scan not possible. When the access point is opened, it is not possible to scan the WLAN networks. A static IP address can be assigned to the Ohmpilot via the user interface. The Ohmpilot can then be reached at http://ohmpilotW.local or at the fixed IP address assigned. Alternatively, the Ohmpilot can also be searched on the network using the Fronius Solar.web App.
NOTE! Device connections. Only one device can connect to the Ohmpilot.
NOTE! Accessing the Ohmpilot via the network. In networks with a DNS suffix, the Ohmpilot can be accessed at http:// ohmpilotW., e.g. http://ohmpilotW.fronius.com
117

Boost Mode

Boost Mode

Boost Mode is used to supply the load at the “Heater 1” output with 100% of the available power for a short time. Over a maximum period of 4 hours, the dimmer level is activated at 100%, L2 and L3 are switched through. This may result in electricity being sourced from the grid.
Boost Mode can be activated and deactivated by pressing the button on the Ohmpilot (see Indicators/controls on the device ) or via the user interface.

Settings in the menu area

Boost Mode, symbolic representation
1 Open the Ohmpilot user interface Chapter Establishing the data connection on page 113 describes how you can access the Ohmpilot user interface.
2 Activate Boost Mode by clicking on the button of the same name. 3 Click the button again to deactivate Boost Mode.

118

Ohmpilot user interface
119

120

User interface
Status indicators on the web interface

EN

Status indicators, symbolic representation

Status

OK

Ohmpilot is operating in normal mode.

Minimum tempera- The minimum temperature has been exceeded. Heater 1

ture

heats up to 100%.

Legionella preventi- Legionella prevention program is active. Heater 1 heats

on

up to 100%.

Boost Mode

The Ohmpilot has been switched to Boost Mode manually. Heater 1 heats up to 100%.

Error

A fault has been detected. More information can be found on Fronius Solar.web.

Temperature

Currently measured temperature. A valid value is only displayed when a temperature sensor is connected.

Heat output

Current power being used by the Ohmpilot.

Heater 2

Heater 2 is active. Heater 2 may be a second heating element, a heat pump or an external source (e.g. gas-fired heating).

L2 heating element Phase 2 of 3-phase heating element is active.

L3 heating element Phase 3 of 3-phase heating element is active.

121

Optional settings

Manual settings for HEATER 1

NOTE!
Settings not absolutely necessary. The settings described here can be made for all the application examples shown above. If they are not described for the respective example, they are not absolutely necessary.

General settings, symbolic representation
Setting the output of HEATER 1 manually: 1 Under HEATER 1, select “Manual” 2 Select “Single-phase” or “Three-phase” Consumer 3 Enter the output of the load NOTE! It is not possible to measure heating element 1 automatically. In the case of applications with a 1-phase and a 3-phase heating element, it is not possible for the Ohmpilot to measure heating element 1 automatically due to the cabling. In this case, the configuration must be carried out manually.
122

EN

Activating legionella prevention

When the legionella prevention function is activated, the hot water is heated to 60 °C at a set interval.
1 Activate the “Temperature sensor present” field 2 Activate the “Legionella prevention (h)” field 3 Enter the desired legionella prevention cycle

NOTE!
If no hygienic storage tank is being used, measures must be taken to kill legionella bacteria. If the boiler is operated at a temperature <60 °C for a relatively long period of time and no hygienic storage tank is being used, measures must be taken to kill the legionella bacteria. For private use, it is recommended to implement legionella prevention at least once a week (168 hours). In the case of a large hot water storage tank or a comparatively low consumption of hot water, legionella prevention should be carried out regularly. A PT1000 temperature sensor is required for this function and can be sourced from Fronius under item number 43,0001,1188.

Despite the setting of the “Legionella prevention” function, contamination of water with legionella is not completely ruled out.

Adapting the day curve

This function ensures that the user-specified temperature is not undershot. If there is not sufficient surplus power available, the external source will be started up, if activated, or otherwise electricity will be drawn from the grid in order to ensure a minimum temperature.

Up to four time periods can be defined so that, for example, higher hot water temperatures are only certain to be available at night, but more potential is possible for the surplus during the day due to the fact that a lower target temperature is selected.

Adapting the day curve:
1 Activate the “Temperature sensor present” field 2 Activate the “Adapt day curve” field 3 Under “Time from”, enter the time from which the Ohmpilot should start to
heat to the new minimum temperature.
4 Under “Time to” enter the time until which the Ohmpilot should heat to the minimum temperature.
5 Under “Minimum temperature”, select the desired end temperature.

NOTE!
Time ranges overlap. If time ranges overlap, the higher temperature is used, so that, for example, a basic temperature of 40 °C can be set for the whole day and is increased to 50 °C at certain times.

NOTE!
Undefined time ranges. If time ranges are not defined, then in this time the system is not heated via the grid or the external source, but only using PV surplus.

123

NOTE!
Primary heat source. If heater 1 is the primary heat source, the daily cycle must be adjusted to ensure the desired minimum temperature. A PT1000 temperature sensor is required for this function and can be sourced from Fronius under item number 43,0001,1188. The position of the temperature sensor in the boiler should be selected so that sufficient hot water is available. However, it must be mounted above the heating element / external source.
Example 1: 03:00 – 05:00 45 °C => So that in the morning at 06:00 there is hot water available for showering. After showering, the water should only be heated using surplus energy. 16:00 – 18:00 45 °C => If there was not enough surplus energy available, the water is reheated for showering. After showering, reheating should no longer be carried out in order to keep heat losses to a minimum.

Temperature limitation

If heater 1 does not have a configurable thermostat, this function can be used to limit the temperature.
1 Activate the “Temperature sensor present” field 2 Activate the “Temperature limitation” field 3 Enter maximum temperature (e.g. 60 °C)
NOTE!
This function is only possible for heater 1. If a second heating element is used as heater 2, it must have a thermostat. A PT1000 temperature sensor is required for this function and can be sourced from Fronius under item number 43,0001,1188. The position of the temperature sensor should be just above the heating element, so that the incoming cold water is immediately heated again and thus the maximum amount of storage is used.

124

Appendix
125

126

EN

Status Codes

Status codes

Sending of errors – Errors are saved in the Datamanager 2.0 and can be sent via Fronius So-
lar.web. – Possible error outputs (as at 07/12/2015):

Cod e 906
907 908 909 910 911
912
913 914 915 916 917
918 919 920
921
922
923

Description

Cause

Remedy

Heating element 1 faulty – short circuit L1
HS 1 – Overload on L2 HE 1 – Overload on L3
HE 1 faulty – L1 highly resistive HE 1 faulty – L2 highly resistive HE 1 faulty – L3 highly resistive
HE 2 faulty – short circuit L1
HS 2 – Overload on L2 HE 2 – Overload on L3
HE 2 faulty – L1 highly resistive HE 2 faulty – L2 highly resistive HE 2 faulty – L3 highly resistive
Relay 2 faulty Relay 3 faulty
TS short circuit
TS not connected or faulty
60 °C for legionella prevention could not be achieved within 24 hours. Minimum temperature could not be achieved within 5 hours

The load on L1 is higher than 3 kW. Short circuit on L1. Current on L2 greater than 16 A. Current on L3 greater than 16 A. No current is flowing through L1/L2/L3. L1/L2/L3 of HE 1 faulty. Phase L1/L2/L3 interrupted.
The load on L1 is higher than 3 kW. Short circuit on L1. Current on L2 greater than 16 A. Current on L3 greater than 16 A. No current is flowing through L1/L2/L3. L1/L2/L3 of HE 2 faulty. Phase L1/L2/L3 interrupted.
Relay R2/R3 does not switch.
TS input resistance less than 200 Ohm. No PT1000 TS connected. TS defective. No TS connected (input resistance greater than 2000 Ohm). TS is activated (should be deactivated). TS cable defective. TS defective. No PT1000 TS connected. ES is switched off/faulty (922 only). TS has not been fitted correctly. Heating system has not been dimensioned properly (hot water consumption too high, etc.). HE/TS faulty.

Check heating element 1. Check wiring. Check HE 1 and replace if necessary. Check L1/L2/L3. Check L1/L2/L3 connections.
Check HE 2. Check wiring. Check HE2 and replace if necessary. Check L1/L2/L3. Check L1/L2/L3 connections.
Replace Ohmpilot.
Check cable and connections on TS cable. Replace TS. Connect TS to device. Deactivate TS via the user interface (if sensor not needed). Check TS cable. Replace TS. Switch on ES (922 only). Fit TS above the HE (in the protective tube). Legionella prevention via the user interface. Replace HE/TS.

127

924 ES could not achieve minimum temperature within 5 hours.

ES switched off/defective. ES not connected to Ohmpilot. TS incorrectly mounted. Heating system not dimensioned properly (hot water consumption too high, etc.). TS faulty.

Switch on ES. Connect ES to relay 1. Fit TS above the heater battery of the ES. Check minimum temperature setting. Replace TS.

925 Time not synchronised

Time not synchronised in the last 24 hours. Router has been switched off/ reconfigured.

Check connection between Ohmpilot and inverter. Switch on router. Check network settings.

926 No connection to inver- No connection between inverter and Check connection.

ter

Ohmpilot. Inverter switched off. The Switch on the inverter.

Ohmpilot also needs a connection to Update the software.

the inverter at night. Router switched Switch Ohmpilot and

off/faulty/reconfigured. Night switch- inverter off and on

off function enabled on the inverter. again. The night switch-

Poor WLAN connection between in- off function of the in-

verter or Ohmpilot and router.

verter must be disabled.

On the inverter display,

set night mode to ON

under “SETUP/Display

settings/Night mode”

menu. Switch on router.

Reposition the WLAN

antenna in a better lo-

cation. Check network

settings.

927 Ohmpilot overtempera- Ambient temperature too high (>40

Install Ohmpilot in a

ture

°C). The output of the heating element cooler location. Use a

is too high Ventilation slots are cover- heating element with a

ed.

permissible output. Un-

cover the ventilation

slots.

928 Ohmpilot undertempe- Ambient temperature too low (<0 °C). Install Ohmpilot in a

rature

warmer location. Instal-

lation outdoors is not

permitted.

Residual current-operated circuit breaker is triggered

N and L mixed up.

Connect N and L correctly.

Ohmpilot is not using any surplus

Thermostat on heating element has switched off. Safety thermostat (STC) on the heating element has triggered.

Wait until thermostat switches on again. Reset safety thermostat.

Ohmpilot is using only part of the surplus power

Heating element power is lower than surplus power.

Select a larger heating element where necessary

Power at the feed-in point is not always adjusted to 0

Load and generation fluctuations require a few seconds to settle down.

After switch-on, the

Thermostat on heating element has

green LED makes 2 long switched off. Heating element is not

flashes

connected.

Briefly turn up the thermostat for the power measurement. Connect the heating element.

128

After a power failure, the Ohmpilot will no longer work

After a power failure, if it does not receive an IP address after 40 seconds, the Ohmpilot automatically assigns a fixed IP address to 169.254.0.180 (only valid if the Ohmpilot is connected to the router via WLAN).

Restart Ohmpilot so that the WLAN connection is re-established.

HE=heating element TS=temperature sensor WR=inverter ES=external source (e.g. gas-fired heating)

EN

129

Technical data

Input data

Frequency Nominal Voltage Max. Input current

50 Hz 230 V / 400 V 1 X 16 A / 3 x 16 A

Interfaces

Modbus RTU LAN WLAN Temperature sensor

RS 485, max 1000 m, screened and twisted Ethernet min. CAT5, screened IEEE 802.11 b/g/n PT1000 (max. 30 m)

Output data

Analogue out 1-phase / 3-phase Nominal current analogue per phase Short circuit current analogue out Max. Current relay out Multi-function relay out Efficiency in rated operation Consumption in standby

Continuously variable 0 – 3 / 0 – 9 kW 13 A 16 A (max. 5 sec.) L2 / L3 16A (max. 5 sec.) min. 15V / 2mA; max. 16 A (max. 5 sec.) min. 98% type 1.8 W

General data

Dimensions (height x width x depth) Weight Protection class Installation Ambient temperature range Permissible humidity Cooling Storage temperature EMC device class Overvoltage category Pollution degree

340 mm x 270 mm x 123 mm 3.9 kg IP54 Wall 0 to 40 °C 0-99% (non-condensing) Convection -40 to 70 °C B 3 3

130

EN

Tests/specifications

Tests/specifications

Tests/information according to EN60730 Section 1 Table 7.2

6a Construction

Electronic RS 2.5.5, independently mounted RS

19 Screwless terminals

2.10.6.1 type X mounting

24 Classification of the RS according Protection class I 6.8.3 to protection against electric shock, Section 6.8

29 Type of shutdown or open circuit Micro interruption according to

for each circuit

2.4.4.

30 PTI value of the insulation materi- PTI 175 as per 6.13.2 als used for insulation

31a Type of ground conductor connec- N in accordance with 7.4.3, groun-

tion

ding terminal according to 9.1.1

39 Operating principle

Operating principle TYPE 1 according to 2.6.1

40 Additional properties for operating C in accordance with 6.4.3.3 principle

51 Glow wire test temperatures (Sec- Housing 550 °C, cable gland/

tions 21.2.1, 21.2.2, 21.2.3 and

strain-relief device 650 °C; catego-

21.2.4)

ry B according to EN

60730-1:2000/A1:2004;

75 Rated surge voltage (Sections 2.1.12, 20.1)

According to EN 61000-6-2:2005, EN 60730-1:2011, EN 301 489-1 (V1.9.2) Wire to wire | Wire(s) to ground Signal and control lines: — ± | 1 kV DC mains inputs: ± 0.5 kV | ± 0.5 kV AC mains inputs: ± 1 kV |± 2 kV

77 Temperature of the ball pressur

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals