Drayton RF902 Digistat 3rd Generation Wireless 2-Channel Programmable Thermostat Installation Guide
- June 13, 2024
- Drayton
Table of Contents
Drayton RF902 Digistat 3rd Generation Wireless 2-Channel Programmable
Thermostat
Product Information
Product Name: Digistat 3rd Generation Wireless 2-channel Programmable
Thermostat
Model: RF902
Manufacturer: Drayton Controls
Technical Helpline: Tel: 0333 6000 622
Website: www.draytoncontrols.co.uk
Email:
customer.care@draytoncontrols.co.uk
Product Usage Instructions
Installation of the wallplate
- Loosen the securing screws and remove the wallplate.
- If surface wiring is to be used, snap out the cable entry strip on the bottom edge of the wallplate with a pair of pliers.
- Fix the wallplate with the terminals at the top directly onto the wall, ensuring minimum wallplate clearances.
Installing the Digistat Receiver
- Choose a convenient location for the receiver, close to the boiler or central heating system wiring center.
- Mount the receiver on the wall nearest the final location, ensuring it is not less than 1m from the boiler side panel.
- Avoid installing the receiver too close to metal objects or mains cables, as it may interfere with the radio signal.
Wiring
-
This product is double insulated and does not require an earth connection.
-
Wire the receiver to the combi boiler or central heating wiring using the correct type of cable or flex.
-
Refer to the system or boiler wiring diagrams to replace
hard-wired room or programmable thermostats. -
Always check other manufacturers’ instructions for compatibility.
Pairing guide for the RF902
- Press and hold the cog button for 3 seconds until you see “USEr 01”.
- Press the plus button twice until you see “InSt 03” and press the O button to select.
- You will now see “bEEP 01”, press the minus button twice to reset to “20” and press the O button to select.
- The number will be flashing, press the plus button to see “YEs” flashing. Do not press anything else.
- Go to the receiver and press and hold the left button until the lights flash orange and green, then release.
- Go back to the digistat and press the O button once to liven up the screen and align to select “YEs”.
- “SCAn” will be displayed.
- After a few seconds, a big “CH” will appear on the screen.
- Press the plus button until you see “dHW and CH”, press O, and you will see “PAIr rEC”. All lights will go off on the receiver.
- To test if the pairing has worked, press the plus button on your digistat to call for heat. A green light will be visible on the receiver, indicating the call for heat.
Wireless 2-channel Programmable Thermostat
- Model: RF902
- Consists of Thermostat RF90T and Receiver RF90D
- Technical Helpline Te l: 0333 6000 622
- Website: www.draytoncontrols.co.uk
- Email: customer.care@draytoncontrols.co.uk
- User and Installation Guide 06490311001 Iss E
Installation Guide
Before Installation
If you do not have the knowledge to install the thermostat safely then you
must arrange for a competent electrician to install it for you. Wiring must
conform to the current IEE regulations.
Prior to commencing the installation you must ensure the mains supply is
switched off.
Installing the Digistat Receiver
1a. Location of the receiver
Location
The Digistat Receiver should be mounted in a convenient position, close to
the bolier or central heating system wiring centre. It is recommended that the
receiver is mounted on the wall nearest the final location and not less than
1m from the boiler side panel.
Warning : Installing the receiver too close to metal objects or mains cables may interfere with the radio signal.
Installation of the wallplate
Fixing (minimum wallplate clearances shown below)
- Loosen the securing screws, remove the wallplate, and if surface wiring is to be used, snap out the cable entry strip on the bottom edge of the wallplate with a pair of pliers.
- Fix the wallplate, terminals at the top, either direct onto the flat wall using wall plugs and no 6 x1″ wood screws or on a flush-mounting single conduit box using M3.5 x 14 screws2.
Wiring
This product is double insulated and does not require an earth connection. The
receiver should be wired to the combi boiler or central heating wiring using
the correct type of cable or flex. The receiver should be wired in to replace
hard-wired room or programmable thermostats shown on the system or boiler
wiring diagrams. Always check other manufacturers’ instructions for
compatibility.
Relay Output3
Replace the front cover of the receiver by locating the two latches at the top and then fasten the two screws at the bottom. As soon as the Digistat receiver has power it will be ready for pairing with the Digistat RF Thermostat .
Note: Second channel can be used f or hot water or second heating channel
Pairing guide for the RF902
-
Press and hold cog 3s button until you see USEr 01.
-
Press the plus button twice until you see InSt 03 an press O button to select.
-
You will now see bEEP 01, press minus twice to rSEt 20 and press the O button to select.
-
no will be flashing, press plus button to see YEs is flashing DON’T PRESS ANYTHING ELSE (Go to receiver)
-
Press and hold the left button until the lights flash orange and green, then release. (Go back to digistat)
-
Press the O selected button once to liven up screen and align to select YEs.
-
SCAn will be displayed.
-
After a few seconds you will see a big CH appear on the screen.
-
Press the plus button so you see dHW and CH, press O and you will see PAIr rEC.
All lights will go off on the receiver. -
To test this has worked, press the plus button on your digistat to call for heat,
A green light will be visible on the receiver to indicate the call for heat this means it’s all working.
Two heating Zones
- Pair the First Digistat up to step 8 from above.
- Press the O button to see the big CH on the Digistat, just press O. Do not press + to see dHW.
- It will display SCAn, then PAIr rEc and your first Digistat will be controlled on the right channel on the receiver.
- Pair the second Digistat up to step 7 from above.
- PAIr rEc will be displayed and your second Digistat will be paired to the left channel on the receiver.
- The Digistat is now installed and will automaticly start to control room temperatures and hot water times.
INSTALLER OPTIONS
To make changes to the default Installer Options shown below, enter the
Installer Options menu by pressing the settings button for 3 seconds. This
allows access to the User Menu 01, the Advanced User Settings Menu 02, the
Installer Settings 03, and Service Interval Settings 04. Use the + and –
buttons to scroll to Installer Options and press O to select. You can exit the
menu by pressing until you have returned to the home screen. In the Installer
Options menu (Fig 7), scroll through the options using the + and – buttons and
press O to select. Scroll through the different settings using the + and –
buttons and press O to select and save. (Fig 8shows Option 02 OFF).
(Option 01) Partial Sight Assistant (beep)
When enabled, audible tones indicate when the setpoint is more than, less than
or equal to the current room temperature when a user manually adjusts the
setpoint using the + button: Setpoint > room
- temperature – single high tone per 0.5°C increase
- Setpoint = room temperature – double tone
- Setpoint < room temperature – single low tone per 0.5°C decrease
(Option 02) Frost Protection
The Digistat will switch on the heating if the temperature falls to 5°C and
maintains a temperature of 7°C even when in OFF mode.
(Option 03) Minimum Setpoint Limit
Change minimum setpoint temperature. After any changes to setpoint limits, all
setpoints in AUTO, MANUAL, BOOST and HOLIDAY modes will be modified to conform
accordingly.
(Option 04) Maximum Setpoint Limit
Change maximum setpoint temperature. After any changes to setpoint limits, all
setpoints in AUTO, MANUAL, BOOST and HOLIDAY modes will be modified to conform
accordingly.
(Option 05) Optimum Start
When enabled, this uses current ambient temperature, the next scheduled
setpoint and heat gain data captured by the device to adjust the thermostat
setpoint early, so the ambient temperature is at the required level when the
next event starts.
Delayed Start
When enabled, this uses current ambient temperature, current event setpoint
and heating characteristics of the environment to delay implementation of the
setpoint if the ambient temperature is already close to it, therefore saving
energy.
(Option 06) Valve Protection Time
In some hydronic heating systems it may be required to protect the valve by
operating it for a given time. When enabled, this maintenance feature ensures
that each relay output is operated for at least one (1) minute each week.
(Option 07) Sensor Fault Function
In the event of a sensor fault, central heating output is
reduced to 30% by turning heating ON for 3 minutes, then OFF for 7 minutes.
(Option 08) Application Type
Select the central heating system energy type.
(Option 09) System Capability
(Option 13) Installer Settings Lock
When enabled, installers can lock the installer settings menu until a 3 digit
code is entered. If the code is forgotten while device is locked, please call
the Technical Helpline.
( Option 20) Reset (Service Interval settings are NOT reset) Reset the
Digistat to its original factory settings.
Note that resetting a thermostat will lose the pairing with the receiver.
(Si Option 01) Si Status
Enable or disable Service Interval Mode.
(Si Option 02) Si Type
Select effect imposed on the heating when service is due.
(Si Option 03) Service Due Date
Set date when next service is due.
(Si Option 04) Warning
Select no. of days before service due date.
(Si Option 05) Service Due Alarm
Enable or disable the audible service due alarm.
(Si Option 06) Si Boost
Enable or disable the Service Boost feature (5 boosts).
(Si Option 07) Password Reset
Change the 4 digit PIN. If you forget your Si password, please call the
Technical Helpline.
Technical Data
- Power supply 230VAC +/-10%, 50Hz
- Switch type & rating 3(1)A 230V/50Hz
- current
- Min. recommended SPDT
- 10mA@24VAC (inductive)
- Ambient temperature
- (receiver)
- Operating 0°C to 45°C
- Storage – 20°C to 65°C
- Ambient temperature
- (thermostat)
- Operating 0°C to 40°C
- Storage – 20°C to 65°C
- Ambient humidity
- (non condensing) 20% to 80%, 90% non-condensing
- Temperature range 5°C to 30°C
- Rated impulse voltage 4KV
- Ball pressure test 75°C
- Disconnection means 1B
- Automatic action 100,000 cycles
- Operating Frequency 2402-2480 MHz
- Radio Frequency 433.92 MHz
- +10dBm Max RF Power
- transmitted (Bluetooth)
- Pollution situation Degree 2
- Protection level IP30
- Wiring
- Energy Class IV = 2%
- comply with IEE wiring regulations
- Relevant EC Directives : 2014/53/EU (RED)
- 2011/65/EU (RoHS)
- 2012/19/EU (WEEE)
- Standards : EN 60730-1
- EN 60730-2-7
- EN 60730-2-9
- ESTI EN 300 328
- EN IEC 63000
- ESTI EN 301 489
User Guide
The Drayton Digistat thermostat is a universal thermostat with 24 hour, 5-2day
or 7day program types and up to 8 time/temperature events per day and can also
be used as a simple room thermostat.
Clock Setting
- Press and hold the cog button until User 01 appears,
- Press the plus button to Advanced 02, then press O to enter,
- Press O to enter Time settings,
- Using the + and – you can adjust the time, then pess O to save,
- Press the cog button twice to bring you back to the home screen.
General Operation
Programmable thermostats do not have “On” and “Off” times like traditional
timers. They offer temperature control both day and night and you simply
select which temperatures you require at each point in the day.
With the unit in “Auto Mode” (the calendar icon is visible at the bottom of
the screen) the temperature can be changed for a short time by using the + and
– buttons. Changing the temperature in this way will keep the Digistat set to
your new temperature until the next pre-programmed event (at which time it
will revert to programmed temperature). The temperature you are setting will
flash on the screen. Once temperature is set, the unit will revert to showing
the room temperature again. The indicator will show on the screen if the unit
is calling for heat.
Programming the Digistat
Your Digistat comes with the following settings pre-programmed for your
convenience and is suitable for those working out of the house during a
typical 9-5 pattern. When the 5-2day program type is selected the pre-set
temperatures will be different Mon-Fri and Sat-Sun, as per the tables below
Pre-set Program 1 (24h, 5-2day weekdays, or 7day)
Pre-set Program 1 (5-2day weekend)
To add these additional time periods manually (max. 8 per day) please refer to
the steps to the right.
The Bluetooth® word mark and logos are registered trademarks owned by
Bluetooth SIG, Inc. and any use of such marks by Schneider Electric is under
license. Other trademarks and trade names are those of their respective
owners.
Hereby, Schneider Electric Controls UK Ltd, declares that Digistat RF902 is in compliance with Directive 2014/53/EU. The declaration of conformity may be consulted at www.draytoncontrols.co.uk
Setting up Times/Temperatures on the Digistat
- With the product operating as normal in Auto Mode, press once. Use + and – to select the day or set of days you want to adjust the times and temperatures for. Press O to confirm.
- The time on the display will now be f ashing as shown, use + and – to adjust the first period start time. Press O to confirm.
- Once the time has been set the temperature on the display will now be f ashing, use + and – to adjust the temperature for the first time period. Press O to confirm.
- Move to the next time and temperature periods and adjust as needed, confirming the changes by pressing O. The new schedule will be saved pressing O when the word SAvE is f ashing.
- In Pre-set Program 1 you will have 4 time periods available, to add more (max. 8 per day) press + when you see the SAVE option on-screen and time period 5 at the bottom of the screen, to scroll to the Add option. Press O to add time period then adjust time and temperature as required.
- To exit press to go back until you return to the home screen.
Heating or Hot Water
- Press the cog button so the tap or radiator symbol in the bottom left-hand corner starts to flash,
- Press the + button to change between the options, then press O to select your option.
Automatic to Manual
- Press and hold the Cog button until you see USEr 01,
- Press the O button to select and you will see Mode,
- Press O to enter and you will see either Auto, man or off.
- Use the + and – button to choose between these options.
- Press the O button to select your option then press the Cog buton twice to take you to the home page.
Where to find User Guide
Please use the QR code to the right or go to our website
www.draytoncontrols.co.uk to download our
full online user guide which also features Bluetooth pairing, and how to use
the smartphone app.
- 401 Southway Drive Plymouth
- PL6 6QT
- United Kingdom
- Schneider Electric Industries SAS 35 rue Joseph Monier
- F-92500 Rueil-Malmaison France
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>