NuTone FG7TE Series Smartlite Two Stage Fixed Speed ECM High Efficiency Upflow Gas Furnace Owner’s Manual

May 15, 2024
NuTone

NuTone FG7TE Series Smartlite Two Stage Fixed Speed ECM High Efficiency Upflow Gas Furnace Owner’s Manual

FEATURES and BENEFITS

  • Multi-speed Direct Drive Blower: Energy-efficient brushless DC (ECM) fixed-speed motor offers 16 speeds designed to give a wide range of cooling capacities.
  • SmartLite® Technology: Auto-adjusts igniter on time to extend igniter life.
  • Hot Surface Igniter: Innovative application of a silicon nitride type igniter.
  • 30 Second Blower Delay: At start-up assures a warm duct temperature at furnace start-up. Adjustable blower off settings (60, 90, 120 and 180 seconds).
  • 30 Second Post Purge: Increases life of heat exchanger.
  • 60 Second Fixed Cooling Cycle Blower-Off Delay (TDR): Increases cooling performance when matched with a Nortek Global HVAC coil.
  • Color Coded Wire Harness: Designed to fit the components, all with quick-connect fittings for ease of service and replacement.
  • Diagnostic Lights: Dedicated light for flame signal strength and 2 lights in combination to indicate all other fault codes with easy to recognize states without counting flashes.
  • Integrated Control Boards: With connections for electronic air cleaner, humidifier, and dehumidification. Ergonomically located for ease of service.
  • 2 Stage Inducer: Optimizes efficiency on first stage heat and reduces sound levels.
  • Heat Exchanger: Heavy gauge aluminized steel primary heat exchanger and stainless steel secondary heat exchanger assures a long life.
  • 100% Fired and Tested: All units and each component are tested on the manufacturing line.
  • Best Packaging in the Industry: Unique corner post design assures product will arrive to the homeowner dent free.
  • Flexible Category IV Venting System: May be vertically or horizontally vented using either a one-pipe or two-pipe system for maximum flexibility in installation.
  • Low Boy Height: Easy to apply in low ceiling applications, works well with taller high SEER coils, easier to handle and install.
  • LP Convertible: Simple burner orifice and regulator spring change for ease of convertibility (as an accessory).
  • Two Piece Door Design: Enhances furnace appearance and uses captured screws to prevent losing door screws.
  • Blower Compartment: Sealed door to reduce air leakage and insulated for ultra quiet operation.
  • Sealed Vestibule: Reduces burner and inducer sound levels.
  • Furnace Air Leakage: These furnaces comply with Energy Star cabinet air leakage requirement of less than or equal to 2%. Keep the conditioned air flowing to where it’s needed.

LOCATION OF COMPONENTS

DIMENSIONS

TOP VIEW

**BOTTOM VIEW


**

MODEL IDENTIFICATION CODE

SPECIFICATIONS

FG7TE MODEL NUMBERS| -035D-E23A1| -060D-E24B1| -080D- E35C1| -100D-E35C1| -115D-E45D1
---|---|---|---|---|---
Input – Btuh (a)| 35000 / 23000| 60000 / 39000| 80000 / 52000| 100000 / 65000| 115000 / 74750
Heating Capacity – BtuH| 33000 / 22000| 58000 / 37000| 77000 / 50000| 96000 / 62000| 110000 / 72000
AFUE| 96.0| 96.0| 96.0| 96.0| 96.0
Motor H.P. – Speed – Type| 1/2 – BLDC| 3/4 – BLDC| 1 – BLDC| 1 – BLDC| 1 – BLDC
Motor FLA| 6.9| 8.8| 11.5| 11.5| 11.5
Rated Ext. SP – In. W.C.| 0.50| 0.50| 0.50| 0.50| 0.50
Temperature Rise Range – F| 30-60| 30-60| 30-60| 35-65| 40-70
Shipping Weights| 101 lb| 120 lb| 130 lb| 135 lb| 145 lb
SKU| 1037159F| 1025958F| 1025959F| 1025960F| 1025961F

Note:
All models are 115V, 60 Hz. Gas Connections are 1/2″ N.P.T. AFUE = Annual Fuel Utilization Efficiency
(a) Ratings to 2,000 ft. Over 2,000 ft. reduce 4% for each 1,000 ft. above sea level.

BLOWER PERFORMANCE

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)

Model Number/ Heating Input| MOTOR SWITCH SETTINGS (0=OFF, 1=ON)| External Static Pressure (in.w.c.)
0.1| 0.2| 0.3| 0.4| 0.5
1| 2| 3| 4| CFM| RISE| CFM| RISE| CFM| RISE| CFM| RISE| CFM| RISE

G7TE-035D-E23A1 35,000 BTU/hr

| 0| 0| 0| 0| | | | | | | | | |
1| 0| 0| 0| 560| 56| 515| 60| | | | | |
0| 1| 0| 0| 570| 55| 540| 58| | | | | |
1| 1| 0| 0| 670| 46| 635| 49| 595| 52| 565| 55| 525| 59
0| 0| 1| 0| 700| 44| 670| 46| 635| 49| 600| 52| 565| 55
1| 0| 1| 0| 765| 41| 725| 43| 690| 45| 660| 47| 625| 50
0| 1| 1| 0| 795| 39| 755| 41| 720| 43| 690| 45| 650| 48
1| 1| 1| 0| 845| 37| 810| 38| 775| 40| 740| 42| 705| 44
0| 0| 0| 1| 895| 35| 860| 36| 825| 38| 790| 39| 760| 41
1| 0| 0| 1| 905| 34| 870| 36| 840| 37| 805| 39| 770| 40
0| 1| 0| 1| 950| 33| 920| 34| 885| 35| 850| 37| 820| 38
1| 1| 0| 1| 990| 31| 955| 33| 925| 34| 890| 35| 860| 36
0| 0| 1| 1| 1010| 31| 980| 32| 945| 33| 910| 34| 885| 35
1| 0| 1| 1| 1050| 30| 1015| 31| 985| 32| 955| 33| 925| 34
0| 1| 1| 1| | | 1045| 30| 1020| 31| 990| 31| 960| 32
1| 1| 1| 1| | | | | | | | | |

COOLING AIRFLOW (CFM)


Model Number/ Heating Input| MOTOR SWITCH SETTINGS (0=OFF, 1=ON)| External Static Pressure (in.w.c.)
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
5| 6| 7| 8| CFM| CFM| CFM| CFM| CFM| CFM| CFM| CFM

G7TE-035D-E23A1 35,000 BTU/hr

| 0| 0| 0| 0| | | | | | | |
1| 0| 0| 0| 560| 515| 475| | | | |
0| 1| 0| 0| 570| 540| 505| 460| | | |
1| 1| 0| 0| 670| 635| 595| 565| 525| 485| |
0| 0| 1| 0| 700| 670| 635| 600| 565| 530| 485|
1| 0| 1| 0| 765| 725| 690| 660| 625| 585| 550| 510
0| 1| 1| 0| 795| 755| 720| 690| 650| 615| 580| 545
1| 1| 1| 0| 845| 810| 775| 740| 705| 675| 640| 600
0| 0| 0| 1| 895| 860| 825| 790| 760| 725| 695| 660
1| 0| 0| 1| 905| 870| 840| 805| 770| 740| 700| 670
0| 1| 0| 1| 950| 920| 885| 850| 820| 785| 760| 720
1| 1| 0| 1| 990| 955| 925| 890| 860| 830| 800| 765
0| 0| 1| 1| 1010| 980| 945| 910| 885| 850| 820| 790
1| 0| 1| 1| 1050| 1015| 985| 955| 925| 895| 865| 830
0| 1| 1| 1| 1080| 1045| 1020| 990| 960| 930| 895| 865
1| 1| 1| 1| 1105| 1075| 1045| 1015| 985| 955| 920| 895

NOTES :

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only)

BLOWER PERFORMANCE (Continued)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)

Model Number/ Heating Input| MOTOR SWITCH SETTINGS (0=OFF, 1=ON)| External Static Pressure (in.w.c.)
0.1| 0.2| 0.3| 0.4| 0.5
1| 2| 3| 4| CFM| RISE| CFM| RISE| CFM| RISE| CFM| RISE| CFM| RISE

G7TE-060D-E24B1 60,000 BTU/hr

| 0| 0| 0| 0| | | | | | | | | |
1| 0| 0| 0| | | | | | | | | |
0| 1| 0| 0| | | | | | | | | |
1| 1| 0| 0| | | | | | | | | |
0| 0| 1| 0| | | | | | | | | |
1| 0| 1| 0| 940| 57| 890| 60| | | | | |
0| 1| 1| 0| 990| 54| 945| 56| 905| 59| | | |
1| 1| 1| 0| 1,055| 51| 1,015| 53| 970| 55| 930| 57| 890| 60
0| 0| 0| 1| 1,135| 47| 1,095| 49| 1,055| 51| 1,010| 53| 960| 56
1| 0| 0| 1| 1,185| 45| 1,145| 47| 1,105| 48| 1,065| 50| 1,030| 52
0| 1| 0| 1| 1,250| 43| 1,210| 44| 1,170| 46| 1,135| 47| 1,095| 49
1| 1| 0| 1| 1,290| 41| 1,255| 42| 1,220| 44| 1,180| 45| 1,145| 47
0| 0| 1| 1| 1,315| 41| 1,275| 42| 1,240| 43| 1,200| 44| 1,160| 46
1| 0| 1| 1| 1,350| 40| 1,315| 41| 1,280| 42| 1,245| 43| 1,205| 44
0| 1| 1| 1| 1,390| 38| 1,350| 40| 1,315| 41| 1,275| 42| 1,240| 43
1| 1| 1| 1| | | | | | | | | |

COOLING AIRFLOW (CFM)


Model Number/ Heating Input| MOTOR SWITCH SETTINGS (0=OFF, 1=ON)| External Static Pressure (in.w.c.)
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
5| 6| 7| 8| CFM| CFM| CFM| CFM| CFM| CFM| CFM| CFM

G7TE-060D-E24B1 60,000 BTU/hr

| 0| 0| 0| 0| | | | | | | |
1| 0| 0| 0| | | | | | | |
0| 1| 0| 0| | | | | | | |
1| 1| 0| 0| 725| | | | | | |
0| 0| 1| 0| 810| | | | | | |
1| 0| 1| 0| 940| 890| 845| 795| 750| 700| |
0| 1| 1| 0| 990| 945| 905| 860| 820| 775| 735| 690
1| 1| 1| 0| 1,055| 1,015| 970| 930| 890| 845| 805| 760
0| 0| 0| 1| 1,135| 1,095| 1,055| 1,010| 960| 930| 890| 850
1| 0| 0| 1| 1,185| 1,145| 1,105| 1,065| 1,030| 990| 950| 910
0| 1| 0| 1| 1,250| 1,210| 1,170| 1,135| 1,095| 1,055| 1,020| 980
1| 1| 0| 1| 1,290| 1,255| 1,220| 1,180| 1,145| 1,110| 1,075| 1,040
0| 0| 1| 1| 1,315| 1,275| 1,240| 1,200| 1,160| 1,120| 1,085| 1,045
1| 0| 1| 1| 1,350| 1,315| 1,280| 1,245| 1,205| 1,170| 1,135| 1,100
0| 1| 1| 1| 1,390| 1,350| 1,315| 1,275| 1,240| 1,200| 1,160| 1,125
1| 1| 1| 1| 1,420| 1,380| 1,345| 1,310| 1,270| 1,235| 1,200| 1,160

NOTES:

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

BLOWER PERFORMANCE (Continued)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)

Model Number/ Heating Input| MOTOR SWITCH SETTINGS (0=OFF, 1=ON)| External Static Pressure (in.w.c.)
0.1| 0.2| 0.3| 0.4| 0.5
1| 2| 3| 4| CFM| RISE| CFM| RISE| CFM| RISE| CFM| RISE| CFM| RISE

FG7TE-080D-E35C1 80,000 BTU/hr

| 0| 0| 0| 0| 1,125| 63| | | | | | | |
1| 0| 0| 0| 1,205| 59| 1,120| 63| | | | | |
0| 1| 0| 0| 1,305| 54| 1,225| 58| 1,150| 62| | | |
1| 1| 0| 0| 1,430| 50| 1,350| 53| 1,270| 56| 1,190| 60| 1,110| 63
0| 0| 1| 0| 1,525| 47| 1,450| 49| 1,375| 52| 1,300| 55| 1,225| 57
1| 0| 1| 0| 1,620| 44| 1,540| 46| 1,465| 49| 1,390| 51| 1,315| 54
0| 1| 1| 0| 1,695| 42| 1,620| 44| 1,545| 46| 1,465| 49| 1,390| 51
1| 1| 1| 0| 1,770| 40| 1,700| 42| 1,630| 44| 1,555| 46| 1,485| 47
0| 0| 0| 1| 1,875| 38| 1,805| 39| 1,730| 41| 1,655| 43| 1,580| 45
1| 0| 0| 1| 1,905| 37| 1,840| 39| 1,775| 40| 1,710| 42| 1,640| 43
0| 1| 0| 1| 1,980| 36| 1,910| 37| 1,845| 39| 1,780| 40| 1,715| 41
1| 1| 0| 1| 2,025| 35| 1,960| 36| 1,895| 38| 1,830| 39| 1,765| 40
0| 0| 1| 1| | | 2,025| 35| 1,960| 36| 1,900| 37| 1,840| 38
1| 0| 1| 1| | | | | 2,010| 35| 1,945| 37| 1,880| 37
0| 1| 1| 1| | | | | | | 2,035| 35| 1,980| 36
1| 1| 1| 1| | | | | | | | | |
COOLING AIRFLOW (CFM)

Model Number/ Heating Input| MOTOR SWITCH SETTINGS (0=OFF, 1=ON)| External Static Pressure (in.w.c.)
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
5| 6| 7| 8| CFM| CFM| CFM| CFM| CFM| CFM| CFM| CFM

FG7TE-080D-E35C1 80,000 BTU/hr

| 0| 0| 0| 0| 1,125| 1,040| 960| 880| 795| | |
1| 0| 0| 0| 1,205| 1,120| 1,040| 960| 875| 795| |
0| 1| 0| 0| 1,305| 1,225| 1,150| 1,070| 995| 915| 840|
1| 1| 0| 0| 1,430| 1,350| 1,270| 1,190| 1,110| 1,030| 950| 865
0| 0| 1| 0| 1,525| 1,450| 1,375| 1,300| 1,225| 1,150| 1,075| 1,000
1| 0| 1| 0| 1,620| 1,540| 1,465| 1,390| 1,315| 1,240| 1,165| 1,090
0| 1| 1| 0| 1,695| 1,620| 1,545| 1,465| 1,390| 1,315| 1,235| 1,160
1| 1| 1| 0| 1,770| 1,700| 1,630| 1,555| 1,485| 1,410| 1,340| 1,265
0| 0| 0| 1| 1,875| 1,805| 1,730| 1,655| 1,580| 1,510| 1,435| 1,340
1| 0| 0| 1| 1,905| 1,840| 1,775| 1,710| 1,640| 1,575| 1,510| 1,445
0| 1| 0| 1| 1,980| 1,910| 1,845| 1,780| 1,715| 1,650| 1,580| 1,515
1| 1| 0| 1| 2,025| 1,960| 1,895| 1,830| 1,765| 1,700| 1,635| 1,570
0| 0| 1| 1| 2,085| 2,025| 1,960| 1,900| 1,840| 1,775| 1,715| 1,655
1| 0| 1| 1| 2,135| 2,070| 2,010| 1,945| 1,880| 1,815| 1,750| 1,685
0| 1| 1| 1| 2,200| 2,145| 2,090| 2,035| 1,980| 1,925| 1,870| 1,820
1| 1| 1| 1| 2,280| 2,225| 2,170| 2,115| 2,065| 2,010| 1,955| 1,900

NOTES:

  1.  Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2.  To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3.  Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5.  Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6.  To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7.  When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

BLOWER PERFORMANCE (Continued)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)

Model Number/ Heating Input| MOTOR SWITCH SETTINGS (0=OFF, 1=ON)| External Static Pressure (in.w.c.)
0.1| 0.2| 0.3| 0.4| 0.5
1| 2| 3| 4| CFM| RISE| CFM| RISE| CFM| RISE| CFM| RISE| CFM| RISE

FG7TE-100D-E35C1 100,000 BTU/hr

| 0| 0| 0| 0| | | | | | | | | |
1| 0| 0| 0| | | | | | | | | |
0| 1| 0| 0| | | | | | | | | |
1| 1| 0| 0| | | | | | | | | |
0| 0| 1| 0| | | | | | | | | |
1| 0| 1| 0| 1,620| 55| 1,540| 58| | | | | |
0| 1| 1| 0| 1,695| 52| 1,620| 55| 1,545| 58| | | |
1| 1| 1| 0| 1,770| 50| 1,700| 52| 1,630| 55| 1,555| 57| 1,485| 60
0| 0| 0| 1| 1,875| 47| 1,805| 49| 1,730| 51| 1,655| 54| 1,580| 56
1| 0| 0| 1| 1,905| 47| 1,840| 48| 1,775| 50| 1,710| 52| 1,640| 54
0| 1| 0| 1| 1,980| 45| 1,910| 47| 1,845| 48| 1,780| 50| 1,715| 52
1| 1| 0| 1| 2,025| 44| 1,960| 45| 1,895| 47| 1,830| 49| 1,765| 50
0| 0| 1| 1| 2,085| 43| 2,025| 44| 1,960| 45| 1,900| 47| 1,840| 48
1| 0| 1| 1| 2,135| 42| 2,070| 43| 2,010| 44| 1,945| 46| 1,880| 47
0| 1| 1| 1| | | | | | | | | |
1| 1| 1| 1| | | | | | | | | |
COOLING AIRFLOW (CFM)

Model Number/ Heating Input

| MOTOR SWITCH SETTINGS (0=OFF, 1=ON)| External Static Pressure (in.w.c.)
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
5| 6| 7| 8| CFM| CFM| CFM| CFM| CFM| CFM| CFM| CFM

FG7TE-100D-E35C1 100,000 BTU/hr

| 0| 0| 0| 0| 1,125| 1,040| | | | | |
1| 0| 0| 0| 1,205| 1,120| 1,040| | | | |
0| 1| 0| 0| 1,305| 1,225| 1,150| 1,070| 995| | |
1| 1| 0| 0| 1,430| 1,350| 1,270| 1,190| 1,110| 1,030| |
0| 0| 1| 0| 1,525| 1,450| 1,375| 1,300| 1,225| 1,150| 1,075| 1,000
1| 0| 1| 0| 1,620| 1,540| 1,465| 1,390| 1,315| 1,240| 1,165| 1,090
0| 1| 1| 0| 1,695| 1,620| 1,545| 1,465| 1,390| 1,315| 1,235| 1,160
1| 1| 1| 0| 1,770| 1,700| 1,630| 1,555| 1,485| 1,410| 1,340| 1,265
0| 0| 0| 1| 1,875| 1,805| 1,730| 1,655| 1,580| 1,510| 1,435| 1,340
1| 0| 0| 1| 1,905| 1,840| 1,775| 1,710| 1,640| 1,575| 1,510| 1,445
0| 1| 0| 1| 1,980| 1,910| 1,845| 1,780| 1,715| 1,650| 1,580| 1,515
1| 1| 0| 1| 2,025| 1,960| 1,895| 1,830| 1,765| 1,700| 1,635| 1,570
0| 0| 1| 1| 2,085| 2,025| 1,960| 1,900| 1,840| 1,775| 1,715| 1,655
1| 0| 1| 1| 2,135| 2,070| 2,010| 1,945| 1,880| 1,815| 1,750| 1,685
0| 1| 1| 1| 2,200| 2,145| 2,090| 2,035| 1,980| 1,925| 1,870| 1,820
1| 1| 1| 1| 2,280| 2,225| 2,170| 2,115| 2,065| 2,010| 1,955| 1,900

BLOWER PERFORMANCE (Continued)

HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)

Model Number/ Heating Input| MOTOR SWITCH SETTINGS (0=OFF, 1=ON)| External Static Pressure (in.w.c.)
0.1| 0.2| 0.3| 0.4| 0.5
1| 2| 3| 4| CFM| RISE| CFM| RISE| CFM| RISE| CFM| RISE| CFM| RISE

FG7TE-115D-E45D1 115,000 BTU/hr

| 0| 0| 0| 0| | | | | | | | | |
1| 0| 0| 0| | | | | | | | | |
0| 1| 0| 0| | | | | | | | | |
1| 1| 0| 0| | | | | | | | | |
0| 0| 1| 0| | | | | | | | | |
1| 0| 1| 0| 1,760| 58| 1,715| 60| | | | | |
0| 1| 1| 0| 1,835| 56| 1,790| 57| 1,745| 59| | | |
1| 1| 1| 0| 1,885| 54| 1,840| 56| 1,790| 57| 1,745| 59| 1,700| 60
0| 0| 0| 1| 1,945| 53| 1,900| 54| 1,850| 55| 1,805| 57| 1,760| 58
1| 0| 0| 1| 1,950| 52| 1,905| 54| 1,860| 55| 1,820| 56| 1,775| 58
0| 1| 0| 1| 2,075| 49| 2,030| 50| 1,990| 51| 1,945| 53| 1,900| 54
1| 1| 0| 1| 2,125| 48| 2,085| 49| 2,040| 50| 2,000| 51| 1,955| 52
0| 0| 1| 1| 2,170| 47| 2,130| 48| 2,090| 49| 2,045| 50| 2,005| 51
1| 0| 1| 1| 2,215| 46| 2,180| 47| 2,140| 48| 2,105| 49| 2,070| 49
0| 1| 1| 1| | | | | | | | | |
1| 1| 1| 1| | | | | | | | | |
COOLING AIRFLOW (CFM)

Model Number/ Heating Input| MOTOR SWITCH SETTINGS (0=OFF, 1=ON)| External Static Pressure (in.w.c.)
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
5| 6| 7| 8| CFM| CFM| CFM| CFM| CFM| CFM| CFM| CFM

FG7TE-115D-E45D1 115,000 BTU/hr

| 0| 0| 0| 0| 1,395| 1,350| 1,305| 1,260| 1,210| 1,165| 1,120|
1| 0| 0| 0| 1,465| 1,420| 1,375| 1,330| 1,290| 1,245| 1,200| 1,155
0| 1| 0| 0| 1,555| 1,510| 1,470| 1,425| 1,380| 1,340| 1,295| 1,250
1| 1| 0| 0| 1,625| 1,585| 1,540| 1,500| 1,460| 1,415| 1,375| 1,335
0| 0| 1| 0| 1,690| 1,650| 1,610| 1,570| 1,530| 1,485| 1,445| 1,405
1| 0| 1| 0| 1,760| 1,715| 1,670| 1,625| 1,575| 1,530| 1,485| 1,440
0| 1| 1| 0| 1,835| 1,790| 1,745| 1,695| 1,650| 1,605| 1,555| 1,510
1| 1| 1| 0| 1,885| 1,840| 1,790| 1,745| 1,700| 1,655| 1,610| 1,565
0| 0| 0| 1| 1,945| 1,900| 1,850| 1,805| 1,760| 1,710| 1,665| 1,620
1| 0| 0| 1| 1,950| 1,905| 1,860| 1,820| 1,775| 1,735| 1,690| 1,650
0| 1| 0| 1| 2,075| 2,030| 1,990| 1,945| 1,900| 1,855| 1,810| 1,770
1| 1| 0| 1| 2,125| 2,085| 2,040| 2,000| 1,955| 1,910| 1,870| 1,825
0| 0| 1| 1| 2,170| 2,130| 2,090| 2,045| 2,005| 1,965| 1,925| 1,880
1| 0| 1| 1| 2,215| 2,180| 2,140| 2,105| 2,070| 2,035| 2,000| 1,965
0| 1| 1| 1| | | | | 2,225| 2,165| 2,100| 2,040
1| 1| 1| 1| | | | | | 2,170| 2,120| 2,065

NOTES:

  1. Motor switch settings for heating speeds use HEAT switches 1, 2, 3, & 4 and for cooling speeds use COOL switches 5, 6, 7, & 8.
  2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  3. Data is shown without filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  7. When in low stage heat, the airflow is approximately 70% of the tables high value (2-stage furnaces only).

VENTING

All models are approved for vertical non direct (1 pipe) and direct (2 pipe) venting applications. See Vent Table below for specified sizes and allowable lengths.

FURNACE MODELS (BTU)

|

FURNACE INSTALLATION

| SINGLE PIPE LENGTH (FT.) with 1 long radius elbow**| DIRECT VENT, DUAL PIPE LENGTH (ft.) WITH 1 long radius elbow on each pipe**
---|---|---|---
OUTLET| OUTLET| INLET/OUTLET| INLET/OUTLET
2” Diameter| 3” Diameter| 2” Diameter| 3” Diameter
35,000| Upflow| 60| 90| 60| 90
60,000| Upflow| 60| 90| 60| 90
80,000| Upflow| 40| 90| 40| 90
100,000| Upflow| 30| 90| 30| 90
115,000| Upflow| N/A| 90| N/A| 90

NOTES:

  1.  Subtract 2.5 ft. for each additional 2 inch long radius elbow, 5 ft. for each additional 2 inch short radius elbow, 3.5 ft. for each additional 3 inch
    long radius elbow, and 7 ft. for each additional 3 inch short radius elbow. Subtract 5ft for each 2” tee and 8ft for each 3” tee.

  2. Two 45 degree elbows are equivalent to one 90 degree elbow.

  3. This table applies for elevations from sea level to 2,000 ft. For higher elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.

ACCESSORIES

FG7TE KITS

Description| SKU
2″ Concentric Vent Kit (US & Canada Approved)| 904952
3″ Concentric Vent Kit (US & Canada Approved)| 904953
2″ Side Wall Vent Kit| 904617
3″ Side Wall Vent Kit| 904347
U.S. LP Conversion Kit (0 to 10,000 ft.)| 905028
Canada LP Conversion Kit (0 to 4,500 ft.)| 905029
Bottom Return Filter 20 per Box, “B” Cabinet| 904916
Bottom Return Filter 20 per Box, “D” Cabinet| 904918
Side Return Filter Kit| 541036
Neutralizer Kit| 902377

GENERAL TERMS OF LIMITED WARRANTY

Nortek Global HVAC, LLC will furnish a replacement for any part of this product which fails in normal use and service within the terms and conditions of the warranty.

For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or
contact the Nortek Global HVAC, LLC warranty department for a copy

Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (11/2021)

www.nutonehvac.com

NuTone® trademark used under license. © Nortek Global HVAC, LLC. All Rights Reserved.