RenewAire MC-C Ceiling Mount Occupancy Sensor Installation Guide

June 15, 2024
RenewAire

RenewAire MC-C Ceiling Mount Occupancy Sensor Installation Guide
RenewAire MC-C Ceiling Mount Occupancy Sensor

OVERVIEW

SPECIFICATIONS

  • Passive infared sensor
  • Adjustable time-off delay to 30 minutes
  • 24VAC power requirement
  • Ceiling mount or directable wall mount
  • Coverage floor space
    • Ceiling mount: 1500 sq. ft.
    • Wall mount: 2500 sq. ft.
  • Major motion area
    • Ceiling mount: 50 ft. diameter
    • Wall mount: 68 x 50 ft.
      Model| Volts| Current| Isolated Relay| Coverage Area| Suggested Mounting Height
      ---|---|---|---|---|---
      MC-C| 15-28VAC| 30 mA| 1 A @ 30 VAC/DC| 1500 sq. ft.| 8-10 ft.
      MC-W| 15-28VAC| 30 mA| 1 A @ 30 VAC/DC| 2500 sq. ft.| 8-10 ft.

INSTALLATION

MC-C CEILING MOUNT

See the Leviton installation instructions provided in the original box for in- details or for more options.
Installation Instruction
FIGURE 2.1.0 MC-C CEILING MOUNT INSTALLATION

MC-W WALL MOUNT
Installation Instruction
FIGURE 2.2.0 MC-W WALL MOUNT INSTALLATION

SETTINGS

ADJUSTMENT KNOBS

KNOB COLOR| SYMBOL| FUNCTION| KNOB SETTING| FACTORY DEFAULT SETTING
---|---|---|---|---
Red| ****| Sets the infrared range| Range SettingFull CCW = min. (OFF) Full CW = max.| 75%

Black| ****| Delayed-Off Time| Full CCW = min. (30 sec.) Full CW = max. (30 min.)| 50%(10 min.)

FIGURE 3.1.0 KNOB ADJUSTMENT TABLE

Adjust Knobs
FIGURE 3.1.1 INFRARED RANGE ADJUSTMENT
Adjust Knobs
FIGURE 3.1.2 DELAYED—OFF TIME ADJUSTMENT

DIP SWITCHES

Switch Switch Functions Switch Settings
Bank A OFF ON
A1 N/A N/A
A2 N/A N/A
A3 Manual Mode Auto Adapting Enabled
A4 Walk-Through Disabled Walk-Through Enabled
Bank B OFF ON
B1 Override to ON Auto Mode
B2 Override to OFF Auto Mode
B3 Test Mode OFF ¢ ON ¢ OFF = Enter/Exit Test Mode
B4 LEDs Disabled LEDs Enabled

FIGURE 3.2.0 DIP SWITCH SETTING TABLE

Adjust Knobs
FIGURE 3.2.1 MC-C DIP SWITCHES
Adjust Knobs
FIGURE 3.2.2 MC-W DIP SWITCHES

ELECTRICAL

WIRING SCHEMATICS
Electrical Connection
FIGURE 4.1.0 EV90, EV90P, EV130, EV200, AND EV300 SCHEMATIC

In this example, Motion Control Occupancy Sensor turns Energy Recovery Ventilator (ERV) on at High speed when space is occupied.
Electrical Connection
FIGURE 4.1.1 EV PREMIUM AND SL75 SCHEMATIC
Electrical Connection
FIGURE 4.1.2 HE1.5IN—STANDARD WIRING (NON-ECM) SCHEMATIC
Electrical Connection
FIGURE 4.1.3 HE1.5IN-MOTORIZED DAMPER(S) OR INDEPENDENT BLOWER CONTROL SCHEMATIC
Electrical Connection
FIGURE 4.1.3 HE1.5IN-MOTORIZED DAMPER(S) OR INDEPENDENT BLOWER CONTROL SCHEMATIC
Electrical Connection
FIGURE 4.1.5 HE1.5RT-MOTORIZED DAMPER(S) OR INDEPENDENT BLOWER CONTROL SCHEMATIC
Electrical Connection
FIGURE 4.1.6 HE2X-8X, LE6X-10X-WITH STANDARD WIRING OR MOTORIZED DAMPER(S) SCHEMATIC
Electrical Connection
FIGURE 4.1.7 HE1.5-ECM WITH TERMINAL BLOCK (SPEED 1-LOW SPEED ON/OFF) SCHEMATIC

In this example, Motion Control Occupancy Sensor turns the ERV on at speed set by potentiometers when space is occupied. Electrical
Connection
FIGURE 4.1.8 HE07, HE10, AND HE1.5—ECM WITH CIRCUIT BOARD (SPEED 1-LOW SPEED ON/OFF) SCHEMATIC

Electrical Connection
FIGURE 4.1.9 RH-W HEATER ACCESSORY THERMOSTAT SCHEMATIC

FACTORY ASSISTANCE

In the unlikely event that you need assistance from the factory for a specific issue, make sure that you have the information called for in the Unit Records page in the Owner Information section of the unit manual. The person you speak with at the factory will need that information to properly identify the unit and the installed options.

To contact RenewAire Customer Service:

Call800-627-4499
Email: RenewAireSupport@RenewAire.com

About RenewAire

For over 40 years, RenewAire has been a pioneer in enhancing indoor air quality (IAQ) in commercial and residential buildings of every size. This is achieved while maximizing sustainability through our fifth-generation, static- plate, enthalpic-core Energy Recovery Ventilators (ERVs) that optimize energy efficiency, lower capital costs via load reduction and decrease operational expenses by minimizing equipment needs, resulting in significant energy savings. Our ERVs are competitively priced, simple to install, easy to use and maintain and have a quick payback. They also enjoy the industry’s best warranty with the lowest claims due to long-term reliability derived from innovative design practices, expert workmanship and Quick

Response Manufacturing (QRM).

As the pioneer of static-plate core technology in North America, RenewAire is the largest ERV producer in the USA. We’re committed to sustainable manufacturing and lessening our environmental footprint, and to that end our Waunakee, WI plant is 100% powered by wind turbines. The facility is also one of the few buildings worldwide to be LEED and Green Globes certified, as well as having achieved ENERGY STAR Building status. In 2010, Renew Aire joined the Soler & Palau (S&P) Ventilation Group in order to provide direct access to the latest in energy efficient air-moving technologies. For more information,
visit: renewaire.com

Member of the S&P Group
Family of Brands

2023 © RenewAire LLC
138280_007_NOV23

RenewAire Logo

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals