RenewAire MC-C Ceiling Mount Occupancy Sensor Installation Guide
- June 15, 2024
- RenewAire
Table of Contents
RenewAire MC-C Ceiling Mount Occupancy Sensor Installation Guide
OVERVIEW
SPECIFICATIONS
- Passive infared sensor
- Adjustable time-off delay to 30 minutes
- 24VAC power requirement
- Ceiling mount or directable wall mount
- Coverage floor space
- Ceiling mount: 1500 sq. ft.
- Wall mount: 2500 sq. ft.
- Major motion area
- Ceiling mount: 50 ft. diameter
- Wall mount: 68 x 50 ft.
Model| Volts| Current| Isolated Relay| Coverage Area| Suggested Mounting Height
---|---|---|---|---|---
MC-C| 15-28VAC| 30 mA| 1 A @ 30 VAC/DC| 1500 sq. ft.| 8-10 ft.
MC-W| 15-28VAC| 30 mA| 1 A @ 30 VAC/DC| 2500 sq. ft.| 8-10 ft.
INSTALLATION
MC-C CEILING MOUNT
See the Leviton installation instructions provided in the original box for in-
details or for more options.
FIGURE 2.1.0 MC-C CEILING MOUNT INSTALLATION
MC-W WALL MOUNT
FIGURE 2.2.0 MC-W WALL MOUNT INSTALLATION
SETTINGS
ADJUSTMENT KNOBS
KNOB COLOR| SYMBOL| FUNCTION| KNOB SETTING|
FACTORY DEFAULT SETTING
---|---|---|---|---
Red| ****| Sets the infrared range| Range SettingFull CCW = min. (OFF) Full
CW = max.| 75%
Black| ****| Delayed-Off Time| Full CCW = min. (30 sec.) Full CW = max. (30 min.)| 50%(10 min.)
FIGURE 3.1.0 KNOB ADJUSTMENT TABLE
FIGURE 3.1.1 INFRARED RANGE ADJUSTMENT
FIGURE 3.1.2 DELAYED—OFF TIME ADJUSTMENT
DIP SWITCHES
Switch | Switch Functions | Switch Settings |
---|---|---|
Bank A | OFF | ON |
A1 | N/A | N/A |
A2 | N/A | N/A |
A3 | Manual Mode | Auto Adapting Enabled |
A4 | Walk-Through Disabled | Walk-Through Enabled |
Bank B | OFF | ON |
B1 | Override to ON | Auto Mode |
B2 | Override to OFF | Auto Mode |
B3 | Test Mode | OFF ¢ ON ¢ OFF = Enter/Exit Test Mode |
B4 | LEDs Disabled | LEDs Enabled |
FIGURE 3.2.0 DIP SWITCH SETTING TABLE
FIGURE 3.2.1 MC-C DIP SWITCHES
FIGURE 3.2.2 MC-W DIP SWITCHES
ELECTRICAL
WIRING SCHEMATICS
FIGURE 4.1.0 EV90, EV90P, EV130, EV200, AND EV300 SCHEMATIC
In this example, Motion Control Occupancy Sensor turns Energy Recovery
Ventilator (ERV) on at High speed when space is occupied.
FIGURE 4.1.1 EV PREMIUM AND SL75 SCHEMATIC
FIGURE 4.1.2 HE1.5IN—STANDARD WIRING (NON-ECM) SCHEMATIC
FIGURE 4.1.3 HE1.5IN-MOTORIZED DAMPER(S) OR INDEPENDENT BLOWER CONTROL
SCHEMATIC
FIGURE 4.1.3 HE1.5IN-MOTORIZED DAMPER(S) OR INDEPENDENT BLOWER CONTROL
SCHEMATIC
FIGURE 4.1.5 HE1.5RT-MOTORIZED DAMPER(S) OR INDEPENDENT BLOWER CONTROL
SCHEMATIC
FIGURE 4.1.6 HE2X-8X, LE6X-10X-WITH STANDARD WIRING OR MOTORIZED DAMPER(S)
SCHEMATIC
FIGURE 4.1.7 HE1.5-ECM WITH TERMINAL BLOCK (SPEED 1-LOW SPEED ON/OFF)
SCHEMATIC
In this example, Motion Control Occupancy Sensor turns the ERV on at speed set
by potentiometers when space is occupied.
FIGURE 4.1.8 HE07, HE10, AND HE1.5—ECM WITH CIRCUIT BOARD (SPEED 1-LOW SPEED
ON/OFF) SCHEMATIC
FIGURE 4.1.9 RH-W HEATER ACCESSORY THERMOSTAT SCHEMATIC
FACTORY ASSISTANCE
In the unlikely event that you need assistance from the factory for a specific issue, make sure that you have the information called for in the Unit Records page in the Owner Information section of the unit manual. The person you speak with at the factory will need that information to properly identify the unit and the installed options.
To contact RenewAire Customer Service:
Call800-627-4499
Email:
RenewAireSupport@RenewAire.com
About RenewAire
For over 40 years, RenewAire has been a pioneer in enhancing indoor air quality (IAQ) in commercial and residential buildings of every size. This is achieved while maximizing sustainability through our fifth-generation, static- plate, enthalpic-core Energy Recovery Ventilators (ERVs) that optimize energy efficiency, lower capital costs via load reduction and decrease operational expenses by minimizing equipment needs, resulting in significant energy savings. Our ERVs are competitively priced, simple to install, easy to use and maintain and have a quick payback. They also enjoy the industry’s best warranty with the lowest claims due to long-term reliability derived from innovative design practices, expert workmanship and Quick
Response Manufacturing (QRM).
As the pioneer of static-plate core technology in North America, RenewAire is
the largest ERV producer in the USA. We’re committed to sustainable
manufacturing and lessening our environmental footprint, and to that end our
Waunakee, WI plant is 100% powered by wind turbines. The facility is also one
of the few buildings worldwide to be LEED and Green Globes certified, as well
as having achieved ENERGY STAR Building status. In 2010, Renew Aire joined the
Soler & Palau (S&P) Ventilation Group in order to provide direct access to the
latest in energy efficient air-moving technologies. For more information,
visit: renewaire.com
Member of the S&P Group
Family of Brands
2023 © RenewAire LLC
138280_007_NOV23
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>