Carrier 30RC065-252 Energy Management Module Accessory Installation Guide
- June 15, 2024
- Carrier
Table of Contents
30RC065-252 Energy Management Module Accessory
Installation Guide
SAFETY CONSIDERATIONS
Installation of this accessory can be hazardous due to system pressures,
electrical components, and equipment location (such as a roof or elevated
structure).
Only trained, qualified installers and service technicians should install,
start up, and service this equipment. When installing this accessory, observe
precautions in the literature, labels attached to the equipment, and any other
safety precautions that apply.
- Follow all safety codes.
- Wear safety glasses and work gloves.
- Use care in handling and installing this accessory.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to
this equipment during installation. There may be more than one disconnect
switch. Tag and lock all disconnect locations to alert others not to restore
power until work is completed.
GENERAL
The standard Carrier Controller software provided on all 30RC chillers is programmed to accept various options to modify the unit operation. The Energy Management Module (EMM) board is required for 4 to 20 mA, 2 or 3-step demand limit control, chilled water temperature reset by space temperature, and Ice Mode. Chilled water temperature reset by return water or cooler delta T does not require the addition of this accessory. See Table 1 for EMM functions. The following functions are available with the EMM board:
-
Chilled Water Temperature Reset — Resets the chilled water set point under less than full load capacity conditions the following method: – Space Temperature: A field-supplied space temperature sensor is required.
-
Demand Limit — Limits the capacity of the machine from unit capacity by the following methods:
– 4 to 20 mA Input: A field-supplied signal generator is required.
– 2 or 3-Step Switch Control: A field-supplied dry contact switch is required (One-Step Demand Limit does not require the EMM board). -
Occupancy Override — Extends the occupied period for machine operation. A field-supplied dry contact switch is required.
-
Remote Chiller Lockout — Disables the chiller when closed. A field-supplied dry contact switch is required.
-
Ice Done Control Switch — Signals the machine to exit the Ice Build mode and enter an unoccupied time period. A field-supplied dry contact switch is required. The following status functions are available with the EMM board:
-
Capacity Output Signal — A 0 to10 vdc analog output signal indicating chiller capacity is available.
-
Shutdown Status Relay — A 24 vac output signal indicating that the machine is shutting down.
-
Alert Relay — A 24 vac output signal indicating the unit has an active alert.
The EMM board can be configured with the Carrier Controller module.
Table 1 — EMM Functions
| INPUT/OUTPUT
---|---
INPUTS| Demand Limit, 2 or 3-Step
Demand Limit, 4-20 mA
Ice Done
Occupancy Override
Space Temperature Thermistor
Remote Chiller Lockout
OUTPUTS| Alert Relay
Shutdown Status Relay
Total Capacity Output, 0-10 vdc
Desuperheater Pump Command
Package Contents
Examine the package contents for correct part numbers. Refer to Table 2 for
package contents and usage. If any of the components are damaged, file a claim
with the shipping company and notify your Carrier representative.
Table 2 — 30RC Accessory Package Contents and Usage
DESCRIPTION | PART NO. | QTY |
---|---|---|
Energy Management Board | 00PSN500038300A | 1 |
Terminal Block (TB6) | 30XV50074301 | 1 |
Wiring Harness | 30RCHAAAE–A00 | 1 |
Wiring Harness | 30RCHAAAMB-A20 | 1 |
Terminal Block Mounting Screws, No. 8 | AL04AU166 | 3 |
EMM Board Mounting Screws,8-32 x 0.38 in. long | AL04AU166 | 6 |
Circuit Breaker CB6 | HH83ZB010 | 1 |
Wire Tie | HY76TB110 | 1 |
NOTE(S):
a. Terminal Block (TB6, P/N 30XV50074301) is pre-wired with wiring harness
assembly for P/N 30RCHAAAE–A00.
INSTALLATION
- Disconnect unit power. Follow proper lockout/tag-out procedures.
- Locate the control panel enclosure. See Fig. 1-2 for control panel layout and location for installation of EMM board and TB6.
- Install EMM board in the location shown using the screws included in the accessory package.
- Install TB6 in the location shown in Fig. 1 or Fig. 2 as applicable using the screws included in the accessory package. TB6 should have harness already attached as shown in Table 3. Correct connections should be verified.
- Install circuit breaker CB6 in the hole on the bracket. See Fig. 1-2 for location. Locate the accessory-supplied wiring harness 30RCHAAAE–A00 and install 2-pin power plug labeled EMM-J15 on the EMM board terminal J15. nnect the 2 red wires labeled CB6 to the installed CB6 circuit breaker. Run red wires labeled TB7-X1 and brown wires labeled TB7-X2 to the terminal blocks with matching labels.
- See Fig. 3. Locate the accessory-supplied wiring harness (30RCHAAAMB-A20) and connect it to EMM board J13. Connect the other end of the harness to AUX-3 board J9 if installed, otherwise connect to AUX-2 board J9 if installed, otherwise connect to SIOB-B board J-12.
- Each of the remaining accessory-supplied EMM board wiring harness connectors labeled J1, J2, J4, J7, J9, J10, J22, J23, and J25 should be connected to their respective connectors on the EMM board.
Table 3 — EMM Board Wiring
UNIT| WIRING HARNESS| EMM BOARD CONNECTION LOCATION| WIRE
COLOR| CONNECTION LOCATION
---|---|---|---|---
3ORC (ALL VOLTAGES)| 3ORCHAAAE–A00| EMM-J1-1| BLUE| TB6-12
EMM-J1-2| BLUE| TB6-13
EMM-J1-3| RED| TB6-14
EMM-J1-4| RED| TB6-15
EMM-J1-5| VIOLET| TB6-5
EMM-J1-6| VIOLET| TB6-6
EMM-J1-7| GRAY| TB6-9
EMM-J1-8| GRAY| TB6-10
EMM-J2-2| BLACK| TB6-21
EMM-J4-3| RED| TB6-20
EMM-J7-1| BLACK| TB6-28
EMM-J7-2| RED| TB6-29
EMM-J7-3| BLACK| TB6-26
EMM-J7-4| RED| TB6-27
EMM-J7-5| BLACK| TB6-24
EMM-J7-6| RED| TB6-25
EMM-J7-7| BLACK| TB6-22
EMM-J7-8| RED| TB6-23
EMM-J9-1| BLACK| TB6-2
EMM-J9-2| ORANGE| TB6-1
EMM-J10-1| BLACK| TB6-19
EMM-J10-2| ORANGE| TB6-18
EMM-J22-1| BLACK| TB6-17
EMM-J22-2| RED| TB8-4
EMM-J23-1| BLACK| TB6-16
EMM-J23-2| RED| TB8-4
EMM-J25-1| ORANGE| TB6-8
EMM-J25-2| ORANGE| TB6-7
3ORC (ALL VOLTAGES)| 3ORCHAAAMB-A20| EMM-J13-1| RED| Connect to AUX-3-J9 if
installed, otherwise connect to AUX-2-J9 if installed, otherwise connect to
SIOB-B-J12
EMM-J13-2| WHITE
EMM-J13-3| BLACK
Configuration (All Sizes)
The controls must be configured to recognize the EMM board.
The Carrier Controller display may be used to do this. See the Energy
Management Module (EMM) section in the Controls, StartUp, Operation, Service
and Troubleshooting guide for configuration information. The Carrier
Controller must be set up to communicate with the EMM module (Main Menu →
Configuration Menu → Factory Configuration → Energy Management Module = Yes).
Temperature Reset
CAUTION
Care should be taken when interfacing with other control systems due to
possible power supply differences such as a full wave bridge versus a half
wave rectification. Connection of control devices with different power
supplies may result in ermanent damage. Carrier Controller controls
incorporate power supplies with half wave rectification. A signal isolation
device should be utilized if the signal generator incorporates a full wave
bridge rectifier.
SPACE TEMPERATURE
A field-supplied 10K thermistor can be used to provide leaving laid
temperature reset. The thermistor must be connected to TB6-7,8. See Fig. 4.
See the Controls, Start-Up, Operation, Service and Troubleshooting guide for
configuration information.
Demand Limit
4 TO 20 mA
A field-supplied and generated, externally powered 4 to 20 mA signal can be
used to provide a demand limit signal for chiller capacity reduction. The
signal must be connected to TB6-1, 2 (positive, negative). See Fig. 4. See the
Controls, tart-Up, Operation, Service and Troubleshooting guide for
configuration information.
CAUTION
Care should be taken when interfacing with other control systems due to
possible power supply differences such as a full wave bridge versus a half
wave rectification. Connection of control devices with different power
supplies may result in permanent damage. The Carrier Controller controls
incorporate power supplies with half wave rectification. A signal isolation
device should be utilized if the signal generator incorporates a full wave
bridge rectifier.
SWITCH CONTROLLED
A field-supplied set of dry contacts can be used to provide up to three steps
of chiller capacity reduction. The three steps are achieved through two sets
of dry contacts. The contacts for De- mand Limit Switch 1 must be connected to
TB5-5,14 and are on the standard unit. The contacts for Demand Limit Switch 2
must be connected to TB6-14,15. See Fig. 4. The position of these contacts
will allow for up to three steps of demand limit according to the following:
CONTACT | AMOUNT OF CAPACITY REDUCTION |
---|---|
None | Switch Limit Setpoint 1 |
Switch Limit Setpoint 3
Switch 1| Open| Close| Open| Close
Switch 2| Open| Open| Close| Close
Refer to the Controls, Start-Up, Operation, Service and Troubleshooting guide
for configuration information. Additional EMM Functions
INPUTS
A field-supplied set of dry contacts can be used to provide an occupancy
override signal (TB6-12,13), remote chiller lockout (TB6-5,6) or ice done
switch (TB6-9,10) to the controls. See Fig. 4. The occupancy override switch
can be used to put the chiller in an occupied mode during a normally scheduled
unoccupied mode of operation. The remote chiller lockout function will disable
the chiller when closed. With ice mode configuration en- abled and ice done
switch contact open, a brine chiller will be able to operate as desired during
off peak times in conjunction with an ice storage system. Operation in ice
mode ends when the contact closes. Refer to the Controls, Start-Up, Operation,
Service and Troubleshooting guide supplied with the chiller for more
information on the correct configuration of these options.
OUTPUTS
One analog and three discrete outputs are available from the Energy Management
Module. The analog output indicates percentage of total capacity with a 0 to
10 vdc signal. Three discrete outputs, Desuperheater Pump Command, alert
relay, and shutdown relay, indicate unit operation.
EMM-J22 and J23 Connection
To utilize this connection, field-supplied wiring should be connected to
TB6-11, 17 for shutdown relay (SHDR) and TB6-11, 16 for alert relay (ALT R).
See Fig. 5.
Shutdown Relay
This feature provides an output signal whenever the unit is in an alarm
condition and at 0% capacity. The maximum load for this relay is 10 VA sealed,
25 VA inrush at 24 vac. For connection information, see the EMM-J22 Connection
section. Alert Relay This feature provides an output signal to indicate that
at least1 circuit is off duet an alert. The maximum load for this relay is
10 VA sealed, 25 VA inrush at 24 vac. For connection information, see the
EMM-J22 and J23 Connection section.
Desuperheater Pump Command
This feature provides outputs to command a customer-supplied desuperheater
pump ON or OFF. The maximum load for this relay is 5 VA sealed, 10 VA inrush
at 24 vac. Connections are made to TB6-20 and 21. See Fig. 6.
Percent Total Capacity
This feature allows the unit control to provide a 0 to 10 vdc signal based on
the unit capacity. The signal is a linear function from 0 to 10 vdc, with 0
vdc representing 0% capacity and 10 vdc representing 100% capacity. See Fig. 7
for iring. Field wiring connections are made to terminal TB6-18, 19.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300244-01
Printed in U.S.A.
Form 30RC-6ASI Rev A
Replaces: New
© 2023 Carrier
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>