Eaton 5P1150iR UPS System User Manual
- June 15, 2024
- EATON
Table of Contents
Eaton 5P1150iR UPS System
Introduction
- Thank you for selecting an EATON product to protect your electrical equipment.
- The 5P range has been designed with the utmost care.
- We recommend that you take the time to read this manual to take full advantage of the many features
- of your UPS (Uninterruptible Power System).
- Before installing 5P, please read the booklet presenting the safety instructions.
- Then follow the instructions in this manual.
- To discover the entire range of EATON products and the options available for the 5P range, we invite you to visit our website at www.eaton.com/powerquality or contact your EATON representative.
Environmental protection
-
EATON has implemented an environmental protection policy.
-
Products are developed according to an eco-design approach.
-
Substances
- This product does not contain CFCs, HCFCs or asbestos.
-
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.- The cardboard we use comprises over 50 % of recycled cardboard.
- Sacks and bags are made of polyethylene.
- Packing materials are recyclable and bear the appropriate identification symbol 01
-
Follow all local regulations for the disposal of packing materials.
-
End of life
- EATON will process products at the end of their service life in compliance with local regulations.
- EATON works with companies in charge of collecting and eliminating our products at the end of their service life.
-
Product
- The product is made up of recyclable materials.
- Dismantling and destruction must take place in compliance with all local regulations concerning waste. At the end of its service life, the product must be transported to a processing centre for electrical and electronic waste.
-
Battery
- The product contains lead-acid batteries that must be processed according to applicable local regulations concerning batteries.
- The battery may be removed to comply with regulations and given correct disposal.
Specifications
Model| Output Power @ 230 V| Output Power @ 230 V VA| Output
Power @ 208 V| Output Power @ 208 V W| Output Power @ 200 V| AC
Input Power| Input voltage range| Input frequency range|
Voltage| Frequency| Battery Standard| Battery Rack|
Operating temperature range| Storage temperature range| Relative
humidity| Noise level
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
5P 650i| 650| 420| 585| 378| 378| Single phase 200-240 V| 160| 47 to 70 Hz (50
Hz system), 56,5 to 70 Hz (60 Hz system)| 200/208/220/230/240 V| 50/60 Hz
±0.1 Hz| 1 x 12 V 9 Ah| 2 x 6 V 9 Ah| 0 to 35 °C| -15 to +50 °C| 0 to 90 %
(without condensation)| < 40 dBA
5P 850i| 850| 600| 765| 540| 540| Single phase 200-240 V| 160| 47 to 70 Hz (50
Hz system), 56,5 to 70 Hz (60 Hz system)| 200/208/220/230/240 V| 50/60 Hz
±0.1 Hz| 2 x 12 V 7 Ah| 4 x 6 V 7 Ah| 0 to 35 °C| -15 to +50 °C| 0 to 90 %
(without condensation)| < 40 dBA
5P 1150i| 1150| 770| 1035| 693| 693| Single phase 200-240 V| 160| 47 to 70 Hz
(50 Hz system), 56,5 to 70 Hz (60 Hz system)| 200/208/220/230/240 V| 50/60 Hz
±0.1 Hz| 2 x 12 V 9 Ah| 4 x 6 V 9 Ah| 0 to 35 °C| -15 to +50 °C| 0 to 90 %
(without condensation)| < 40 dBA
5P 1550i| 1550| 1100| 1395| 990| 990| Single phase 200-240 V| 160| 47 to 70 Hz
(50 Hz system), 56,5 to 70 Hz (60 Hz system)| 200/208/220/230/240 V| 50/60 Hz
±0.1 Hz| 3 x 12 V 9 Ah| 6 x 6 V 9 Ah| 0 to 40 °C| -15 to +50 °C| 0 to 90 %
(without condensation)| < 40 dBA
Frequently Asked Questions
What are the available user settings for the Eaton 5P1150iR UPS System?
User settings include options such as language selection, LCD screen settings, audible alarm settings, input/output settings (voltage, thresholds, sensitivity), load segment settings (auto start and shutdown delay, overload pre-alarm), ON/OFF settings (cold start, forced reboot, auto restart, energy- saving mode, sleep mode, remote command, RPO delay), and battery settings (automatic battery test, low battery warning, restart battery level, battery charge mode, deep discharge protection).
How can I dispose of the Eaton 5P1150iR UPS and its batteries in an environmentally friendly manner?
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning batteries. The battery may be removed for correct disposal. Follow all local regulations for the disposal of packing materials and electronic waste.
What is the purpose of the special symbols mentioned in the documentation?
The special symbols are used on the UPS and its accessories to convey important information. For example, the symbol indicating the risk of electric shock warns users to observe associated warnings and safety instructions. The recycling symbols remind users not to discard the UPS or its batteries in the trash and to follow proper disposal procedures.
Can the Eaton 5P1150iR UPS System be used in rack-mounted installations?
Yes, the Eaton 5P1150iR is available in rack-mounted configurations, making it suitable for rack-mounted installations. Rack models include the necessary dimensions and specifications for rack deployment.
What is the purpose of the control panel on the Eaton 5P1150iR UPS, and what information does it display?
The Eaton 5P1150iR UPS System features a control panel with a graphical LCD and buttons. It provides information about the UPS's status, load, events, measurements, and settings. The panel allows users to access and configure various UPS functions and settings.
How can I change the language displayed on the Eaton 5P1150iR UPS's LCD screen?
You can change the language displayed on the LCD screen through the user settings. Navigate to the Local settings menu and select the desired language from the available options.
What is the purpose of the Energy saving feature, and how does it work in Eaton 5P1150iR?
The Energy saving feature, when enabled, allows the UPS to automatically shut down after 5 minutes of backup time if no load is detected on the output. This feature helps conserve energy by turning off the UPS when it's not actively providing power to connected equipment.
How can I perform a manual battery test on the Eaton 5P1150iR UPS System?
To perform a manual battery test, navigate to the UPS's control panel and find the Start battery test option in the menu. Select it to initiate the test. This can help ensure the batteries are functioning properly.
What is the significance of the Overload prealarm setting of Eaton 5P1150iR, and how does it work?
The Overload prealarm setting allows users to define a critical percentage of load capacity. When the predefined percentage of load capacity is reached, the UPS triggers a warning. This setting helps users proactively manage their power loads and avoid overloading the UPS.
What is the Sensitivity setting in Eaton 5P1150iR, and how does it affect UPS behavior?
The Sensitivity setting allows users to choose between High and Low sensitivity levels. High sensitivity means the UPS will transfer to battery power more easily when utility conditions deteriorate, making it suitable for sensitive equipment. Low sensitivity is for equipment that can withstand bad utility conditions, and the UPS will not transfer to battery power as readily.
What is the purpose of the Auto restart feature in Eaton 5P1150iR?
The Auto restart feature, when enabled, allows the UPS to automatically restart when mains power recovers after a complete battery discharge. This ensures that the UPS resumes normal operation without manual intervention.
How does the Energy saving mode in Eaton 5P1150iR work, and when is it useful?
When the Energy saving mode is enabled, the UPS will automatically shut down after 5 minutes of backup time if no load is detected on the output. This feature is useful for conserving energy by turning off the UPS when it's not actively powering connected equipment, thus reducing energy consumption.
User Manual
Reference:Eaton 5P1150iR UPS System User Manual- device.report