AKO-DH14023 Series Panel Mounting Thermometer Instructions
- June 15, 2024
- AKO
Table of Contents
AKO-DH14023 Series Panel Mounting Thermometer
Specifications
- Product Model : AKO-DH14023 V2
- Voltage : 230 V
- Frequency : 50/60 Hz
- Probe Compatibility : AKO-H158xx V2
- Double isolation between power input and secondary circuit
Product Usage Instructions
Installation
The probe and its cable should NEVER be installed in the same conduit as
power, control, or supply cables.
Maintenance
Clean the surface of the unit with a soft cloth, water, and soap. Do not
use abrasive detergents, petrol, alcohol, or solvents, as this might damage
the unit.
Operation
Connection of the Approved Probe
When connecting the approved probe, the equipment will automatically
display the temperature of said probe on the screen. This temperature is
subject to metrological control and complies with the ICT/155/2020 directive,
as well as the EN13485 standard.
Display
The display shows the temperature indication. Press the SET key to access
the set point or programming.
Parameter Adjustment
Access the programming menu by pressing the SET key for more than 5
seconds. After 20 seconds without pressing any key, the equipment will revert
to the previous level. If at level 3, changes will not be saved.
FAQ
-
Q: Can I install the probe and its cable in the same conduit as power cables?
A: No, the probe and its cable should NEVER be installed in the same conduit as power, control, or supply cables. -
Q: How should I clean the unit?
A: Clean the surface of the unit with a soft cloth, water, and soap. Do not use abrasive detergents, petrol, alcohol, or solvents, as this might damage the unit. -
Q: Which probes are compatible with the AKO-DH14023 V2 thermometer?
A: Probes AKO-H158xx V2 are compatible ONLY with thermometers AKO-DH14023 V2. -
Q: What happens if I manipulate the approved probe’s label?
A: Any manipulation of the approved probe’s label may cause the certification to lose its validity.
Installation
Wiring diagram
The probe and its cable should NEVER be installed in the same conduit as power, control or supply cables.
Description
Thermometer with calibration certificate and approved according to
ICT/155/2020
Warnings
- Using the equipment without following the manufacturer’s instructions may affect the device’s safety requirements. To ensure that the device operates correctly, only probes supplied by AKO should be used.
- The unit must be installed in a location protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed that shown in the technical data.
- To ensure a correct reading, the probe must be situated in a location without any external heat influences except for the temperature which is being measured or controlled.
- The power supply circuit must be provided with a main switch rated at at least 2 A,230 V, located close to the equipment. The cables will enter through the back and should be type H05VV-F or H05V-K. 2
- The gauge will depend on local regulations, but should in no case be less than 1 mm . 2
NOTE : Homologated probe CANNOT BE EXTENDED
NOTE : Equipment NOT compatible with AKO-14917 (external communication module) and AKO-14918 (programming key)
Double isolation between power input and secondary circuit
MAINTENANCE
Clean the surface of the unit with a soft cloth, water and soap. Do not use abrasive detergents, petrol, alcohol or solvents, as this might damage the unit.
Operation
SET key /
- Pressing for 5 seconds activates Stand-by mode; pressing for 2 seconds returns the device to normal mode. In Stand-by mode, the device takes no action, and only the indicator “ ****“ is displayed on the screen.
- Pressing for 10 seconds accesses the programming menu.
- Pressing for 5 seconds in the programming menu accesses the level shown on the screen, or during the adjustment of a parameter, accepts the new value.
In the programming menu, a short press allows you to navigate through different levels or, during the adjustment of a parameter, change its value, always in an upward direction. Upon reaching the upper limit, it will start again from the lower limit.
Connection of the approved probe
When connecting the approved probe, the equipment will automatically display
the temperature of said probe on the screen.
This temperature is subject to metrological control and complies with the
ICT/155/2020 directive, as well as the EN13485 standard.
Probes AKO-H158xx V2 are c ompatible ONLY with thermo-meters AKO- DH14023 V2.
IMPORTANT : Any manipulation of the approved pro-be’s label may cause the certification to lose its validity
- AKO ELECTROMECÁNICA , S.A.L.
- Avda. Requites, 30-3808812
- Sant Pere de Ribes. Barcelona
- Spain.
- www.ako.com
- We reserve the right to supply materials slightly different to those described in our Data Sheets. Up-to-date information on our website.
Parameter Adjustment
Programming menu
After 20 seconds without pressing any key, the equipment will revert to the
previous level. If at level 3, changes will not be saved
Table of Parameters and Messages
The Def. column indicates the default parameters configured at the factory.
Unless otherwise indicated, temperature values are expressed in ºC.
Level 1 | Menus and description |
---|---|
CnF | Level 2 General status |
Level 3 Description | Min. |
P2 | Access code function (password) 0 = inactive; 1 = Lock access to |
parameters; 2 = Keyboard lock | 0 |
TID | Level 2 Access Control / Information |
Level 3 Description | Min. |
L5 | Access Code (password) |
PU | Display program version |
PR | Display program review |
PSR | Display program subreview |
SK | Level 2 Approved probe |
Level 3 Description | Min. |
ssN | Serial number of approved probe connected |
spu | Approved probe program version |
spR | Approved probe program review |
sps | Approved probe program sub review |
Messages
- Damaged probe 1 or incorrect reading of digital probe. “ºC” symbol turns off.
- Reading above the measurement range of the digital probe. “ºC” symbol turns off and symbol turns on.
- Reading below the measurement range of the digital probe. “ºC” symbol turns off and symbol turns on.
- Request for access code (password)
Technical specifications
- Power supply …………………………………………………. 230 V~ ±10 % 50/60 Hz 3.5 VA
- Working ambient Display …………………………….-10 to 50 ºC, humidity <90 %
- Probe ………………………… -40 to 80 ºC , humidity 0 – 100 %
- Storage ambient Display ………………………..-30 to 70 ºC, humidity <90 %
- Probe ……………………. -40 to 80 ºC , humidity 0 – 100 %
- Front protection degree ………………………………………………………………………… IP65
- Fixation ……………………………………………………………. Panel-mounted with anchors
- Panel cutout dimensions …………………………………………………………….. 71 x 29 mm
- Front panel dimensions ………………………………………………………………. 79 x 38 mm
- Depth …………………………………………………………………………………………….43 mm
- Connections. ……………………………………… Screw terminals for cables up to 2.5 mm²
- Pollution degree ………………………………………………………….II s/ EN 61010-1:2010.
- Use of the equipment ………………………………… indoor and in non-wet environments
- Maximum altitude expected above sea level ………………………………………….2000 m
- Compatible probes …………………………..AKO-H15811 / AKO-H15861 / AKO-H15801
- Measurement range ……………………………………………………………….. de -40 a 40 ºC
- Degree of protection of probe AKO-H158x1 ……………………………………………….IP68
- Resolution …………………………………………………………………………………………0,1 ºC
- Suitability for storage use. …………………………………………………………………………..S
- Type of climatic environment …………………………………………………………………….. A
- Accuracy class (between -40 and +40ºC) ……………………………………………………… 1
- Complies with :…………………………………………………………….. ORDEN ICT/155/2020
- …………………………………………………………………………………. UNE-EN 13485:2002
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>