WORCESTER Horizontal External Flue Kit 80 125mm Instruction Manual
- June 15, 2024
- WORCESTER
Table of Contents
Horizontal External Flue Kit 80 125mm
FLUE KIT INSTALLATION MANUAL
EXTERNAL BALANCED FLUE
GREENSTAR OILFIT EXTERNAL
6720646882a (2010/
FOR USE WITH THE FOLLOWING GREENSTAR OIL-FIRED BOILER:
GREENSTAR UTILITY 18/25
GREENSTAR DANESMOOR 18/25
GREENSTAR HEATSLAVE 12/18, 18/25 & 25/32
GREENSTAR HEATSLAVE EXTERNAL 12/18, 18/25 & 25/32
GREENSTAR CAMRAY KITCHEN 12/18, 25/32 & 25/32
GREENSTAR CAMRAY UTILITY & SYSTEM 12/18, 18/25 & 25/32
GREENSTAR CAMRAY EXTERNAL 12/18, 18/25 & 25/32
KEY TO SYMBOLS AND SAFETY INSTRUCTIONS
1.1 EXPLANATION OF SYMBOLS
WARNINGS
Warnings in this document are framed and identified by a warning triangle
which is printed on a grey background.
Electrical hazards are identified by a lightning symbol surrounded by a
warning triangle.
Keywords indicate the seriousness of the hazard in terms of the consequences of not following the safety instructions.
- NOTE indicates that material damage may occur.
- CAUTION indicates that minor to medium injury may occur.
- WARNING indicates that serious injury may occur.
- DANGER indicates possible risk to life.
IMPORTANT INFORMATION
Important information in cases where there is no risk of injury or material
losses is identified by the symbol shown on the left.
It is bordered by horizontal lines above and below the text.
ADDITIONAL SYMBOLS
Symbol B | Meaning |
---|---|
a step in an action sequence | |
a reference to a related part in the document or to other related documents | |
• | a list entry |
– | a list entry (second level) |
Table 1
1.2 SAFETY INSTRUCTIONS
OIL SMELLS, LEAKS OR FUMES FROM THE BOILER:
- Extinguish any naked flames.
- Open windows and doors (internal models only).
- Isolate the electrical supply.
- Isolate the fuel supply to the boiler.
- Rectify fault.
HEALTH AND SAFETY:
The appliance contains no asbestos and no substances have been used in the
construction process that contravene the COSHH Regulations (Control of
Substances Hazardous to Health Regulations 1988).
Where applicable, the CE mark indicates compliance with relative EU
Directives.
COMBUSTIBLE AND CORROSIVE MATERIALS:
Do not store or use any combustible materials (paper, thinners, paints etc.)
inside or within the vicinity of the appliance.
The combustion air must be kept clear of chemically aggressive substances
which can corrode the appliance and invalidate any warranty.
FITTING AND MODIFICATION:
Fitting the appliance and any controls to the appliance may only be carried
out by a competent engineer in accordance with these instructions and the
relevant Installation Regulations.
Flue systems must not be modified in any way other than as described in the
fitting instructions.
Any misuse or unauthorised modifications to the appliance, flue or associated
components and systems could invalidate the warranty. The manufacturer accepts
no liability arising from any such actions, excluding statutory rights.
SERVICING:
Advise the user to have the system regularly serviced by a competent,
qualified engineer (such as OFTEC registered personnel) using approved spares,
to help maintain the economy, safety and reliability of the appliance.
INSTALLATION AND SERVICING
2.1 INSTALLATION & SERVICING INSTRUCTIONS
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION THESE
INSTRUCTIONS ARE APPLICABLE TO THE WORCESTER APPLIANCE MODEL(S) STATED ON THE
FRONT COVER OF THIS MANUAL ONLY AND MUST NOT BE USED WITH ANY OTHER MAKE OR
MODEL OF APPLIANCE.
THE INSTRUCTIONS APPLY IN THE UK ONLY AND MUST BE FOLLOWED EXCEPT FOR ANY
STATUTORY OBLIGATION.
THIS APPLIANCE MUST BE INSTALLED BY A COMPETENT PERSON. FAILURE TO INSTALL
CORRECTLY COULD LEAD TO PROSECUTION.
IF YOU ARE IN ANY DOUBT CONTACT THE WORCESTER TECHNICAL HELPLINE.
DISTANCE LEARNING AND TRAINING COURSES ARE AVAILABLE FROM WORCESTER, BOSCH
GROUP.
PLEASE LEAVE THESE INSTRUCTIONS WITH THE USER OR WITH THE APPLIANCE AFTER
INSTALLATION OR SERVICING.
ABBREVIATIONS USED IN THIS MANUAL:
Ø | Diameter |
---|---|
CF | Conventional flue |
BF | Balanced flue |
SEDBUK | Seasonal Efficiency of Domestic Boilers in the United Kingdom |
OFTEC | Oil Firing Technical Association for the petroleum Industry |
2.2 INSTALLATION REGULATIONS
Failure to install appliances correctly could lead to prosecution.
COMPLYING WITH THE BUILDING REGULATIONS:
The boiler and flue form part of the controlled services for the building. It is law that all controlled services for buildings must comply with building regulations. You must be able to satisfy your Local Authority Building Control Body (LABC) that the work carried out concerning the installation and commissioning of the heating appliances has been carried out to a satisfactory standard.
OFTEC operate a competent persons scheme and registered installers are able to
certify that their work complies with building regulations.
Under the scheme;
OFTEC must be informed about every installation.
OFTEC will issue a building regulations compliance certificate to the
householder and will notify the LABC.
OFTEC provide controlled document forms CD10 and CD11 for use during
installation and commissioning respectively.
Other organisations operate self-certification schemes e.g. NAPIT and BESCA
Ltd. and it may be possible for installers who are members of these
organisations to self certify their work.
Alternatively you must submit a building control notice to the LABC before
installing any boiler.
The LABC will then arrange regular inspection visits during the work to ensure
that the installation complies with the regulations.
The appliance must be installed by a competent person.
The person installing the appliance should be aware of the Health and Safety
at Work Act and take appropriate action to ensure that the regulations are
adhered to. In order to give optimum efficiency and trouble free operation the
appliance must be commissioned by a qualified OFTEC engineer.
The compliance with a British Standard does not, in itself, confer immunity
from legal obligations. In particular the installation of this appliance must
be in accordance with the relevant requirements of the following British
Standards and regulations in respect of the safe installation of equipment.
BS 5410: part 1: Code of practice for Oil Fired Boilers.
The Building Regulations Part J and L1 England and Wales;
Part F and Part J Section III Scotland;
Part L and Part F Northern Ireland.
Local water company bye-laws.
The Control of Pollution (Oil) Regulations.
OFTEC Standards. Where no specific instruction is given, reference should be
made to the relevant codes of practice.
PRODUCT INFORMATION
3.1 BALANCED HORIZONTAL EXTERNAL FLUE COMPONENTS
80/125MMØ HORIZONTAL EXTERNAL FLUE KIT:
Part Number: 7 716 190 057
- Terminal assembly
- 80/125 weather seal
- External elbow
- External cabinet flue seal and plate
- Clamp bracket
- Drill Pack containing 3.3mm HSS Jobber drill and solvent free grease sachets
3.2 BALANCED VERTICAL EXTERNAL FLUE COMPONENTS
80/125MMØ VERTICAL EXTERNAL FLUE KIT:
Part Number: 7 716 190 053
- Terminal assembly
- 80/125 weather seal
- External elbow
- External cabinet flue seal and plate
- Clamp bracket
- Drill Pack containing 3.3mm HSS Jobber drill and solvent free grease sachets
3.3 BALANCED VERTICAL EXTERNAL FLUE COMPONENTS
100/150MMØ VERTICAL EXTERNAL FLUE KIT:
Part Number: 7 716 190 058
- Terminal assembly
- 100/150 weather seal
- In-line External 80/125 to 100/150mm adaptor
- 80/125 weather seal
- External elbow
- External cabinet flue seal and plate
- Clamp bracket
- Drill Pack containing 3.3mm HSS Jobber drill and solvent free grease sachets
3.4 EXTENSION COMPONENTS
-
80/125mm Ø 1000mm BALANCED FLUE EXTENSION
Part Number: 7 716 190 054
1. Extension tube
2. Pipe clamp with screws, washers, and wall plugs
5. 80/125 weather seal
6. Solvent free grease pack containing 2 No. 8 screws and grease sachets -
80/125mm Ø 600mm BALANCED FLUE EXTENSION
Part Number: 7 716 190 098
1. Extension tube
2. Pipe clamp with screws, washers, and wall plugs
5. 80/125 weather seal
6. Solvent free grease pack containing 2 No. 8 screws and grease sachets -
80/125mm Ø BALANCED FLUE 90° ELBOW
Part Number: 7 716 190 055
3. 90° swept elbow
5. 80/125 weather seal
6. Solvent free grease pack containing 2 No. 8 screws and grease sachets -
100/150mm Ø BALANCED FLUE 90° ELBOW
Part Number: 7 716 190 096
3. 90° swept elbow
5. 100/150 weather seal
6. Solvent free grease pack containing 2 No. 8 screws and grease sachets -
80/125mm Ø BALANCED FLUE 45° ELBOW
Part Number: 7 716 190 056
4. 45° elbow x2
5. 80/125 weather seal
6. Solvent free grease pack containing 2 No. 8 screws and grease sachets -
100/150mm Ø BALANCED FLUE EXTENSION Part Number: 7 716 190 060
1. Extension tube
2. Pipe clamp with screws, washers, and wall plugs
5. 100/150 weather seal
6. Solvent free grease pack containing 2 No. 8 screws and grease sachets
100/150mm Ø BALANCED FLUE 45° ELBOW
Part Number: 7 716 190 061
4. 45° elbow x2
5. 100/150 weather seal
6. Solvent free grease pack containing 2 No. 8 screws and grease sachets
PRE-INSTALLATION
4.1 FLUE TERMINAL POSITIONS
NOTE:
- All measurements are the minimum clearances required.
- The flue must be fitted and terminated in accordance with the recommendations of BS5410
- Use suitable brackets and fittings to support the flue at approximately one metre intervals and at a change of direction.
- Terminals must be positioned so to avoid combustion products entering the building.
- Avoid discharging flue gases into a carport or narrow passageway.
- In spite of the dimensions given here, the terminal must not be closer than 300mm to combustible material, in the case of a thatched roof double this dimension.
- Terminals must be positioned so to avoid products of combustion accumulating in stagnant pockets around the building or entering the building.
- Flue gases have a tendency to plume and in certain weather conditions a white plume of condensation will be discharged from the flue outlet which could be regarded as a nuisance, for example, near security lighting.
- A protective terminal guard must be fitted if the terminal is 2m or less above a surface where people have access. The guard must be spaced equally (minimum 50mm) around the flue and fixed to the wall with plated screws.
- Terminals must be at least 1.8m from an oil storage tank unless a wall with of at least 30 minutes fire resistance and extending 300mm wider and higher than the tank is between the tank and the terminal.
KEY TO ILLUSTRATION
- 600mm above the highest point of an intersection with a roof.
- 600mm below a gutter, drainage pipe or eaves without protection for combustible materials. -OR75mm below a gutter, drainage pipe or eaves with protection for combustible materials.
- 600mm horizontally or vertically to an opening, air brick or opening window.
- 300mm to an internal or external corner.
- 750mm between a vertical structure and a flue terminal.
- The terminal outlet must face directly away from the wall. The outlet can be swivelled through 90° but must not be any closer than 45° to the wall.
- 600mm to a boundary, unless the discharge will cause a nuisance. BS5410: Part 1 recommends that care is taken when siting terminals in relation to boundaries.
4.2 INTERNAL BOILERS – BALANCED EXTERNAL FLUE OPTIONS
Various flue options are shown opposite, the components used and the effective
length of the elbows used. The effective length of the elbows used must be
subtracted from the maximum flue length (L) shown in the table below.
To achieve the maximum flue length (L), a flue section will have to be reduced
in length. Only flue extensions can be reduced in length by cutting.
NOTE: All horizontal sections must rise from the boiler by 52mm per metre (3°)
to allow condensate to drain back to the boiler.
NOTE: #
B Flue damper required.
CALCULATING THE FLUE LENGTH
Measure the total flue length required, noting that the maximum straight flue
length including the terminal is:
Internal Boilers | Maximum effective flue length (L) mm | FlueØ (mm) |
---|---|---|
Boiler Model | High level | |
horizontal* | Vertical** | |
Danesmoor models | 18/25 | 5000 |
Wall hung Danesmoor | 12/18 & 18/25 | 4000 |
Heatslave | 18/25 | 5000 |
Heatslave models | 12/18 & 25/32 | 2000 |
Camray | 18/25 | 5000# |
– | 10000st | 100/150 |
Camray models | 12/18 | 2000 |
25/32 | 2000 | – |
– | 8000 | 100/150 |
Flue damper required Refer to section 5.2.1 for fitting instructions
- from the boiler casing, (the horizontal kit elbow is ignored when calculating the flue length).
** from the boiler casing (the vertical kit elbow is ignored when calculating the flue length) maximum 2 metres of horizontal flue.
Table 3 Maximum flue for internal boilers
Effective length of elbows:
The total straight flue length is reduced for each additional elbow used by:
- 1000mm for each 90° elbow
- 500mm for each 45° elbow
Flue extension lengths:
Horizontal or vertical extensions have an overall length of 1000mm.
But the actual length of the extension when engaged into the sockets within
the flue run is 950mm
Flue terminal lengths:
The following lengths form part of the overall maximum flue length.
- Horizontal 80/125mmØ: 305mm (item 1)
- Vertical 80/125mmØ: 185mm + cage (item 5)
- Vertical 100/150mmØ: 270mm + cage (item 6)
NOTE : Vertical flues
B For satisfactory flue performance it is recommended that no more than two
metres of vertical flue is run horizontally.
FLUE COMPONENTS:
- Horizontal Terminal Kit 80/125 (including 90° elbow)
- Straight Flue Extension Kit 80/125
- 90° Flue Elbow Kit 80/125
- 45° Flue Elbow Kit 80/125 (2 x 45° elbows)
- Vertical Terminal Kit 80/125 (including 90° elbow)
- Vertical Terminal kit 100/150 (including 90° elbow)
- Straight Flue Extension Kit 100/150
- 90° Flue Elbow Kit 100/150
- 45° Flue Elbow Kit 100/150 (2 x 45° elbows)
INTERNAL BOILER TERMINAL OPTIONS: TOP OUTLET 80/125mm Ø
For this flue option: item 3 x 2 = 2000mm.
2000mm of effective length must be deducted from the boiler maximum flue
lengths stated in table 3
SIDE OUTLET – HORIZONTAL
For this flue option: item 3 = 1000mm.
1000mm of effective length must be deducted from the boiler maximum flue
lengths stated in table 3
REAR OUTLET – HORIZONTAL
For this flue option:
Nothing is deducted from the boiler maximum flue lengths stated in table 3
TOP OUTLET Camray 18/25 & 25/32 100/150mm Ø
For this flue option: item 8 x 2 = 2000mm.
2000mm of effective length must be deducted from the boiler maximum flue
lengths stated in table 3
SIDE OUTLET – VERTICAL
For this flue option: item 3 = 1000mm + horizontal section = 1000mm.
2000mm of effective length must be deducted from the boiler maximum flue
lengths stated in table 3
REAR OUTLET – VERTICAL
For this flue option: 1000mm for horizontal section.
1000mm is deducted from the boiler maximum flue lengths stated in table 3 due
to the horizontal section of the flue.
REAR OUTLET – VERTICAL
Camray 18/25 & 25/32 100/150mm ØFor this flue option: 1000mm for
horizontal section.
1000mm is deducted from the boiler maximum flue lengths stated in table 3 due
to the horizontal section of the flue.
TOP OUTLET – VERTICAL 80/125 Ø
For this flue option: item 4 = 1000mm.
1000mm of effective length must be deducted from the boiler maximum flue
lengths stated in table 3
SIDE OUTLET – VERTICAL
Camray 18/25 & 25/32 100/150mm ØFor this flue option: item 3 = 1000mm +
horizontal section = 1000mm.
2000mm of effective length must be deducted from the boiler maximum flue
lengths stated in table 3
TOP OUTLET – VERTICAL
Camray 18/25 & 25/32 100/150mm ØFor this flue option: item 9 = 1000mm.
1000mm of effective length must be deducted from the boiler maximum flue
lengths stated in table 3
4.3 EXTERNAL BOILERS – BALANCED EXTERNAL FLUE OPTIONS
Various flue options are shown opposite, the components used and the effective
length of the elbows used. The effective length of the elbows used must be
subtracted from the maximum flue length (L) shown in the table below.
To achieve the maximum flue length (L), a flue section will have to be reduced
in length. Only flue extensions can be reduced in length by cutting.
NOTE : All horizontal sections must rise from the boiler by 52mm per metre (3°) to allow condensate to drain back to the boiler.
NOTE : #
- Flue damper required.
CALCULATING THE FLUE LENGTH
Measure the total flue length required, noting that the maximum straight flue
length including the terminal is:
External Boilers | Maximum effective flue length (L) mm | Flue Ø (mm) |
---|---|---|
Boiler Model | High level | |
horizontal* | Vertical** | |
Heatslave External | 18/25 | 5000 |
Heatslave External | 12/18 & 25/32 | 2000 |
Camray External | 18/25 | 5000# |
– | 9000# | 100/150 |
Camray External
models| 12/18| 2000| 7000| 80/125
25/32| 2000| –| 80/125
–| 7000| 100/150
4t Flue damper required. Refer to section 5.2.1 for fitting instructions
- from the boiler casing, (the horizontal kit elbow is ignored when calculating the flue length).
** from the boiler casing (the vertical kit elbow is ignored when calculating the flue length) maximum 2m of horizontal flue.
Table 4 External boiler maximum flue length
Effective length of elbows:
The total straight flue length is reduced for each elbow used by:
- 1000mm for each 90° elbow (including the terminal bend of the Horizontal Terminal kit)
- 500mm for each 45° elbow
Flue extension lengths:
Horizontal or vertical extensions have an overall length of 1000mm.
But the actual length of the extension when engaged into the sockets within
the flue run is only 950mm
Flue terminal lengths:
The following lengths form part of the overall maximum flue length.
- Horizontal 80/125mmØ: 305mm (item 1)
- Vertical 80/125mmØ: 185mm + cage (item 5)
- Vertical 100/150mmØ: 270mm + cage (item 6)
NOTE: Vertical flues
- For satisfactory flue performance it is recommended that no more than two metres of vertical flue is run horizontally.
FLUE COMPONENTS:
- Horizontal Terminal Kit 80/125 (including 90° elbow)
- Straight Flue Extension Kit 80/125
- 90° Flue Elbow Kit 80/125
- 45° Flue Elbow Kit 80/125 (2 x 45° elbows)
- Vertical Terminal Kit 80/125 (including 90° elbow)
- Vertical Terminal kit 100/150 (including 90° elbow)
- Straight Flue Extension Kit 100/150
- 90° Flue Elbow Kit 100/150
- 45° Flue Elbow Kit 100/150 (2 x 45° elbows)
EXTERNAL BOILER TERMINAL OPTIONS:
SIDE OUTLET – HORIZONTAL
For this flue option: item 1=1000mm + item 3=1000mm 2000mm of effective length must be deducted from the boiler maximum flue lengths stated in table 4
REAR OUTLET – HORIZONTAL
For this flue option:
Nothing is deducted from the boiler maximum flue lengths stated in table 4
SIDE OUTLET Camray 18/25 & 25/32 100/150mm Ø
For this flue option: item 3=1000mm 1000mm of effective length must be deducted from the boiler maximum flue lengths stated in table 4
SIDE OUTLET – VERTICAL
For this flue option: item 3=1000mm 1000mm of effective length must be deducted from the boiler maximum flue lengths stated in table 4
REAR OUTLET – VERTICAL
For this flue option:
Nothing is deducted from the boiler maximum flue lengths stated in table 4
REAR OUTLET Camray 18/25 & 25/32 100/150mm Ø
For this flue option:
Nothing is deducted from the boiler maximum flue lengths stated in table 4′
NOTE: Vertical flues
- For satisfactory flue performance it is recommended that no more than two metres of vertical flue is run horizontally.
INSTALLATION
5.1 BALANCED FLUE MEASURING & CUTTING
All horizontal flue sections must rise at 52mm for each metre away from the
boiler to ensure that condensate flows back into the boiler for safe discharge
via the condensate waste pipe.
Any internal sections of the flue can be run in either the standard Oilfit
(white) or the External Oilfit (black) flue components depending upon the
customers requirements. All standard Oilfit and External Oilfit components
with the same diameter have the same
dimensions and connections and are fully interchangeable.
Only External Oilfit components should be used externally as these incorporate
an additional weather seal.
MEASURING THE FLUE:
Measure the flue length (L) required from the flue terminal to the outer
boiler casing at the required flue outlet position (1, 2, 3 or 4).
Flue outlet position 1 is not available on external models.
Add dimension ‘X’ to the flue length, as shown for flue outlet 1, 2, 3 or 4 in
the table opposite (to allow the flue to fit to the outlet/elbow inside the
boiler casing).
LENGTH X (mm)
Flue
outlets| Danesmoor| Heatslave| Camray| Heatslave
External| Heatslave
External
---|---|---|---|---|---
1| 40| 40| 30| N/A| N/A
2| 100| 250| 100| 350| 235
3| 100| 100| 100| 235| 270
4| 210| 210| 270| 425| 470
REDUCING THE FLUE LENGTH:
Only cut straight extension tubes.
- Measure and mark the flue extension from the seal end, cut both inner and outer tubes square taking care not to distort the tubes.
- Remove any burrs and chamfer the outer edges of the tubes to ease connection and prevent seal damage.
- Required flue section
- Discarded flue section
5.2 BALANCED FLUE FITTING
To ease assembly of the flue components, grease seals lightly with the solvent free grease supplied. Check all the seals are seated properly in the grooves provided and are in good condition.
- All flue joints must be sealed to prevent leakage of condensate and flue products.
- Check seal (6) is located in the groove of the boilerflue outlet (5).
EXTERNAL BOILER MODELS
For all outlets fit the outlet plate and the seal to the appropriate cabinet
flue outlet before fitting the flue to the boiler.
NOTE : Flue weight
- The flue system must be supported throughout the run as the boiler is not designed to take the weight of the flue.
2. REAR OUTLET “4”
- Loosely fix support bracket/s to support the flue weight.
- Slide flue clamp (7) onto the flue tube (8).
- Push-fit the flue (8) into the boiler flue outlet ensuring a good fit to seal (6).
- Secure flue (8) to boiler outlet with clamp (7).
- Secure flue support bracket/s.
3. OUTLETS “1”, “2” AND “3”
-
When connecting a flue elbow directly to the boiler flue outlet, loosen the flue elbow retaining bracket screws (11)** before fitting the flue elbow.
-
Slide flue clamp (7) over the flue elbow (9).
-
Push-fit the flue elbow (9) into the boiler flue outlet ensuring a good fit to seal (6).
-
Rotate flue elbow (9) to outlet position 1*, 2 or 3.
-
Secure flue elbow (9) to boiler outlet with clamp (7) then tighten the bracket screws (11)**.
-
Check the seals are located properly in the grooves of flue elbow (9).
-
Position 1 , outlet not available on external models.
items 10 and 11 are not fitted to external models NOTE** : The retaining bracket must be fitted if a flue elbow is used on the flue outlet, on internal models.- Loosely fix support brackets (12) to support the weight.
- Push-fit flue (8) into elbow (9).
NOTE : Camray 25/32 models using a vertical terminal, the 80/125 to 100/ 150mmØ vertical adaptor MUST be fitted vertically at the lowest point of the verticalsection of the flue. Failure to fit the adaptor vertically will cause the condensate pool within the flue and will adversely affect the flue’s performance.
- Secure flue support brackets (12).
- Drill two holes with the drill provided (180° apart if possible) through the outer flue elbow (9) into the outer flue tube (8) taking care NOT to drill the inner flue tube.
- Secure with screws supplied.
FITTING FLUE ADAPTERS, ELBOWS & EXTENSIONS:
Fit the extensions and elbows together firmly.
Orient the extensions and elbows correctly.
Drill two holes with the drill provided (180° apart if possible) through the
outer flue elbow (9) into the extension outer tube (8) taking care NOT to
drill the inner tube.
Secure the flue extension to the elbow(s) with the stainless steel screws
provided.
Support the flue extensions at regular intervals with the brackets provided.
If a 100/150 flue extension is required the 80/125 to 100/150 adapter must be
employed:
The adapter must be mounted vertically at the lowest point on the vertical
section. The adapter would be mounted in the 90° elbow.
- Fit the 80/125 to 100/150 adapter (12) to the elbow.
- Orient the elbow (9) vertically.
- Fit the flue extension (13) firmly into the adapter.
- Secure the elbow (9) to the boiler/flue extension (8).
- Secure with the stainless steel screws provided.
5.2.1 FLUE DAMPER
WARNING : Fitting the flue damper
- Failure to fit the flue damper, when required, will effect the performance of the boiler and may cause “lockouts”
The flue damper is only fitted to the Greenstar Camray 18/25 models and thenonly according to flue length.
Greenstar Camray 18/25 models
Flue type
Vertical 100/150| High level horizontal
Fit a damper at the following effective flue lengths
All| Greater than 2 metres
Table 5 Damper required
The CO2 must be readjusted when a damper is used, refer to the relevant Installation Commissioning & Servicing manual for the Camray 18/25 boiler.
18kW | 21.5kW | 25kW |
---|---|---|
11% | 11.50% | no change |
Fit the flue damper into the flue as shown in figure 17.
Ensure that the rubber seal is fitted into the inner tube.
Insert the flue damper into the inner flue tube of the 90° elbow or straight extension and fit the flue as detailed in figure 18 or figure 19 as required.
FITTING AN ELBOW TO THE BOILER OUTLET
-
Ensure that the seal [1] is correctly seated and grease has been applied to ease assembly.
-
Loosen the nuts and bolts securing the retaining bracket [2], but do not remove.
-
Slide the clamping collar [4] over the elbow [3] and mate the elbow to the boiler outlet.
Ensuring that the inner tube slides fully into the seal of the boiler outlet. -
Align the elbow to the direction of the flue path, either left, right or vertically.
-
Position the clamp over the elbow and boiler outlet and tighten firmly.
-
With the elbow in the required position.
-
Re-secure the retaining bracket [1]
5.3 BALANCED FLUE TERMINAL & EXTENSIONS
NOTE: Flue joints
- To ease assembly of the flue components, grease seals lightly with the solvent free grease supplied.
- Check all the seals are seated properly in the grooves provided and are in good condition.
- All flue joints must be sealed to prevent leakage of condensate and flue products.
- Fit a weather seal onto the bottom of each external section and push the seal up clear of the socket mating area.
- Fasten the flue supports (12) to the wall, the flue supports should support each extension piece just below the socket. An additional support (supplied) will be needed directly after any elbows.
- Push fit all extensions together starting at the boiler and working upwards to the terminal, securing the wall clamp (12) on each piece before inserting the next piece.
- Slide the weather seal onto the top of every socket to form a seal.
- Each extension must be supported using the wall clamps (12) supplied or a suitable alternative.
VERTICAL TERMINALS ONLY:
- The terminal must extend beyond the roof or wall by 600mm.
- The terminal must be at least 600mm horizontally from any vertical structure.
- Each extension must be supported using the wall clamps (12) supplied or a suitable alternative.
HORIZONTAL TERMINALS ONLY
- The terminal outlet must face directly away from the wall or no more than 45° from this direction, all flue clearances must be measured from the end of the terminal in the direction the terminal is facing during use.
- Each extension must be supported using the wall clamps supplied or a suitable alternative.
ALL FLUES
- Drill two holes with the drill provided (180° apart if possible) through the outer flue tube (8) on each flue joint taking care NOT to drill the inner flue tube and secure with the screws provided.
- The flue must be sealed to the wall using a suitable sealant where it leaves the building (internal boiler models only).
NOTES
WORCESTER, BOSCH GROUP:
TECHNICAL SUPPORT: 0844 892 3366
APPOINTMENTS: 0844 892 3000
SPARES: 01905 752571
LITERATURE: 0844 892 9800
TRAINING: 01905 752526
SALES: 01905 752640
Worcester, Bosch Group
Cotswold Way, Warndon, Worcester WR4 9SW.
Tel. 0844 892 9900
Worcester, Bosch Group is a brand name
of Bosch Thermotechnology Ltd.
worcester-bosch.co.uk
6 720 646 882a (2010/12)
Documents / Resources
|
WORCESTER Horizontal External Flue Kit 80
125mm
[pdf] Instruction Manual
Horizontal External Flue Kit 80 125mm, Horizontal, External Flue Kit 80 125mm,
Flue Kit 80 125mm, Kit 80 125mm
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>