WORCESTER GREENSTAR HEATSLAVE II Floor Standing Oil Fired Combi Boiler User Manual
- June 1, 2024
- WORCESTER
Table of Contents
- WORCESTER GREENSTAR HEATSLAVE II Floor Standing Oil Fired Combi Boiler
- Product Information
- Product Usage Instructions
- Key to symbols and safety instructions
- General Information
- Using your boiler
- Using your boiler
- Maintenance
- General information
- Energy saving
- Guarantee
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
WORCESTER GREENSTAR HEATSLAVE II Floor Standing Oil Fired Combi Boiler
Product Information
Specifications
- Model: GREENSTAR HEATSLAVE II External 2022+ 12/18, 18/25 & 25/32
- Boiler Type: Floor standing oil-fired condensing boiler
- Flue Type: Conventional flue and room sealed flue
- Heating System: Sealed central heating systems with mains fed domestic hot water
- Fuel Type: Kerosene (Class C2) only
Product Usage Instructions
Key to Symbols and Safety Instructions:
Key to Symbols
Refer to the symbol key provided in the manual for understanding various
indicators and symbols related to the boiler.
Safety Instructions
Follow all safety instructions provided in the manual to ensure safe
operation of the boiler and prevent any hazards.
General Information
Energy Efficiency
The boiler is designed for high energy efficiency, converting more fuel
into heat, resulting in economical running costs.
Servicing
Regular servicing of the boiler is recommended to maintain its performance
and efficiency. Refer to the servicing section for detailed instructions.
User Caution
Users should exercise caution while operating the boiler and follow all
guidelines provided in the manual to ensure safe usage.
Maintenance
The maintenance section covers troubleshooting, servicing, fault finding,
system gassing, and general maintenance procedures to keep your boiler in
optimal condition.
General Information
Important Information:
Review the important information section for any critical details regarding
the operation and maintenance of the boiler.
General Notes:
Read through the general notes for additional tips and guidelines on using
the Greenstar oil-fired condensing boiler.
FAQ
-
Q: Can this boiler be used with other types of fuel?
A: No, this boiler is designed for use with Kerosene (Class C2) fuel only. -
Q: How often should the boiler be serviced?
A: It is recommended to service the boiler regularly as per the guidelines provided in the manual, usually on an annual basis.
User Instructions
Floor standing oil-fired condensing boiler using conventional flue and room sealed flue
GREENSTAR HEATSLAVE II External 2022+
12/18, 18/25 & 25/32
For sealed central heating systems with mains fed domestic hot water
For use with Kerosene (Class C2) only.
User instructions & customer care guide
- Please read these instructions carefully before operating your boiler.
- These instructions are applicable to the Worcester,
- Bosch Group boiler model(s) stated on the front cover of this manual only and must not be used with any other make or model of boiler.
- The instructions apply in mainland UK only and should be followed except for any statutory obligation.
- If you are in any doubt contact the Worcester, Bosch Group technical support.
- This boiler must be installed by a competent person, e.g. an OFTEC registered engineer, failure to install correctly could lead to prosecution.
- Please leave this guide, the installation instructions and the completed checklist with the user.
- A checklist and service interval record can be found at the rear of the Installation, Commissioning and Servicing Instruction manual.
Abbreviations
- SEDBUK Seasonal Efficiency for Domestic Boilers in the United Kingdom.
- OFTEC Oil Firing Technical Association for the Petroleum Industry.
Dedicated to heating comfort
Thank you for purchasing a Greenstar oil fired condensing boiler from
Worcester, Bosch Group. The company prides itself on manufacturing boilers to
the strictest quality control standards throughout every stage of production.
Worcester, Bosch Group has led the field in innovative boiler design and
performance for more than 50 years. This heritage means all products are of
exceptional quality and proven reliability.
The condensing range in particular, is extremely energy efficient, converting
more of the fuel consumed into heat offering you economical running costs and
value for money. It sits in ErP heating efficiency, band A, at the top of the
energy rated boilers available.
There is also the assurance of our no-nonsense parts and labour guarantee –
backed up by an optional servicing and maintenance contract to keep your
boiler operating at peak condition and efficiency.
To find out more about Worcester, Bosch Group, log onto www.worcester-
bosch.co.uk.
Key to symbols and safety instructions
Key to symbols
Warnings
Safety instructions in this document are framed and identified by a warning triangle which is printed on a grey background.
The following keywords are defined and can be used in this document:
- NOTICE indicates a situation that could result in damage to property or equipment.
- CAUTION indicates a situation that could result in minor to medium injury.
- WARNING indicates a situation that could result in severe injury or death.
- DANGER indicates a situation that will result in severe injury or death.
Important information
This symbol indicates important information where there is no risk to people or property.
Additional symbols
Table 1
Examples of additional symbols used
A numbered step in an action sequence
A sequence of numbered steps or actions carried out in a specific order to
complete a task.
- First action
- Second action
- Third action etc.
A step in an action sequence
A sequence of defined actions or steps carried out in order to complete a
task.
- Action
- Next action
- etc.
A reference to a related part in the document or to other related
documents.
To refer the reader to a specific figure/table/section within the manual.
e.g. figure 1.
A reference number to identify or refer to a part or item.
In a related figure, items or parts identified by a sequential number.
List entries, first and second levels
- A single component/item
- A component/list, made up of multiple parts/items.
- Sub component or sublist of main component/list.
- etc.
Safety instructions
These operating instructions are intended for the user of the heating system.
- Read any operating instructions (boiler, heating controls, etc.) carefully before operation and keep them.
- Observe the safety instructions and warnings.
Oil fumes or leaks from the appliance
If you smell oil fumes, observe the following rules.
- Extinguish any naked flames
- Isolate the electrical supply
- Isolate the fuel supply to the boiler
- Contact an approved contractor and have the fault rectified
Health and safety
The appliance contains no asbestos and no substances have been used in the
construction process that contravene the COSHH Regulations (Control of
Substances Hazardous to Health Regulations). Where applicable, the CE mark
indicates compliance with relative EU Directives.
Combustion air/room air
The air in the installation room must be free of combustible or chemically
aggressive substances.
Do not use or store combustible or explosive materials (paper, propellants, thinners, paints, etc.) within the vicinity of the appliance.
Safety of electrical devices for domestic use and similar purposes
The following requirements apply in accordance with EN 60335-1 in order to
prevent hazards from occurring when using electrical appliances:
“This appliance can be used by children of 8 years and older, as well as by
people with reduced physical, sensory or mental capabilities or lacking in
experience and knowledge, if they are supervised and have been given
instruction in the safe use of the appliance and understand the resulting
dangers. Children shall not play with the appliance. Cleaning and user
maintenance must not be performed by children without supervision.”
“If the power cable is damaged, it must be replaced by the manufacturer, its
customer service department or a similarly qualified person, so that risks are
avoided.”
Intended use
This appliance must only be used as a heat appliance in a sealed hot water
heating system for domestic purposes.
Any misuse or unauthorised modifications to the appliance, flue or associated
accessories and heating system will invalidate the guarantee.
- Do not modify the appliance or flue system in any way. Worcester, Bosch Group accepts no liability arising from any such actions. This does not affect your statutory rights.
General Information
Energy efficiency
Energy efficiency information is given in the Installation, Commissioning and
Servicing Instructions supplied with the appliance.
Servicing
The Service Checklist can be found at the rear of the boiler’s installation
instructions. It will be required in the event of any guarantee work and may
be required by the local Building Control Inspector.
- Have the boiler serviced regularly by a competent, OFTEC registered engineer.
- Ensure that the service engineer completes the Service Record, at the rear of the Installation, Commissioning and Servicing Instruction manual, after each service.
- Have any work carried out only by a competent, OFTEC registered engineer.
- Always use original spares, to help maintain the efficiency, safety and reliability of the appliance.
User caution
It is forbidden for any interference with the appliance other than those
actions allowed in this document.
CAUTION: Incorrect use
Any incorrect use can result in danger to the householder.
Using your boiler
Controls
To access controls:
To access controls first remove the front panel:
-
Unscrew the two screws [A] on the bottom of the front panel using the tool [B] provided.
The panel will drop down and can be carefully removed. -
Pull control drawer [C] fully forwards.
To replace: -
Push control drawer [C] firmly back into place.
-
Push the front panel up behind the top panel, push in and secure in place with the screws [A] using tool [B].
Using your boiler
Controls
- [A] Spanner/return button
- [B] Reset button
- [C] ECO button
- [D] Boiler LCD display
- [E] Central heating temperature control
- [F] Scroll up button
- [G] OK – Select/confirmation button
- [H] Scroll down button
- [I] Demand/fault indicator (blue)
- [J] Position for optional programmer
- [K] Hot water, heat store, temperature control
- [L] Diagnostic port (service engineer)
- [M] System pressure gauge
- [N] Burner service mode button (service engineer)
Operating the boiler
Switching the boiler on/off
- To switch on the boiler; turn on the water, oil and electricity supply to the boiler.
- Check the programmer/timer is correctly configured and is set to ON.
- Set the room thermostat to the desired temperature.
- Open and set thermostatic radiator valves as required.
- Turn the boiler controls to the required setting.
- To switch off the boiler; turn the programmer/timer to OFF for heating and hot water.
Setting central heating temperature
- Turn the central heating temperature control knob to the desired flow temperature between 50 and 82°C, this will be indicated on the digital display. This is not the room temperature but the flow temperature through the radiators.
- The radiator symbol will be displayed to confirm that the a central heating setting is being changed.
- The value is displayed during this process, press ok to exit or after five seconds of inactivity the boiler display will return to the default screen.
Controlling the central heating
- Set the programmer/timer to the correct time with the required ON/OFF periods.
- Turn the room thermostat to the temperature required.
- Set the thermostatic radiator valves to achieve the required temperature for each room.
Turning the central heating off during the summer
- Turn your programmer/timer to the off position.
- Please refer to the programmer/timer manufacturer’s instructions.
Setting the hot water temperature
The hot water temperature control knob sets the temperature of the heat store.
A high setting will give a higher hot water temperature and greater quantities
of hot water.
- Turn the hot water temperature control knob to the desired level between 1 and 8, this will be shown on the digital display.
- The tap symbol will be displayed to confirm that the hot water setting is being changed.
- The value is displayed during this process, press ok to exit or after five seconds of inactivity the boiler display will return to the default screen.
Domestic hot water (DHW)
The GREENSTAR HEATSLAVE II is microprocessor controlled and at low DHW flow
rates (washing hands etc), the burner will not fire up immediately when the
tap is opened as the heat store will meet the demand, but at high flow rates
(filling a bath for example) the burner will fire up to boost the heat store
and meet the demand.
If DHW is OFF on the programmer, the appliance will still supply DHW using
heat stored in the tank, but it will not reheat the tank, therefore the amount
of water available is limited but is adequate for washing up, filling basins
etc.
We recommend that DHW is timed off overnight and when the home is unoccupied
to save energy. The timer should be set for at least half an hour before
normal hot water demands are expected to reheat the heat store.
When reheating the heat store the controls will reclaim heat from the boiler
for the tank, this means that the pump will run (and the blue light will be
on) for some time after the burner has turned off whilst heat reclaiming takes
place.
WARNING: Scalding hazard
Care should be taken when using slow running taps and showers.
- In some circumstances, the combination of low water flow rate and high setting of the hot water control thermostat can result in very hot water.
Eco mode
Domestic hot water eco mode
Eco mode is an energy saving feature which alters the cycling function of the
burner for heating the heat store tank. In normal operation the burner will
fire more frequently between demands in order to maintain a stored temperature
close to the hot water set point you have entered. In Eco mode, the burner
fires less frequently between demands meaning that the heat store temperature
is maintained at a lower average level, but the tank set point remains the
same.
By selecting Eco mode you will be using less energy as the tank is allowed to
cool a little more before reheating to the set point.
Selecting eco mode
- Press and hold for at least four seconds to enter the energy saving Eco mode, when Eco mode is active, “Eco” will be displayed.
Exit eco mode
To exit ECO mode, press and hold for at least four seconds, “Eco” will disappear.
Frost protection
- The boiler has built in frost protection to protect the boiler, the boiler must have power for this to operate.
- If you are leaving the property unoccupied during cold weather, please leave your programmer on constant and your room thermostat set to 15°C.
- If the temperature within the boiler falls below 8°C the pump will run to circulate water and prevent the system freezing.
- If the temperature within the boiler falls below 4.5°C the boiler will fire immediately, bringing the boiler temperature up to 12°C to avoid the possibility of the system freezing.
- This process will be repeated until such time that the boiler temperature does not drop below 4.5°C.
System pressure
This boiler is fitted to a sealed heating system which is pre-pressurised.
Your installer will advise you of the minimum and maximum pressure indicated
on the pressure gauge.
Check regularly that the pressure is maintained.
Optimum system pressure when your boiler is cold (area A) and the pump is off. The indicated pressure will change as the pump switches on, for more accurate readings check pressure when the pump is not running.
- If the pressure gauge reads less than 1 bar then the system requires re-charging.
- Check for leaks on heating system (pipe work and radiator valves).
- Contact your installer or maintenance engineer if a permanent significant decrease or increase in pressure is indicated on the pressure gauge.
- Constantly having to re-pressuring the heating system should be investigated as the concentration of inhibitor in the system will be reduced; this can result in corrosion within the heating system
Filling loop
If the sealed system pressure within your system drops to below 0.5 bar (shown
on the pressure gauge) you will need to increase the pressure to ensure your
boiler continues to run without problems.
Your installer should have informed you where to find the filling system and instructed you in its use.
Once the external filling loop has been located, follow the instructions for re-pressurising the system.
- Unscrew blanking cap.
- Attach the hose to the valves, screw on hand-tight.
- Turn the handle/screwdriver slot through 90° to open valves.
- The handle/screwdriver slot will be in line with the valves.
- When the pressure reaches between the 1 and 1.5 bar marks (zone A), turn the handles/screwdriver slots back, through 90°, to close the valves.
- The handle/screwdriver slot will be at 90° to the valves.
- Remove the hose and replace the blanking caps.
Maintenance
Troubleshooting
Boiler alert state
Should a fault develop with this boiler (or the system), the boiler will enter
into a fault conditions
- A fault condition is indicated by a flashing blue operation/ fault light and a triangular alert symbol on the display. A flashing fault code is also displayed, see figure 8.
This type of fault can often be cleared by pressing the Reset button .
Fault codes 9F and 855
- This is a burner lockout condition, press the Reset button to restart the burner
- If the burner fails to fire and fault 9F 855 is displayed again, check the oil supply to the boiler
- If you try more than four times to reset the boiler and fail, no more resets can be attempted and the fault code 9F 856 will be displayed, call Worcester, Bosch Group for assistance, quoting the fault codes, contact details are on the back page.
Boiler reset
- Press the Reset button on the fascia to clear the fault.
Reset and a tick symbol will be briefly displayed.
- If the reset was successful the boiler will return to normal operation.
- If the reset was not successful then the fault code will be displayed again, and the blue operation/fault light will continue to flash.
- Make a note of these fault codes, in the table below as an example see figure 8, fault codes E5 and 218.
- Contact Worcester, Bosch Group for assistance and quote any fault codes displayed.
Flashing fault code Three figure number
e.g. E5| e.g. 218
|
|
|
|
Boiler stops with no fault code
In most cases these fault conditions will clear automatically when the
associated fault clears e.g. waiting for an area of the boiler to cool down.
If the boiler fails to automatically reset itself after a period of 30mins,
call Worcester, Bosch Group, contact details are on the back page of this
manual.
Servicing
You must have the boiler regularly serviced by a competent, qualified OFTEC
registered engineer using approved spares, to help maintain the economy,
safety and reliability of the boiler. The boiler should be serviced once each
year after installation unless the installation conditions and usage demand
more frequent services.
The service engineer must complete the Service Record in the checklist after
each service. The completed checklist will be required in the event of any
warranty work and may be required by the local Building Control Inspector.
The checklist and service interval record can be found at the rear of the
Installation, Commissioning and Servicing Instructions.
Fault finding
Problem | Cause | Remedy |
---|
Boiler stops working, blue light and warning triangle flashing and fault code
displayed| Internal error| Press the Reset button and the boiler should
restart, if not call Worcester, Bosch Group, quoting fault codes
Boiler stops with no fault codes| Possible overheat| Wait 30 minutes for
boiler to cool
Boiler stops working, blue light and warning triangle flashing and fault codes
9F 855 are displayed| Burner lockout| Press the Reset button to restart the
burner.
If the burner fails to fire and fault 9F 855 is displayed again, check the oil level in the tank.
Fault codes 9F 856| More than 4 attempts at a reset during Burner lockout fault 9F 855,
no more reset attempts can be made.
| Call Worcester, Bosch Group, quoting fault codes
Desired room temperature is not reached| Thermostatic radiator valve(s) set
too low| Increase thermostatic radiator valve setting(s)
Room thermostat set too low| Increase room thermostat setting
Temperature control for CH flow on boiler set too low| Increase CH flow
temperature control setting
Air trapped in heating system| Bleed radiators and recharge heating system
Desired room temperature exceeded by large amount| Radiators are too hot| Turn
down thermostatic radiator valves/room stat
Room temperature rises instead of
falling
| Clock is incorrectly set| Check setting
No display or display unit does not
respond
| Momentary power failure| Switch off boiler at master switch, wait 30
seconds then switch on again
Hot water temperature too low| Hot water temperature set too low| Check
setting
Hot water not in timed period on the programmer| Check programmer settings
System pressure low| Leak within the heating system| Check system for obvious
leaks
System gassing
WARNING
Caution must be exercised when venting radiators or adjusting system pressure
after commission of your boiler.
Do not repeatedly vent your radiators, if the problem persists, contact a
heating engineer.
- Do not vent air from radiators whilst the central heating is switched on: turn your boiler off.
- Whilst venting radiators do not allow the pressure on the boiler to drop below the pressure at which it is normally set.
CAUTION
If the pressure in your heating system is repeatedly rising (this can be
checked via the boiler pressure gauge and should be checked when the system is
cold), and especially if you need to keep venting the radiators, urgent action
is required and you must contact a heating engineer. This can indicate that
there is corrosion occurring within the heating system.
- This must be properly addressed to prevent serious damage to the entire system.
- Failure to properly maintain the heating system may affect your warranty.
Maintaining your boiler
Your new boiler represents a long term investment in a reliable, high quality
product.
In order to realise its maximum working life and to ensure it continues to
operate at peak efficiency and performance, it is essential that servicing and
maintenance checks are performed at least once a year by an OFTEC engineer or
other suitably qualified person.
If you would like to know more about servicing options from Worcester, Bosch
Group, please visit worcester-bosch.co.uk. Please tick the appropriate box on
your warranty registration card for further details of the Worcester, Bosch
Group Service Contract.
When your boiler requires servicing please contact a Worcester, Bosch Group
contact centre (see inside front cover for details).
In addition to the service contract we are pleased to offer a one-off annual
service or breakdown call out for your boiler. Maintenance tips
Regularly check the oil level in the tank. Running the tank empty or low can
lead to damage to the burner.
Do not obstruct the flue outlet or the air inlet.
Use in hard water areas
In exceptionally hard water areas a device to prevent scale formation may be
fitted. Installation of a scale inhibitor assembly should be in accordance
with the requirements of the local water company. An isolating valve should be
fitted to allow for servicing.
General information
Important information
WARNING: External equipment operating at 230 Volts must not be serviced
or repaired during adverse weather conditions.
Do not use pressure washers or steam cleaners on this appliance or cabinet.
Fuel
This appliance is designed to use Kerosene (Class C2), no other fuel must be
used.
Boiler location
WARNING: This boiler must not be installed where there is a potential for excessive ground water coverage.
To prevent “wetting” it is recommended that the flue terminal faces away from
walls.
Never allow the flue terminal or air inlet to become obstructed by plants or
any other objects.
This boiler is only suitable for installing externally at a suitable location
onto a fixed, permanent, rigid surface capable of supporting the boiler
weight. Wood and tarmac hard-standings are not recommended.
The boiler must be installed on a flat level surface to ensure that condensate
does not enter the primary heat exchanger.
The cabinet is not load bearing, and only provides weather protection for the
boiler inside.
There must be sufficient hard standing and access around the boiler for
servicing.
Installation & servicing clearances
General notes
To get the best from your boiler. please read these instructions carefully.
Central heating systems
During the first few hours of operation of the central heating system, check
that all radiators are being heated at an even rate. If the top of a radiator
is at a lower temperature than the bottom then it should be vented by
releasing air through the venting screw at the top of the radiator. Ask your
installer to show you how this is done. Repeated venting will reduce the
quantity of water in the system and this must be replenished for safe and
satisfactory operation of the boiler.
When excessive venting or water leaks are found in the system you must contact
a service engineer to inspect the installation and rectify any fault.
Only use additives compatible with the boiler and system. Use of incompatible
additives can cause damage and will invalidate the boiler guarantee.
Condensate drain
This is a condensing boiler and the terminal will, at times give out a plume
of water vapour. This is quite normal.
The boiler also produces quantities of condensate which is discharged
regularly via a pipe to disposal point. This pipe must not be blocked or
altered in any way.
Clearances – Service
Your installer will have provided adequate space around the boiler for safety
and servicing access.
Do not restrict this space with the addition of trellises, fences etc. next to
the boiler.
Room thermostat
A room temperature controller must be fitted to control the central heating.
Refer to instructions supplied with the thermostat for information on siting
and setting.
Thermostatic radiator valves
It is recommended that this type of valve is fitted to all but one of the
radiators (or at least those in the sleeping accommodation). The remaining
radiator, which must be where the room thermostat is located, should be un-
controlled and must be left open.
Energy saving
Tips on energy saving
Room thermostats
Reducing the setting of the room thermostat by 1°C can reduce fuel consumption
by up to 10%.
New control systems
Upgrade your heating control system with the latest equipment available. The
minimum level of control for a heating system is a programmer, interlocking
room thermostat and thermostatic radiator valves.
Radiators
More often than not radiators will be sited underneath a window, so the warm
air from the radiator heats the colder incoming air from the window.
The performance of the radiator will be affected if the curtains are allowed
to drape over the radiator or shelves are fitted above it.
The positioning of furniture and tables in front of the radiator should also
be avoided.
It is advisable to manually adjust all radiator valves every 2-3 months to
prevent them from sticking. It is also important that the plastic tops of all
valves are always in position and not cracked or damaged to help prevent
accidents. Care should be taken when vacuum cleaning carpets to avoid damage
to valves and pipework.
The heating system and the outputs of the radiators have been carefully
selected by your installer. The temperature obtainable in any given room is
dependent on all radiators being operated at the same time. If you decide to
turn off radiators in unused rooms, spare bedrooms etc., you may experience
slightly lower room temperatures in rooms adjacent to unheated rooms.
Heating economically
The boiler is designed to provide a high level of comfort while keeping oil
consumption and the resulting environmental effect as low as possible.
The central heating control on the boiler should be set as low as possible
while still maintaining a comfortable room temperature.
The temperature of each room can be set individually using the thermostatic
radiator valves (except the primary room with the room thermostat).
Roof insulation
Around 30% of the heat loss from a property is through the roof. Replace any
old insulation with new insulation, preferably to a minimum thickness of
200mm.
Window frames
Single glazed windows, particularly those with steel frames, can lose a great
deal of heat.
Consideration should be given to replacement with PVCu or wooden framed double
glazed units.
Curtains
Lined curtains, or heavier full length curtains can provide excellent
insulation. However, always ensure that the curtains do not drape over
radiators.
Draughts
Try to ensure that draughts around doors, windows, letterboxes and keyholes
etc., are reduced by using a suitable draught excluder.
WARNING
Do not block or seal any air vents that are installed to ensure the central
heating boiler (or other appliance) operate safely.
Guarantee
Fault or breakdown
This boiler is supported in mainland UK by Worcester, Bosch Group, part of
Bosch Thermotechnology Ltd.
Specialist trained, Worcester, Bosch Group Service Engineers are available to
attend in the unlikely event that a breakdown occurs on this boiler.
-
No charge will be made for parts and/or labour providing
-
A boiler fault is found and the boiler has been installed within the guarantee period. Reasonable evidence of this must be supplied on request.
-
A call-out charge will be made where
-
The boiler has been installed for longer than the guarantee period.
-or- -
Our Field Service Engineer finds no fault with the boiler ( Note).
– or- -
Evidence cannot be provided that the first year service inspection has been carried out.
(i.e. an entry in the service interval record found at the rear of the boiler installation and servicing manual).
– or- -
The cause of breakdown is misuse or with other parts of your plumbing/heating system, or with equipment not supplied by Bosch Thermotechnology Ltd.
-
Before calling the help line check the central heating system pressure. If the pressure is low then check for obvious leaks around the heating system; repair before the system is re-pressurised
-
For further support refer to the trouble shooting tool on the website.
No boiler fault is found on over 30% of all service call outs.
Please read this guide carefully to gain a good understanding of the operation of your boiler. In the case of a suspected fault, refer to the fault finding section of this guide.
If in doubt contact our Technical Support
In the event of an boiler fault or breakdown plea se contact our Service
Department. Your service administrator will arrange for an Engineer to call
with the minimum of delay. Under normal circumstances this will be from 1 to 3
working days (excluding weekends) for priority breakdown situations (no hot
water and/or heating).
Invoices for attendance and repair work carried out on this boiler by any
third party will not be accepted.
Boiler data label
The data label can be found on the inside of the left hand side panel.
To access first remove the front panel:
- Release the two latches [A] on the bottom of the front panel using the key [B] provided.
- The panel will drop down and can be carefully removed.
To replace
- Push the front panel up behind the top panel, push in and secure in place with the latches [A] using the key [B].
(You can record this information on the inside back cover of this manual.)
Guarantee registration
You should complete and return the postpaid Guarantee Registration Card within
30 days of installation.
Returning your card will register you as the owner of your new boiler and will
assist us in maintaining an effective and efficient customer service by
establishing a reference and permanent record for your boiler.
This does not affect your statutory rights.
For your own records
Model
Serial number
(See identity label inside boiler casing)
____ Type/size
Date of installation
Installer details
Your guarantee
This boiler is guaranteed against faulty materials or workmanship from the
date of installation subject to the following conditions:
-
During the period of this guarantee any components of the unit which are proved to be faulty or defective in manufacture will be exchanged or repaired free of material charges and free of labour charges if repaired directly by Bosch Thermotechnology Ltd.
-
The householder may be asked to prove, when requested, the date of installation, that the boiler was correctly commissioned and, where appropriate, that the 12 month service inspection has been carried
-
out to the satisfaction of Bosch Thermotechnology Ltd.
This should be documented in the Oil Boiler Commissioning Checklist and Service Interval Record in the back of the Installation, Commissioning and Servicing manual. -
Bosch Thermotechnology Ltd will not accept responsibility for damage caused by faulty installation, neglect, misuse or accidental damage and non-observance of the instructions contained in the
-
Installation and Users Instructions manuals.
-
The boiler has been used only for normal domestic purposes, for which it was designed.
-
This guarantee applies only to equipment purchased and installed in the mainland UK.
-
This guarantee is given in addition to all your normal statutory rights.
-
Worcester, Bosch Group is a brand name of Bosch Thermotechnology Ltd.
Guarantee registration
Your Greenstar appliance carries a guarantee against faulty material or
manufacture subject to Terms and Conditions. To read the full Terms and
Conditions please visit us on-line at www.worcester-
bosch.co.uk/guarantee. The
guarantee registration form is available on the same page and can be completed
and submitted electronically.
Alternatively, please telephone one of our Guarantee Registration advisors on
0330 123 2552.
Your statutory rights are not affected by the manufacturer’s guarantee.
If the boiler fails to give complete satisfaction, please make the general checks shown on the back page this manual before calling for a service engineer.
General checks before calling a Service engineer
Check the
- Oil level in the tank?
- Power to the boiler?
- Control settings?
No boiler fault is found on over 30% of all service call outs.
Please read the fault section of the manual before contacting our service team.
Worcester, Bosch Group
Cotswold Way, Warndon, Worcester WR4 9SW. Tel. 0330 123 9559
Worcester, Bosch Group is a brand name of Bosch Thermotechnology Ltd.
worcester-bosch.co.uk
6 721 843 981 (2022/01)
WORCESTER, BOSCH GROUP
- TECHNICAL SUPPORT: 0330 123 3366
- APPOINTMENTS: 0330 123 9339
- SPARES: 0330 123 9779
- LITERATURE: 0330 123 9119
- TRAINING: 0330 123 0166
- SALES: 0330 123 9669
References