EN.IO.APC.APR.ALW
APRIL 2023
Revision 02.B.001
USER’S MANUAL
PRESSURE AND DIFFERENTIAL PRESSURE TRANSMITTERS
APC-2000ALW, APR-2000ALW, APR-2000ALW/G, APR-2000ALW with diaphragm seals
APR-2000ALW-G Pressure Differential Pressure Transmitters
APLISENS S.A., 03-192 Warsaw, Morelowa 7 St.
tel. +48 22 814 07 77; fax +48 22 814 07 78
www.aplisens.com, e-mail:
export@aplisens.com
PRODUCT CODE – see: ➔ Transmitter identification.
The QR code or ID number identifies the transmitter and provides quick access
to the following documentation on the manufacturer’s website: user’s manual,
explosion-proof device user manual, technical information, declarations of
conformity and copies of certificates.
APC-2000ALW
ID:0005 0007 0005 0000 0000 0000 0001 05
https://www.aplisens.pl/ID/000500070005000000000000000105| APR-2000ALW
ID:0006 0007 0005 0000 0000 0000 0001 02
https://www.aplisens.pl/ID/000600070005000000000000000102
APC-2000ALW (Exi)
ID:0005 0007 0005 0000 0000 0015 0001 46
https://www.aplisens.pl/ID/000500070005000000000015000146| APR-2000ALW
(Exi)
ID:0006 0007 0005 0000 0000 0015 0001 43
https://www.aplisens.pl/ID/000600070005000000000015000143
APC-2000ALW (Exd)
ID:0005 0008 0006 0000 0000 0017 0001 86
https://www.aplisens.pl/ID/000500080006000000000017000186| APR-2000ALW
(Exd)
ID:0006 0008 0006 0000 0000 0017 0001 83
https://www.aplisens.pl/ID/000600080006000000000017000183
APC-2000ALW (Exi/Exd)
ID:0005 0004 0006 0000 0000 0018 0001 64
https://www.aplisens.pl/ID/000500040006000000000018000164| APR-2000ALW
(Exi/Exd)
ID:0006 0004 0006 0000 0000 0018 0001 61
https://www.aplisens.pl/ID/000600040006000000000018000161
---|---
APC-2000ALW
(For sea uses)
ID:0005 0007 0005 0000 0000 0003 0001 52
https://www.aplisens.pl/ID/000500070005000000000003000152| APR-2000ALW
(For sea uses)
ID:0006 0007 0005 0000 0000 0003 0001 49
https://www.aplisens.pl/ID/000600070005000000000003000149
APC-2000ALW (Exi)
(For sea uses)
ID:0005 0007 0005 0000 0000 0019 0001 44
https://www.aplisens.pl/ID/000500070005000000000019000144| APR-2000ALW
(Exi)
(For sea uses)
ID:0006 0007 0005 0000 0000 0019 0001 41
https://www.aplisens.pl/ID/000600070005000000000019000141
APC-2000ALW (Exd)
(For sea uses)
ID:0005 0008 0006 0000 0000 0020 0001 36
https://www.aplisens.pl/ID/000500080006000000000020000136| APR-2000ALW
(Exd)
(For sea uses)
ID:0006 0008 0006 0000 0000 0020 0001 33
https://www.aplisens.pl/ID/000600080006000000000020000133
APC-2000ALW (Exd)
(UKCA)
ID:0005 0008 0006 0000 0000 0022 0001 35
https://www.aplisens.pl/ID/000500080006000000000022000135| APR-2000ALW
(Exd)
(UKCA)
ID:0006 0008 0006 0000 0000 0022 0001 32
https://www.aplisens.pl/ID/000600080006000000000022000132
APC-2000ALW (Exi, Exi/Exd)
(UKCA)
ID:0005 0004 0006 0000 0000 0022 0001 62
https://www.aplisens.pl/ID/000500040006000000000022000162| APR-2000ALW
(Exi, Exi/Exd)
(UKCA )
ID: 0006 0004 0006 0000 0000 0022 0001 59
https://www.aplisens.pl/ID/000600040006000000000022000159
APC-2000ALW (IS)
ID:0005 0004 0006 0000 0000 0010 0001 68
https://www.aplisens.pl/ID/000500040006000000000010000168| APR-2000ALW
(IS)
ID:0006 0004 0006 0000 0000 0010 0001 65
https://www.aplisens.pl/ID/000600040006000000000010000165
APC-2000ALW (XPC)
ID:0005 0008 0006 0000 0000 0011 0001 89
https://www.aplisens.pl/ID/000500080006000000000011000189| APR-2000ALW
(XPC)
ID:0006 0008 0006 0000 0000 0011 0001 86
https://www.aplisens.pl/ID/000600080006000000000011000186
APC-2000ALW (IS/XPC)
ID:0005 0004 0006 0000 0000 0012 0001 67
https://www.aplisens.pl/ID/000500040006000000000012000167| APR-2000ALW
(IS/XPC)
ID:0006 0004 0006 0000 0000 0012 0001 64
https://www.aplisens.pl/ID/000600040006000000000012000164
APC-2000ALW (XP)
ID:0005 0008 0006 0000 0000 0013 0001 88
https://www.aplisens.pl/ID/000500080006000000000013000188| APR-2000ALW
(XP)
ID:0006 0008 0006 0000 0000 0013 0001 85
https://www.aplisens.pl/ID/000600080006000000000013000185
APC-2000ALW (IS/XP)
ID:0005 0004 0006 0000 0000 0014 0001 66
https://www.aplisens.pl/ID/000500040006000000000014000166| APR-2000ALW
(IS/XP)
ID:0006 0004 0006 0000 0000 0014 0001 63
https://www.aplisens.pl/ID/000600040006000000000014000163
APR-2000ALW/G
ID:0008 0007 0005 0000 0000 0000 0001 93
https://www.aplisens.pl/ID/000800070005000000000000000193| APR-2000ALW/G
(Exi, Exi/Exd)
(UKCA)
ID:0008 0004 0006 0000 0000 0022 0001 26
https://www.aplisens.pl/ID/000800070005000000000022000182
APR-2000ALW/G (Exd)
(UKCA)
ID:0008 0008 0006 0000 0000 0022 0001 26
https://www.aplisens.pl/ID/000800080006000000000022000126
APC-2000ALW (Exi, Exi/Exd)
(Inmetro Brasil)
ID: 0005 0004 0006 0000 0000 0021 0001 14
https://www.aplisens.pl/ID/000500040006000000000021000114| APC-2000ALW
(Exd)
(Inmetro Brasil)
ID: 0005 0008 0006 0000 0000 0021 0001 84
https://www.aplisens.pl/ID/000500080006000000000021000184
APR-2000ALW (Exi, Exi/Exd)
(Inmetro Brasil)
ID: 0006 0004 0006 0000 0000 0021 0001 11
https://www.aplisens.pl/ID/000600040006000000000021000111| APR-2000ALW
(Exd)
(Inmetro Brasil)
ID: 0006 0008 0006 0000 0000 0021 0001 81
https://www.aplisens.pl/ID/000600080006000000000021000181
APR-2000ALW/G (Exi, Exi/Exd)
(Inmetro Brasil)
ID: 0008 0004 0006 0000 0000 0021 0001 05
https://www.aplisens.pl/ID/000800040006000000000021000105| APR-2000ALW/G
(Exd)
(Inmetro Brasil)
ID: 0008 0008 0006 0000 0000 0021 0001 75
https://www.aplisens.pl/ID/000800080006000000000021000175
Symbols used
Symbol | Description |
---|---|
Warning to proceed strictly in accordance with the information contained in |
the documentation in order to ensure the safety
and full functionality of the device.
| Information particularly useful during installation and operation of the
device.
| Information particularly useful during installation and operation of an Ex
type device.
| Information on disposal of used equipment.
BASIC REQUIREMENTS AND SAFE USE
The manufacturer will not be liable for damage resulting from incorrect
installation, failure to maintain a suitable technical condition of the device
or use of the device other than for its intended purpose.
Installation should be carried out by qualified staff having the required
authorizations to install electrical and I&C equipment. The installer is
responsible for performing the installation in accordance with manual as well
as with the electromagnetic compatibility and safety regulations and standards
applicable to the type of installation. In systems with I&C equipment, in case
of leakage, there is a danger to staff due to the medium under pressure. All
safety and protection requirements must be observed during installation,
operation and inspections. If a malfunction occurs, the device should be
disconnected and handed over to the manufacturer for repair.
In order to minimize the risk of malfunction and associated risks to staff,
the device is not to be installed or used in particularly unfavourable
conditions, where the following hazards occur:
−possible mechanical impacts, excessive shocks and vibration;
− excessive temperature fluctuation;
− water vapour condensation, dusting, icing.
Changes made to the manufacturing of products may be introduced before the
paper version of the manual is updated. The up-to-date manuals are available
on the manufacturer’s website: www.aplisens.com.
INTRODUCTION
1.1. Purpose of the document
The subject of manual are smart pressure transmitters APC-2000ALW, smart
differential pressure transmitters APR-2000ALW, APR-2000ALW with diaphragm
seals (formerly APR-2200ALW), APR-2000ALW/G (formerly APR-2000GALW),
hereinafter referred jointly to as the transmitters. The manual applies to the
following versions: standard, PED, flameproof Exd (XP), intrinsically safe Exi
(IS) and Exi/Exd (IS/XP).
Within the meaning of Directive 2014/68/EU (PED), the transmitters are
designed to category I, module A. PED marking does not apply to additional
equipment of the transmitters, i.e. separators, valves, connectors, impulse
tubes, etc. In the manufacturer’s EU declarations of conformity, the
transmitters as designed above have the CE markings. The transmitters with
permissible overload of 200 bar and lower are manufactured in accordance with
good engineering practice according to article 4 point 3 of Directive
2014/68/EU.
The manual contains data, tips and general recommendations for safe
installation and operation of the transmitters, as well as troubleshooting in
case of possible failure.
The manual does not cover explosion protection issues.
The use of the equipment in hazardous zones without appropriate approvals is
forbidden.
It is mandatory to read:
− EN.IX.APC.APR.ALW Explosion-proof Device User Manual, containing important
information related to the installation of intrinsically safe and flameproof
versions of the transmitters;
− EN.FM.APC.APR.ALW Hazardous Area Installation Manual, containing important
information related to the installation of intrinsically safe (IS) and
explosionproof versions (XP) of the transmitters.
In addition, please refer to the Technical Information, which contains
detailed technical data, parameters and recommendations forinstallation and
operation.
1.2. Trademarks HART® is a registered trademark of FieldComm Group.
Windows® is a registered trademark of Microsoft Corporation.
Google Play® is a service registered and managed by Google® Inc.
1.3. Definitions and abbreviations
Table 1. Definitions and abbreviations
Item no. | Abbr. | Meaning |
---|---|---|
1 | LRV | “Lower Range Value” – the value of the set range expressed in |
physical units corresponding to the current of 4,000 mA, i.e. 0% of the output
setpoint. The set range cannot exceed the set range limits. The minimum width
of the set range |(URV-LRV)| is limited to 10% of the base range (URL-
LRL).
2| URV| “Upper Range Value” – the value of the set range expressed in
physical units corresponding to the current of 20,000 mA, i.e. 100% of the
output setpoint. The set range cannot exceed the set range limits. The minimum
width of the set range |(URV-LRV)| is limited to 10% of the base range
(URL-LRL).
3| LRL LSL| “Lower Range Limit” or “Lower Sensor Limit” – lower
limit of set range expressed in physical units. Value (URL-LRL) or
(USL-LSL) is referred to as the base transmitter range.
4| URL USL| “Upper Range Limit” or “Upper Sensor Limit” – upper
limit of set range expressed in physical units. Value
(URL-LRL) or (USL-LSL) is referred to as the base transmitter range.
5| LPL| “Lower Processing Limit” – lower limit of digital processing of
measured value. The transmitter processes a digital measurement up to 50% of
the base range width below the lower limit of set range LRL (LSL). After
reaching the LPL and when below this value up to LSAL, the transmitter
freezes the refreshing of digital value of the measurement. In this situation,
for Exd (XP) or Exi/Exd version of transmitter, error number E0128 will be
displayed on the display and diagnostic alarm mode I_AL < 3,600 mA will be
set. For standard or Exi transmitters, a message ‘’UndEr’’ will be displayed,
and diagnostic alarm mode will be activated depending on the settings I_AL <
3,650 mA or I_AL > 21,500 mA. Additionally, collective status PV_OUT_OF_LIMITS
and status PV_LOW_LIMITED in the Transducer Block will be set, which can be
read out in the diagnostic tab via HART communication.
6| UPL| “Upper Processing Limit” – upper limit of digital processing of
measured value. The transmitter processes a digital measurement up to 50% of
the base range width above the upper limit of set range URL (USL). After
reaching the UPL and when above this value up to USAL , the
transmitter freezes the refreshing of digital value of the measurement. In
this situation, for Exd or Exi/Exd (also IS, XP, IS/XP) version of trans-
mitter, error number E0128 will be displayed on the display and diagnostic
alarm mode I_AL < 3,600 mA will be set. For standard or Exi transmitters, a
message ‘’OvEr’’ will be displayed and diagnostic alarm mode will be activated
depending on the settings I_AL < 3,650 mA or I_AL > 21,500 mA.
Additionally, collective status PV_OUT_OF_LIMITS and status PV_HIGH_LIMITED in
the Transducer Block will be set, which can be read out in the diagnostic tab
via HART communication.
7| LSAL| “Lower Saturation Limit” – lower limit of the A/D transmitter
processing range. The lower limit of the A/D transmitter saturation is on the
pressure / differential pressure scale below the LPL point and is
associated with the minimum pressure, at which the analogue-digital pressure
measurement transmitter reaches the lower limit of the processing capacity.
The exact determination of this pressure is not possible, however usually the
pressure does not exceed the pressure corresponding to 200% of the base range
width (URL- LRL) below the lower limit of the digital processing of
measured LPL value. After reaching LSAL and when below this value,
error number E0136 will be displayed on the display and the diagnostic alarm
mode I_AL < 3,600 mA will be activated (applies to Exd or Exi/Exd (also IS,
XP, IS/XP) version of transmitter). For standard or Exi transmitters, error
number E0256 will be displayed and diagnostic alarm mode will be activated
depending on the settings I_AL < 3,650 mA or I_AL > 21,500 mA. Additionally,
collective status SENSOR_FAULT, PV_OUT_OF_LIMITS, status NOREF+ERR@AIN1_AD7794
in the Sensor Block and PV_LOW_LIMITED in the Transducer Block will be set,
which can be read out in the diagnostic tab via HART communication.
8| USAL| “Upper Saturation Limit” – upper limit of the A/D transmitter
processing range. The upper limit saturation point of A/D transmitter is on
the pressure / differential pressure scale above the UPL point and is
associ- ated with the maximum pressure at which the analogue-digital pressure
measurement transmitter reaches the upper limit of the processing capacity.
The exact determination of this pressure is not possible, how- ever usually
the pressure does not exceed the pressure corresponding to 200% of the base
range width (URL-LRL) above the upper limit of the digital processing of
measured UPL value. After reaching USAL and when above this value,
error number E0136 will be displayed on the display and the diagnostic alarm
mode I_AL < 3,600 mA will be activated (applies to Exd or Exi/Exd (also IS,
XP, IS/XP) version of trans- mitter). For standard or Exi transmitters, error
number E0256 will be displayed and diagnostic alarm mode will be activated
depending on the settings I_AL < 3,650 mA or I_AL > 21,500 mA. Additionally,
collective status SENSOR_FAULT, PV_OUT_OF_LIMITS, status NOREF+ERR@AIN1_AD7794
in the Sensor Block and PV_HIGH_LIMITED in the Transducer Block will be set,
which can be read out in the diagnostic tab via HART communication.
9| AL_L| Low current alarm.
10| AL_H| High current alarm.
11| I_AL| The alarm current set by the transmitter controller in the
current loop.
1.4. Transmitter set range
The figure below shows the transmitter set range and limits related to
allowable set range, digital processing range and saturation limits of A/D
pressure measurement transducer. As standard, values of 4 mA/20 mA currents
are assigned to LRV/URV points. In order to obtain reverse characteristics, it
is possible to reverse the assignment so that the LRV/URV points are assigned
to 20 mA/4 mA currents.
SAFETY
- The installation and start-up of the device and any activities related to operation shall be carried out after thorough examination of the contents of user’s manual and the instructions related thereto.
- Installation and maintenance should be carried out by qualified staff having the required authorizations to install electrical and measuring devices.
- The device shall be used according to its intended purpose in line with the permissible parameters specified on the nameplate (➔ Transmitter identification).
- The protection elements used by the manufacturer to ensure transmitter safety may be less effective if the device is operated in a manner not consistent with its intended purpose.
- Before installing or disassembling the device, it is absolutely necessary to disconnect it from the power source.
- No repairs or alterations to the transmitter electronic system are permitted. Assessment of damages and possible repair may only be performed by themanufacturer or authorized representative.
- Do not use instruments if damaged. In case of malfunction, the device must be put out of operation.
- In case of transmitters equipped with factory-mounted process connector of C and CR type, it is unacceptable to loosen the fixing screws of the connector cover.
TRANSPORT AND STORAGE
3.1. Delivery check
After receiving the delivery of the equipment, it is necessary to:
− make sure that the packaging and its contents were not damaged during
transport;
− check the completeness and correctness of the received order, and make sure
no parts are missing.
3.2. Transport
Transport of transmitters shall be carried out with the use of covered means
of transport, in original packages with diaphragm provided with protection.
The packaging shall be protected against movement and direct impact of
atmospheric factors.
3.3. Storage
Transmitters shall be stored in a factory packaging, in a room without vapours
and aggressive substances, protected against mechanical impact.
Allowable range of storage temperature: -40…80°C (-40…176°F).
GUARANTEE
General terms and conditions of guarantee are available on the manufacturer’s
website:
www.aplisens.com/ogolne_warunki_gwarancji.
The guarantee shall be repealed if the device is used against its intended
use, failure to comply with user’s manual or interference with the structure
of the device.
IDENTIFICATION
5.1. Manufacturer’s address
APLISENS S.A.
03-192 Warsaw
Morelowa 7 St.
Poland
5.2. Transmitter identification
Depending on the version of the transmitter, the nameplates may differ in the
amount of information and parameters.
Table 2. Symbols occurring on the transmitter nameplate
| Logo and name of manufacturer
---|---
| CE/UKCA mark
| CE/UKCA mark with the number of notified body
| QR code
TYPE:| Transmitter type
Process connection:| Process connector
ID:| Transmitter model ID
P| Measurement range
Tamb| Permissible range of ambient temperature
PS| Permissible static pressure
U| Power supply voltage
I| Output signal
Mat.| Material of wetted parts
Ser:- No.| Serial number
Electrical connection| Type of electrical connection
Year of production| Year of production
IP| IP protection rating
//Lower part of the nameplate//| Special execution
| Note about obligation to read the manual
Aplisens S.A. ul. Morelowa 7,03-192 Warszawa| Manufacturer address
5.3. CE or UKCA mark and declaration of conformity
The device has been designed to meet the highest safety standards, has been
tested and has left the factory in a condition that is safe for operation. The
device complies with the applicable standards and regulations listed in EU and
UK Declaration of Conformity. The CE or UKCA nameplate marking is dependent on
delivery region of the transmitter.
INSTALLATION
6.1. General recommendations
In order to avoid measurement errors caused by the accumulation of
condensate (in gas installations) or gas bubbles (in liquid installations) in
impulse lines, assembly solutions using constructions based on available
engineering knowledge should be used. For a gaseous medium, this may mean
installing the transmitters above the pressure measuring point, and for
liquids below this point. Differential pressure transmitters for gases
APR2000ALW/G should be obligatorily installed vertically.
6.1.1. Examples of transmitter installation
Figure 2. Examples of pressure transmitter installation
Figure 3. Examples of differential pressure transmitter installation
Figure 4. Examples of transmitter installation on tanks
6.1.2. Installation instructions for transmitters with distance
separators
The protection of the separator diaphragm can only be removed shortly before
installation.
Hydrostatic pressure of the manometric liquid column in the transmitter-
separator system may cause incorrect indication of the measured value. After
installation, the transmitter must be pressure-reset.
Do not clean or touch separator diaphragms using hard or pointy objects.
Separators with pressure transmitter form a closed, calibrated system filled
with gauge fluid. The opening for filling the device with gauge fluid is
sealed and must not be opened.
When choosing a mounting location, it is necessary to ensure sufficient stress
relief of the capillaries tension in order to avoid excessive bending.
Incorrect installation of the sealing may result in incorrect measurement
indications.
Special attention must be paid when selecting correct dimensions of the
sealing.
As standard, the separators are not provided with the gaskets.
ELECTRICAL CONNECTION
7.1. Cable connection to transmitter internal terminals
All connection and installation operations shall be performed with
disconnected supply voltage and other external voltages, if used.
Failure to provide proper connection of the transmitter may result in danger.
Risk of electric shock and/or ignition in potentially explosive atmospheres.
7.1.1. Cable connection
In order to perform correct connection of the cables, the following steps
shall be performed:
- disconnect power supply;
- unscrew the rear cover of the transmitter body to access the power connector;
- pull the cable through the cable gland;
- connect the transmitter according to the figure below, paying attention to the correct tightening of the bolts fixing the conductor core to the terminal;
- check the correct fixing of the HART local communication jumper;
- tighten the rear cover of the transmitter body;
- leaving a small clearance of the cable inside the body, tighten the gland nut so that the gland seal is clamped on the power cable.
Figure 5. Electrical connection to transmitter
- Housing.
- Jumper for local HART communication.
- Internal ground terminal.
- External ground terminal.
- Transmitter power terminals, 4…20 mA current loop.
- Ammeter connection terminals for uninterruptible current measurement (optional).
- Designation SA variant with integrated overvoltage protection (applies to Exi version).
In hazardous zone, do not unscrew the housing covers after connecting the Exd
flameproof transmitter to the power source.
7.1.2. Connection of transmitter with the option of using local HART
communication
The transmitter allows to use the local HART communication. To do this you can
use a HART communicator unit or modem connected to a computeror a smartphone.
In order to establish the local communication, it is necessary to:
- remove HART communication jumper (item 2);
- connect the communicator or modem to electrical terminals (item 7).
Opening of the HART jumper results in applying resistance of 240 Ω in series
in line 4…20 mA. This resistance reduces voltage on transmitter supply
terminals by approximately 5 V DC for Exd or Exi/Exd transmitters (5,28 V DC
for standard or Exi transmitters) for maximum current that can be set by the
transmitter. To avoid the supply voltage deficit on the transmitter terminals,
the HART jumper must be dismantled only for the time of performing the HART
local communication.
Connection diagram of the communicator or modem to transmitter power supply
and measurement system is presented below:
Figure 6. Electrical connection 4…20 mA of HART to transmitter in standard version
- Housing.
- Removed local HART communication jumper.
- Internal ground terminal.
- External ground terminal.
- Transmitter power terminals, 4…20 mA current loop.
- Ammeter connection terminals for uninterruptible current measurement (optional).
- Terminals – point of connection of the communicator or HART modem.
Figure 7. Electrical connection 4…20 mA of HART to transmitter in Exd version
Figure 8. Electrical connection 4…20 mA of HART to transmitter in Exi version
It is mandatory to read:
- EN.IX.APC.APR.ALW Explosion-proof Device User Manual, containing important information related to the installation of intrinsically safe and flameproof versions of the transmitter;
- EN.FM.APC.APR.ALW Hazardous Area Installation Manual, containing important information related to the installation of intrinsically safe (IS) and explosionproof versions (XP) of the transmitter.
The converter may also be operated using Aplisens Mobile Configurator
installed on smartphones with Android system and connected using wireless
communication.
The software is available on Google Play® :
https://play.google.com/store/apps/details?id=com.aplisens.mobile.amc.
7.2. Transmitter power supply
7.2.1. Transmitter supply voltage
Power cables may be live.
There is a risk of electric shock and/or explosion.
Installation of the transmitter in explosion-risk atmospheres must comply with
national standards and regulations.
All explosion protection data is given in manual EN.IX.APC.APR.ALW.
Table 3. Permissible transmitter supply voltages
Version | Minimum supply voltage | Maximum supply voltage |
---|---|---|
Exi/Exd* | IS/XP** | **11,5 V DC***** |
55 V DC (Exd, XP)
Exd*| XP| 13,5 V DC**| 55 V DC
Standard| 10,0 V DC| 55 V DC
Exi*| 10,5 V DC| 30 V DC
IS| 11,5 V DC| 30 V DC**
- For details on intrinsically safe and flameproof version see manual EN.IX.APC.APR.ALW.
** For details on intrinsically safe (IS) and flameproof variant (XP) see manual EN.FM.APC.APR.ALW.
* Minimum supply voltage with backlight off. Possibility of turning on the backlight only by manufacturer at the transmitter production stage (then Umin=14,5 V DC).
** Minimum supply voltage with backlight on. Possibility of turning off the backlight only by manufacturer at the transmitter production stage (then Umin=10,5 V DC).
7.2.2. Uninterruptible current measurement in 4…20 mA current loop
The transmitter is capable of continuous current measurement in the current
loop using an ammeter. In order to maintain the current measurement error
below 0,05%, the internal resistance of the ammeter shall be less than 10 Ω.
Ammeter connection diagram – see: ➔ Figure 5. Electrical connection to
transmitter.
7.2.3. Specifications of electrical switching terminals
Internal electrical switching terminals are suitable for conductors with the
cross-section from 0,5 to 2,5 mm² . The internal and external electrical
ground terminal of the body is suitable for conductors with cross-section from
0,5 to 5 mm² .
7.2.4. Cabling specification
Aplisens S.A. recommends using two-wire screened twisted pair cable. The outer
diameter of the cable shell from 5 to 9 mm is recommended.
7.2.5. Resistance load in power supply line
The power line resistance, power source resistance and other additional serial
resistances increase the voltage drops between the power source and the
transmitter terminals. The maximum current of IS, Exd, XP, Exi/Exd or IS/XP
transmitters under normal operation conditions is defined as I_max = 20,500 mA
- E, where E is the acceptable safety error, which is ± 0,160 mA. The maximum current of standard or Exi transmitters under normal operation conditions is 20,500 mA, but during high alarm the value of current I_max is 22,000 mA. The maximum resistance value in the power circuit (along with the power cables resistance) is defined by the formula:
where:
U – voltage at the supply terminals of the 4…20 mA current loop [V].
Umin – minimum supply voltage of transmitter ➔ Table 3. Permissible
transmitter supply voltages.
RL_MAX – maximum power supply line resistance [Ω].
7.2.6. Shielding, equipotential bonding
When using a cable in the screen, connect the screen on one side to ground,
preferably in place where transmitter is powered.
7.3. Equipotential bonding
When using an intrinsically safe transmitter with an additional overvoltage
protection, having the designation “SA version” on the plate, the transmitter
should be powered from a galvanically separated power source or, if this is
not possible, equipotential bonding of the transmitter and the power supply
device should be ensured by means of equipotential bonding conductors. In this
respect the locally applicable regulations must be observed.
7.4. Overvoltage protection
Transmitters comply with EMC standards for safety-related products used in
general industrial environment. Transmitters in standard and flameproof
versions are fitted with overvoltage protection. In intrinsically safe
transmitters, in order to increase the resistance to excessive surge, it is
possible to use the overvoltage protection SA version. Transmitters with
integrated overvoltage protection SA should be grounded. Overvoltage
protection parameters in transmitters in standard, Exd, XP or SA versions:
- discharge threshold voltage: 230 V DC;
- discharge threshold impulse voltage: 450 V (impulse 100 V/µs);
- discharge threshold impulse voltage: 600 V (impulse 1000 V/µs);
- discharge current for 1 surge: 20 kA, 8/20 µs;
- discharge current for 10 surges: 10 kA, 8/20 µs;
- discharge current for 300 surges: 200 A, 10/1000 µs.
7.5. Final inspection of cabling
After completing the electrical installation of the transmitter it is
necessary to check the following:
- does the supply voltage measured at the transmitter terminals at maximum set current match the range of supply voltage specified on the transmitter nameplate?
- Is the transmitter connected according to the information given in section ➔ Cable connection to transmitter internal terminals?
- Are all the screws tightened?
- Are the transmitter covers tightened?
- Are the cable gland and the gland plug tightened?
START-UP
As standard, the transmitter is adjusted to a set range equal to the base
range, unless a specific set range is provided in the order. The base range
and the basic unit of the transmitter can be read out from its nameplate (➔
Transmitter identification).
Use the transmitter within the allowable pressure limits. Risk of injury due
to component breakage after exceeding the maximum permitted operating
pressure.
8.1. Alarm configuration
Transmitters has a developed internal diagnostics, which monitors the work of
their electronic circuits, process and environmental parameters. For
transmitters in Exd or Exi/Exd (also IS, XP, IS/XP) version, diagnosed
dangerous states or malfunctions of the internal transmitter systems result in
setting the alarm current I_AL < 3,600 mA. For transmitters in standard or Exi
version, diagnosed dangerous states or malfunctions of the internal
transmitter systems result in setting the alarm current depending on the
configuration I_AL < 3,650 mA or I_AL > 21,500 mA. The user has an option of
enabling/disabling of the current alarms. Current alarms are disabled by
default. The figures below shows the normal operation ranges of the
transmitter process output and the ranges of saturation and alarm currents.
Figure 9. Set range current, saturation currents, alarm currents of transmitters in Exd or Exi/Exd (also IS, XP, IS/XP) version
- Set 4…20 mA current area is corresponding to setpoint 0…100% of the process output.
- Lower saturation current of 3,800 mA for NAMUR mode.
- Lower saturation current of 3,900 mA for NORMAL mode.
- Upper saturation current of 20,500 mA for NAMUR and NORMAL mode.
- Alarm current area I_AL < 3,600 mA for internal diagnostic alarms.
- Alarm current area I_AL > 20,660 mA for alarms related to safe failures with external diagnostics.
Figure 10. Set range current, saturation currents, alarm currents of transmitters in standard or Exi version
- Set 4…20 mA current area is corresponding to setpoint 0…100% of the process output.
- Lower saturation current of 3,800 mA for NAMUR mode.
- Lower saturation current of 3,900 mA for NORMAL mode.
- Upper saturation current of 20,500 mA for NAMUR and NORMAL mode.
- Alarm current area AL_L < 3,650 mA for internal diagnostic alarms.
- Alarm current area AL_H > 21,500 mA for internal diagnostic alarms.
The transmitter diagnostics continually tests the environmental parameters:
- Temperature of the pressure measurement structure sensor.
- Temperature of the ADC transducer converting the electric signal from the pressure sensor to the digital value of measurement.
- Temperature of the CPU structure (transmitter’s main microcontroller). For transmitters in Exd or Exi/Exd (also IS, XP, IS/XP) version, if the operating temperature limits are exceeded, the diagnostics will trigger an alarm I_AL < 3,600 mA. Temperature return to permissible range of the transmitter operation will result in deactivation of the diagnostic alarm mode and return to normal operation. For transmitters in standard or Exi version, if alarms from 2, 3 and 4 process variable (temperatures) are enabled, when the transmitter operating temperature limits are exceeded, the diagnostics will trigger an alarm depending on the settings AL_L < 3,650 mA or AL_H > 21,500 mA. Temperature return to permissible range of the transmitter operation will result in deactivation of the diagnostic alarm mode and return tonormal operation.
The transmitter diagnostics continually tests the pressure process parameters:
- If the pressure/differential pressure value increases above 50% of the base range width from URL point reaching the UPL point, the diagnostics of transmitter in Exd or Exi/Exd (also IS, XP, IS/XP) version will trigger an alarm I_AL < 3,600 mA. The return of the pressure / differential pressure below the UPL point will result in deactivating the alarm and returning the transmitter to its normal operation. In case of transmitters in standard or Exi version, if the pressure / differential pressure value increases to the upper limit of ADC measurement converting transducer, reaching the USAL point, the diagnostics will trigger an alarm depending on the configuration AL_L < 3,650 mA or AL_H > 21,500 mA. The return of the pressure / differential pressure below the USAL point will result in deactivating the alarm and returning the transmitter to its normal operation.
- If the pressure / differential pressure value decreases below 50% of the base range width from LRL point reaching the LPL point, the diagnostics of transmitter in Exd or Exi/Exd (also IS, XP, IS/XP) version will trigger an alarm I_AL < 3,600 mA. The return of the pressure / differential pressure above the LPL point will result in deactivating the alarm and returning the transmitter to its normal operation. In case of transmitters in standard or Exi version, if the pressure / differential pressure value decreases to the lower limit of ADC measurement converting transducer, reaching the LSAL point, the diagnostics will trigger an alarm depending on the configuration AL_L < 3,650 mA or AL_H > 21,500 mA. The return of the pressure / differential pressure above the LSAL point will result in deactivating the alarm and returning the transmitter to its normal operation.
The transmitter diagnostics continually tests electric parameters and
software resources of transmitter:
- If the inner diagnostics detects the malfunctioning or failure of the transmitter which are not critical with regard of integrity of hardware and software – software of the transmitter in Exd or Exi/Exd (also IS, XP, IS/XP) version will activate alarm I_AL < 3,600 mA. The diagnostic alarm condition will continue until the failure or damage is resolved. Error/failure number Exxxx will appear on LCD2; the ERROR message will be displayed on LCD3. The image will blink to attract the operator’s attention. The transmitter will set the current output to alarm status I_AL < 3,600 mA. In case of transmitter in standard or Exi version, software will activate alarm depending on the configuration AL_L < 3,650 mA or AL_H > 21,500 mA. The diagnostic alarm condition will continue until the failure or damage is resolved. Error/failure number Exxxx will appear on LCD2; the ERROR message will be displayed on LCD3. The image will blink to attract the operator’s attention.
- If the internal diagnostics detects malfunctioning or failure of the transmitter which are critical from the point of view of integrity of hardware and software, such as the hardware error of RAM, FLASH, SVS, CPU logs, mathematical computation error, or if there is a difference exceeding 1% between the set process current and the current measured in the line, the transmitter will immediately stop operation and activate the critical diagnostic alarm mode. The transmitter display will be switched off. HART communication with the transmitter will not be possible. In case of transmitter in Exd or Exi/Exd (also IS, XP, IS/XP) version, in the critical diagnostic alarm mode the additional protection of the transmitter disconnects its power supply from loop 4…20 mA. In such a case, alarm current I_AL is much lower than 3,600 mA and is less than 0,500 mA. The transmitter will remain in OFF state until the power is disconnected and the transmitter is switched on again. In case of transmitter in standard or Exi version, in the critical diagnostic alarm mode the additional protection of the transmitter will lower the current in the loop 4…20 mA. In such a case, alarm current I_AL is much lower than 3,650 mA, amounting about 0,150 mA. The transmitter will remain in the critical alarm status for approx. 10 seconds, then it will attempt to restart. When the internal diagnostics detects no hardware errors after restart, the transmitter will return to normal operation.
8.2. Configuration of operating mode
Before starting the work with the transmitter, the following parameters must
be configured:
- basic unit of transmitter;
- processing characteristics;
- the beginning of the set LRV range;
- the end of the set URV range;
- damping time constant;
- NORMAL/NAMUR analogue output operation mode;
- analog output operation mode in alarm status AL_L/AL_H (applies to transmitters in standard or Exi version);
- alarm mode for indicating environmental events and defects;
- transmitter tag (TAG/LONG_TAG);
- LCD display configuration parameters;
- setting of the settings change lock password.
8.3. Correction of impact of transmitter mounting position on site –
pressure reset
Once the transmitter is mounted in a target location, it must be reset. This
operation will eliminate the possible influence of the mounting position on
the indication of pressure / differential pressure. In order to do so:
- in case of relative pressure transmitter without pressure supplied (vented), perform the pressure reset operation using the local MENU or HART communication;
- in the case of a differential pressure transmitter, at compensated pressures on the L and H supply, perform the pressure reset operation by means of local MENU or HART communication;
- in case of absolute pressure transmitter the resetting is only possible with an absolute pressure calibration device. Otherwise an attempt to reset the transmitter will display an error.
8.4. Correction of impact of spacing of distance separators on site
In pressure / differential pressure transmitters with distance separator(s), it is required to make an adjustment depending on the impact of the separator position. The adjustment is made after the transmitter has been installed on site, before filling the plant. To do this, select “SETLRV” and “BYPRES” in the transmitter menu. Upon acknowledgement (“DONE”), a 4 mA signal, including the impact of the separator positions, is set in the transmitter. The 20 mA signal is set by selecting “SETURV”. For level measurements, fill the tank to a level corresponding to 20 mA, select “BYPRES” and confirm. If it is not possible to fill the tank/plant to the value corresponding to the 20 mA signal, the URV value may be set by selecting “BYVALU” function and entering the value. The value (in pressure units) is calculated by adding the planned measurement span value to the pressure value (PV) obtained after setting the LRV signal (4 mA).
Once the transmitter parameters have been entered and it has been reset at the workstation, it is required to:
-
Secure the device against the possibility of making changes in the local setpoint change MENU.
-
Set your own password different from default password of “00000000”. The new password may consist of any combination of 8 hexadecimal characters 0…9, A…F. Store the password in a safe place.
If the password is lost, its restoration or resetting to factory settings may only be performed by the manufacturer. -
Activate the setpoint change lock to secure the transmitter against accidental, unintentional change of parameters.
Pressure reset can be done via local setpoint change MENU or HART
communication. The remaining operations described in this section may only be
performed using HART communication.
For Exd or Exi/Exd (also IS, XP, IS/XP) type transmitters, opening the housing
cover in the hazardous zone in order to use the local setpoint change MENU is
forbidden.
8.5. Flow measurements
Differential pressure transmitter APR-2000ALW can be used for venturi flow
measurements. Flow measurements often require setting of pressure-processing
characteristics for output current setpoints other than linear. In APR-2000ALW
transmitter the following characteristics are available for the user:
- linear characteristics;
- second-stage root characteristics with relay characteristics and 0,2% hysteresis in the deadband
- manufacturer’s dual linear characteristics No.1+ second-stage root characteristics for constant deadband = 0,6% of setpoints;
- manufacturer’s single linear characteristics No.2+second-stage root characteristics and 0,2% hysteresis in the deadband;
- square characteristics;
- special characteristics based on user-modified table.
8.6. Level measurements
Transmitters APC-2000ALW, APR-2000ALW, APR-2000ALW with diaphragm seals can be
used for liquid level measurement in open or closed tanks. Examples of
transmitter installation are shown in ➔ Figure 4. Examples of transmitter
installation on tanks. The transmitter can be configured in physical units of
liquid column such as water and mercury at several temperatures of the liquid.
It is also possible to enter the user’s unit and perform any scaling of the
setpoint indication. In case of tanks with irregular shapes, it is possible to
use the user’s characteristics to compensate the effect of the shape on the
converted volume of liquid in the tank.
8.7. Pressure and differential pressure measurements
The APC-2000ALW transmitter is intended for measuring the relative
(overpressure and underpressure) and absolute gas, vapour and liquid pressure.
Examples of transmitter installation are shown in ➔.Figure 2. Examples of
pressure transmitter installation. The transmitters APR-2000ALW and APR-
2000ALW with diaphragm seals measure differential pressure on orifices, impact
pressure tubes, filters, level in pressure tanks, etc. Examples of transmitter
installation are shown in ➔.Figure 3. Examples of differential pressure
transmitter installation. The transmitter may be configured for one of many
physical units of pressure. It is also possible to enter the user’s unit and
perform any scaling of the setpoint indication. For more issues regarding
pressure, vacuum, differential pressure, level, flow measurements, refer to
the Technical Information.
OPERATION
The transmitter gives the possibility of rotating the housing and adjusting the display position to the mounting position of the body. To rotate the housing, loosen the screw (item 1), position the transmitter housing (item 2) as required, tighten the screw (item 1). Access to the extensions (item 6) used to rotate the display is provided after tighten blocking screw (item 5) and opening the front cover (item 3). The display can be rotated by 345° with 15° step.
Figure 11. Rotation of the housing, change of display position and access to buttons
- Screw blocking transmitter rotation.
- Transmitter housing.
- Front cover.
- Local buttons.
- Screw blocking front cover unscrewing.
- Extensions for display rotation.
In hazardous zone, do not unscrew the housing covers after connecting the Exd, XP flameproof transmitter to the power source.
9.1. Local LCD display
The LCD has three primary information fields identified in the figure below as
LCD1, LCD2, LCD3.
Figure 12. Display information fields
LCD1 field:
[mA] – value (milliamperes) of process current in line 4…20 mA, proportional
to the measured pressure.
[%] – value (percentage) of the setpoint U(t) of current controller in current
loop 4…20 mA. This value is the ratio of the process current Ip(t) to the
current range width according to the following formula:
LCD2 field:
The LCD2 field is used mainly to display floating point decimal values in a
unit displayed on LCD3. In some cases, other messages may be displayed:
− ERROR in case of some operating errors or failure diagnosed in the
transmitter, error/failure number Exxxx will appear on LCD2, the ERROR message
will be displayed on LCD3. The image will blink to attract the operator’s
attention. The transmitter in Exd or Exi/Exd (also IS, XP, IS/XP) version will
set the current output to alarm status I_AL < 3,600 mA. The transmitter in
standard or Exi version will set the current output to alarm status depending
on the configuration I_AL < 3,650 mA or I_AL > 21,500 mA. In order to identify
the cause, please refer to the chapter “Troubleshooting” placed in Technical
Information;
− undEr if the limit below LRV of the set range (only in MID mode) is exceeded
by the process, the LCD1 display of transmitter in Exd or Exi/Exd (also IS,
XP, IS/XP) version will show the message undEr (under). The image will blink
to attract the operator’s attention. The transmitter will set the current
output to alarm status I_AL < 3,600 mA. For transmitters in standard or Exi
version, the message will appear when 50% of the base range below the lower
limit range of the set LRL (LSL) is exceeded. After reaching the LPL and when
below this value up to LSAL, the transmitter freezes the refreshing of digital
value of the measurement. In this situation, message “UndEr” will be
displayed. The image will blink to attract the operator’s attention. The
diagnostic alarm mode will be enabled depending on the settings I_AL < 3,650
mA or I_AL > 21,500 mA. Additionally, common status PV_OUT_OF_LIMITS and
status PV_LOW_LIMITED in the Sensor Block will be set, which can be read out
in the diagnostic tab via HART communication. If the limit below LRV of the
set range (only in MID mode) is exceeded by the process, undEr (under) message
will appear on LCD1. The image will blink to attract the operator’s attention.
The transmitter will set the current output to alarm status depending on the
configuration I_AL < 3,650 mA or I_AL > 21,500 mA;
− ouEr if the limit above URV of the set range (only in MID mode) is exceeded
by the process, the LCD1 display of transmitter in Exd or Exi/Exd (also IS,
XP, IS/XP) version will show the message ouEr (over). The image will blink to
draw the operator’s attention. For transmitters in standard or Exi version,
the message will appear when 50% of the base range above the upper limit range
of the set URL (USL) is exceeded. After reaching the UPL and when above this
value up to USAL, the transmitter freezes the refreshing of digital value of
the measurement. In this situation, the message ‘’ovEr” will be displayed. The
image will blink to attract the operator’s attention. The diagnostic alarm
mode will be enabled depending on the settings I_AL < 3,650 mA or I_AL >
21,500 mA. Additionally, common status PV_OUT_OF_LIMITS and status
PV_HIGH_LIMITED in the Sensor Block will be set, which can be read out via
HART communication. If the limit above URV of the set range (only in MID mode)
is exceeded by the
process, ouEr (over) message will appear on LCD1. The image will blink to draw
the operator’s attention. The transmitter will set the current output to alarm
status depending on the configuration I_AL < 3,650 mA or I_AL > 21,500 mA; − ●
● ● ● when the set position of comma (point) on LCD2 does not allow for the
correct display of the process variable, four dots ● ● ● ● will appear on LCD.
The image will blink to attract the operator’s attention. In this situation,
change the decimal point position in the local setpoint change MENU or via
HART communication.
LCD3 field:
Abbreviations of physical units of pressures and levels and their description:
INH2O | inches of water column with temperature of 0°C |
---|---|
INGH | inches of mercury column with temperature of 0°C |
FTH2O | feet of water column with temperature of 20°C (68°F) |
MMH2O | millimeters of water column with temperature of 20°C (68°F) |
MMHG | millimeters of mercury column with temperature of 0°C |
PSI | pounds per square inch |
BAR | millibars |
MBAR | bars |
GSQCM | grams per square centimeter |
KGSQCM | kilograms per square centimeter |
PA | pascals |
KPA | kilopascals |
TORR | torrs |
ATM | atmosphere |
MH2O4 | meters of water column with temperature of 4°C |
MPA | megapascals |
INH2O4 | inches of water column with temperature of 4°C |
MMH2O4 | millimeters of water column with temperature of 4°C |
NOUNIT | the shortcut displayed when a unit not implemented in the transmitter |
is configured via HART
communication
Abbreviations of temperature measurement point name:
SENS °C Temperature of pressure / differential pressure sensor measurement
structure in degrees Celsius.
CPU °C Temperature of the main CPU structure in degrees Celsius.
Abbreviations displayed during configuration via local MENU and their
descriptions:
< -BACK | Return to one level above in local MENU. |
---|---|
EXIT | Going out of the local MENU. |
UNIT | Pressure and level unit selection menu. |
SENS_T | Option of measuring the temperature of pressure / differential |
pressure sensor measurement structure.
CPU_T| Option of measuring the main CPU structure temperature.
DAMPIN| Menu of selecting damping time constant of process variable.
TRANSF| Menu of selecting the current output linearization function.
%SQRT| Menu of selecting the deadband percentage of the root
characteristics of the current output linearization.
PVZERO| Pressure transmitter resetting menu and option.
SETURV| URV setting menu (upper pressure of the set range).
SETLRV| LRV setting menu (lower pressure of the set range).
BYPRES| Option of setting the range according to pressure.
BYVALU| Option of setting the set range by entering a value.
RESET| transmitter hot restart software menu
LCD1VR| Menu for selection of the type of measurement displayed on LCD1.
LCD2VR| Menu for selection of the type of measurement displayed on LCD2.
LCD2DP| Menu for selecting position of comma/decimal point.
FACTOR| Return to factory values menu.
RECALL| Option of return to factory settings. Factory pressure /
differential pressure calibrations, zero setpoints of pressure and current
will be restored.
LINEAR| Option of linear function of current output setpoint
linearization.
SQRT| Option of root function of current output setpoint linearization.
SPECIA| Option of the user’s special characteristics of current output
setpoint linearization.
SQUARE| Option of square function of current output setpoint
linearization.
CURREN| Option of selecting the display of set current on LCD1.
PERCEN| Option of selecting the display of set percentage on LCD1.
PRESS| Option of selecting the display of pressure / differential
pressure on LCD2.
USER| Option of selecting user’s units and scaling to be displayed on
LCD3.
MID_WP
| MID mode setting menu. In this mode, the option of changing the setpoints
related to the transmitter me- trology is disabled. Additionally for Exd or
Exi/Exd (also IS, XP, IS/XP) versions, exceeding of LRV and URV limits results
in displaying undEr or ouEr message, blinking of the display and setting of
the process output to the current alarm mode I_AL < 3,600 mA. For standard or
Exi transmitters, the exceeding of LRV and URV limits results in displaying
the undEr or ouEr message, blinking of the display and setting of the process
output to the current alarm mode depending on the configuration I_AL < 3,650
mA or I_AL > 21,500 mA.
ON| MID mode activation option.
OFF| MID mode deactivation option.
X.XXXX| Option of selecting position of comma/decimal point.
XX.XXX| Option of selecting position of comma/decimal point.
XXX.XX| Option of selecting position of comma/decimal point.
XXXX.X| Option of selecting position of comma/decimal point.
XXXXX.| Option of selecting position of comma/decimal point.
0 [S]| Option of selecting damping time constant.
2 [S]| Option of selecting damping time constant.
5 [S]| Option of selecting damping time constant.
10 [S]| Option of selecting damping time constant.
30 [S]| Option of selecting damping time constant.
60 [S]
| Option of selecting damping time constant. The 60-second damping constant
is only available from the local keypad; the configuration via HART in
revision 5 does not allow a damping value greater than 30 seconds. Other
damping values are possible to be set via HART communication.
0.0 %| Option of selecting root characteristics deadband point.
0.2 %| Option of selecting root characteristics deadband point.
0.4 %| Option of selecting root characteristics deadband point.
0.6 %| Option of selecting root characteristics deadband point.
0.8 %| Option of selecting root characteristics deadband point.
1.0 %| Option of selecting root characteristics deadband point.
| Other deadband values are possible to be set via HART communication.
DONE| Message about the acceptance and implementation of the set-point
change.
Abbreviations of local configuration errors and description of abbreviations:
ER_L07| Message displayed on LCD3. It is displayed if a user tries to
change the setpoint in the transmitter pro- tected against entry (change of
setpoints) or in active MID mode.
---|---
ER_L09
| Message displayed on LCD3. It is displayed if:
– a user tries to change the set range by set pressure which is not within the
allowable upper URL pressure;
– a user tries to pressure reset when the pressure exceeds the allowable upper
limit.
ER_L10
| Message displayed on LCD3. It is displayed if:
– a user tries to change the set range by set pressure which is not within the
allowable lower LRL pressure;
– a user tries to pressure reset when the pressure exceeds the allowable
lower limit.
ER_L14
| Message displayed on LCD3. It is displayed if:
– the adopted URV value through the set pressure or entry of a value cannot
be accepted because it causes a reduction of the set pressure range set below
the allowable limit.
ER_L16
| Message displayed on LCD3. It is displayed if:
– a user tried to perform an operation that is disabled or unavailable. It
may be caused by:
– attempting to access the local setpoint change MENU when the access to the
local MENU is disabled;
– attempting to pressure reset in the absolute pressure measurement
transmitter.
WG_L14
| The message will appear if the assumed LRV value through the set pressure or entry of a value causes a decrease of the current set range. Entry of LRV automatically results in the transmitter’s attempt to set URV in such a way that the current width of the set range is maintained. If this is not possible due to exceeded URL, the transmitter automatically adopts the URV=URL value and a new LRV value. Since the set range width and URV deviate from previous values, a message is displayed.
ASCII characters displayed on LCD3 in user’s unit:
Using HART communication, the user can configure its own 6-character unit
displayed on LCD3. It is possible to display ASCII characters from the range
32…96 dec or 20…60 hex, i.e.:
!”#$%&'()*+,-./0123456789:;<=>?@ABCDEFGHIJKLMNOPQRSTUVWXYZ[\]^_`
9.2. Local buttons
Local buttons are used to enable the configuration mode of some transmitter
parameters and to navigate through MENU and accept MENU options. The MENU can
be accessed by pressing and holding any of the buttons for at least 4 seconds.
After this time, the LCD3 field of the local display will show an EXIT
message. This signals entering into the MENU navigation mode.
9.3. Local configuration of setpoints
Transmitter enables local configuration of some of the most common setpoints
via local buttons and local LCD display.
9.4. Navigation in local setpoints MENU
The MENU can be accessed by pressing and holding any of the buttons for at
least 4 seconds. After this time, the LCD3 field of the local display will
show an EXIT message. This signals entering into the local configuration MENU.
By pressing the buttons with arrows [↑] [↓] for at least 1 second you can move
up or down in MENU.
9.5. Acceptance of local setpoints
The button marked with symbol [●] is used to accept the selection. The
acceptance of setpoint change is confirmed by a DONE message displayed on
LCD3. After changing the setpoint, the transmitter leaves the local
configuration change MENU. If no selection is made in the MENU mode, after 2
minutes the transmitter automatically returns to display of standard messages.
The MENU can also be left by selecting and accepting the EXIT option.
9.6. Structure of local setpoints MENU
Press and hold any of 3 buttons for 4 seconds. When navigating in the area of
the active local MENU, holding the button required to trigger the action is
minimum 1 second. Continuous pressing of the ↑ or ↓ button results in
scrolling of the MENU positions every 1 second. If the local MENU remains
inactive for more than 2 minutes, after this time the transmitter will
automatically leave the MENU mode and will display the process variable.
9.7. Remote configuration of setpoints (HART 5/HART 7)
The transmitter allows to read out and configure the parameters via HART
communication using
4…20 mA loop as a physical layer for FSK BELL 202 modulation.
9.7.1. Compatible devices
The following devices may be used to communicate with the transmitter:
− Aplisens S.A. KAP-03, KAP-03Ex communicator (HART 5 only);
− communicators from other companies, including those using DDL and DTM
libraries;
− PC computers equipped with HART modem (e.g. HART/USB converter by Aplisens
S.A.) with Windows7 or Windows10 operating system with installed Raport 2;
− PC computers equipped with HART modem using software from other companies,
accepting DDL and DTM libraries;
− smartphones with Android system, using a converter providing wireless
communication (e.g. HART/USB converter by Aplisens S.A.) using Aplisens Mobile
Configurator. The software is available on Google Play under the link:
https://play.google.com/store/apps/details?id=com.aplisens.mobile.amc.
9.7.2. Compatible configuration software
− Raport 2 Aplisens under control of Windows 7 or Windows 10;
− Aplisens Mobile Configurator under control of the Android system;
− every software from other companies accepting DDL and DTM libraries.
9.7.3. Local HART communication jumper
The transmitter allows to use the local HART communication. To do this you can
use a HART communicator unit or modem interoperating with a computer or a
smartphone. In order to establish communication, it is necessary to:
− remove the HART communication jumper (➔Figure 6. Electrical connection 4…20
mA of HART to transmitter in standard version);
− connect the communicator or modem to terminals (➔ Connection of transmitter
with the option of using local HART communication).
MAINTENANCE
10.1. Periodic inspections
Periodic inspections shall be carried out in accordance with applicable
standards. During the inspection, the condition of the pressure (absence of
loosened elements and leaks) and electrical (check of connections reliability
and condition of gaskets and glands) connectors, condition of separating
diaphragms (tarnish, corrosion) and stability of fixing of the housing and
mounting bracket (if used) shall be checked. Check the processing
characteristics by performing the operations specific for the CALIBRATION and
possibly CONFIGURATION procedure.
10.2. Non-periodic inspections
If the transmitter at the installation site has been exposed to mechanical
damage, pressure overload, hydraulic pulses, overvoltage, deposits, medium
crystallization, undercutting of the diaphragm, or incorrect operation of the
transmitter is detected, the device
should be inspected. Check the condition of the diaphragm, clean it, check the
electrical functionality of the transmitter and the processing
characteristics.
If there is no signal in the transmission line or its value is improper, check
the supply line, connection status on terminal blocks, connectors, etc. Check
if the supply voltage and load resistance are correct.
10.3. Cleaning/washing
To remove impurities from the external surfaces of the transmitter wipe it
with a cloth dampened in water.
10.4. Diaphragm cleaning
The only possible method of cleaning the transmitter diaphragms is to dissolve
the sludge produced.
Do not remove deposits and impurities from the transmitter diaphragms, which
are formed during operation, mechanically using tools, since the diaphragms
and the transmitter can be damaged.
10.5. Spare parts
Parts of the transmitter that may be worn or damaged and thus replaced: cover
seal.
Other parts in the case of ATEX, PED type of transmitter may be replaced only
by the manufacturer or an authorized representative.
10.6. Repair
Faulty or non-operational transmitter shall be provided to the manufacturer.
10.7. Returns
In the following cases, the transmitter should be returned directly to the
manufacturer:
– need for repair;
– need for factory calibration;
– replacement of improperly selected/shipped transmitter.
SCRAPPING, DISPOSAL
Worn or damaged devices shall be scrapped in accordance with WEEE Directive (2012/19/EU) on waste electrical and electronic equipment or returned to the manufacturer.
HISTORY OF REVISIONS
Revision No. | Document revision | Description of changes |
---|---|---|
– | 01.A.001/2019.07 | Initial document version. Prepared by DR, DKD, KBF, DCF. |
1 | 01.A.002/2019.09 | QR codes and ID numbers have been changed. Prepared by |
DR, DKD, KBF, DCF.
2| 01.A.003/2019.10| Change of QR codes and ID numbers due to introduction of
soft- ware with HART 7 stack. Prepared by DR, DKD, KBF, DCF.
3| 01.A.004/2020.03| Added information about PED execution. Prepared by DBFD.
4| 02.A.005/2020.06| New document edition. Prepared by DBFD.
5| 02.A.006/2020.10| Supplemented the ID numbers. Prepared by DBFD.
6| 02.A.007/2021.06| Added information about FM certificate for US and Canada,
edito- rial changes.
7| 02.B.001/2023.04| Editorial changes, change of QR codes and ID numbers due
to the update of explosion proof certificates. Added UKCA transmit- ters.
Prepared by DBFD.
References
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- APLISENS S.A. - Pressure transmitters, differential pressure transmitters, hydrostatic level probes, level transmitters.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. is one of the leading manufacturers of high quality process instrumentation.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
- Aplisens S.A. - Produkcja Przemysłowej Aparatury Pomiarowej i Elementów Automatyki.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>