APLISENS RAPORT 2 HART Communicator Tools Instructions
- June 13, 2024
- APLISENS
Table of Contents
APLISENS RAPORT 2 HART Communicator Tools Instructions
Table: Permissible ambient temperature and temperature code for gas hazardous are
Temperature code | Temperature ambient |
---|---|
T4 | -40…80°C |
Table: Permissible ambient temperature and temperature code for dust hazardous are
Temperature code | Temperature ambient |
---|---|
T5 | -40…80°C |
105°C | -40…80°C |
Note:
No modification to be made without reference/approval from FM Approvals and
APLISENS S.A.
Intrinsically safe for Cl. I, Div. 1, Groups A, B, C, D, Cl. II, Div. 1, Groups E, F, G T5, Cl. III, Div. 1 T5 ZN 0 AEx/Ex ia IIC T4 Ga, ZN 20 AEx/Ex ia IIIC T105°C Da Hazardous Locations Installations
Installation
-
Control room equipment may not use or generate over 250 V.
-
Install per the Canadian Electrical Code or National Electrical Code (ANSI/NFPA70) and ISA RP 12.06.01.
-
For entity installations: Use Listed certified intrinsic safety barrier or other associated equipment that satisfy the following conditions: Voc≤Vmax, Isc≤Imax, Ca≥Ci+Ccable, La≥Li+Lcable. Transmitter entity parameters are as follows:
a) Supply frorn a power source with linear output characteristic:
Ui / Vmax = 30 VDC
Ii / I max = 100 mA
Pi / Pmax=0.75W
Ci=2.5 nF
Li=18 μH for T-code see tables
b) Supply frorn a power source with trapezoidal output characteristic:
Ui / Vmax = 24 VDC
Ii / I max = 50 mA
Pi / Pmax=0.7W
Ci=2.5 nF
Li=18 μH for T-code see tables
c) Supply frorn a power source with rectangular output characteristic:
Ui / Vmax = 24 VDC Ui / Vmax = 24 VDC
Ii / I max = 25 mA Ii / I max = 50 mA
Pi / Pmax=0.6W Pi / Pmax=1.2W
Ci=2.5 nF Ci=2.5 nF
Li=18 μH Li=18 μH for T-code see tables -
Use Listed certified safety barriers with entity parametrs meeting the requirements of note 3.
-
Hazardous (classified) location equipment may be simple apparatus or FM Approved equipment with entity parametrs meeting the requirements of note 3.
-
Remark: Versions with surge arrester marked on plate “Version SA”, do not meet the requirements of dielectric strength tests 500Vrms between terminal connections and transmitter housing.
-
Under certain extreme circumstances in Zone 20 the device with painting of aluminum enclosure and with plastic rating plate may store an ignition-capable level of electrostatic charge. The device shall not be installed in a location where the external conditions are conducive to the build-up of electrostatic charge.
-
The enclosure made of aluminum alloy and given a protective polyurethane paint finish; care should be taken to protect it from impact or abrasion of located in Zone 0.
-
When the transmitter with a nameplate containing various types of explosion-proof the user must permanently mark the type IS of protection chosen for the intrimisically Safe installation. Once the type of protection has been marked the IS destiny of the transmitter shall not be changed.
Drawn:| D.lzdebski| | 12.2020| Title
ontroFM CIS Version APC-2000ALW, APC-2000ALW APR-2000ALW and APR-2000ALW| l|
SafetyDrawingSafety,| DISIV1ZONE 0 ZONE 20|
---|---|---|---|---|---|---|---|---
Checked:| J.Wasowski| | 12.2020
Accepted| D.Knap| | 12.2020
Replaced drawing No.| Replaced by drawing No.|