APLISENS RAPORT 2 HART Communicator Tools Instructions

June 13, 2024
APLISENS

APLISENS RAPORT 2 HART Communicator Tools Instructions
APLISENS RAPORT 2 HART Communicator Tools

Table: Permissible ambient temperature and temperature code for gas hazardous are

Temperature code Temperature ambient
T4 -40…80°C

Table: Permissible ambient temperature and temperature code for dust hazardous are

Temperature code Temperature ambient
T5 -40…80°C
105°C -40…80°C

Note:
No modification to be made without reference/approval from FM Approvals and APLISENS S.A.

Intrinsically safe for Cl. I, Div. 1, Groups A, B, C, D, Cl. II, Div. 1, Groups E, F, G T5, Cl. III, Div. 1 T5 ZN 0 AEx/Ex ia IIC T4 Ga, ZN 20 AEx/Ex ia IIIC T105°C Da Hazardous Locations Installations

Installation

Installation

  1. Control room equipment may not use or generate over 250 V.

  2. Install per the Canadian Electrical Code or National Electrical Code (ANSI/NFPA70) and ISA RP 12.06.01.

  3. For entity installations: Use Listed certified intrinsic safety barrier or other associated equipment that satisfy the following conditions: Voc≤Vmax, Isc≤Imax, Ca≥Ci+Ccable, La≥Li+Lcable. Transmitter entity parameters are as follows:
    a) Supply frorn a power source with linear output characteristic:
    Ui / Vmax = 30 VDC
    Ii / I max = 100 mA
    Pi / Pmax=0.75W
    Ci=2.5 nF
    Li=18 μH for T-code see tables
    b) Supply frorn a power source with trapezoidal output characteristic:
    Ui / Vmax = 24 VDC
    Ii / I max = 50 mA
    Pi / Pmax=0.7W
    Ci=2.5 nF
    Li=18 μH for T-code see tables
    c) Supply frorn a power source with rectangular output characteristic:
    Ui / Vmax = 24 VDC Ui / Vmax = 24 VDC
    Ii / I max = 25 mA Ii / I max = 50 mA
    Pi / Pmax=0.6W Pi / Pmax=1.2W
    Ci=2.5 nF Ci=2.5 nF
    Li=18 μH Li=18 μH for T-code see tables

  4. Use Listed certified safety barriers with entity parametrs meeting the requirements of note 3.

  5. Hazardous (classified) location equipment may be simple apparatus or FM Approved equipment with entity parametrs meeting the requirements of note 3.

  6. Remark: Versions with surge arrester marked on plate “Version SA”, do not meet the requirements of dielectric strength tests 500Vrms between terminal connections and transmitter housing.

  7. Under certain extreme circumstances in Zone 20 the device with painting of aluminum enclosure and with plastic rating plate may store an ignition-capable level of electrostatic charge. The device shall not be installed in a location where the external conditions are conducive to the build-up of electrostatic charge.

  8. The enclosure made of aluminum alloy and given a protective polyurethane paint finish; care should be taken to protect it from impact or abrasion of located in Zone 0.

  9. When the transmitter with a nameplate containing various types of explosion-proof the user must permanently mark the type IS of protection chosen for the intrimisically Safe installation. Once the type of protection has been marked the IS destiny of the transmitter shall not be changed.

Drawn:| D.lzdebski| | 12.2020| Title ontroFM CIS Version APC-2000ALW, APC-2000ALW APR-2000ALW and APR-2000ALW| l| SafetyDrawingSafety,| DISIV1ZONE 0 ZONE 20|
---|---|---|---|---|---|---|---|---
Checked:| J.Wasowski| | 12.2020
Accepted| D.Knap| | 12.2020