NUVA THINGS H-GTW Equipment For Fire Alarm Control Instruction Manual
- June 15, 2024
- NUVA THINGS
Table of Contents
NUVA THINGS H-GTW Equipment For Fire Alarm Control
Product Information
Specifications
- Model: H-GTW v 2.25
- Compatibility: Fire Alarm Control Panel integration
- Supported Control Units: ID3000, ID50, ID60, AM8200
- Integration: Modbus systems
- Version: 2.25 (07/12/2022)
- Format: RAIL DIN Box 4 Modules (H-GTW)
- Power Supply (Individual Mode): 12-28Vdc
- Power Supply (Network Modes): 12-28Vdc
- Regulations: 2014/30/EU, 2014/35/EU, 2011/65/EU, 2014/53/EU, EN 62368-1
- Electromagnetic Compatibility Directive
- Low Voltage Directive
- ROHS Directive
- RED Directive – Electrical safety for IT equipment
Introduction
The H-GTW equipment allows for the integration of a control panel individually ID50 or 60, ID-3000, or AM8200. The H-GTW-N model provides integration not only to individual control units but also to network control units. It supports integration with 8ID3000 control units connected in the ID2Net network, up to 8 AM8200 control units with a Special map, and up to 4 control units with a Normal map.
Warranty
The device is guaranteed for 12 months from the date of purchase. Misuse,
normal wear, and tear are excluded from the guarantee. The technical
characteristics of the device may be subject to technical changes without
prior notice.
Technical Features
- Input Channels:
- i1, i2, i3 (external resistors)
- Resistive EOL: 2k2
- Fault: 820
- Pull-down 4-20mA: 150 ± 1%
- Open Collector Outputs:
- o1: Negative / 200mA
- o2: Negative / 200mA
- Cellular Antenna:
- Gain: 3 dBi
- Frequency: 700/960-1800/2700MHz
- PCB Dimensions:
- Height: 90 mm
- Width: 71 mm
- Depth: 53 mm
- Weight (approx.): 150 g
Usage Instructions
Installation and Configuration
To install and configure the H-GTW equipment, follow these steps:
- Ensure you have a stabilized power supply within the range of 12-28Vdc.
- Connect the input channels (i1, i2, i3) using external resistors according to the specified values (Resistive EOL: 2k2, Fault: 820, Pull-down 4-20mA: 150 ± 1%).
- Connect the open collector outputs (o1, o2) to the desired devices. Ensure the polarity is correct (Negative / 200mA).
- If using a cellular antenna, connect it to the H-GTW equipment. Set the gain to 3 dBi and ensure the frequency range is within 700/960-1800/2700MHz.
- Mount the H-GTW equipment in a RAIL DIN Box with a 4-moduleformat.
Addressing and Communication
For correct communication and addressing of the equipment, follow these guidelines:
- For Detectors:
- For loop addresses from 1 to 15, only devices with 10 sub-addresses can be installed.
- For loop addresses from 16 to 40, only devices with 3 sub-addresses can be installed.
- For loop addresses from 41 to 159, only devices with 2 sub-addresses can be installed.
- Ensure there are no modules with a sub-address of 10 at loop address 25.
FAQ
Q: What is the warranty period for the H-GTW equipment?
A: The device is guaranteed for 12 months from the date of purchase.
Q: What power supply is required for the H-GTW equipment?
A: The H-GTW equipment requires a stabilized power supply within the
range of 12-28Vdc.
Q: Can the H-GTW equipment be used in industrial environments?
A: Yes, the device is designed for residential, commercial, and
industrial environments.
H-GTW equipment for Fire Alarm Control Panel integration
ID3000 / ID50 / ID60 / AM8200 in Modbus systems
Version 2.25 (07/12/2022)
Introduction
The H-GTW enables the integration of Notifier fire alarm control panels into
supervisory/control systems integrating Modbus master connectivity, using the
gateway of Notifier ID3000 / ID50 / ID60 / AM8200 fire alarm control panels
from supervisory/control systems with Modbus master connectivity. Gateway
works from the Modbus system’s point of view, as a Modbus slave device,
responding to data queries from the Modbus master, and from the Notifier
system’s point of view, as a serial device connected to its RS232 port,
serving data received from the Notifier to the Modbus side.
The H-GTW-1 model allows the integration of a control panel individually ID50
or 60, ID-3000 or AM8200 The H-GTW-N model allows integration to any of the
individual control units indicated above, but also to network control units,
according to the following list: 8 ID3000 control units connected in the
ID2Net network or it allows the integration of up to 8 AM8200 control units
with a “Special” map” and up to 4 control units with a “Normal” map.
Note: In the “Special” map, the following installation/configuration must be given for it to be a correct communication. They must arrange the addressing of the equipment in each loop as follows:
For Detectors
-
159 detectors
For Modules -
In the loop address from 1 to 15, only devices with ≤ 10 sub-addresses can be installed.
-
In the loop direction from 16 to 40 ≤ 3 sub-addresses
-
In the loop address from 41 to 159 ≤ 2 sub-addresses
For example: There cannot be a module of 10 sub-addresses at loop address 25
Warranty
The device is guaranteed for 12 months from the date of purchase.
Misuse and normal wear and normal tear are excluded from the guarantee.
The technical characteristics of the device may be subject to technical
changes without prior notice.
FORMAT
RAIL DIN Box 4 Modules (H-GTW)
Models
The device is available in different models depending on the housing format,
power supply and communication options.
Models H-GTW, RAIL-DIN 4-module format
Mode | Power supply | MODEL |
---|---|---|
Individual mode | 12…28Vdc | H-GTW-1 |
Network modes | 12…28Vdc | H-GTW-N |
Regulations
The equipment is designed in accordance with the following directives and
harmonized standards.
2014/30/EU | General Electromagnetic Compatibility Directive |
---|---|
2014/35/EU | Low Voltage Directive |
2011/65/EU | ROHS Directive |
2014/53/EU | RED Directive. |
EN 62368-1 | Electrical safety for IT equipment |
These regulations lapse if changes are made to the device without the consent
of Nuvathings.
The device is designed for residential, commercial and industrial
environments.
Technical features
- Environmental class……………………………………………………………………………………………………………………..class III
- Operating temperature range………………………………………………………………………………. -30 to + 85 C ̊
- Operating humidity …………………………………………………………………. ………………………….0…75% non-condensing
- Main board external power supply……………………………………………………………..…..5…30 VDC – 350 mA
- Communication method Via TCI/IP………………………………………………………………………..With automatic detection
- Communication method RS-232……………………………………………………………………………4800 Bds to 115200 Bds
- RAM capacity…………………………………………………………………………………………………………………………….256kbys
- Supported speed Via TCI/IP………………………………………………………………………………………… 10/100Mbts/1Gbts
- Processor……………………………………………………………………………………………………………………………….Cortex M4
The circuit must be powered from a stabilized power supply in accordance with LVD electrical safety.
- Average power consumption in active state at 24 V ……………………………………………..10 mA average
- PCB ……………………………………………………………………………………………5 mA
- GSM …………………………………………………………………………………………..5 mA
- WIFI ……………………………………………………………………………………………7mA
- ETHERNET… ………………………………………………………………….20mA
- During transmission NB-IOT…………………………………………………..75mA
- During transmission LORA…………………………………………………….50mA
Input channels i1-i2-i3 (external resistors)
- Resistive EOL……………………………………………………………………2k2 Ω
- Fault……………………………………………………………………………….820 Ω
- Pull-down 4-20mA……………………………………………………………….150 Ω 1%
Open collector outputs
- o1…………………………………………………………………………………Negative / 200mA
- o2…………………………………………………………………………………Negative / 200mA
Cellular antenna.
- Gain ……………………………………………………………………………………………3 dBi
- Frequency……………………………………………………………………….700/960-1800/2700MHz
PCB dimensions
- Height………………………………………………………………………………90 mm
- Width……………………………………………………………………………….71 mm
- Depth……………………………………………………………………………….53 mm
- Weight (approx.) …………………………………………………………………………..…150 g.
Installation
Installation conditions
Products are certified under the following conditions:
For better compliance, shielded cable must be used on all input/output
connections.
The connection between the devices must be made with a cable with a flame-
retardant sheath.
Attention, this product is only suitable for installation on fixed, non-
combustible surfaces.
Device’s wiring must also comply with national standards.
Package Contents
Content of H-GTW
- 1 x DIN RAIL box
- 1 x CIRCUIT CONNECTOR
- 1 GUIDE, QR CODE
WIRING DIAGRAM H-GTW
Device connections
Before power on the device, make sure all connections are made properly.
Connection | Description |
---|---|
i4 | Opto-isolated digital input / pulse counter input. |
AnOut | Programmable 4-10 V power output or PWM dimming. |
V+ | External power supply input, 5…28VDC . |
GND | Power negative. |
RS- 232 | GND = negative COM Pin5 FACP reference TX = |
transmission with Pin2 RX of the FACP RX = Receive with Pin3 TX from FACP
USB| Micro USB connector for PC communication (configuration utility)
A,B| RS485 / SDI12 bus terminals.
i1,i2,i3| Digital channel inputs (pull up 10K 1%), capable of detecting
open, closed or resistive terminations, 4..20mA probes, NTC 10K measurement,
Inputs are referenced to terminal GND.
O1..O2| Open collector outputs, max. 200mA.
Connections with Fire Alarm Control Panels
Plant Configuration
ID50/60
To enable the RS232 port on the control panel, proceed as follows:
- Release the control panel programming lock, remove jumper J9 or MEN
- Run the programme and open the programming file.
- If you do not have the programming file, run the programme and click on
- Tools > Receiving Data from Central
- When finished, press Save, specifying a path and a name for the file.
- Click on the Central icon on the left-hand side of the screen.
- Select the ‘Device Options’ window.
- In the part marked RS232 (right), where it says RS232 Protocol, enter
- Integration
- Under “RS232 Options” select HALF DUPLEX
- In the section entitled ‘Communication Integration Monitoring’, select Overwrite.
- Save the data, click on Tools>Send to Central Office
- When prompted, enter installer code 3333, in order to perform the dump
- Reposition jumper J9 or MEN at the end of programming.
ID3000
To enable the RS232 port of the ISO-RS232 option card, follow the steps below
in the control panel menu (to unlock the keyboard and access the menu, turn
the service button on the front panel, next to the keyboard, a quarter turn to
the right):
Configuration
Central configuration
18. Conf. Isolated RS232 port
3. Integration Protocol
4800 bps
- Version: 2: 011 (only if Half Duplex is not available)
- Controls: enabled/disabled *1
- Com. monitoring: disabled
- Time monitoring: 0
- Mandatory selections are highlighted in bold.
- Default password level 3B: 27835
1 If the controls are disabled, no commands can be sent to the control panel.
AM-8200
To enable the RS232 port on the control panel using the SIB-8200 board,
proceed as follows:\
- Press PRGM (default code 44444)
- Select ‘Program or device configuration’.
- Select ‘SIB’.
- In Installed, press Enter and use the ‘up/down’ cursor keys to change to ‘YES’.
Operating modes
Functional description
The scope of H-GTW is to associate the states of the PCI Notifier system
elements with the address values of the ModBus registers, using a fixed
address mapping for Sensors, Modules and Events, depending on the control
panel model to which the equipment is connected.
The commissioning process of the H-GTW requires only the connection to the
device, the configuration of the communication speeds and the model of the
control panel connected, using the HnyExpress application described at the end
of this manual.
H-GTW allows you to manage 1 ID50/60 control panel, up to 8 networked ID3000
control panels or 4 complete AM8200 control panels, but there is also a
‘special’ map that allows you to represent more AM8200 control panels.
Note: For the ‘special’ method, please consult our technical support
service.
In network mode, the map generated for each control panel retains the
addresses of the main map, but each control panel will appear as a different
Modbus address, i.e. the Modbus address ‘n’ will contain the data of control
panel ‘n’.
Once configured, the equipment maintains constant communication with the
control center to obtain the main statuses. When an event is received, it is
analyzed, and different addresses are activated on the map depending on the
type of event.
Two-way communication.
Two-way communication is always established between the device and a software for commissioning and monitoring the equipment.
HnyExpress application
HnyExpress application
To establish communication with the gateway from the HnyExpress application,
proceed as follows:
Setup USB
- It is necessary to configure the drivers, for this go to /Program Files (x86)/HnyExpress/drivers
- Install the 64 or 32 bit driver according to your machine, run the installable in administrator mode
- Once the drivers are loaded, it will be necessary to run HNYEXPRESS in administrator mode whenever we want to use this type of connection, we recommend leaving the icon permanently in Administrator mode
- Connect a micro-USB cable to the equipment on the right side, once connected the equipment will turn on, no power supply will be necessary to parameterize the equipment
Setup TCP-IP
-
Set a fixed IP on the computer in the range 192.168.1.x in TCP-IP connection mode.
-
Power the equipment in the indicated ranges (12Vdc-24Vdc).
-
If the equipment is brand new or if we do not know its IP address, we must use a crossover cable and connect it directly to the PC (even with a switch that is not connected to the router); 15 seconds after the equipment has started up, it will self-configure with the IP: 192.168.1.234 and will listen on port 61534, so that a two-way connection can be established with it.
Once the connection method has been established, follow these steps to configure the gateway: -
from the HnyExpress application, click on the blue ribbon button (the one in the middle).
-
Select the IP of the equipment to be connected, by default 192.168.1.234 Port 61534, the connection will be established, the progress bar below will inform about the connection status; once the connection is established, the equipment configuration will be received automatically.
-
(Rx button), the changed data will be sent according to the requirements of the installation.
-
(Tx button), data can be retrieved from the gateway.
-
To stop communication with the device by pressing the red close button, so that changes are permanently saved.
-
In the ‘RS232 speed’ window, select the same speed as configured in the control panel. Follow the table below
Fire Alarm Control Panel| ID50/60| ID3000| AM8200
---|---|---|---
Transmission speed| 9600 (Half Duplex)| 4800 (Half Duplex)| 38400- Note: The gateway with ID3000 does not work via RS232 communication on the motherboard.
-
“RS485 speed” window not currently used.
-
Under ‘IP Address’ change the desired address.
-
Under ‘Gateway address’, change the address as required.
-
Under ‘Netmask’, change the desired address.
-
Under “Choose model” TPP11 for ID50/60 or ID3000, TPP13 Normal for AM8200 all addresses or TPP13 Special for AM8200 with fixed addresses.
-
‘Network mode’: activate this checkbox if you intend to communicate vith a network of panels. For single plane this option must be deactivated.
-
Supervision via Cloud: activating this option allows the gateway configuration to be supervised via a Cloud connection (the connection must be free, without port blocking, firewalls, etc.).
-
Using the “Modbus addresses Base 1” checkbox, you can select whether the Modbus transmission is in Base 0 or Base 1. For this selection, please consult the integrator.
Panel selection
In the Panels tab, it is possible to address the different panel numbers that
are part of the networked system; in the example, we have defined a structure
consisting of 2 networked panels, panel 01 and panel 02.
For individual panels, without ‘Network Mode’, no selections are allowed.
This section must be sent (TX) / received (RX) separately from the Configuration tab.
Firmware
In this Firmware window, the gateway version can be updated.
Select the path where the file you wish to upload to the gateway is located
and click on the TX icon. At this point, follow the instructions that appear
on the screen.
Sniffer
The Sniffer window allows you to monitor the communication between the H-GTW
and the main panel of the Fire Alarm System. You can select the text shown in
the logging area and, by copying and pasting, you can save it in a text file
for Technical Service review.
To proceed, click on the Sniffer window and the blue ETH/USB icon, (connect).
When finished, do not forget to click on the red ribbon (disconnect).