NOTIFIER Spartan-25 NSP-25C Addressable FACP With Built-in Communicator Owner’s Manual
- June 9, 2024
- NOTIFIER
Table of Contents
Addressable Fire Alarm Control Panels
Spartan-25® (NSP-25C)
Addressable FACP
With Built-in Communicator
General
The NOTIFIER Spartan-25 (NSP-25C) is a 25 point addressable Fire Alarm Control
Panel (FACP) with built-in Digital Alarm Communicator Transmitter (DACT). This
control panel supports up to 25 addressable devices in any combination of
detectors and modules and then reports these devices into one of 5 available
zones.
With simple programming, operation on standard wire, and features such as
drift compensation and maintenance alert, the Spartan-25 is a preferred
alternative to conventional control panels in both new and retrofit
applications.
The JumpStart® (or auto-learn) feature and easy-to-set code wheel addressing
of Honeywell Fire Systems detectors and modules enable the system to be
quickly configured for fire protection without a programming utility. The
default programming can be easily modified on a PC using the panel’s embedded
web server.
The integral DACT transmits system status (alarms, troubles, supervisory,
etc.) for up to 5 zones to a remote monitoring location via the public
switched telephone network. Reporting formats are contact ID, SIA 8 or SIA 20.
Features
- ULC listed and ETL certified to ULC Standard S527 and S559
- JumpStart® auto-learn feature reduces installation time and makes programming easy.
- Built-in digital communicator.
- Two programmable Style Y (Class B) notification appliance circuits (NACs).
- Selectable strobe synchronization for System Sensor®, Gentex®, Wheelock® or AMSECO devices.
- Two programmable Form-C relays and one Form-C trouble relay.
- Drift compensation.
- Alarm verification per zone of detectors.
- Walk-test.
- Honeywell Fire Systems detectors and modules are code- wheel addressed for faster installation time.
- Maintenance alert region.
- Uses standard wire (unshielded or twisted pair).
- Central Station reporting up to five zones.
- On Board Annunciator.
- Custom programming performed through the control panel’s built-in browser; no programming software is required.
DCL Communication
- Single addressable DCL loop which meets ULC DCLB requirements.
- 25 addressable device capacity (any combination of addressable detectors and modules).
- Compatible with Honeywell Fire Systems detectors and modules.
Notification Appliance Circuits (NACS)
- Two independently programmable output circuits. Circuits can be configured for the following outputs:
- Style Y (Class B).
- Door Holder Service (cannot be used for notification appliances).
- Aux Power Source (cannot be used for notification appliances).
- Silence Inhibit and Auto-silence timer options.
- Continuous or Temporal code.
- Selectable strobe synchronization per NAC.
- Up to 2.0 A total output power, 1.0 A for auxiliary power and door holder. Each circuit can source up to the total system current 2.0 A.
Programming and Software
- Auto-learn “JumpStart®” feature for easy programming reduces installation time.
- Custom programming can be performed through control panel’s built-in browser. (Requires PC with MS Internet Explorer or Mozilla Firefox and standard Cat5e Ethernet cable)
- 5 programmable zones (combination of alarm / supervisory)
User Interface
The panel has a 3-character, 7-segment display for Point ID status.
LED INDICATORS
- AC Power (green)
- Fire Alarm per zone (red)
- Supervisory per zone (yellow)
- Trouble / Disable per zone (yellow)
- Active per NAC (green)
- Trouble / Disable per NAC (yellow)
- Alarm Silenced (yellow)
- System Trouble (yellow)
- Low Battery Fault (yellow)
- System Ground Fault (yellow)
- Walk Test (yellow)
KEYPAD CONTROLS
- Acknowledge
- Silence
- Reset (Lamp Test)
- Drill
- Walkies
- Disable per zone
- Disable per NAC
- JumpStart
- 0 – 9 numeric keypad
Product Line Information
NSP-25C: 25 point addressable fire alarm control panel.
Includes main circuit board, chassis, backbox and door. Black; 120 VAC. Listed
for Canadian applications.
Note: For versions used outside Canada, see DN-60609.
HONEYWELL FIRE SYSTEMS DEVICES
HFS-PA: Honeywell Fire Systems addressable photoelectric smoke detector.
Includes base.
HFS-PTA: Honeywell Fire Systems addressable photoelectric smoke detector
with thermal sensor. Includes base.
HFS-TA: Honeywell Fire Systems addressable fixed temperature heat
detector. Includes base.
HFS-MMA: Honeywell Fire Systems addressable Mini-Monitor module for
normally-open contact devices.
HFS-MRA: Honeywell Fire Systems addressable relay module.
HFS-DA: Honeywell Fire Systems addressable photoelectric duct smoke
detector. Includes detector.
NOT-BG12LX: Addressable dual-action manual pull station.
SB-I/O: Surface-mount backbox for the NOT-BG12LX, plastic.
BG12TR: Optional trim ring for semi-flush mounting the pull station.
BB-26: Battery backbox, holds up to two 25 AH batteries and CHG-75.
NFS-LBB: Battery box, houses two 55 AH batteries.
CHG-120: Remote battery charging system for lead-acid batteries with a
rating of 55 to 120 AH. Requires additional NFSLBB for mounting.
BAT Series: Batteries. See data sheet DN-6933.
007860: DACT Phone Cord (2 required)
Wiring Requirements
While shielded wire is not required, it is recommended that all DCL wiring be twisted-pair to minimize the effects of electrical interference. Refer to the panel manual for wiring details.
SYSTEM SPECIFICATIONS
System Capacity
- Intelligent DCL Circuits………………………………………………. 1
- Addressable device capacity …………………………………….. 25
- Programmable software zones ……………………………………. 5
Electrical Specifications
- AC Power: NSP-25C: 120 VAC, 60 Hz, 1.5 A. AC wire size is minimum 14 AWG (2.00 mm²) with 600 V insulation. Nonpower-limited, supervised.
- Battery: Charging capacity 7-18 AH. NSP-25C cabinet holds maximum of two 7 AH batteries. Larger batteries require a separate battery cabinet, such as the BB-26 or NFS-LBB.
- DCL Circuit: Supervised and power-limited.
- Notification Appliance Circuits:
- Terminal Strip provides connections for two NACs, Style Y (Class B).
- Maximum signaling current: 2.0 A.
- End-of-Line Resistor: 4.7 kOhm, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC. Refer to the NSP-25C manual for listed compatible devices.
- Standby Current: 135 mA
- Alarm Current: 220 mA
- Aux Power Circuits: 1.0A @ 24 VDC per circuit, powerlimited
- Two Programmable Relays and One Fixed Trouble Relay:
- Contact rating: 2.5 A @ 24 VDC (resistive).
- Form-C relays, nonpower-limited, nonsupervised.
Physical Specifications
- Dimensions: 38.42 cm H x 32.39 cm W x 8.57 cm D
- Weight: 5.2 kg
- Color: Black
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 –49°C and at a relative
humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C. However, the useful life
of the system’s standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and its peripherals be installed in an
environment with a normal room temperature of 15 – 27°C.
Agency Listings and Approvals
The listings and approvals below apply to the basic NSP-25C control panel. In
some cases, certain modules may not be listed by certain approval agencies, or
listing may be in process. Consult factory for latest listing status.
- ULC Listed: S635(DAYRC, UOJZC)
- ETL listed: Report # 3189837NYM-001a
Note: For versions used outside Canada, see DF-60610.
NFPA Standards
The NSP-25C complies with the following NFPA 72 Fire Alarm Systems
requirements:
- LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory).
- REMOTE STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory) Where a DACT is not accepted, the alarm, trouble and supervisory relays may be connected to ULC listed transmitters.
- PROPRIETARY (Automatic, Manual and Waterflow).
- CENTRAL STATION (Automatic, Manual and Waterflow, and Sprinkler Supervised).
JumpStart®, NOTIFIER®, and System Sensor® are registered trademarks of
Honeywell International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use of
this document is strictly prohibited.
This document is not intended to be used for installation purposes. We try to
keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements. All
specifications are subject to change without notice.
For more information, contact Notified.
888-289-1114
10 Whitmore Road
Woodbridge, Ontario LZL 7Z4
www.notifier.com Canadian DN-60640:A2 •
12/03/2010
firealarmresources.com
References
- Fire Alarm Resources | Download fire alarm documents
- Home (USA) | NOTIFIER by Honeywell | Engineered Fire Alarm System.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>