RO-HM Reverse Osmosis System Condair Instruction Manual
- June 15, 2024
- condair
Table of Contents
- RO-HM Reverse Osmosis System Condair
- Product Information
- Specifications
- Product Overview
- Condair RO-H Description
- Inlet Water Quality Requirements
- Installation Considerations
- Electrical Schematic Diagrams
- Important Notes on Installation
- Delivered Packages
- Installation of Condair RO-HM
- Electrical Installation
- Installation of Filters and RO Membrane
- Maintenance
- Troubleshooting
- Disinfection
RO-HM Reverse Osmosis System Condair
Product Information
Specifications
-
Model: Condair RO-H
-
Humidification and Evaporative Cooling System
-
Variants:
-
RO-HB: RO-H 3.17 gal (12 l) Expansion tank Used with Condair
MN -
RO-HM: RO-H 4.8 gal Used with Condair US (20 lbs/h), Condair
RS, size S (23 lbs/h), Condair Omega Pro, size S (23 lbs/h),
Condair RM
-
-
Scope of Delivery:
- 4.8 gal (18 l) tank
- 3.17 gal (12 l) tank
Product Overview
Condair RO-H Description
The Condair RO-H is a reverse osmosis system designed for
humidification and evaporative cooling. It utilizes advanced
technology to provide efficient and reliable performance.
Inlet Water Quality Requirements
Before installation, ensure that the inlet water meets the
following quality requirements:
-
* Insert water quality requirement 1
- Insert water quality requirement 2
- Insert water quality requirement 3
Installation Considerations
When installing the Condair RO-H, consider the following:
-
* Qualification of personnel
- Safety precautions
- Positioning and installation guidelines
- Water connection instructions
- Installation of the Condair RO-H system
- Installation of the tank
- Water piping and connections
Electrical Schematic Diagrams
Refer to the provided electrical schematic diagrams for proper
electrical installation of the Condair RO-H system.
Product Usage Instructions
Important Notes on Installation
Qualification of Personnel
Only qualified personnel should perform the installation of the
Condair RO-H system to ensure proper setup and functionality.
Safety
Follow all safety guidelines and precautions during the
installation process to prevent accidents and injuries.
Delivered Packages
Upon receiving the Condair RO-H system, check that all delivered
packages are complete and undamaged.
Installation of Condair RO-HM
Please Observe the Following on Positioning and
Installation
Ensure proper positioning and installation of the Condair RO-HM
system according to the provided guidelines.
Water Connection
Follow the instructions for connecting the water supply to the
Condair RO-HM system.
Installation of Condair RO-H System
Install the Condair RO-H system according to the provided
installation instructions.
Installation of Tank
Properly install the tank for the Condair RO-HM system.
Water Piping and Connections
Connect the necessary water pipes and ensure proper connections
for the Condair RO-HM system.
Electrical Installation
Follow the provided electrical installation instructions to
connect the Condair RO-H system to the power supply.
Installation of Filters and RO Membrane
Perform the following steps for commissioning work and
installation of filters and RO membrane:
Maintenance
Regular maintenance is essential to ensure optimal performance
of the Condair RO-H system.
Troubleshooting
If any issues arise during the operation of the Condair RO-H
system, refer to the troubleshooting section for assistance in
identifying and resolving problems.
Disinfection
Periodic disinfection is necessary to maintain a clean and
hygienic environment. Follow the provided instructions for
disinfecting the Condair RO-HM system.
FAQ (Frequently Asked Questions)
Q: How often should I perform maintenance on the Condair RO-H
system?
A: Regular maintenance should be performed according to the
maintenance schedule provided in the manual. This will ensure the
system operates efficiently and prolong its lifespan.
Q: Can I use the Condair RO-H system for both humidification
and evaporative cooling?
A: Yes, the Condair RO-H system is designed to provide both
humidification and evaporative cooling functionalities. Follow the
installation and usage instructions to utilize both features
effectively.
2600606-B EN 2311
INSTALLATION, OPERATION AND SERVICE MANUAL
Reverse Osmosis System Condair RO-H
Humidification and Evaporative Cooling
Thank you for choosing Condair
Installation date (MM/DD/YYYY): Commissioning date (MM/DD/YYYY): Site: Model:
Serial number:
Proprietary Notice This document and the information disclosed herein are
proprietary data of Condair Ltd. Neither this document, nor the information
contained herein shall be reproduced, used, or disclosed to others without the
written authorization of Condair Ltd., except to the extent required for
installation or maintenance of recipient’s equipment. Liability Notice Condair
Ltd. does not accept any liability due to incorrect installation or operation
of the equipment or due to the use of parts/components/equipment that are not
authorized by Condair Ltd. Copyright Notice © Condair Ltd., All rights
reserved. Technical modifications reserved.
Contents
1
Introduction
5
1.1
First things first
5
1.2
About this installation and operation manual
5
1.3
Variants
5
1.4
Scope of delivery
6
2
For your safety
7
2.1
Qualification of personnel
7
2.2
Intended use and not intended use
7
2.3
Hygiene
7
2.3.1 Guidelines to ensure your system stays clean and prevent the growth of Legionella
9
2.4
Ensure safe operation
9
3
Important notes
10
3.1
Warranty
10
3.2
Delivery and storage
10
3.3
Disposal
10
3.4
Disinfection
10
4
Product overview
11
4.1
Condair RO-H description
11
4.2
Inlet water quality requirements
11
4.3
Installation considerations
11
4.4
Electrical schematic diagrams
14
5
Installation Condair RO-H
15
5.1
Important notes on installation
15
5.1.1 Qualification of personnel
15
5.1.2 Safety
15
5.2
Delivered packages
16
5.3
Installation of Condair RO-HM
16
5.3.1 Please observe the following on positioning and Installation
17
5.3.2 Water connection
17
5.3.3 Installation of Condair RO-H system
19
5.3.4 Installation of tank
19
5.3.5 Water piping and connections
20
5.4
Installation of Condair RO-HB
21
5.4.1 Please observe the following on positioning and Installation
22
5.4.2 Installation of Condair RO system
22
5.4.3 Installation of tank
23
5.4.4 Water piping and connections
23
5.5
Electrical installation
24
Contents 3
5.6
Installation of filters and RO membrane
24
5.6.1 Commissioning work
25
5.6.2 Install RO membrane
26
5.6.3 RO membrane flush and startup, RO-HM
27
5.6.4 Equipment protection
28
5.6.5 Controller menu
28
6
Maintenance
29
6.1
Important notes on maintenance
29
6.2
Optical inspection
29
6.3
Maintenance work
30
6.3.1 Maintenance work to be carried out on the Condair RO-H
30
6.3.2 Replacing the filter cartridge
31
6.3.3 Membrane Flushing
33
6.3.4 Disinfection
33
6.4
Preventive spare parts chart
33
6.5
Maintenance check list
34
7
Troubleshooting
35
7.1
Qualification of personnel
35
7.2
Issue indication and resolution
35
8
Disinfection
36
8.1
Disinfecting the RO-HM
36
8.1.1 Preparations for disinfection
36
8.1.2 Cleaning and disinfection
38
8.1.3 Flushing and transition to control operation
38
9
Product Data
40
10
Spare parts and Consumables
41
10.1
Spare parts
41
10.2
Consumables
41
11
Declaration of conformity
42
4 Contents
1 Introduction
1.1 First things first
Thank you for choosing the Condair RO-H Reverse Osmosis System. The Condair
RO-H Reverse Osmosis System incorporates the latest technical advances and
meets all recognized safety standards. Nevertheless, improper use of the
Condair RO-H Reverse Osmosis System may result in danger to the user or third
parties and/or damage to property. To ensure a safe, proper, and economical
operation of the Condair RO-H Reverse Osmosis System, please observe and
comply with all information and safety instructions contained in the present
documentation as well as in the separate documentations of the components used
together with the Condair RO-H Reverse Osmosis System. If you have questions
after reading this documentation, please contact your Condair representative.
They will be glad to assist you.
1.2 About this installation and operation manual
The subject of this manual is the Condair RO-H Reverse Osmosis System. This
manual has been written to ensure the safe use, performance and longevity of
the equipment, and is intended for installation and commissioning by engineers
and properly trained technical personnel. Please read this manual thoroughly
before specifying, designing or installing an RO System from Condair Ltd. Keep
for future reference. As our policy is one of continuous research and
development, we reserve the right to amend, without notice, the specifications
provided in this document. Condair Ltd. does not guarantee nor accept
liability for the accuracy of information in this document.
1.3 Variants
RO-HB: RO-H 3.17 gal (12 l) Expansion tank Used with Condair MN RO-HM: RO-H
4.8 gal Used with Condair US ( 20 lbs/h) Condair RS, size S ( 23 lbs/h)
Condair Omega Pro, size S ( 23 lbs/h) Condair RM
Introduction 5
1.4 Scope of delivery
RO-HM: · RO-H base · Pressure tank 4.8 gal (18 l)
including mounting kit · Installation kit · Sediment filter 5 µm · Granular
Active Carbon Filter · RO Membrane 400 gal · Wrenches (3x)
RO-HB: · RO-H base · Expansion tank 3.17 gal (12 l)
including fittings · Installation kit · Sediment filter 5 µm · Granular Active
Carbon Filter · RO Membrane 400 gal · Wrenches (3x) · Housing cover
4.8 gal (18 l) tank Symbols used in this manual
3.17 gal (12 l) tank
CAUTION!
The catchword “CAUTION” used in conjunction with the caution symbol in the
circle designates notes in this installation manual that, if neglected, may
cause damage and/or malfunction of the unit or other material assets.
WARNING!
The catchword “WARNING” used in conjunction with the general caution symbol
designates safety and danger notes in this installation manual that, if
neglected, may cause injury to persons.
DANGER!
The catchword “DANGER” used in conjunction with the general caution symbol
designates safety and danger notes in this installation manual that, if
neglected, may lead to severe injury or even death of persons.
Safekeeping Please safeguard this installation manual in a safe place, where
it can be immediately accessed. If the equipment changes hands, the
documentation must be passed on to the new operator. If the documentation gets
mislaid, please contact your Condair representative.
Language versions This manual is available in various languages. Please
contact your Condair representative for information or check on our website.
6 Introduction
2 For your safety
2.1 Qualification of personnel
Every person working with the Condair RO-H Reverse Osmosis System must have
read and understood this installation and operation manual before carrying out
any work. Knowing and understanding the contents of the manual is a basic
requirement for protecting the personnel against any kind of danger, to
prevent faulty operation, and to operate the unit safely and correctly. All
ideograms, signs and markings applied to the components of the Condair RO-H
Reverse Osmosis System must be observed and kept in readable state.
All installation work described in this manual may only be carried out by
persons who are well trained and adequately qualified and are authorized by
the customer. For safety and warranty reasons any action beyond the scope of
this manual must be carried out only by qualified personnel authorised by the
manufacturer. It is assumed that all persons working with the Condair RO-H
Reverse Osmosis System are familiar and comply with the appropriate
regulations on work safety and the prevention of accidents.
2.2 Intended use and not intended use
The Condair RO-H Reverse Osmosis System is intended to be used exclusively for
pure water production within the operating conditions as specified in chapter
5.3 and must not be installed/used in explosion hazard areas. Any other use
without the written consent of Condair is considered as not conforming with
the intended purpose and may lead to the Condair RO-H Reverse Osmosis System
becoming dangerous and will void any warranty. Operation of the equipment in
the intended manner requires that all the information contained in this manual
are observed (in particular the safety and hygiene instructions).
Not intended use The pure water (RO water) is not drinking water and must not
be connected to any drinking water outlet.
2.3 Hygiene
Please observe the local health and safety executive’s technical guidance on
the control of Legionellosis in water systems.
The user is responsible for ensuring that the water system complies with local
regulations, bylaws and guidelines (such as the HSE ACoP L8, VDI 6022, ISO
22000, HACCP or equivalent). If inadequately maintained, the RO System, can
support the growth of microorganisms, including the bacterium that causes
Legionnaires’ disease.
The RO-H is produced according to best hygiene standards, which means that we
have considered all aspects of this equipment to reduce the risk of
Legionnaires’ disease and other similar conditions. However, the user is
responsible for ensuring that the installation, operation and maintenance work
on the equipment is performed in a manner, ensuring that the system stays
clean!
Any risks or hazards relating to the system, including during installation and
maintenance, should be identified by a competent health and safety
representative who is responsible for introducing effective control measures.
For your safety 7
DANGER! The RO-H must be installed, operated and maintained in accordance with
this manual. Failure to do so could result in contamination that might cause
Legionnaires’ disease, which can be fatal.
WARNING! To prevent water stagnation and microbial contamination, the RO-H
power supply must be left switched on. If the system is switched off for more
than 48 hours, the pipe work and system must be disinfected as per the
instructions in chapter 8, and a full risk assessment in case of a Condair MN
and Condair US must be undertaken to ensure safe operation.
DANGER! Risk of electric shock! A person may come in contact with live parts
when the pump station/control unit is open. Touching live parts may cause
severe injury or death. Prevention: Before carrying out any work on the
system, disconnect power and water supply.
WARNING! Poorly maintained Condair RO-H Systems may be hazardous. Prevention:
Read, understand and follow maintenance guidelines to ensure your system stays
safe.
WARNING! Water produced from a Condair RO-H System is very aggressive and can
cause metals to corrode quickly. The Condair RO-H System should always be
connected to piping / equipment suitable for handling RO water. Prohibited
modifications to the unit No modifications must be undertaken on the Condair
RO-H Reverse Osmosis System without the express written consent of the
manufacturer.
8 For your safety
2.3.1
Guidelines to ensure your system stays clean and prevent the growth of
Legionella
· Carry out a risk assessment of the water system using a competent person and
implement an appropriate monitoring and control program.
· Initiate procedures for checking the system, cleaning tanks, changing
filters, disinfection etc.
· The RO-H must be connected to a clean, potable mains water supply.
· Enter into a service contract that suits you or your company.
· Stop the system if polluted drinking water is found in your area.
· Avoid water temperatures above 77 °F that favor the growth of Legionella. If
the water temperature surpasses 86 °F, the RO-H cannot be used in connection
with a Condair MN.
· Do not stop the system unless it is faulty or leaking (avoid water
stagnation).
· Disinfect the Condair RO-H System at least once a year and after every
maintenance or repair. Always carry out a complete system disinfection
inclusive humidifier if it has been turned off for more than 48 hours.
· Have water samples taken and tested for harmful bacteria at least once a
year.
· Conduct follow-up measurements until the system is clean if bacteria have
been detected in the system.
The Condair service team can help. Condair has expert technicians who can provide: · Bacteriological troubleshooting on site * · Cleaning and disinfecting · Preventive maintenance · Repair and fault finding · Training and guidance
*Condair uses a quick method for measuring bacterial activity in the water: the approved and patented BactiQuant. Once the water sample has been taken, we can read the bacteriological quality of the water within 30 minutes, and disinfect the system if necessary.
2.4 Ensure safe operation
If it is suspected that safe operation has been compromised, the RO-H should
immediately be shut down and secured against accidental power-up. Shut down
the RO-H if: · Components are damaged, worn or very soiled. · The RO-H does
not work correctly. · Joints, pipes or hoses are leaking.
No modifications must be made on the RO-H without the manufacturer’s consent.
All persons working with the RO-H must report any alterations made to the RO-H
to the owner immediately. Use only original accessories and spare parts
available from your Condair representative.
For your safety 9
3 Important notes
3.1 Warranty
The RO-H is covered by a two-year warranty from the invoice date with the
exception of the replacement parts listed in the routine maintenance section.
Failure to observe the manufacturer’s installation and maintenance
recommendations and instructions will invalidate the warranty. Condair Ltd.
cannot be made liable for damage or injury attributable to failure to observe
the manufacturer’s installation and maintenance recommendations and
instructions.
3.2 Delivery and storage
To ensure consistent quality, each RO-H is tested and preserved before leaving
the factory. If put into storage prior to use, the RO-H must be covered and
protected from physical damage, dust, frost and rain. Storage Until
installation, the components of the RO-H must be stored in their original
packaging in a place protected from dripping water under the following
conditions: · Room temperature: 41 … 104 °F · Room Humidity: 10 … 75 %rh (non-
condensing) Inspection Upon receipt, remove the transit packaging and inspect
the unit to ensure that no damage has occurred during transit. Any visible
damage must be reported to your Condair distributor immediately.
3.3 Disposal
You must observe local laws and regulations when disposing of your RO-H at the
end of its working life. The pumps and piping are constructed from stainless
steel and plastic which may be fully recycled. This includes all consumables
such as the sediment filter, the granular active carbon filter and the RO
membrane.
3.4 Disinfection
Depending on the system hygiene, it is advised that preventative disinfection
fluid is added to the RO-H at an appropriate frequency, but at least once a
year. Please read the maintenance section for more information on
disinfection, chapter 8. If you are in any doubt about the suitability of
water quality, please contact your Condair distributor, who will be happy to
support you.
10 Important notes
4 Product overview
4.1 Condair RO-H description
Reverse osmosis system (from now on called RO) with reservoir tank for removal
(>95 %) of salts and minerals in tap water. The systems are designed by
Condair Ltd. with focus on reliable and hygienically correct solutions. The
system uses a separation process in which water molecules can pass through a
membrane, while the majority of salts and minerals are retained and thereafter
flushed out to drain. From the inlet, the water passes through a two steps of
filtering before reaching the RO membrane. First step is an activated carbon
filter to remove any residual free Chlorine in the inlet water. Second filter
step is a sediment filter to remove particles above a size of 5 µm.
4.2 Inlet water quality requirements
The quality of the water being used in the Condair RO-H System should be
checked prior to system commissioning. The RO-H system must be connected to a
clean, potable drinking water quality mains. If the inlet water does not meet
the quality specified in the preconditions table in chapter 4.3, it may be
necessary to install additional water treatment.
4.3 Installation considerations
Do not install the RO-H in a room that often surpasses an air temperature of
77 °F. Also keep installation away from heat producing applications, such as
boiler, central heating etc. Observe the following restrictions concerning
length of piping: – Junction from tap water line to RO inlet: max. 6.5 ft – RO
to tank: max. 6.5 ft – Tank to product inlet: max. 9.8 ft – RO to drain
siphon: max. 16.4 ft
Product overview 11
Preconditions for Condair RO-H water treatment:
Water supply
Tap water / drinking water quality, no pathogens allowed
Incoming dynamic pressure @ max. flow
850 psi *1)
Min. flow requirement @ min. dynamic pressure of inlet water connection
52.8 gal/h
*2) Water temperature (**)
4177 °F *3)
*2) pH max.
8.0
pH in incoming water
pH 6.57.0
pH 7.17.5
pH 7.68.0
*2) Max. US hardness
31 gpg
18 gpg
10 gpg
*2) Max. conductivity incoming @ pH:
1300 µS/cm
750 µS/cm
600 µS/cm
*2) Max. TDS incoming @ pH:
210 ppm/l
130 ppm/l
100 ppm/l
Silt index:
max. 3
Cl2 Residual Chlorine
max. 1.0 ppm
NTU:
max. 1.0
1) If the pressure exceeds 50 psi, it is mandatory to install a pressure reducer upstream of the RO-H in the supply line, which is set to 50 psi max. pressure.
2) If any of these values are higher, a water softener should be installed in front of the RO-H. * When used with Condair MN max. 68 °F
3) The RO-H may only be connected to a cold water line.
12 Product overview
Flow diagram for RO-HB
V3
S2
P
tank
Carbon filter Sediment filter
F1
S1
Inlet
P
F2
RO
M V1 P1
R1 V2
M M
Expansion tank
T1
Booster pump
to Condair MN
F1: Carbon filter (free chlorine removal) F2: Sediment filter, 5 µm P1: Pressure pump in front of RO cartridge, 24 VDC, max. 70 psi RO: RO cartridge, size 400 gpd R1: Flow restrictor 0.18 gpm S1: Low pressure switch 8 psi S2: High pressure switch 32 … 44 psi, adjustable T1: Expansion tank, steel, 3.17 gal (effective) V1: Inlet on/off valve 24 VDC V2: Auto-flush valve 24 VDC V3: Backflow preventer after RO cartridge
Flow diagram for RO-HM
RO
to humidification
tank
application
Pressure tank
2.5 G / 6 G
Carbon filter Sediment filter
inlet
F1: Carbon filter (free chlorine removal) F2: Sediment filter, 5 µm P1:
Pressure pump in front of RO cartridge, 24 VDC, max. 70 psi RO: RO cartridge,
size 400 gpd R1: Flow restrictor 0.18 gpm S1: Low pressure switch 8 psi S2:
High pressure switch 32 … 44 psi, adjustable T1: Pressure tank 2.5 or 4.8 gal,
steel V1: Inlet on/off valve 24 VDC V2: Auto-flush valve 24 VDC V3: Backflow
preventer after RO cartridge
drain
Product overview 13
Switch Mode Power Supply
4.4 Electrical schematic diagrams
Electrical wiring with Condair MN
Switch Mode Power Supply
RO control board
Condair MN
MN-booster connection box
Electrical wiring with all other applications
RO control board
High pressure switch Low pressure switch Inlet water valve Quality flush valve
incl. flow restrictor RO Pump TDS Sensor
Booster Pump
High pressure switch Low pressure switch Inlet water valve Quality flush valve
incl. flow restrictor RO Pump TDS Sensor
14 Product overview
5 Installation Condair RO-H
5.1 Important notes on installation
WARNING! Do not retighten/unscrew hoses while the system is pressurized!
CAUTION! Do not use oil, grease, glue, silicon, O-ring lubrication, etc. when
assembling pipes or hose connections. All of the above products can act as
food for bacteria and are thus pose health risks. Only approved lubricant:
Liquid dish soap. Wash your hands before or wear clean gloves while assembling
parts in direct contact with water. Keep dust covers on pipes and hoses until
just before assembly.
CAUTION!
Do not fasten the pump station or hoses/pipes to vibrating installations.
5.1.1
Qualification of personnel
All installation work must be performed only by persons familiar with the Condair RO-H System and sufficiently qualified for such work. All work on electric installations must only be performed by adequately qualified electricians.
In addition, when installing the Condair RO-H in conjunction with a Condair MN with DGUV certification, it is essential that the personnel have completed training in accordance with VDI 6022, Sheet 1:
· Category B
for installation, maintenance, inspection
· Category A
for hygiene-relevant tasks in planning, construction, commissioning and hygiene inspections
5.1.2
Safety
The pump station and any control units may only be connected to the mains
after all installation work has been completed. All statements relating to
correct positioning and installation must be followed and complied with. When
installing components of the RO-H, use the materials and hoses supplied with
the unit. In case of doubt, please contact your Condair supplier.
Installation Condair RO-H 15
5.2 Delivered packages
The Condair RO-HM package consists of:
· 1 Reverse Osmosis System · Wall mount RO · 1 Pressure Tank and Bottom Stand
· Installation pack (see fittings below)
The Condair RO-HB package consists of:
· 1 Reverse Osmosis System · Wall mount RO · 1 Expansion Tank + fittings ·
Hood · Installation pack (see fittings below)
[1] [2] [7] [3] [4] [5] [6] [1][2]: 1/2″ male to 1/2″ female connector with 3/8 push on and manual valve [3]: 3/8″ quick connect to 1/4″ quick connect adapter [4]: 1/4″ push fit equal tee [5]: Tank valve 1/4″ push fit to 1/4″ female thread [6]: Connection to humidifier [7]: 1/2″ push fit – 1/2″ female connector | (used for RO-HB) [8] [8]: 1/4″ push fit manual flush valve
Note: The tank valve [5] needs to be attached to tank using Teflon tape
5.3 Installation of Condair RO-HM
Before positioning the RO-H pump and tank, it is important to consider the
position of the equipment in the room prior to installing the RO-H unit.
Depending on the type of humidifier connected, different tank sizes are
needed. Please see table below.
Voltage
AC 110120 V, 60 Hz
Power rating
90 W
Suitable water pressure 8…50 psi
Operating pressure
max. 116 psi
Inlet temperature
4177 °F
Max. inlet water TDS value
See preconditions for water supply
Max. pure water production 0.22 gpm
Size depends on application:
Eff. Volume
Condair MD Condair MN
1.7 gal 2.4 gal
Tank size
Condair Omega Condair RM Condair RS
3.6 gal 3.6 gal 3.6 gal
Condair Omega Pro 3.6 gal
Condair US
3.6 gal
Tank size 2.5 gal 3.17 gal 4.8 gal 4.8 gal 4.8 gal 4.8 gal 4.8 gal
Tank type Pressure Expansion Pressure Pressure Pressure Pressure Pressure
Suitable water quality
With the pressure tank type, the effective volume is smaller than the tank
size due to the pressure bubble in the tank.
Municipal tap water according to the local drinking water regulations.
16 Installation Condair RO-H
5.3.1
Please observe the following on positioning and Installation
· The room temperature should be between 45 °F and 86 °F all year round and
the air humidity between 15 %rh and 50 %rh (non-condensing) and the room
should be ventilated.
· The Condair RO-H System can only be installed in a location with a floor
drain.
· The site must be freely accessible with sufficient space for convenient
operation and maintenance. The lateral and vertical spaces can be determined
from the figure below. To the front, the minimal free space is 11.8 in.
· The system is designed for operation in a frost-free and dry environment,
always indoors.
· The installation site must not be exposed to direct sunlight and must be
sufficiently far away from other heat sources.
· Do not install the Condair RO-H System in exposed locations or locations
with heavy dust loads.
· When installing the RO-H with a HumiLife product such as Condair MD, a wall
mount of the System is mandatory. For any other application, floor or wall
mount is possible.
· When installing the RO-HB variant, a wall mount of the tank is mandatory.
For RO-HM the water tank can either be placed on the floor or mounted on the
wall
5.3.2 Water connection
WARNING!
Do not open and fill hoses, pumps, filters or tanks with water if the system
is not to be started immediately after installation (48 hours). Stagnant water
acts as a breeding ground for potentially dangerous micro-organisms.
Measures on site
· A class 2 backflow preventer must be installed near the “tap water
connection” (see figure on page 18).
· A siphon must be available for the discharge of the concentrate water. The
siphon as well as the drain pipe on the building side must be dimensioned in
such a way that the drainage of the condensate water max. 1.2 gpm during
flushing for 30 s after switching on the RO-H max. 0.4 gpm in regular
operation
is guaranteed.
Installation Condair RO-H 17
tap water connection
150 mm max. 2 m
150 mm 150 mm
max. 5 m 15°
200 mm
max. 3 m
to application
max. 2 m
20 mm
installation with floor mount
tap water connection
installation with wall mount
1 18 Installation Condair RO-H
1. Inlet (3/8″ push fit)
2. Pure water (3/8″ push fit)
2
3 3. Drain (1/4″ push fit)
5.3.3
Installation of Condair RO-H system
The RO-H is mounted to the wall, using the enclosed wall mount set (SAP No).
Consider that the wall needs to have a holding capacity of 40 lbs. Do not
mount the RO-H on plywood, dry plaster or sheetrock walls.
Procedure:
1. Draw drilling pattern (see figure below) on wall, drill holes. 11.8 in
2. Insert dowels 3. Correctly arrange screw and spacer and washers.
thick washer thin washer
4. Insert and tighten the screws so that a gap of approx. 0.2 in is still
open between the damper and the screw head.
5. Lift up and hang the RO-H to the wall so that the holes in the backside of
the RO are in between the screw head and the damper.
6. For the RO-HB variant, tighten the screws so that an overall gap of 0.1 in
is retained between the back wall of the RO-H and the wall. The remaining gap
is needed to attach the RO-H hood. With the RO-HM variant, the gap is not
needed, screw the RO to the wall completely.
5.3.4
Installation of tank
The tank can be either placed on the floor, using the floor stand and secured
with one bracket. Alternatively, it can be mounted to the wall, using two
brackets. Consider that the wall needs to have a holding capacity of
· 40 lbs with the tank shipped with the RO-HM
Do not mount the RO-H tank on plywood, dry plaster or sheetrock walls. Two brackets are included in the installation pack. The second bracket can be discarded if floor mount is chosen.
Bottom mount / wall mount of RO-H tank
Installation Condair RO-H 19
5.3.5
Water piping and connections
The following flow diagram shows the needed fittings and their placement.
Please follow the information strictly.
Water pipe (on site) 1/4″ hose
RO-H
3/8″ hose Inlet
[1]
Pure water
3/8″ hose [3] 1/4″ hose [4] 3/8″ – 1/4″ push fit connector
drain
1/4″ hose
[6] [1] 1/2″ male – 1/2″ female connector with 3/8″ push on and manual valve
1/4″ hose
[3] 3/8″ – 1/4″ push fit connector [4] [4] 1/4″ push fit equal tee [8] [5] Tank valve 1/4″ push fit to 1/4″
female thread [5] [6] Connection to humidifier (see next
page)
[8] 1/4″ push fit manual flush valve
The tank valve [5] needs to be attached to tank using Teflon tape.
Siphon (on site)
Use [1] (1/2″ thread) to connect the RO-H to a drinking water line. If the RO is the last tapping point in the line, use the blind cap [2].The cap is screwed on using Teflon tape (not included in the shipment). Use the white 3/8″ hose is to connect the push-on outlet of [1] to the inlet of the RO-H (max hose length is 2m). Please make sure that the push-on cap is screwed tight on [1] and that the hose is securely pushed-in on the side of the RO. To test the latter, after pushing the hose in as far as it will go, try to pull it out. If the hose withstands the pull, it is secure. Close the manual valve on the fitting.
Use an appropriate length of 1/4″ hose to connect the drain of the RO to a
suitable water drain (maximal length of hose is 16.4 ft). · In order to avoid
stagnating water and thus possible stagnation contamination of the unit, the
hose
must have a downward slope of >15° over its whole length. · The drain water
must flow into a siphon. The end of the hose must have a distance of approx.
0.8 in
from all walls and the floor. · The hose must be positioned in such a way that
no water splashes out of the siphon or the siphon
overflows even with a brief water flow of 1 gpm.
To connect the RO to the tank and further to the humidification application,
follow the diagram on this page. With all push-fit connections, make the
security test described at the beginning of this section to avoid leaks.
All push fit connectors have blue security rings. These rings must be removed
before attaching a hose to the connectors and afterwards applied again.
Acertain yourself that the cut of the house is clean and the hose is neither
damaged nor buckled.
20 Installation Condair RO-H
1. The tank valve [5] must be tightened using teflon tape.
2. Use connector [6] to connect the RO-H to the following humidifier
applications: · Condair MD · Condair RS · Condair Omega · Condair Omega Pro ·
Condair RM
If you have purchased the RO-H with an ultrasonic humidifier (US), use the
second 1/4″ – 3/8″ pushfit adapter [3] as well as the 3/8″ pushfit to 1/2″ NPT
male thread adapter to connect to this humidifier.
Do not connect the hose to the humidifier inlet yet. This will be done during
commissioning.
5.4 Installation of Condair RO-HB
Before positioning the RO-H pump and tank, it is important to consider the
position of the equipment in the room prior to installing the RO-H unit.
The RO-HB is shipped with a 3.17 gal (12 l) expansion tank. For further
technical details regarding the installation, please refer to the table below:
Voltage
AC 110120 V, 60 Hz
Power rating
90 W
Suitable water pressure 8…50 psi *1)
Operating pressure
max. 116 psi
Inlet temperature
4168 °F *2)
Max. inlet water TDS value
See preconditions for water supply
Max. pure water production 0.22 gpm
Suitable water quality
Municipal tap water according to the local drinking water regulations.
1) If the pressure exceeds 50 psi, it is mandatory to install a pressure reducer upstream of the RO-H in the supply line, which is set to 50 psi max. pressure.
2) The RO-H may only be connected to a cold water line.
Installation Condair RO-H 21
5.4.1
Please observe the following on positioning and Installation
· The RO System can only be installed in a location with a floor drain.
· The site must be freely accessible with sufficient space for convenient
operation and maintenance. The lateral and vertical spaces can be determined
from the figure below. To the front, the minimal free space is 3 ft.
· The system is designed for operation in a frost-free and dry environment,
always indoors.
· The installation site must not be exposed to direct sunlight and must be
sufficiently far away from other heat sources.
· Do not install the RO System in exposed locations or locations with heavy
dust loads.
· Wall mount of the System is mandatory.
· When installing the RO-H with the HumiLife product Condair MN, a wall mount
of the tank is mandatory. 5.9 in
5.2 in
5.2 in
max. 7.9 in
max. 16.4 ft 15°
7.9 in
max. 6.5 ft
5.4.2
Installation of Condair RO system
The RO-H is mounted to the wall, using the enclosed wall mount set (dowels,
screws, spacers, dampers). Consider that the wall needs to have a holding
capacity of 18 kg. Do not mount the RO on plywood, dry plaster or sheetrock
walls.
The correct arrangement of the dampers are necessary in order to minimize the
transmission of vibrations from the RO to the wall.
Procedure: 1. Draw drilling pattern (see figure below) on wall, drill holes. 11.8 in
2. Insert dowels 3. Correctly arrange screw and spacer and damper. The
correct arrangement of the dampers are
necessary in order to minimize the transmission of vibrations from the RO to
the wall.
thick washer thin washer
22 Installation Condair RO-H
4. Insert and tighten the screws so that a gap of approx. 0.2 in is still
open between the damper and the screw head.
5. Lift up and hang the RO-H to the wall so that the holes in the backside of
the RO are in between the screw head and the damper.
6. Tighten the screws so that an overall gap of 0.1 in is retained between
the back wall of the RO and the wall. The remaining gap is needed to attach
the RO-H hood.
5.4.3
Installation of tank
The tank is installed to the wall using the two brackets and the dowels / wood
screw from the installation package. Consider that the wall needs to have a
holding capacity of 40 lbs. Do not mount the RO-H tank on plywood, dry plaster
or sheetrock walls.
4.8 gal tank for RO-HM
3.17 gal tank for RO-HB
5.4.4
Water piping and connections
The following flow diagram shows the needed fittings and their placement.
Please follow the information strictly.
Water pipe (on site) 1/4″ hose
RO-H
3/8″ hose Inlet
[1]
Pure water
3/8″ hose
drain
[1] 1/2″male – 1/2″ female connector with 3/8″ push on and manual valve
Siphon (on site)
Tank fittings (SS parts need to be attached using Teflon tape): 1″ fNPT Tee 1″ mNPT 3/8″ fNPT Bushing 3/8″ 3/8″ JG push fit adaptor (grey) 3/8″ 10mm JG push fit adaptor (black)
Installation Condair RO-H 23
RO-H
3/8″ hose Inlet
[1]
Pure 3/8″ hose water
drain
Water pipe (on site) 1/4″ hose
Siphon (on site)
[7] [1] 1/2″male – 1/2″ female connector with 3/8″ push on and manual valve
[7] 1/2″ push fit – 1/2″ female connector
Use [1] to connect the RO-H to a drinking water line. If the RO is the last tapping point in the line, use the blind cap. The cap is screwed on using Teflon tape (not included in the shipment). Use the white 3/8″ hose is to connect the push-on outlet of [1] to the inlet of the RO-H (max hose length is 6.5 ft). Please make sure that the push-on cap is screwed tight on [1] and that the hose is securely pushed-in on the side of the RO. Close the manual valve on the fitting.
To test the latter, after pushing the hose in as far as it will go, try to
pull it out. If the hose withstands the pull, it is secure. Use an appropriate
length of 1/4″ hose to connect the drain of the RO to a suitable water drain
(maximal length of hose is 16.4 ft). · In order to avoid stagnating water and
thus possible stagnation contamination of the unit, the hose
must have a downward slope of >15° over its whole length. · The drain water
must flow into a siphon and the hose must end approx. 0.8 in above the siphon
(open drain). · The hose must be positioned in such a way that no water
splashes out of the siphon or the siphon
overflows even with a brief water flow of 1.2 gpm.
To connect the RO to the tank, follow the diagram at the beginning of this
chapter. With all push-fit connections, make the security test described at
the beginning of this section to avoid leaks. For RO-HB specifically, cut an
appropriate length of 3/8″ hose and use connector [7] to connect the hose to
the upper inlet of the tank.
5.5 Electrical installation
DANGER! Danger of electrical shock! Connect the RO-H to a 110120 VAC socket,
according to local standards. High voltages, danger of electric shock!
Touching live parts may cause severe injury or death.
Make sure to have a power socket within 3.3 ft of the RO-H application.
24 Installation Condair RO-H
5.6 Installation of filters and RO membrane
WARNING!
The system start-up must be carried out or monitored by persons approved and
trained by Condair. Errors in the start-up phase may ultimately result in
illness, injury and death of humans.
CAUTION!
When fitting water filters, RO membranes, hoses and other components in direct
contact with water please, wear sterile gloves or touch only the packing paper
to keep the filter bacteria-free. Remember to wash your hands!
CAUTION!
Commissioning of the pump should be the last thing performed at an
installation site. When the pump has run with water and the preservation fluid
(windscreen wash) has been flushed out, it should always be kept on (summer
and winter) in order to keep the system hygienically clean by allowing it to
run its automatic flushing.
5.6.1
Commissioning work
Disconnect the power before starting any commissioning work.
Install filters The filters are already packaged inside their housings.
Note: The front right filter will house the granular active carbon (GAC)
filter, the front left filter will house the silt filter. Check the
configuration before installation. See picture.
1. Remove the housings from the filter heads.
2. Take off the plastic covers. 3. Remove the plastic packaging from the
filter elements. 4. Place the filters back into their housings. 5. Screw the
housings back into their heads
and tighten with the wrench.
Sediment filter
GAC filter
Installation Condair RO-H 25
5.6.2
Install RO membrane
The RO membrane is part of the accessory kit. 1. Disconnect the pipe from the
push-fit connector on the right side of the RO membrane housing. 2. Lift up
the right side of the membrane housing from its holder. 3. Unscrew the lid. If
it sits tight, use the black wrench to unscrew the lid and the white wrench to
counter hold.
Pure water inside membrane housing
2 O-rings
Waste water
Pure water
O-ring RO membrane housing
Inlet water
Membrane housing
Sealing ring
Membrane housing lid
Warning: When installing the RO membrane, you should pay attention to the
direction of the membrane. Put the end with the two O-rings into the housing
first. When installing correctly you only need a little force to put the
reverse osmosis membrane into the housing. If you encounter too much
resistance, please do not force installation. Doing so may cause permanent
damage to the membrane shell or membrane components.
4. Remount the lid. Tighten it using the wrenches. 5. Reconnect the water
inlet pipe to the push fit.
26 Installation Condair RO-H
5.6.3 RO membrane flush and startup, RO-HM
CAUTION!
The first time a new RO membrane is to be used, it is important to flush out
any preservation fluids so that they do not end up in the system.
After confirming that the water route connections are correct, confirm that
inlet water, power supply, drain and connection to the application are
installed. The latter should not be connected yet. Then follow these steps to
commission/troubleshoot the unit (see graphic chapter 5.3.5):
1. Open the tap water inlet valve [1], close the storage tank valve [5] and
plug in the power source. An automated, 30-second flushing process starts;
water will start to drain through the discharge outlet. Do not connect to
humidifier yet!
2. Wait for the water treatment system to operate stably (about 510
seconds), check each connection to make sure it is secure, see if there is any
leakage from the membrane shell, filters, etc.
3. Connect the RO line to the humidifier unit. Make sure the inlet valve of
the unit is closed. Wait approximately 30 seconds, check whether the RO stops
producing water.
Open the application’s inlet valve. If no water is flowing after 510 s, check
if the water line is open. the RO is powered on. concentrate water is
flowing. 4. Close the RO inlet valve [1]. After a short time observe whether
the RO has stopped operating. Open the RO inlet valve [1] again. 5. Flush the
RO unit for at least 10 min before using any water for humidification. Reason:
the reverse osmosis membrane element package contains a small amount of
protective solution and the post-activated carbon filter will emit activated
carbon powder the first time it is used. Now close valve [8]. 6. Before
starting the commissioning of the humidifier unit, open the tank valve [8] and
let the tank fill (15 min for 3.17 gal tank, 18 min for 4.8 gal tank).
Notes on commissioning 1. The major components of the RO membrane are plastic.
When using the product always observe the integrity of the water treatment
unit to ensure safe use. 2. When you start operating the water treatment
system the pure water TDS value may be a little high. After running for some
time the TDS value for pure water will gradually decrease until it is stable.
3. Once the RO has been installed, the inlet ball valve should never be closed
except for short periods of maintenance work. If the ball valve is closed for
longer periods, bacterial contamination will happen in the pipes (bacterial
contamination on standstill) which may cause serious bodily harm when the
water thereafter is used for humidification. When the RO is not in use, the
highpressure switch will automatically cut off the water supply automatically.
In these “usage methods”, “usage” refers to when the power supply is connected
and/or the inlet water ball valve is open so the water treatment system is in
a working condition.
Installation Condair RO-H 27
5.6.4 Equipment protection
Pressure switch (inlet water) The RO-H has a pressure switch, which monitors
the inlet water pressure. If the inlet water pressure drops, the controller
will stop the pump, thus protecting it against dry running. If the water
pressure drops, the starter screen will display a zero, equalling `PM Water
pressure too low’.
5.6.5
Controller menu
The computer box controls the working status, to ensure the machine work
normally, and the RO membrane is in good working condition.
Function display:
– F:
Flushing
– Running 8: Water production
– Lit 8:
Tank full, not water need
– Lit 0:
No water, too low incoming
pressure
– Lit 6:
Service needed
Qulity flush countdown + TDS display
Manual quality flush
Letter state
Display instructions
8 (dynamic rotation) means water production
When the high-pressure switch detects that the water pressure in the tank is lower than the set value, the water purifier enters the water production process.
F means flushing
Flushing of RO either at startup or when the “strong washing” button has been pressed. If there has not been any pure water production within 12 h, the function is triggered automatically.
8 (static display) means the water tank is full and there is no water demand
When the high-pressure switch detects that the water pressure in the tank reaches the set value, the RO will stop production.
0 means lack of water
When the low-pressure switch detects that the inlet water pressure is lower than 8 psi, the water purifier will stop working and the buzzer sounds.
6 means maintenance
The buzzer sounds. A service (filter, RO membrane change) is necessary. Please contact Condair Service.
28 Installation Condair RO-H
6 Maintenance
6.1 Important notes on maintenance
Qualification of personnel All maintenance work must only be carried out by
qualified and trained personnel authorized by the owner. Maintenance and
repair of the electrical installation of the RO-H must only be carried out by
qualified personnel who are aware of possible dangers and implications. It is
the owner’s responsibility to verify proper qualifications of the personnel.
General note The instructions and details for maintenance work must be
followed. Only maintenance work described in this documentation may be carried
out. Use only original Condair spare parts to uphold the system warranty.
Safety Before maintenance is initiated, the RO-H must be taken out of
operation in accordance with instructions in the section “Taking the system
out of service. The RO-H must be serviced at the intervals described in this
manual and cleaning and disinfection must be performed by trained and
instructed personal.
WARNING! A poorly maintained RO system may endanger health if used to supply
an adiabatic humidification system. Therefore it is mandatory to observe the
specified maintenance intervals and to carry out maintenance and cleaning in
strict accordance with the instructions.
6.2 Optical inspection
During operation, the RO-H has to be inspected weekly. On this occasion, check
the following: · Entire system for leakage · Electric installation for damage
· Operating display for warning or error messages · Carbon filter, softener
and optional water treatment system in front of the RO.
Condair Ltd. recommends to perform the visual inspection on a weekly basis. If
the inspection reveals any irregularities (e.g. leakage, error indication) or
any damaged components take the RO-H out of operation. Have a qualified
specialist or Condair service technician correct the damage or malfunction.
Maintenance 29
6.3 Maintenance work
To ensure safe, hygienic and economic operation of the RO-H, vital components
must be checked and maintained periodically according to the table below. The
maintenance intervals and maintenance work stated below are guideline values.
Local conditions, quality of the water, etc. could influence the maintenance
intervals. The relevant personnel is responsible for any maintenance work
carried out.
Service, to be carried out
Service interval [months]
Control weekly monitoring checklist (chapter 6.5)
12
Check the condition of the pump (pressure & noise) pressure should be
min. 60 psi above inlet water pressure if pressure is unstable replace
12
filters and test again.
Functional testing of pressure switch. Close inlet water and check that
system stops Close pressure tank valve and check that RO system
12
stops. “8” should be shown in display.
Leak testing (check for leaks).
6
Disinfection / cleaning of tank
12
Control units
Test display for errors (visual inspection)
6
Hygiene
Disinfection/cleaning of the system
12
6.3.1 Maintenance work to be carried out on the Condair RO-H
When maintenance is due, carry out the following maintenance work:
· Replace the filter cartridge of the integrated filter (see chapter 6.3.2). ·
Disinfect the water system incl. external pure water tank (by Condair service
technician)
30 Maintenance
6.3.2 Replacing the filter cartridge
WARNING! Always wear disposable protective gloves when handling filters to
prevent infection due to opportunistic pathogens!
Sediment filter
GAC filter
To replace the filter cartridges proceed as follows (also see chapter 5.3.5
and chapter 5.4.4): 1. Set the Condair RO-H system out of operation by
unplugging from mains supply cable to unit. 2. Close the inlet water valve
[1]. 3. Plug in the RO-H to the mains power supply for 5 seconds, to release
pressure from the water line. 4. Place a bucket (min. 2.5 gal) underneath the
filter. 5. Turn filter housing counterclockwise and remove filter housing. If
the housing sits tight, use the wrench to unfasten. 6. Remove filter cartridge
and O-ring from housing. Note: Filter cartridge can be disposed with the
household waste. 7. Wash filter housing and O-ring with a lukewarm soap
solution and rinse filter housing and O-ring well with tap water before
remounting. 8. Check if O-ring is placed correctly in the housing. Insert
O-ring into the groove inside the filter housing. 9. Carefully take new filter
cartridge out of its packaging and remove plastic foil without damaging the
filter cartridge. 10. Insert filter cartridge into the filter housing.
Centrically align filter cartridge inside the housing and ensure the sealing
of the filter cartridge is correctly placed. 11. Screw tight the housing.
Maintenance 31
Replacing the membrane(s):
WARNING!
Always wear disposable protective gloves when handling filters to prevent
infection due to opportunistic pathogens!
Pure water inside membrane housing
2 O-rings
Waste water
O-ring RO membrane housing
Inlet water
Pure water
Membrane housing
Sealing ring
Membrane housing lid
To replace the membrane(s) proceed as follows: 1. Make sure the Condair RO-H
is disconnected from mains and pressure is released from water line. 2. Close
the inlet water valve [1]. 3. Plug in the RO-H to the mains power supply for 5
seconds, to release pressure from the water line. 4. Place a bucket (min. 2.5
gal) underneath the unit. Disconnect hose from inlet water. 5. Lift up the
membrane housing from its holder and unscrew the housing cover. 6. Remove the
old membrane, by using a small screwdriver to lift out the membrane. 7.
Inspect inside of the housing for dirt and biofilm. If cleaning is required: ·
Wash the membrane housing, O-rings and shell cover using warm water, soap and
a lintfree cloth. · Put on disposable gloves, then carefully take new membrane
out the packaging and remove plastic foil without touching or damaging the
membrane.
8. Follow the instruction in chapter 5.6.2 Install RO membrane, then ·
Reconnect water pipe to “inlet water” in membrane housing and place the
membrane shell in its holders. · When all maintenance work is completed,
connect the RO-H to water and mains supply.
32 Maintenance
6.3.3
Membrane Flushing
1. Membrane Flushing: After installation of a new membrane, it is important
to flush the membrane. The RO-H automatically flushes for 30 seconds at start
up, but this might not be sufficient when a new membrane is installed.
2. Press “Strong Washing” on the display and observe the TDS. When it is
below 1015 ppm, the units can be set into normal operation.
6.3.4
Disinfection
If the system is part of a DGUV approved system, the RO-H must be disinfected
every 6 month, by Condair Service team. Please refer to chapter 8 for the
disinfection of the system.
6.4 Preventive spare parts chart
Defined preventive replacement of spare parts in connection with service
Products Carbon filter Sediment filter 5 micron RO cartridge RO pump Booster pump Inlet valve Flush valve Low pressure switch High pressure switch
Condair MN
1yr *
1yr *
2yr
Condair Omega
1yr
1yr
1yr
Condair RM
1yr
1yr
1yr
Condair RS
1yr
1yr
1yr
Condair Omega Pro 1yr
1yr
1yr
Condair US
1yr *
1yr *
2yr
replace replace replace replace replace replace
replace ——
repair repair repair repair repair repair
repair repair repair repair repair repair
repair repair repair repair repair repair
repair repair repair repair repair repair
- Depending on Condair service cycle.
Replace = Repair =
If defect, RO needs to be completely replaced. If defect, the part can be replaced by qualified technical personnel.
Maintenance 33
6.5 Maintenance check list
34 Maintenance
Date
Check for leaks Visual inspection
()
TDS in display ppm
Manual Flush ()
RO pump, pressure-check
(check manometer on front when unit is producing water)
Empty pressure tank completely
(open up valve [6] until empty)
psi
()
7 Troubleshooting
7.1 Qualification of personnel
Problems occurring during operation of the RO-H must always be eliminated by
qualified and trained personnel. Malfunctions caused by the electrical
installation must only be repaired by authorized personnel (e.g. electrician).
7.2 Issue indication and resolution
When working on the system, the RO-H must be taken out of operation and
prevented from further inadvertent operation. Make sure the power supply to
the RO-H is disconnected and that the water supply is cut off.
Fault indication
RO not starting
No pure water production / no visible drain water
RO starts over repeatedly
Permeate quality decreases Permeate flow decreases (below 5.3 gal/h)
Cause of the problem Indication
Power off
Lights off on RO Detected by humidifier low water pressure
No water Too low water pressure High/low pressure switch damaged
Status of RO = “0” Detected by humidifier low water pressure
Inlet valve failed to open or clogged
No drain/pure water on RO. Detected by humidifier low water pressure
Check valve blocked. Check valve defect.
No pure water, only drain water on RO. Detected by humidifier low water pressure
RO membrane clogged or scaled
Very little pure water on RO. Detected by humidifier low water pressure
Expansion / pressure tank defect
Detected during optical inspection of RO. Detected by humidifier low water pressure.
System loses pressure (possible leak)
Insufficient water production. Detected by humidifier low water pressure.
High pressure switch defect
Insufficient water production. Detected by humidifier low water pressure.
Membrane defect
TDS meter in RO display will indicates high value. Detected by humidifier filter exhausted.
Resolution Plug power. Check power supply. Check inlet valve. Check raw water
pressure. Switch needs replacement. Call Condair support. Inlet valve needs
replacement. Call Condair support.
Check valve needs replacement. Call Condair support.
Replace RO membrane, check incoming water quality and drain valve.
Replace tank.
Call Condair support. Locate leak and replace defect part(s). Switch needs
replacement. Call Condair support.
Replace membrane.
Membrane scaled or clogged
Detected by humidifier low water pressure.
Troubleshooting 35
8 Disinfection
The disinfection of the RO-HB variant is described in in the Installation and
Operation Manual of the Condair MN and is part of it’s standard service.
Before starting disinfection, the connected humidifier must be switched off
and secured against being switched on again unintentionally.
8.1 Disinfecting the RO-HM
Combined instruction for Condair service and for private end users:
Condair Ltd. recommends that these work steps are only carried out by well- trained personnel.
Protective clothing: Plastic gloves and goggles
Warning notice:
Disinfectants can cause serious skin and eye damage. Always wear protective gloves and eye protection when working with disinfectants. Read the safety data sheet for complete safety instructions.
Disinfectants:
RO-H disinfection connector set (SAP No. 2600112) HaloMist HM10 Ag 5 % Qt (SAP No. 2300001)
Further material: Bucket, min. 2 gal / absorbent cloth
*If this disinfection liquid is not available in your country, please contact Condair Support for an alternative, approved disinfection liquid.
The following time should be scheduled for the entire procedure: 1. active
work on the system 30 – 45 min 2. exposure time of the chemical 30 min
Note on the correct handling of John Guest hose connectors
Please make sure that the hoses are always fully inserted into the push fit
connectors. To test proper fit, try to pull the hose out again after you have
pushed it all the way in. If the hose can withstand the pull, it will sit
securely and leak free in the connector. If you need to shorten hoses, always
use a hose cutter suitable for PA material. The cut edge must always be at
right angle to the hose direction and smooth. The hose end must never be
squeezed or kinked.
8.1.1
Preparations for disinfection
All instructions in the text refer to the sketches in this chapter. 1. Close
inlet water [1] and unplug the RO-H from the power outlet. 2. Wait a few
seconds and plug in the RO-H in again until an acoustic signal is heard.
Unplug the RO-H again. 3. Close the tank valve [5]. 4. Place the bucket under
the flush valve. 5. Release the pressure by opening the manual flush valve
[8]. 6. Empty the pressure vessel completely by slowly opening the tank valve
[5]. 7. Remove the drain hose on the RO-H side (the drain hose is connected to
the drain (3)).
36 Disinfection
Water pipe (on site) 1/4″ hose
Connection to humidifier
RO-H
Pure 3/8″ hose
1/4″ hose
1/4″ hose
Inlet
water
[1] [4] disconnect hose from Tee
drain
[8]
disconnect hose
[6]
from drain (3)
[5][5]
Siphon (on site)
Water pipe (on site) 1/4″ hose from disinfection connector set
1. Inlet (3/8″ push fit)
1
2
3
2. Pure water (3/8″ push fit) 3. Drain (1/4″ push fit)
8. Remove the connecting hose to the humidifier at the T-piece [4].
9. Connect the hose from the RO-H disinfection connector set to the T-piece
[4] on the one side and to the drain (3) on the other side as shown in the
graph below.
RO-H
Inlet
Pure 3/8″ hose water
1/4″ hose
1/4″ hose
[1] [4] [8]
drain
[5]
Connect drain (3) and T-piece [4] with hose
Disinfection 37
8.1.2
Cleaning and disinfection
10. Remove the active carbon filter (GAC) and sediment filter housings.
11. Clean the filter housings with lukewarm water, soap and a sponge.
12. Fill 1 liter of disinfectant into each of the filter housings and mount
them again (instructions see chapter 5.6.1, step 5).
Sediment filter
GAC filter
13. Open the RO membrane housing and remove the RO membrane. Clean the membrane housing analogous to the filter housings (instructions see chapter 6.3.2). Put an absorbent cloth underneath the membrane housing catch dripping water.
14. Check the correct fit of the O-ring on the housing thread (see diagram, page 39). Mount the lid back on the membrane housing and insert the hose.
15. Place the bucket under the flush valve [8]. Close the tank valve [5] and open the flush valve.
16. Open the inlet valve [1] to the system.
17. Wait approx. 1 min and then plug the RO-H into the power outlet.
18. Wait until approx. 0.3 gal of the water/disinfectant mixture has flowed out through the flush valve [8].
19. Close the flush valve [8] and open the tank valve [5]. The tank fills up.
20. Wait about 2min and unplug the RO-H from the power outlet.
21. Close the inlet valve [1].
22. Exposure time of the chemical: wait approx. 30 minutes.
8.1.3
Flushing and transition to control operation
23. Place the bucket under the flush valve. Open the tank valve [5] and then
the flush valve [8] and empty the tank into the bucket.
24. Check that there is no visible dirt or particles Empty the bucket into
the normal drain.
25. Remove the hose from the disinfection connector set from the T-piece [4]
and the drain (3) (page 37).
26. Reconnect the waste water hose to the drain (3) (chapter 8.1.1).
27. Reconnect the hose to the humidifier to the T-piece [4].
28. Plug the RO-H again into the power outlet and wait until an acoustic
signal sounds. Unplug again the RO-H.
29. Close the flush valve [8] and the tank valve [5].
30. Unscrew the filter housing and empty the remaining liquid into the
bucket. Insert new filters. Follow the instructions in chapter 6.3.1.
31. Open the membrane housing. Empty it carefully and completely into the
bucket. Insert a new membrane. Follow the instructions in chapter 6.3.2. Make
sure that the O-ring is correctly seated on the thread of the membrane housing
before screwing on / tightening the lid. Reconnect the hose of the water inlet
to the cap.
38 Disinfection
Pure water inside membrane housing
2 O-rings
Waste water
O-ring RO membrane housing
Inlet water
Pure water
Membrane housing
Sealing ring
Membrane housing lid
32. Place the bucket under the flush valve [8] and open it.
33. Open the inlet valve [1]. The filter housings are now filled and the
system is pressurized.
34. Check for leakage.
35. Plug the RO-H again into the power outlet.
36. The plant rinses for 30 seconds before permeate production starts. A
countdown is shown on the display. Then check the TDS display (see sketch,
page 39). If the displayed value is > 30 after rinsing, press the “Strong
Wash” button to trigger another rinse. Repeat this until the value in the
display is <30.
Qulity flush countdown + TDS display
Manual quality flush
37. Close the flush valve [8] and open the tank valve [5].
38. After 2 minutes, unplug the RO-H from the power outlet.
39. Place the bucket under the flush valve [8] and open it. The tank empties
into the bucket. Close the flush valve [8] again.
40. Plug the RO-H again into the power outlet. The pressure tank is filled
after approx. 10 minutes. The humidifier can then be switched on and put into
regular operation.
This concludes the disinfection procedure.
Disinfection 39
9 Product Data
Technical parameters Voltage / frequency; protection Power Rating Incoming
water quality Incoming conductivity (see page 12) Incoming TDS Incoming
pressure (see page 12) max. permissible operating pressure Incoming water
temperature RO permeate capacity @ 5° C Salt rejection Water efficiency Output
pressure Prefilter 1 Prefilter 2 Low pressure switch trigger High pressure
switch trigger
Tank sizes and types
Noise Connection inlet Connection pure water Connection drain Outer dimensions
RO (HxLxW) Outer dimensions hood (HxLxW) Outer dimensions tank 3.17 gal DxH
Outer dimensions tank 4.8 gal DxH Weight RO Weight hood Weight tank 3.17 gal
Weight tank 4.8 gal
Unit VAC / Hz W
µS/cm ppm psi psi °F gal/h % % psi
Micron psi psi gal dBA
inch inch inch inch lbs lbs lbs lbs
Value 110120 / 60 1) 90 Tap water 1501000 95700 850 2) 116 4177 *3) 3.17 9598 50/50 43.587.0 Act. Carbon 5 8 32.043.5 3.17 Expansion tank 4,8 Pressure tank <50 Adapter to 3/8″ push to connect JG 3/8″ push fit JG 1/4″ push fit 18.3 x 14.0 x 8.5 18.5 x 15.2 x 9.8 12.68 x 8.15 11.0 x 16.7 18.7 8.8 13.2 9.0
1) The Condair RO-H is energized by 24 VDC from an UL listed class 2 power source. The system needs to be protected by a ground fault circuit interruptor 5 A.
2) If the pressure exceeds 50 psi, it is mandatory to install a pressure reducer upstream of the RO-H in the supply line, which is set to 50 psi max. pressure. A suitable pressure reducer is available from Condair (2600230).
*3) The RO-H may only be connected to a cold water line.
40 Product Data
10 Spare parts and Consumables
10.1
Spare parts
SAP No. 2600097 2600098 2606940 2601023 2601024 2501660 2599774
Description Low/high pressure switch, set Inlet/drain valve, set Expansion tank 3.17 gal (12 liters) Set SP Worm drive bracket 260-280/12, Set SP Housing cover RO-H Hydraulics Installation set Booster pump 5bar/72.5psi, 3/8″ female
10.2
Consumables
SAP No. 2604425 2599771 2600099 2600112 2300001
Description Service-kit RO-H (2599771 & 2600099) RO membrane 3013 400G GAC/Sediment filter set Disinfection fittings set, RO-H Disinfection HaloMist HM10 Ag, 5 % Qt
Spare parts and Consumables 41
11 Declaration of conformity
Konformitätserklärung
EC
Declaration of conformity
Déclaration de conformité
Wir, Condair Group AG CH-8808 Pfäffikon SZ erklären in alleiniger Verantwortung, dass das Produkt
We, Condair Group AG CH-8808 Pfäffikon SZ declare under our sole responsibility, that the product
Nous, Condair Group AG CH-8808 Pfäffikon SZ déclarons sous notre seule responsabilité, que le produit
Condair RO-H
auf das sich diese Erklärung bezieht, mit den folgenden Normen oder normativen Dokumenten übereinstimmt
to which this declaration relates is in
auquel se réfère cette déclaration est
conformity with the following standards or conforme aux normes ou autres
other normative standards
documents normatifs
EN 60335-1 EN 60335-2 EN 60335-3 EN 61000-3-2
EN 61000-3-3
und den Bestimmungen der folgenden and is corresponding to the following
Richtlinien entspricht
provisions of directives
2014 / 35 / EU 2014 / 30 / EU
2014 / 68 / EU
Pfäffikon , August, 2020
Condair Group AG
et est conforme aux dispositions des directives suivantes
Robert Merki Head of Engineering
2599874 DE/EN/FR 2008
Condair Group AG Gwattstrasse 17 8808 Pfäffikon, Switzerland Tel. +41 55 416
61 11, Fax +41 55 588 00 07 info@condair.com, www.condair-group.com
42 Declaration of conformity
CONSULTING, SALES AND SERVICE:
U.S.A 1021 6th Street Racine, WI 53403 CANADA 2740 Fenton Road Ottawa, Ontario
K1T 3T7 TEL: 1.866.667.8321 FAX: 613.822.7964 EMAIL: na.info@condair.com
WEBSITE: www.condair.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>