ATO GK3000 Single Phase VFD Drive User Manual
- June 15, 2024
- ATO
Table of Contents
- Reminder
- GK3000 Quick Setup Test Manual
- External terminal control
- Potentiometer control/0-10V control (VI port)
- 0-10V control (CI port)
- 4-20mA control (CI port)
- Multi-function terminal application, multi-speed operation
- Constant pressure water supply system
- Modbus-RTU control
- CUSTOMER SERVICES
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
ATO GK3000 Single Phase VFD Drive
Reminder
This quick-set-user-manual is for the ATO single phase VFDs whose SN numbers on the nameplate begin with the 9000 series. If the SN number on the VFD nameplate you receive does not start with the 9000 series, please contact us to obtain related electronic quick-set-user-manual and related instruction video. Thank you for your understanding and cooperation.
GK3000 Quick Setup Test Manual
Check whether the input and output power wiring is correct and whether the input voltage is correct. It is recommended to connect the motor with no load for testing.
Take the 3-phase 220V/60Hz 0.75kW asynchronous motor as an example to set the parameters:
Group P0, operation parameter group setting
P0.00=0 (V/F control, used in occasions with low load, such as fans and
pumps)
P0.01=1 (digital setting frequency is given mode, power-off memory)
P0.02=60 (running frequency setting–set according to actual needs)
P0.03=0 (running command channel is selected as panel operation)
P0.04=0 (running direction setting)
P0.05=60 (maximum frequency setting)
P0.06=60 (upper limit frequency setting)
P0.07=0.00 (lower limit frequency setting, minimum operating frequency)
P0.12=10 (acceleration time 10s)
P0.13=10 (deceleration time 10s)
Group P8, motor parameter group setting
P8.00=0 (select the motor type as ordinary asynchronous motor)
P8.01=0.8 (motor rated power – set according to the motor nameplate)
P8.02=220V (motor rated voltage – set according to the motor nameplate)
P8.03=3.45 (motor rated current – set according to the motor nameplate)
P8.04=60 (motor rated frequency – set according to the motor nameplate)
P8.05=1390 (motor rated speed–set according to the motor nameplate)
P8.37=2 (1 asynchronous motor static self-learning, 2 asynchronous motor
dynamic self learning)
The above is a simple setting method, please refer to the complete instruction
manual for detailed explanation.
If you connect a Single-phase motor, please make sure that the phase loss
protection is off.
PA.13=0
External terminal control
Before operation, please ensure that the wiring is correct. The basic function
parameters of group P0 have been set, and the motor parameters of group P8
have been set. (Refer to the Quick Setup
Test Manual for the setting method)
Setting parameters P0 function parameter setting:
P0.01=0 (set frequency by panel potentiometer)
P0.03=1 (external terminal control)
P3.00=1 (X1 terminal function is defined as FWD forward function) self-
reset button, normally open contact.
P3.01=2 (X2 terminal function is defined as REV reverse function) self-
reset button, normally open contact.
P3.02=3 (X3 is three-wire control mode reset/stop) self-locking button,
normally closed contact
P3.14=2 (3-wire control mode 1)
Operation logic explanation:
Press SB1 (self-reset button), the motor starts forward.
Press SB3 (self-locking emergency stop button), the motor stops.
Press SB2 (self-reset button), the motor reverses and starts.
Potentiometer control/0-10V control (VI port)
Before operation, please ensure that the wiring is correct. The basic function
parameters of group P0 have been set, and the motor parameters of group P8
have been set. (Refer to the Quick Setup
Test Manual for the setting method)
P0.01=2 (VI analog given port takes effect, 0-10V voltage is used as
frequency source)
P0.03=1 (terminal run command channel)
P0.24=002 (VI analog setting)
P2.43=0 (lower limit of input voltage protection value) D0 alarm setting
range, can be ignored.
P2.44=10 (upper limit of input voltage protection value) D0 alarm setting
range, can be ignored.
P3.00=1 (X1 terminal function is defined as FWD forward function) self-
reset button.
P3.01=2 (X2 terminal function is defined as REV reverse function) self-
reset button.
P3.02=3 (X3 is three-wire control mode reset/stop) self-locking button,
normally closed contact.
P3.16=0 (VI input minimum value 0V)
P3.17=0.0 (VI minimum input corresponds to 0%)
P3.18=10.00 (VI input maximum 10V)
P3.19=100.00 (VI input maximum input corresponds to 100%)
When it is found that it is always running at low frequency, please check
the wiring of the potentiometer, try to exchange the wiring position of VI and
GND, or the wiring position of +10V and GND.
0-10V control (CI port)
Before operation, please ensure that the wiring is correct, the basic function
parameters of group P0 have been set, and the motor parameters of group P8
have been set. (Refer to the Quick Setup
Test Manual for the setting method)
The left jumper plug CI needs to be connected to V.
P0.01=3 (CI analog given port takes effect)
P3.21=0 (CI minimum input voltage 0V)
P3.22=0 (the minimum CI corresponds to 0%)
P3.23=10 (CI maximum voltage input 10V)
P3.24=100 (the maximum CI corresponds to 100%)
4-20mA control (CI port)
Before operation, please ensure that the wiring is correct, the basic function
parameters of group P0 have been set, and the motor parameters of group P8
have been set. (Refer to the Quick Setup Test Manual for the setting method)
The left jumper plug CI needs to be connected with I
(When the analog input is current input, 1mA current is equivalent to 0.5V
voltage. Therefore, the parameter of converting 4-20mA into voltage should be
2~10V.)
P0.01=3 (CI analog given port takes effect)
P3.21=2 (CI minimum input voltage 0V)
P3.22=0 (the minimum CI corresponds to 0%)
P3.23=10 (CI maximum voltage input 10V)
P3.24=100 (the maximum CI corresponds to 100%)
Multi-function terminal application, multi-speed operation
Before operation, please ensure that the wiring is correct, the basic function
parameters of group P0 have been set, and the motor parameters of group P8
have been set. (Refer to the Quick Setup
Test Manual for the setting method)
P0.01=6 (multi-speed given frequency)
P3.00=1 (X1 function is defined as FWD)
P3.01=2 (X2 function is defined as REV)
P3.02=3 (X3 is defined as three-wire emergency stop/reset)
P3.03=12 (X4 is defined as multi-stage speed control terminal 1)
P3.04=13 (X5 is defined as multi-stage speed control terminal 2)
P3.05=14 (X6 is defined as multi-stage speed control terminal 3)
Pb group
Pb.00=15Hz (multi-segment frequency 0)
Pb.01=20Hz (multi-segment frequency 1)
Pb.02=25Hz (multi-segment frequency 2)
Pb.03=30Hz (multi-segment frequency 3)
Pb.04=35Hz (multi-segment frequency 4)
Pb.05=40Hz (multi-segment frequency 5)
Pb.06=45Hz (multi-segment frequency 6)
Pb.07=50Hz (multi-segment frequency 7
K3 (X6) | K2 (X5) | K1 (X4) | Set Frequency (Hz) | Code |
---|---|---|---|---|
OFF | OFF | OFF | 15 | Pb.00 |
OFF | OFF | ON | 20 | Pb.01 |
OFF | ON | OFF | 25 | Pb.02 |
OFF | ON | ON | 30 | Pb.03 |
ON | OFF | OFF | 35 | Pb.04 |
ON | OFF | ON | 40 | Pb.05 |
ON | ON | OFF | 45 | Pb.06 |
ON | ON | ON | 50 | Pb.07 |
Constant pressure water supply system
Take the 4-20mA pressure sensor access system as an example.
Before operation, please ensure that the wiring is correct, the basic function
parameters of group
P0 have been set, and the motor parameters of group P8 have been set. (Refer
to the Quick Setup
Test Manual for the setting method)
The left jumper plug CI needs to be connected with I (When the analog
input is current input, 1mA current is equivalent to 0.5V voltage. Therefore,
the voltage parameter converted from 4-20mA should be 2~10V)
P0.01=10 (constant pressure water supply parameter setting)
P0.03=1 (terminal run command channel)
P2.43=3.10 (lower limit of input voltage protection value)
P2.44=6.80 (upper limit of input voltage protection value)
P3.00=1 (X1 terminal function is defined as FWD forward function) Whether
the button needs to be self-locking.
P3.01=2 (X2 terminal function is defined as REV reverse function)
P3.02=3 (X3 terminal function is defined as STOP)
P3.21=2 (CI minimum input voltage 0V)
P3.22=0 (the minimum CI corresponds to 0%)
P3.23=10 (CI maximum voltage input 10V)
P3.24=100 (the maximum CI corresponds to 100%)
P4.02=43 (alarm lower limit pressure output)
P6.30= (given pressure)
P6.31= (maximum pressure value)
P6.32= (minimum pressure value)
P6.33= (alarm pressure value, upper limit, to judge whether the pipe
network is blocked)
P6.34= (alarm pressure value, lower limit, to judge whether the pipe
network is short of water)
P6.35= (Wake-up pressure value, when the water consumption increases and
the pipe network pressure is less than this value, it will enter the working
state, and the VFD will run at full frequency at this time)
P6.36=0 (duration of wake-up pressure operation, full frequency)
P6.37= (sleep pressure level value, when the pipe network pressure is
greater than this value, the frequency will gradually decrease to the sleep
frequency )
P6.38=10 (sleep pressure level duration, the time that the pipe network
pressure is continuously maintained at the sleep pressure level)
P6.39= (sleep frequency, running frequency before entering sleep)
P6.40=10 (sleep frequency continuous time, sleep frequency running time)
Therefore, after the pressure drops to the wake level, the VFD runs at a higher sleep frequency (or at full frequency). After reaching the sleep pressure, the frequency is higher than the sleep frequency, gradually decreases and runs for a period of time (P6.38), then runs at the sleep frequency (P6.39) for a period of time (P6.40), and finally enters sleep. When the pressure value drops to the awakening position, repeat the action.
Modbus-RTU control
P0.01=9 (RS485 interface takes effect)
P0.03=2 (serial port running command takes effect)
P0.05=60 (maximum frequency, this frequency can be input manually or
written by command 06)
PC.00=5 (9600BPS, =6 19200, =7 38400)
PC.01=3 (no checksum)
PC.02=1 (station number, =0 broadcast address)
PC.03=2 (0-20ms response delay)
PC.04=0 (serial port timeout is invalid, 0.1~60.0s)
PC.05=1 (standard Modbus protocol)
Executable code 03 read, 06 write (not save), 07 write (save)
Example address, the following are 0x hexadecimal 0x5000 address is the
running speed percentage storage area, (read/write)
(Decimal, it needs to be converted to hexadecimal and written into VFD. The
maximum value corresponds to the percentage of the maximum operating frequency
of the VFD, such as
5000=50.00% of the maximum speed.)
5000 speed percentage (Read/Write)
5001 running frequency (Read only)
5002 bus voltage (Read only)
5003 output voltage (Read only)
5004 output current (Read only)
5005 output power (Read only)
Control command address area 0x6000
Command code
Forward 0001
Reverse 0002
FWD Jog 0003
REV Jog 0004
Free stop 0005
Deceleration stop 0006
Fault reset 0007
Function code address 0xF0~0xFF/ can also be written.
For example, to query P0.03 of P0 group, the query address is 0xF003.
Query P6 group P6.10, the query address is 0xF60A.
Write frequency 60.00Hz into P0.05:
01 06 F0 05 17 70 — — (– is checkcode)
Write output frequency percentage 100.00% into 0x5000
01 06 50 00 27 10 — — (– is checkcode)
Write forward run
01 06 60 00 00 01 — — (– is checkcode)
Read output current
01 03 50 04 00 01 — — (– is checkcode)