theben 1610011 Analog Timer with Synchronous Motor Instruction Manual
- June 14, 2024
- theben
Table of Contents
theben 1610011 Analog Timer with Synchronous Motor
Product Information
Specifications
- Model: SYN 161 d
- Part Number: 1610011
Product Usage Instructions
Safety Precautions
Before using the product, please read and understand the following safety precautions:
- Ensure the power supply is disconnected before installation or maintenance.
- Do not touch any live parts to avoid electric shock.
- Avoid using the product in wet or damp conditions.
- Keep the product away from flammable materials to prevent fire hazards.
Installation
To install the product, follow these steps:
- Consult a qualified electrician for installation to ensure proper electrical connections.
- Disconnect the power supply before proceeding with the installation.
- Mount the product securely on a suitable surface.
- Connect the necessary electrical wires according to the provided wiring diagram.
- Ensure all connections are tight and secure.
- Once installed, double-check all connections before restoring power.
Operation
To operate the product, follow these instructions:
- Ensure the power supply is connected and turned on.
- Refer to the user manual for specific functions and settings.
- Use the provided controls or interface to adjust the desired settings.
- Observe any safety guidelines or restrictions mentioned in the user manual.
- If any issues or malfunctions occur during operation, disconnect the power supply and consult a qualified technician.
Maintenance
To maintain the product and ensure its longevity, follow these guidelines:
- Regularly clean the product using a soft, dry cloth. Avoid using abrasive materials or solvents.
- Inspect the product for any signs of damage or wear. Replace any damaged parts immediately.
- Keep the product free from dust and debris by cleaning it regularly.
- Do not attempt to repair or modify the product yourself. Contact an authorized service center for assistance.
FAQ
Q: Can I install the product myself without consulting an electrician?
A: It is highly recommended to consult a qualified electrician for installation to ensure proper electrical connections and safety.
Q: What should I do if there is a power outage?
A: During a power outage, the product will not function. Once the power is restored, the product will resume normal operation.
Q: How often should I clean the product?
A: It is recommended to clean the product regularly using a soft, dry cloth to remove dust and debris. The frequency of cleaning depends on the environment in which the product is used.
WARNING
Danger of death through electric shock or ire!
- Installation should only be carried out by professional electrician!
- Disconnect the mains power supply prior to installation and/or disassembly!
General information
- Analogue time switch
- Daily programme
- 1 channel
- Shortest switching time 15 min
Technical data
- Operating voltage : 230 V~, +10 %/-15 %
- Frequency : 50 Hz
- Power consumption : 1 VA
- Rated impulse voltage: 4 kV
- Contact : wo way switch
- Opening width : < 3 mm (μ)
- Switching capacity: 16 A, 250 V~, cos ϕ = 1
- 4 A, 250 V~, cos ϕ = 0,6
- Min. switching capacity: 24 V / 100 mA AC
- Incandescent lamp load: 1100 W
- Operating temperature : –20 °C … +55 °C
- Protection class: II in accordance with EN 60669-1 subject to designated installation
- Protection rating: IP 20 in accordance with EN 60529
- Time accuracy: synchronised with mains
- Pollution degree : 2
- Type : 1 BRTU
Designated Use
- The time switch can be used for lighting, ventilation, fountains, advertising hoardings etc.
- Only for use in closed, dry rooms
- Installation on DIN top hat rail (in accordance with DIN EN 60715)
- The switching of any external wire is permitted, switching of SELV is not permitted.
Installation
- Install on DIN top hair rails (in accordance with EN 60715)
- Disconnect power source
- Strip cable by 8 mm (max. 9 mm)
- Insert cable at 45° in the open terminal L 2 cables per terminal is possible
- Only with lexible wires: Press screwdriver downwards to open spring terminal
Disconnecting the cable
- Use the screwdriver to push the load line connection opener downwards
Connection
- Note connection diagram
Description
- Switching pre-selection/ switching status indicator
- – 0 = off
- – 1 = on
- Timing disc for time display (switching time)
- Switching segments for programming SYN 161 d (1 = 15 min)
- Morning/afternoon (AM/PM) time display (current time)
- Hand for setting time (hours and minutes) can be adjusted clockwise; turn minute handirmly to right
- Three way switch: Permanent ON – AUTO – Permanent OFF
Do not turn at the switching disc! Set the times only with the clock hand
-
Set time
-
Set current time
-
e.g. 3:00 (morning)
-
e.g. 15:00 (afternoon)
-
Set switching times
-
e.g. 6:15–10:45; 16:15–21:00 ON
-
Set manual operation / switching pre-selection
-
in advance 3:00 ON (= 1)
→ The time switch operates the set switching
times, i.e. it returns to program. -
Set 1 – – 0 permanent switching
-
- → Program is not operated.
-
1 = Permanent ON
-
0 = Permanent OFF
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>