theben TP-RF KNX Media Coupler Instruction Manual

June 12, 2024
theben

theben TP-RF KNX Media Coupler Instruction Manual

WARNING

Danger of death through electric shock or fire!
• Installation should only be carried out by professional electrician!
• Disconnect the mains power supply prior to installation and/or disassembly!
• Please refer to the KNX manual for detailed functional descriptions.

General information

  • The media coupler TP/RF KNX connects KNX-RF devices with the KNX medium Twisted Pair.
  • The device supports KNX Data Security.
  • The Security Proxy and Segment Coupler functionality is only supported with the ETS 6 database.
  • The media coupler has a filter table (8 k bytes), supports long frames and is compatible with the ETS 5 software.
  • The buttons on the front can be used to disable the telegram filters for testing purposes.
  • The LEDs indicate the operating states and communication errors on the bus.

Technical data

You can find the ETS database at

www.theben.de and in the ETS online catalogue.
Theben AG herewith declares that this type of radio installation complies with Directive 2014/53/EU. The complete text of the EU Declaration of Conformity is available at the following Internet address:
www.theben.de/red-konformitaet

  Dispose of the device separately from domestic waste at an official collection point.

Proper use

  • The media coupler transmits radio signals between uni- or bidirectional radio products and twisted-pair components.

  • For use in residential and other buildings
    (office buildings, public buildings, hotels etc.)

  • Only for use in closed, dry rooms

1. Installation

  • Install in conventional flush-mounted boxes (according to DIN 49073).
  • Installation location: Observe the range of the radio devices to be linked to the device.
  • Avoid shielding objects or interfering transmitters (e.g. computers etc.) in the vicinity of the device.

2. Bus connection

  • Connect bus terminal with bus cable (note polarity).
  • Attach bus terminal.

3. Manual operation
For twisted-pair (TP)
– Button A: Press button 1 x briefly ▻ TP function will be activated
Button A press 1 x briefly ▻ Routing runtime telegrams (GA: group address) will be de-/activated (LED 1+2 on)
Button B: Press button 1 x briefly ▻ Routing management telegrams (IA: individual address) + broadcast (BC) will be de-/activated (LED 3+4 on)

For radio (RF)
– Button B: Press button 1 x briefly ▻ RF function will be activated
Button A: Press 1 x briefly ▻ Routing runtime telegrams (GA: group address) will be de-/activated (LED 5+6 on)
Button B: Press button 1 x briefly ▻ Routing management telegrams (IA: individual address) + broadcast (BC) + system broadcast (SBC) will be de-/activated (LED 7+8 on)

Button A/B: Press 1 x long
▻ Manual operation is termina

Read More About This Manual & Download PDF:

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

theben User Manuals

Related Manuals