SimpliSafe CA002 Wireless Smoke CO Detector Owner’s Manual
- June 14, 2024
- SimpliSafe
Table of Contents
- PRODUCT INFORMATION
- IMPORTANT WARNING STATEMENTS
- INSTALLATION AND LOCATION
- USAGE, OPERATION AND OPERATING MODES
- LIMITATIONS OF THE SMOKE/CO DETECTOR
- FIRE PREVENTION AND ESCAPE
- INFORMATION ABOUT CARBON MONOXIDE (CO)
- REGULAR MAINTENANCE
- SPECIFICATIONS
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Model: CA002
CA002-IFU2
Smoke/CO Detector
Owner’s Manual
IMPORTANT! Please read this Owner’s Manual carefully before installation and use. Save this manual.
PRODUCT INFORMATION
The SimpliSafe Wireless Smoke/CO Detector (CA002) is a combined photoelectric
Smoke Detector and Carbon Monoxide Detector (referred to in this Owner’s
Manual as the “Smoke/CO Detector”).
A. Smoke Detection
The Smoke/CO Detector is designed to sense smoke that comes into the detector
chamber and gives early warning of developing fires with an alarm sound from
its built-in siren. The built-in wireless transmitter also causes your
SimpliSafe Base Station siren to sound.
These sirens can provide precious time to escape before a fire spreads.
However, such pre-warning of fire is only possible if the Smoke/CO Detector is
located, installed and maintained properly as described in this Owner’s
Manual.
The Smoke/CO Detector also monitors low battery and sensor malfunctions.
These trouble conditions will cause an audible chirp from the Smoke/CO
Detector as described in Section 4 on “Usage, Operation and Operating Modes’’
below.
B. Carbon Monoxide (CO) Detection
The Smoke/CO Detector also monitors the level of CO gas in your home and gives
early warning when a potentially dangerous level exists. It does not detect
any other gas.
If a dangerous concentration of CO is detected, the red light on the front of
the detector turns on and flashes four times, and an internal siren sounds (4
loud beeps followed by a pause). The CO detector also transmits an alarm
signal to the Base Station.
The alarm automatically resets when CO is no longer detected.
The Smoke/CO Detector also monitors low battery, wall tamper and sensor end-
of-life conditions. These trouble codes are NOT transmitted to the Base
Station. You will hear and see them coming from the Smoke/CO Detector.
The SimpliSafe Smoke/CO Detector is intended only for residential indoor
applications and other areas approved by an Authority Having Jurisdiction
(AHJ), which in many jurisdictions may be your local fire department or fire
marshall. It is not intended for use in commercial applications.
IMPORTANT WARNING STATEMENTS
DANGER. ELECTRICAL SHOCK HAZARD.
Installation
- Turn off power to the area where you will install this unit at the circuit breaker or fuse box before beginning installation. Failure to turn off the power before installation may result in serious electrical shock, injury or death.
- Do not restore power until all detectors are completely installed.
Restoring power before installation is complete may result in serious electrical shock, injury or death
WARNING: The Smoke/CO Detector is intended for Residential USE ONLY and
is not to be used in a MOBILE HOME or COMMERCIAL application(s).
WARNING: This product is intended for use in ordinary indoor locations of
family living units. It is not designed to measure compliance with
Occupational Safety and Health Administration (OSHA), commercial, or
industrial standards. It is not suitable for installation in hazardous
locations as defined in the National Electric Code.
The installation of this device should not be used as a substitute for proper
installation, use and maintenance of fuel burning appliances, including
appropriate ventilation and exhaust systems. It does not prevent CO from
occurring, nor can it solve an existing CO problem.
WARNING: This device is designed to protect individuals from acute
effects of carbon monoxide exposure. It may not fully safeguard individuals
with specific medical conditions. If in doubt, consult a medical practitioner.
Individuals with medical problems may consider using warning devices which
provide audible and visual signals for carbon monoxide concentrations under 30
PPM.
WARNING: This carbon monoxide alarm requires a continuous supply of
electrical power. It will not work without power.
WARNING: This carbon monoxide alarm has not been investigated for carbon
monoxide detection below 70 PPM.
WARNING: Never remove the battery from the Smoke/CO Detector to stop a
nuisance alarm. Open a window or fan the air around the Smoke/ CO Detector to
get rid of the smoke. The detector will turn itself off when the smoke is
gone. If nuisance alarms persist, attempt to clean the Smoke/ CO Detector as
described in this Owner’s Manual, or relocate it to a better location.
WARNING: Not suitable for installation in areas where air velocities
exceed 300 meters/minute (985 FPM)
WARNING: Do not stand close to the Smoke/CO Detector when the alarm is
sounding. The alarm is loud in order to wake you in an emergency. Too much
exposure to the horn at close range may be harmful to your hearing.
WARNING: Do not connect the Smoke/CO Detector to any other alarm or
auxiliary device. Connecting anything else to this detector will keep it from
working properly.
WARNING: Never use an open flame of any kind to test your detector. You
may damage it as well as your home. The built-in test switch accurately tests
all functions as required by Underwriters’ Laboratories.
WARNING: When you are not testing the unit and the alarm siren sounds,
the detector is warning of a possible serious situation, which requires your
immediate attention.
WARNING: This device contains a wireless transmitter that can actuate a
remote audible siren. When used in a typical single level or multilevel
dwelling, or in apartment buildings where adjacent apartments may have similar
systems, it is possible that interference for another system could prohibit
the remote siren from sounding in the event of an alarm. Never rely solely on
the remote siren for notification of an alarm. Always make sure that the
internal siren in the Smoke/CO Detector can be heard from all bedrooms and
living areas.
WARNING: Actuation of your CO alarm indicates the presence of carbon
monoxide which can KILL YOU. If the alarm signal sounds:
- Press the mute button
- Call your emergency services (fire department or 911)
- Immediately move to fresh air – outdoors or by an open door/window. Do a headcount to check that all persons are accounted for. Do not reenter the premises nor move away from the open door/window until the emergency services responders have arrived, the premises have been aired out, and your alarm remains in its normal condition.
- After following steps 1–3, if your alarm reactivates within a 24 hour period, repeat steps 1–3 and call a qualified appliance technician to investigate for sources of CO from fuel burning equipment and appliances, and inspect for proper operation of this equipment. If problems are identified during this inspection, have the equipment serviced immediately. Note any combustion equipment not inspected by the technician and consult the manufacturers’ instructions, or contact the manufacturers directly, for more information about CO safety and this equipment. Make sure that motor vehicles are not, and have not been, operating in an attached garage or adjacent to the residence.
WARNING: Smoke detectors CANNOT provide warnings for fires resulting
from explosions, smoking in bed or other furniture, ignition of flammable
liquids, vapors and gasses, children playing with matches or lighters.
WARNING: Smoke detectors are not to be used with detector guards unless
the combination has been evaluated and found suitable for that purpose.
CAUTION: Early warning fire detection is best achieved by the
installation of fire detection equipment in all rooms and areas of the
household as follows:
A smoke alarm or detector installed in each separate sleeping room, outside of
each separate sleeping area, in the immediate vicinity of the sleeping rooms,
and on each level of the dwelling unit, including basements and heat or smoke
detectors in living rooms, dining rooms, kitchens, hallways, attics, furnace
rooms, closets, utility and storage rooms, and attached garages.
CAUTION: This carbon monoxide alarm is designed to detect carbon monoxide
from ANY source of combustion. It is NOT designed to detect fire, or any other
gas.
CAUTION: The CO alarm will only indicate the presence of carbon monoxide
at the sensor. Carbon monoxide may be present in other areas.
CAUTION: This Smoke/CO Detector comes with cover latches that will
prevent the Smoke/CO Detector cover from closing if the batteries are not
installed. This tells you that the Smoke/CO Detector will not work until a new
battery is properly installed.
CAUTION: Continuous exposure to the high sound level of this alarm over
an extended period of time may cause hearing loss.
IMPORTANT: You should never disable the unit to avoid nuisance alarms.
Instead, relocate the detector to a better location.
INSTALLATION AND LOCATION
Always refer to your national and local codes before beginning any
installation. Instructions for the State of California are detailed in Section
A (ii)
The Smoke/CO Detector should be installed in accordance with the NFPA 72 –
National Fire Alarm and Signaling Code created by the National Fire
Protection Association (NFPA).
The Smoke/CO Detector must be replaced within 10 years of the date of
manufacture. This date can be found on the label on the back of the device.
A. Smoke/CO Detector Placement
i. NFPA 72, Section 29.8.1:
Required Detection: where required by applicable laws, codes, or standard(sfor
a specific type of occupancy, approved single and multiple station smok alarms
shall be installed as follows
- in all sleeping rooms and guest rooms
- outside of each separate dwelling unit sleeping area, within 21 feet (6.4m) of any door to his sleeping room, the distance measured along a path of travel
- on every level of a dwelling unit, including basements
- on every level of a residential board and care occupancy (small facility), including basements and excluding crawlspaces & unfinished attics
- in the living area(s) of a guest suite
- in the living area of a residential board & care occupancy (small facility)
Where the area addressed in (2) is separate from the adjacent living areas by
a door, a smoke alarm shall be installed in the area between the door and the
sleeping rooms, and additional alarms shall be installed on the living area
side of the door as specified.
In addition to the requirements of (1) – (3), where the interior floor area
for a given level of a dwelling unit, excluding garage areas, is greater than
1000 ft2, smoke alarms shall be installed as below
All points on the ceiling shall have a smoke alarm within a distance of 30ft
travel distance or shall have an equivalent of one smoke alarm per 500 ft2 of
floor area
Where dwelling units include great rooms or vaulted/cathedral ceilings
extending over multiple floors, smoke alarms located on the upper floor that
are intended to protect the aforementioned area shall be permitted to be
considered as part of the lower floor(s) protection scheme used to meet these
requirements.
NFPA 72 29.11.3 contains the following requirements:
Peaked Ceilings. Smoke alarms mounted on a peaked ceiling shall be
located within 36 inches horizontally of the peak, but not closer than 4
inches vertically to the peak
Sloped Ceilings. Smoke alarms mounted on a sloped ceiling have a rise
greater than 1ft in 8ft horizontally shall be located within 36 inches of the
high side of the ceiling, but not closer than 4 inches from the adjoining wall
surface
Wall Mounting. Smoke alarms mounted on walls shall be located not farther
than 12 inches from the adjoining ceiling surface
Specific Location Requirements
- Smoke alarms shall not be located where ambient conditions, including humidity and temperature, are outside the limits specified in these instructions.
- Smoke alarms shall not be located within unfinished attics or garages or in other spaces where temperatures can fall below 40F or exceed 100F
- Where the mounting surface could be considerably warmer or cooler than the room, such as a poorly insulated ceiling below an unfinished attic or an exterior wall smoke alarms shall be mounted on an inside wall
- Smoke alarms shall not be installed between 10 feet and 20 ft along a horizontal flow path from a stationary or fixed cooking appliance unless the device is listed for resistance to common nuisance sources from cooking sources
- Smoke alarms shall not be installed within an area of exclusion determined by a 10 ft radial distance along a horizontal flow path from a stationary or fixed cooking appliance. When the 10 ft area of exclusion would prohibit the placement of a smoke alarm required by this code (NFPA 72), and when the kitchen or cooking area and adjacent spaces have no clear interior partitions or headers, smoke alarms shall be permitted for installation at a radial distance between 6 ft and 10ft from any stationary or fixed cooking appliance unless the device is listed for resistance to common nuisance sources from cooking.
- Smoke alarms shall not be installed within a 36 inch horizontal path from a door to a bathroom containing a shower or tub unless listed for installation in close proximity to such locations.
- Smoke alarms shall not be installed within a 36 horizontal path from the supply registers of a forced air heating or cooling system and shall be installed outside of the direct airflow from those registers
- Smoke alarms shall not be installed within a 36 inch horizontal path from the tip a the blade of a ceiling suspended fan unless the room configuration restricts meeting this requirement
- Where stairs lead to other occupiable levels, a Smoke/CO Detector shall be located so that smoke rising in the stairway cannot be prevented from reaching the Smoke/CO Detector by an intervening door or obstruction
- For stairways leading up from a basement, Smoke alarms shall be located on the basement ceiling near the entry to the stairs
- For tray shaped ceilings (coffered ceilings), Smoke alarms shall be installed on the highest portion of the ceiling or on the sloped portion of the ceiling within 12 inches vertically down from the highest point
- Smoke alarms installed in rooms with joists or beams shall comply with the requirements of NFPA 72 clause 17.7.4.2.4
ii. Per The California State Fire Marshal (California Code of Regulations,
Title 19, Section 760)
CAUTION: Early warning fire detection is best achieved by the
installation of fire detection equipment in all rooms and areas of the
household as follows:
A smoke alarm or detector installed in each separate sleeping room, outside of
each separate sleeping area, in the immediate vicinity of the sleeping rooms,
and on each level of the dwelling unit, including basements and heat or smoke
detectors in living rooms, dining rooms, kitchens, hallways, attics, furnace
rooms, closets, utility and storage rooms, and attached garages.
For information about establishing a household emergency evacuation plan,
please refer to Section 6 of this Owner’s Manual entitled FIRE PREVENTION AND
ESCAPE.
Recommended locations (single sleeping area)
SMOKE DETECTORS FOR MINIMUM SECURITY
SMOKE DETECTORS FOR MORE SECURITY
Recommended locations (multiple sleeping areas)
SMOKE DETECTORS FOR MINIMUM SECURITY
SMOKE DETECTORS FOR MORE SECURITY
Recommended locations (multi-floor residence)
SMOKE DETECTORS FOR MINIMUM SECURITY
Install the sensor in the center of the ceiling
Best location
Acceptable location
B. Locations to Avoid
To avoid false alarms and optimize detection of real alarms, do not install a
Smoke/CO Detector:
- In locations where combustion particles may normally be present, such as garages where there may be vehicle exhaust, near furnaces, hot water heaters, and space heaters. We recommend leaving at least 20 feet between the detector and such locations.
- In very dusty or dirty areas. Dirt and dust can build up on the sensing chamber, making it overly sensitive, or block openings to the sensing chamber, making it less sensitive.
- In insect-infested areas. If insects enter the sensing chamber, they may cause a nuisance alarm. Where bugs are a problem, get rid of them before putting up a detector.
- Near fluorescent lights. Electrical “noise” from fluorescent lights may cause nuisance alarms. Install Smoke/CO Detectors at least 5 feet (1.5 meters) from such lights.
- Near any cooking appliances. Install Smoke/CO Detectors at least 5 feet (1.5 meters) from any cooking appliances.
IMPORTANT: You should never disable the unit to avoid nuisance alarms.
Instead, relocate the detector to a better location.
WARNING: Never remove the battery from the Smoke/CO Detector to stop a
nuisance alarm. Open a window o r fan the air around the Smoke/ CO Detector to
get rid of the smoke. The detector will turn itself off when the smoke is
gone. If nuisance alarms persist, attempt to clean the Smoke/ CO Detector as
described in this Owner’s Manual, or relocate it to a better location.
WARNING: Not suitable for installation in areas where air velocities
exceed 300 meters/minute (985 FPM)
WARNING: Do not stand close to the Smoke/CO Detector when the alarm is
sounding. The alarm is loud in order to wake you in an emergency. Too much
exposure to the horn at close range may be harmful to your hearing.
C. Installing the Smoke/CO Detector
DANGER. ELECTRICAL SHOCK HAZARD. Turn off power to the area where you
will install this unit at the circuit breaker or fuse box before beginning
installation. Failure to turn off the power before installation may result in
serious electrical shock, injury or death.
DANGER. ELECTRICAL SHOCK HAZARD. Do not restore power until all detectors
are completely installed. Restoring power before installation is complete may
result in serious electrical shock, injury or death.
Install the Smoke/CO Detector on a ceiling or wall:
- Remove the mounting bracket from your unit by rotating it counterclockwise.
- Mount the bracket on the ceiling or wall, using the included screws and wall anchors.
- Push the Smoke/CO Detector onto the mounting bracket and turn it clockwise until it clicks into place. Pull outward on the detector to make sure it is securely attached.
NOTE: After you install the Smoke/CO Detector and whenever you change its battery, you must test it according to the instructions below to make sure it is functioning correctly.
WARNING: Do not connect the Smoke/CO Detector to any other alarm or
auxiliary device. Connecting anything else to this detector will keep it from
working properly.
CAUTION: This Smoke/CO Detector comes with cover latches that will
prevent the Smoke/CO Detector cover from closing if the batteries are not
installed. This tells you that the Smoke/CO Detector will not work until a
nebattery is properly installed.
D. Battery Installation
- Open the battery compartment
- Install two CR123A 3V lithium batteries, making sure the + and – ends of the battery are aligned properly.
- After the batteries are installed and the Smoke/CO Detector is mounted on its bracket, you will see the green LED flash.
NOTE: Use only Panasonic or Duracell CR123A batteries. This Smoke/CO
detector may not operate properly with other kinds of batteries.
E. Pairing to the Base Station
This section describes the basic steps for pairing the Smoke/CO Detector to
the Base Station.
- Go to the Menu on the keypad and select “Setup and Naming”
- Press the Test Button on the Smoke/CO Detector.
- Name the Smoke/CO Detector on the keypad.
- Press “Done” to exit pairing.
F. Verify Pairing and RF Communication Between Smoke/CO Detector and Base
Station
To determine a strong communication path with the Base Station, this
verification test should be performed in accordance with NFPA 72 inspection,
testing and maintenance requirements found in Section 8(A) of this Manual.
-
Go to the Menu on the keypad and select “Test Mode”
-
Press the Smoke/CO Detector Test Button for 1 second.
-
The Smoke/CO Detector will beep once and the Base Station will announce the Smoke/CO Detector.
• If the Base Station does not announce the Smoke/CO Detector, it is out of range. Move the Smoke/CO Detector closer to the Base Station. -
Exit Test Mode by pressing the left arrow on the keypad.
USAGE, OPERATION AND OPERATING MODES
This Smoke/CO Detector CAN ONLY BE interconnected with other SimpliSafe alarms by connecting it to a SimpliSafe Base Station as specified in the Compatible Equipment Table below. This Smoke/CO Detector is not intended to be connected to any non-SimpliSafe devices or systems and you should not attempt to do so. Attempting to connect the Smoke/CO Detector to nonSimpliSafe devices or systems may result in nuisance alarms, failure to alarm or damage to one or all of the devices in the non-SimpliSafe system.
CA002 Compatible Equipment
Description| Manufacturer| Model Number
Base Station| SimpliSafe| SSBS3
A. Normal Operation Testing
Before you test the Smoke/CO detector, make sure the detector does not have
low batteries (Pg 19).
If the Smoke/CO detector has low batteries, it will fail the self-test. Test
your Smoke/CO Detector weekly by pressing the test button (the white button on
the front of the sensor) for 10 seconds. The sensor’s siren will sound (3
beeps, pause, 4 beeps, pause, 4 beeps) and the light will flash at similar
intervals.
If this detector is paired to a Base Station, the Base Station will also sound
during this test if no issues are found.
If the Smoke/CO Detector and Base Station do not sound, the detector either
has a low battery, or the detector is malfunctioning. Replace the batteries in
the detector, and repeat the test.
This is the only way to make sure that the Smoke/CO Detector unit is working
properly. If the unit fails to test properly with new batteries, have it
replaced immediately.
CAUTION: Continuous exposure to the high sound level of this alarm over
an extended period of time may cause hearing loss.
WARNING: Never use an open flame of any kind to test your detector.
You may damage it as well as your home. The built-in test switch accurately
tests all functions as required by Underwriters’ Laboratories.
WARNING: When you are not testing the unit and the alarm siren sounds,
the detector is a warning of a possible serious situation, which requires your
immediate attention.
Go/No-Go Field Test: Please use Home Safeguard Model 25S UL Listed aerosol
Smoke/CO detector tester, following the instructions listed on the canister.
B. Silence Feature
Press the “Test/Silence” button (the white button on the front of the
detector) to temporarily quiet an alarm for up to 10 minutes. If smoke is
still present around the Smoke/CO Detector after 10 minutes of silence, the
unit will re-alarm.
C. Smoke Detector Operating Modes
The LED light on the front of the Smoke/CO Detector indicates the operating
mode of the unit:
Red LED blinks 3 times rapidly: the Smoke/CO Detector has sensed a potentially
dangerous level of smoke and is in smoke alarm mode. The buzzer and alarm
siren will also sound. Please follow the “in case of fire” instructions.
Green LED blinks about once per minute: the Smoke/CO Detector is functioning
normally.
Yellow LED blinks AND chirps once per minute: the Smoke/CO Detector battery is
low. This low battery warning signal should last for up to 30 days, but you
should install two new CR123A 3V lithium batteries immediately.
Yellow LED blinks once and chirps 2 times every minute: this indicates the
Smoke/CO Detector is in low sensitivity and needs to be cleaned.
Yellow LED blinks twice and chirps 2 times every minute: this indicates the
Smoke/CO Detector is in high sensitivity and needs to be cleaned.
Yellow LED blinks once and chirps 3 times every minute: this indicates the
Smoke/CO Detector is no longer operating within its intended sensitivity and
must be replaced.
D. CO Detector Operating Modes
If CO alarm signal sounds on the Smoke/CO Detector:
- Operate reset/silence button
- Call 911 or your local fire department
- Immediately move to fresh air
Green LED Flashes: the Smoke/CO Detector is turning on.
Green LED flashes once every 50 seconds: the Smoke/CO Detector is in Standby
which means the unit is receiving power and also indicates it is functioning
properly.
Red LED light flashes rapidly and the buzzer sounds loudly with repeating 4
quick beeps and pauses for 5 seconds and then 4 quick beeps: the Smoke/ CO
Detector is in CO Alarm Mode. After 4 minutes of an alarm, the pause will
increase to 60 seconds.
Yellow LED blinks AND chirps once per minute: the Smoke/CO Detector battery is
low. This low battery warning signal should last for up to 30 days, but you
should install two new CR123A 3V lithium batteries immediately.
Yellow LED flashes two times a minute and buzzer chirps once a minute: this
indicates the Smoke/CO Detector is malfunctioning and needs to be replaced.
Yellow LED flashes four times a minute and buzzer chirps once a minute: this
indicates the detector is reaching the end of its useful life (10 years after
the unit was manufactured).
Tamper mode: the yellow LED flashes twice every 4 seconds until the Smoke/ CO
Detector is mounted back to the bracket properly.
LIMITATIONS OF THE SMOKE/CO DETECTOR
A. Limitations of Wireless Smoke Detectors
Wireless smoke detectors cannot provide total protection of life or property
and are not a substitute for insurance. All wireless smoke detectors are
subject to possible compromise or failure-to-warn for a variety of reasons.
For example:
- Smoke detectors require a source of power to work. This Smoke/CO Detector will not operate and the alarm will not sound if batteries are dead or not installed properly.
- Smoke detectors may not be heard. A sound sleeper or someone who has taken drugs or alcohol may not awaken if the detector is installed outside a bedroom. It is the responsibility of individuals in the household that are capable of assisting others to provide assistance to those who may not be awakened by the alarm sound, or those who may be incapable of safely evacuating the area unassisted.
- Closed or partially closed doors and distance can block sound.
- This Smoke/CO Detector is not designed for the hearing impaired.
- Radio signals transmitted by this Smoke/CO Detector may be blocked or reflected by metal objects. Adjacent devices or systems using radio frequency signals may interfere with the operation of this alarm.
- Test the system weekly to ensure signals are transmitted and received properly
- Smoke detectors may not detect smoke on other levels of the building.
- Smoke detectors may not always activate and provide warning early enough.
- A smoke detector only activates when enough smoke reaches it.
- If a fire starts in a chimney, wall, roof, on the other side of closed doors, or a different level of the property, not enough smoke may reach the detector.
- Smoke Detectors may not be effective in fires where the victim is intimate with a flaming initiated fire; for example when a person’s clothes catch fire while cooking.
- Smoke Detectors may not be effective in fires where the smoke is prevented from reaching the smoke alarm due to a closed door or other obstruction.
- Smoke Detectors may not be effective in incendiary fires where the fire grows so rapidly that an occupant’s egress is blocked even with properly located smoke alarms.
- Smoke detectors are a significant help in reducing loss, injury and even death.
- No matter how good a detection device is, nothing works perfectly under every circumstance. We must warn you that you cannot expect a Smoke/ CO Detector to ensure that you will never suffer any damage or injury.
B. Limitations of Wireless CO Detectors
Wireless CO detectors provide early warning of the presence of CO, usually
before a healthy adult would experience symptoms. This early warning is
possible only if your Smoke/CO Detector is located, installed, and maintained
as described in this Owner’s Manual.
Because CO is a cumulative poison, long-term exposures to low levels may cause
symptoms, as well as short-term exposures to high levels. This unit has a
time-weighted alarm. The higher the level of CO present, the sooner the alarm
will be triggered.
This Smoke/CO Detector can only warn you of the presence of CO. It does not
prevent CO from occurring, nor can it solve an existing CO problem.
If your unit has alarmed and you’ve provided ventilation by leaving your
windows and doors open, the CO buildup may have dissipated by the time help
responds. Although your problem may appear to be temporarily solved, it is
crucial that the source of the CO is determined and that the appropriate
repairs are made.
Wireless CO detectors have limitations. Like any other electronic device, CO
detectors are not foolproof. CO detectors have a limited operational life.
You must test your Smoke/CO Detector weekly, because it could fail to operate
at any time.
If your Smoke/CO Detector fails to test properly, or if its self-diagnostic
test reveals a malfunction, immediately have the unit replaced. This detector
will not monitor CO levels while in a trouble condition.
The Smoke/CO Detector can only sense CO that reaches the unit’s sensor.
It is possible that CO may be present in other areas without reaching the
alarm. The rate and ability with which CO reaches the alarm may be affected
by:
- Doors or other obstructions.
- Fresh air from a vent, an open window, or other source.
- CO being present on one level of the home and not reaching a CO alarm installed on a different level. (For example, CO in the basement may noreach an alarm on the second level, near the bedrooms).
For these reasons, we recommend you provide complete coverage by placing a Smoke/CO Detector on every level of the home.
FIRE PREVENTION AND ESCAPE
The purpose of an early warning smoke detector is to detect the presence of
fire in its early stages and sound an alarm giving the occupants time to exit
the premises safely. No detection device can protect life in all situations.
Therefore, safeguards should be taken to avoid potentially dangerous
situations as follows:
In Case of Fire
In the event of a fire, you should do the following:
- Leave immediately. Don’t stop to pack or search for valuables.
- In heavy smoke, hold your breath and stay low, crawl if necessary. The clearest air is usually near the floor.
- If you have to go through a closed door, carefully feel the door and door knob to see if undue heat is present. If they seem cool, brace your foot against the bottom of the door with your hip against the door and one hand against the top edge. Open it slightly. If a rush of hot air is felt, slam the door quickly and latch it. Unvented fire tends to build up considerable pressure. Be sure all members of the household realize and understand this danger.
- Use your neighbor’s phone or a street fire alarm box to call the fire department. The job of extinguishing the fire should be left to the professionals.
Be Prepared
Use the following instructions to create an emergency evacuation plan:
- Draw a floor plan showing all doors and windows and show two exits from each room.
- Check that the doors and windows in each room open easily and you can use them to get outside
- If you have children and/or physically challenged people residing in your household, use window decals to help emergency personnel identify the sleeping quarters of these individuals.
- Ensure smoke alarms are properly placed. Test them weekly.
- Establish one meeting place outside the home. Insist that everyone meet there during an alarm. This will eliminate the tragedy of someone reentering the house for a missing member who is actually safe.
- Make sure your house or building number is visible from the street
- Learn the emergency phone number for your fire department.
- Review the plan with everyone in your home. It is important that children be instructed carefully, because they tend to hide in times of crisis.
- Perform fire drills regularly. Use them to assure recognition of an alarm signal.
Avoid Fire Hazards
- Do not smoke in bed.
- Do not leave children home alone.
- Never clean with flammable liquids such as gasoline.
- Properly store materials. Use general good housekeeping techniques to keep your home neat and tidy. A cluttered basement, attic, or storage area is an open invitation to fire.
- Use combustible materials and electrical appliances carefully and only for intended uses.
- Do not overload electrical outlets.
- Do not store explosive and/or fast burning materials in your home.
- Even after proper precautions have been taken, fires can start. Be prepared.
WARNING: Smoke detectors CANNOT provide warnings for fires resulting from
explosions, smoking in bed or other furniture, ignition of flammable liquids,
vapors and gasses, children playing with matches or lighters.
WARNING: Smoke detectors are not to be used with detector guards unless
the combination has been evaluated and found suitable for that purpose.
WARNING: This device contains a wireless transmitter that can actuate a
remote audible siren. When used in a typical single level or multilevel
dwelling, or in apartment buildings where adjacent apartments may have similar
systems, it is possible that interference for another system could prohibit
the remote siren from sounding in the event of an alarm. Never rely solely on
the remote siren for notification of an alarm. Always make sure that the
internal siren in the Smoke/CO detector can be heard from all bedrooms and
living areas.
INFORMATION ABOUT CARBON MONOXIDE (CO)
A. Description of CO and Important Information
Carbon monoxide is a colorless, odorless, and tasteless poison gas that can be
fatal when inhaled. CO inhibits the blood’s capacity to carry oxygen.
Periodically review this Owner’s Manual and discuss your CO alarm emergency
procedure with all members of your family.
- Never ignore a CO alarm.
- A true alarm is an indication of potentially dangerous levels of CO.
- CO alarms are designed to alert you to the presence of CO before an emergency – before most people would experience symptoms of CO poisoning, giving you time to resolve the problem calmly.
- Determine if anyone in the household is experiencing symptoms of CO poisoning.
- Many cases of reported CO poisoning indicate that while victims are aware they are not well, they become so disoriented they are unable to save themselves either by exiting the building or calling for assistance.
- Young children and household pets may be the first affected.
- You should take extra precautions to protect high-risk persons from CO exposure because they may experience ill effects from CO at levels that would not ordinarily affect a healthy adult.
B. Symptoms of CO Poisoning
The following common symptoms are related to CO poisoning and should be
discussed with ALL members of the household:
- Mild exposure = Slight headache, nausea, vomiting, fatigue (often described as “flu-like” symptoms).
- Medium exposure = Severe throbbing headache, drowsiness, confusion, fast heart rate.
- Extreme exposure = Unconsciousness, convulsions, cardio-respiratory failure, death.
- Many cases of reported CARBON MONOXIDE POISONING indicate that while victims are aware they are not well, they become so disoriented they are unable to save themselves by either exiting the building or calling for assistance.
- Young children and household pets are typically the first affected.
If you experience even mild symptoms of CO poisoning, consult your doctor
immediately.
C. Conditions that Can Produce CO
Excessive spillage or reverse venting of fuel burning appliances caused by:
- Outdoor ambient conditions such as wind direction and/or velocity, including high gusts of wind; heavy air in the vent pipes (cold/humid air with extended periods between cycles).
- Negative pressure differential resulting from the use of exhaust fans.
- Simultaneous operation of several fuel burning appliances competing for limited internal air.
- Vent pipe connection vibrating loose from clothes dryers, furnaces, or water heaters.
- Obstructions in or unconventional vent pipe designs which amplify the above situations.
- Extended operation of unvented fuel burning devices (range, oven, fireplace, etc.).
- Temperature inversions which can trap exhaust gasses near the ground.
- Car idling in an open or closed attached garage, or near a home.
D. What to Do In the Event of a CO Alarm
WARNING Actuation of your Smoke/CO Detector indicates the presence of carbon monoxide which can KILL YOU. If the alarm signal sounds:
-
Press the mute button
-
Call your emergency services (fire department or 911)
-
Immediately move to fresh air – outdoors or by an open door/window.
Do a headcount to check that all persons are accounted for. Do not reenter the premises nor move away from the open door/window until the emergency services responders have arrived, the premises have been aired out, and your alarm remains in its normal condition. -
After following steps 1–3, if your alarm reactivates within a 24 hour period, repeat steps 1–3 and call a qualified appliance technician to investigate for sources of CO from fuel burning equipment and appliances, and inspect for proper operation of this equipment. If problems are identified during this inspection, have the equipment serviced immediately.
Note any combustion equipment not inspected by the technician and consult the manufacturers’ instructions, or contact the manufacturers directly for more information about CO safety and this equipment. Make sure that motor vehicles are not, and have not been, operating in an attached garage or adjacent to the residence.
REGULAR MAINTENANCE
To keep your Smoke/CO Detector in good working order, remove from mounting bracket, remove battery cover and vacuum the dust off the sensing chamber at least once a month.
- Remove the batteries before cleaning.
- Use soft brush attachment on your vacuum to carefully remove any dust, especially on the openings of the sensing chamber. Never use water or cleaners – they may damage the unit.
- Replace the batteries after cleaning.
- Test the detector to make sure the batteries are working correctly.
- Avoid spraying air fresheners, hair spray, paint, or other aerosols near the detector.
SPECIFICATIONS
If the Smoke/CO Detector is defective in any way, do not tamper with the unit. Contact SimpliSafe at 1-888-910-1215
Power Source: Required batteries | 2x Panasonic CR123A 3V lithium battery |
---|---|
Smoke Sensor | Photoelectric 1.60 to 2.60 %/ ft obscuration sensitivity |
CO Sensor | Electrochemical |
Audible alarm | Over 85dB at 3m temporal pattern |
Sensitivity | Per UL217 and UL 2034 |
Dimensions | 12cm diameter x 4.5cm |
Weight | 0.6 lbs |
Operating Temperature Operating Relative humidity | 40 to 100°F (4.4 to 37.8°C) |
10 to 95% non-condensing
CO Alarm response times| 70 PPM = 60-240 min.
150 PPM = 10-50 min.
400 PPM = 4-15 min.
Agency Listings| Agency Listings
FCC Part 15 Notice
This device complies with part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Warning: Changes or modifications to this unit not expressly approved by
the party responsible for compliance could void the user’s authority to
operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio TV technician for help
07/23
STR-10632-00
ART-10580-00
CA002-IFU2
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>