Dyness POWERBOX F Battery Energy Storage System Innovator User Manual

June 10, 2024
DYNESS

POWERBOX F Battery Energy Storage System Innovator

Powerbox F Series User Manual

Product Information:

The Powerbox F is a battery management system (BMS) designed by
Daqin New Energy Tech. It has various protection features including
voltage, current, and temperature protection. The BMS is
lightweight and compact, with a user-friendly interface.

Product Properties:

  • Compact design
  • User-friendly interface
  • Voltage, current, and temperature protection
  • Lightweight

Product Identity Definition:

The Powerbox F is a battery management system designed to
provide protection to the battery system. It is intended for use
with electric vehicles and other battery-powered devices.

Product Usage Instructions:

Installation and Configuration:

The Powerbox F should be installed and configured by a qualified
technician. Please refer to the installation and configuration
section of the user manual for detailed instructions.

Use, Maintenance, and Troubleshooting:

When using the Powerbox F, follow these instructions:

  1. Ensure that the battery system is properly connected to the
    Powerbox F.

  2. Turn on the Powerbox F.

  3. Monitor the system using the user-friendly interface.

  4. If an alarm sounds, refer to the alarm description and
    processing section of the user manual.

The Powerbox F requires minimal maintenance. However, it is
recommended that the system be inspected periodically by a
qualified technician to ensure proper functioning.

If a fault occurs, refer to the analysis and treatment of common
faults section of the user manual for troubleshooting
instructions.

By following these instructions, the Powerbox F will provide
reliable and safe protection to your battery system.

Powerbox F series User Manual
POWERBOX F
User Manual

Powerbox F series User Manual
Content
Statement of Law………………………………………………………………………………………. 1
Safety Precautions and maintenance instructions………………………………………….. 2
Preface ……………………………………………………………………………………………………. 3
1 Introduction ………………………………………………………………………………………… 4
1.1 Brief Introduction …………………………………………………………………………………….. 4 1.2 Product Properties……………………………………………………………………………………. 4 1.3 Product identity definition…………………………………………………………………………. 5
2 Product Specification ……………………………………………………………………………. 6
2.1 Size and Weight ……………………………………………………………………………………….. 6 2.2 Performance Parameter ……………………………………………………………………………. 6 2.3 Interface Definition ………………………………………………………………………………….. 7 2.4 Battery Management System(BMS) …………………………………………………………….. 9
2.4.1 Voltage Protection ……………………………………………………………………………………. 9 2.4.2 Current Protection ……………………………………………………………………………………. 9 2.4.3 Temperature Protection ………………………………………………………………………….. 10 2.4.4 Other Protection …………………………………………………………………………………….. 10
3 Installation and Configuration………………………………………………………………. 11
3.1 Preparations for installation …………………………………………………………………….. 11 3.1.1 Environmental requirements……………………………………………………………………. 11 3.1.2 Tools and data ……………………………………………………………………………………….. 12 3.1.3 Technical preparation ……………………………………………………………………………… 12 3.1.4 Unpacking inspection………………………………………………………………………………. 12 3.1.5 Engineering coordination ………………………………………………………………………… 14
3.2 Equipment installation ……………………………………………………………………………. 14 3.2.1 Floor installation …………………………………………………………………………………….. 15 3.2.2 Mounted on the wall ………………………………………………………………………………. 16 3.2.3 Electrical installation……………………………………………………………………………….. 18 3.2.4 Battery module DIP switch definition and description…………………………………. 23 3.2.5 Battery parameter settings on the inverter ……………………………………………….. 29 3.2.6 Register on the website after installation ………………………………………………….. 29
4 Use, maintenance and troubleshooting………………………………………………….. 30
4.1 Battery system usage and operation instructions…………………………………………. 30 4.2 Alarm description and processing ……………………………………………………………… 31
4.2.1 Alarm and countermeasure for affecting system output ……………………………… 31 4.2.2 Alarm and countermeasure for non-affecting system output ………………………. 32 4.3 Analysis and treatment of common faults ………………………………………………….. 32
I

Powerbox F series User Manual
Statement of Law

Copyright of this document belongs to Daqin New Energy Tech (Taizhou) Co., Ltd.
No part of this documentation maybe excerpted,reproduced, translated,annotated or duplicated in any form or by any means without the prior written permission of Daqin New Energy Tech (Taizhou) Co., Ltd. This product complies with the design requirements of environmental protection and personal safety. The storage, use and disposal of the products shall be carried out in accordance with the product manual, relevant contract or relevant laws and regulations.
Customer can check the related information on the website of Daqin New Energy Tech (Taizhou) Co., Ltd. when the product or technology is updated.
Please note that the product can be modified without prior notification.

Manual Version: V1.5 Revision History
Revision NO. 1.0 1.1
1.2
1.3 1.4
1.5

Revision Date

Revision Reason

2019.02.01 1.First Published

2019.08.01 2020.06.28 2020.09.16

1.Add parallel connection description
1.Add battery parameter settings on the inverter. 2.Add DIP setting for ICC. 3.Add register on the website after installation.
1.Add new inverters in DIP switch description

2021.03.24 2021.09.07

1. Update the description of the DIP setting 2.Delete the description of the non-DIP model
1. Update charge current limit value to 4A in protection mode. 2. Company information has changed to Taizhou Daqin 3. Update DIP switch description

1

Powerbox F series User Manual
Safety Precautions and maintenance instructions
Warning
Please do not put the battery into water or fire, in case of explosion or any other situation that might endanger your life.
Please connect wires properly while installation, do not reverse connect. To avoid short circuit, please do not connect positive and negative poles with conductor on
the same device. Please avoid any form of damage to battery, especially stab, hit, trample or strike. Please shut off the power completely when removing the device or reconnecting wires
during the daily use or it could cause the danger of electric shock. Please use dry powder extinguisher to put out the flame when encountering a fire hazard,
liquid extinguisher could result in the risk of explosion. For your safety, please do not arbitrarily dismantle any component in any circumstances.
The maintenance must be implemented by authorized technical personnel or our company’s technical support. Device breakdown due to unauthorized operation will not be covered under warranty.
Caution
Our product has been strictly inspected before shipment. Please contact us if you find any abnormal phenomena such as device outer case bulging.
The product shall be grounded properly before use In order to ensure your safety. To assure the proper use please make sure parameters among the relevant device are
compatible and matched. Please do not mixed-use batteries from different manufacturers, different types and
models, as well as old and new together. Ambient and storage method could impact the product life span, please comply with the
operation environment instruction to ensure device works in proper condition. For long-term storage, the battery should be recharged once every 6 months, and the
amount of electric charge shall exceed 80% of the rated capacity.
Please charge the battery in 18 hours after it fully discharged or over- discharging protection
mode is activated. Formula of theoretical standby time: T=C/I (T is standby time, C is battery capacity, I is total current of all loads). The surface of the Powerbox cabinet is affixed with a torn invalid label. Therefore, before opening the cover to change the DIP switch mode, you need to contact DYNESS and inform the product ID. DYNESS will record this battery ID and authorize the opening operation to be performed. Except for changing the DIP switch mode, no other operations are allowed. In the next stage, you can log in to apply for operations directly on the DYNESS website. Contact the authorized dealer or distributor of DYNESS for a new torn invalid sticker after
2

Powerbox F series User Manual tearing the original invalid label. When the operation is completed, paste the new one at a different position.
Preface
Manual declaration
POWERBOX F Lithium Iron Phosphate Battery is external battery module which can store the electricity for home use. When you apply the grid or photovoltaic system as your powers supply, the product can collect electricity to charges the battery. When grid or photovoltaic system is power off , the product can supply electricity itself for your home loads. POWERBOX F User manual systematically elaborates device structure, parameters, basic procedure and method of installation, operation, maintenance.
Safety Statement
Only qualified trained professionals are allowed to install, operate, maintain the device. Please comply with local safety regulations and operational rules during installation,
operation and maintenance, or it could cause unexpected injury or device damage. The safety declaration mentioned in the manual are only supplement context for your local
safety regulations. The seller does not undertake any responsibility for device operations or usage of violating
general safety requirements and safety standards.
Sign explanation
User should clear the meaning of the caution sign below when configuring or operating Powerbox F series products.
Caution
Neglecting the warnings might cause equipment failure.
3

Powerbox F series User Manual
1 Introduction
1.1 Brief Introduction
Powerbox-F series is equipped with lithium iron phosphate battery for family use . We base on customer needs and market requirement to develop cutting-edge battery storage technology and offer this high quality product to supply stable electricity for all kind of user’ s devices. The product have long life span and can be applied in high temperature environment and take less space for installation. Powerbox-F series carries self-developed battery management system. When you apply the grid or photovoltaic system as your powers supply, the product can collect electricity to charges the battery. When grid or photovoltaic system is power off , the product can supply electricity itself for your home loads. Products also can be paralleled to build a multimodule system with more capacity to satisfy the longtime energy storage demand.
1.2 Product Properties
POWERBOX-F series energy storage product’s anode materials are lithium iron phosphate, battery cells are managed effectively by BMS with better performance, the systems features as below: Comply with European ROHS, Certified SGS, employ non-toxic, non-pollution
environment-friendly battery. Anode materials are lithium iron phosphate (LiFePO4), high safety performance with
longer life span. Equipped with BMS (battery management system) mode with better performance,
possesses protection function like over-discharge, over-charge, over-current, abnormal temperature. Self-management on charging and discharging, Single core balancing function. Intelligent design configures integrated inspection module. Flexible configurations allow parallel of multi battery for longer standby time. Self-ventilation with lower system noise. Less battery self- discharge, then recharging period can be up to 10 months during the storage. No memory effect so that battery can be charged and discharged shallowly.
With wide range of temperature for working environment, -20 ~ +55 , circulation sLpeassn avonldumdisec,hlaigrghitnegr pweerfiogrhmt,asnecael agrerawdeelluupndteor IhPi6gh5 teemmbpeedradtiunrge.design for easier
installation and maintenance.
4

Powerbox F series User Manual
1.3 Product identity definition
FIG1-1 Battery Energy Storage System nameplate
Battery voltage is higher than safe voltage, direct contact may cause electric shock hazard. Be careful with your actions and be aware of the dangers. Read the user manual before using. The scrapped battery cannot be put into the garbage can and must be professionally recycled. After the battery life is terminated, the battery can continue to be used after it recycled by the professional recycling organization and do not discard it at will. This battery product meets European directive requirements. This battery product passed the TUV certification test.
5

Powerbox F series User Manual

2 Product Specification

2.1 Size and Weight

Table 2-1 POWERBOX F Series Device Model

Product Series

Specification Model

Nominal Voltage

POWERBOX POWERBOX F-10

48V

Nominal Capacity
200Ah

Dimension Weight IP

(mm)

(kg) Level

928×555×210 113 IP65

POWERBOX POWERBOX F-7.5

48V

150Ah 928×555×210 91 IP65

POWERBOX POWERBOX F-5.0

48V

100Ah 928×555×210 69 IP65

POWERBOX POWERBOX F-2.5

48V

50Ah 928×555×210 47 IP65

2.2 Performance Parameter
Table 2-2 POWERBOX F performance parameter

Item Nominal Voltage(V)

POWERBOX F2.5
48

POWERBOX F5.0
48

POWERBOX F7.5
48

POWERBOX F10.0
48

Work Voltage Range(V)

42~54

42~54

42~54

42~54

Nominal Capacity(Ah)

50

100

150

200

Nominal Energy(kWh)

2.4

4.8

7.2

9.6

Nominal Power(kW)

0.7

1.5

2.2

2.9

Max Power(kW)

2.4

4.8

4.8

4.8

1S Peak Power(kW)

2.64

5.28

7.92

10.56

1S Peak Current(A)

55

110

165

220

Charging Current(A)

25

50

75

100

Discharge Current(A)

25

50

75

100

6

Powerbox F series User Manual
2.3 Interface Definition
This section elaborates on interface functions of the front panel of the device. Figure2-1 POWERBOX F the sketch of front interface.

12 3 4

5 67 8 9

10

11

7

Powerbox F series User Manual

Table 2-3 Interface Definition

Item Name

Definition

The battery DC output positive pole, which is connected to the

1

Positive socket

positive pole of the inverter through the cable

When the system is used independently:

The CAN/RS485 socket is connected to the inverter CAN/RS485

2

COM IN

interface through the communication cable. When the system is used in parallel: This CAN/RS485 communication socket is connected to the COM OUT interface of the previous Powerbox through communication cable.

The battery DC output negative pole, which is connected to the

3

Negative socket

negative pole of the inverter through the cable

4

COM OUT

When the system is used independently: This CAN/RS485 socket is a reservation interface When the system is used in parallel: This CAN/RS485 communication socket is connected to the COM IN interface of the next Powerbox through communication cable. (Factory default CAN communication mode)

5

LED1

Module 1 status indicator light

6

LED2

Module 2 status indicator light

7

LED3

Module 3 status indicator light

8

LED4

Module 4 status indicator light

Ground

9

Shell ground connection

connection point

10 Reset switch

Press the switch and the battery system turn on. When the battery is in the non-use state such as storage, transportation etc., it needs to be turn off by pressing the Reset switch button, and the battery system will automatically sleep

after the device without external load and power for 72 hours.

DC circuit 11
breaker

Circuit Protection

8

Powerbox F series User Manual

Table 2-4 LED status indicators (Take Powerbox F 10.0 as an example)

State

Protect/ Alarm/ Led1 Led2 Led3 Led4 Normal

Directions

Shut down

off

off

off

off All off

Normal

Always on,11%SOC100%

Stand-

Alarm

Always on, Corresponding module alarm or 0%<SOC10%

by/Charging/

Discharging

Flashing, (Corresponding module

Protection

protection be activated / Over-discharge protection /Over-current protection /

Temperature abnormality, etc.)

Other case

Alarm

Yellow, green and red flash alternately

All module address assignments in the system are incomplete

The master POWERBOX LED1 Communication failure between

yellow flash

batteries

2.4 Battery Management System(BMS)
2.4.1 Voltage Protection
Low Voltage Protection in Charging When any module cell voltage is lower than the rated protection value during discharging, the over-discharging protection is activated, and the battery buzzer makes an alarm sound. Then battery system stops supplying power to the outside. When the voltage of each cell recovers to rated value and total voltage restored to above 45V, the protection is released. Over Voltage Protection in Charging During charging stage, the system will stop charging when the total voltage of the battery pack is higher than rated value or the voltage of any single cell reaches the protection value. When the total voltage returns to below 52V and the cell voltage back to below the rated protection value, the protection is released.
2.4.2 Current Protection
Over Current Protection in Charging
When the charge current of each module45A, current limit protection mode is activated, current will be limited to 4Aprotection is removed after rated time delaying 10S. Circulate like this until the current is lower than 45A.
Over Current Protection in Discharging
9

Powerbox F series User Manual
When the discharge current is higher than the protection value, the battery buzzer alarms and the system stops discharging. The system is released from protection after the rated delay time of 1min.
Caution:
The buzzer sound alarm setting can be manually turned off on the background software, and the factory default is on.
2.4.3 Temperature Protection
Low/Over temperature protection in charging When battery’s temperature is beyond range of -5 ~+55 during charging, temperature protection is activated, device stops charging. The protection is over when temperature back to rated working range. Low/Over temperature protection in discharging When battery’s temperature is beyond range of -20~+55 during discharging, temperature protection is activated, device stops supplying power to the outside. The protection is over when temperature back to rated working range.
2.4.4 Other Protection
Short Circuit Protection When the battery is activated from the off state, if a short circuit occurs, the DC circuit breaker will respond first. If the DC circuit breaker does not operate, the short circuit protection function of BMS will be activated automatically and cut off the device’s output. Self Shutdown When device connects no external loads for over 72hours, device will dormant standby automatically.
Caution
The maximum operating current required for the electrical load shall be less than the maximum discharge current capacity of the battery.
10

Powerbox F series User Manual
3 Installation and Configuration
3.1 Preparations for installation
Safety Requirement
This system can only be installed by personnel who have been trained in the power-supply system and have sufficient knowledge of the power system. The safety regulations and local safety regulations listed below should always be followed during the installation.
All circuits connected to this power system with an external voltage of less than 48V must meet the SELV requirements defined in the IEC60950 standard.
If operating within the power system cabinet, make sure the power system is not charged. Battery devices should also be switched off
Distribution cable wiring should be reasonable and has the protective measures to avoid touching these cables while operating power equipment.
when installing the battery system, must wear the protective items below:

The isolation gloves

Safety goggles

Safety shoes

3.1.1 Environmental requirements
Working temperature: -20 ~ +55 · Charging temperature range is 0~+55 , · Discharging temperature range is -20 ~+55
Storage temperature: -10 ~ +35 Relative humidity: 5% ~ 85%RH Elevation: no more than 4000m Operating environment: Indoor or outdoor installation, sites avoid the sunlight and no wind, no conductive dust and corrosive gas. And the following conditions are met:
· Installation location should be away from the sea to avoid brine and high humidity environment.
· The ground for product arrangement shall be flat and level. · There is no flammable explosive materials near to the installation site. · The optimal ambient temperature is 15 ~ 30 · Keep away from dust and messy zones

11

Powerbox F series User Manual

3.1.2 Tools and data

Hardware tool Tools and meters that may be used are shown in table 3-1.
Table 3-1 Tool instrument

ScrewdriverSlottedPhillips Torque wrench Diagonal pliers
Pointed nose pliers Pliers to hold the wire
Stripping pliers Electric drill

Name

Multimeter Clamp current meter
Insulation tape Temperature meter Anti-static bracelet
Cable tie Tape measure

3.1.3 Technical preparation

Electrical interface check Devices that can be connected directly to the battery can be user equipment, power supplies, or other power supplies. Confirm whether the user equipment, the PV equipment or other power supply equipment has the DC output interface, and measure whether the output voltage of the standby interface meets the requirements of the voltage range of table 2-2 Verify that the maximum discharge current capacity of the user equipment, the PV equipment or other power supplies, the DC standby interface, and the maximum discharge current shall be greater than the maximum charging current of the products used in table 2-2. If the user equipment DC prepared interface maximum discharge capacity is less than the maximum charging current products using table 2-2, the user interface should have the power equipment of DC current limiting function, give priority to ensuring the normal work of user equipment.
The security check Firefighting equipment should be arranged near the equipment, such as portable dry powder fire extinguisher. Automatic fire fighting system shall be provided for the case where necessary. Flammable, explosive and other dangerous materials placed beside the battery are prohibited.

3.1.4 Unpacking inspection
When the equipment arrives at the installation site, loading and unloading should be carried out according to the rules and regulations, so as to prevent from being exposed to sun and rain.

12

Powerbox F series User Manual
Before unpacking, the total number of packages shall be indicated according to the shipping list attached to each package, and the case shall be checked for good condition.
In the process of unpacking, handle with care and protect the surface coating of the object.
Open the package, the professional installation personnel should read the technical documents, verify the list, according to the configuration table and packing list, ensure objects are complete and intact. If the internal packaging is damaged, it must be inspected and recorded in detail.
Packing list is as follows:

Battery×1

Battery bottom bracket ×1

Support bracket ×2

M6 bolt ×8 Fixing battery box with battery bracket

Power cable ×1 pair connect battery with inverter

Standard communication cable×1

RJ45 Waterproof connector ×2

Expansion screw ×8

Positioning cardboard×2

13

Powerbox F series User Manual

120CAN resistor ×1

M6 3 sets of combined screws x 1 (Already installed on the system cabinet)

User manual ×1

3.1.5 Engineering coordination
Attention should be paid to the following items before construction: Power cable specification. The power cable specification shall meet the requirements of maximum discharge
current for each product. Mounting space and bearing capacity. Make sure that the battery has enough space to install, and that the battery rack and
bracket have enough load capacity. Wiring. Make sure the power cable and ground wire are reasonable. Not easy to short-circuit,
water and corrosion.
3.2 Equipment installation
The wall for battery installation shall be solid brick or cement wall with strong bearing capacity and wall thickness no less than 100mm. Mounting space requirements

Floor installation

Wall installation
14

Powerbox F series User Manual

Table 3-2 Installation steps Step1 System outage Mechanical Step 2 installation

Step3

Electrical installation

Ensure that the battery is in a shutdown state 1. Hanger mounting 2.Equipment installation 1. Connect the ground cable 2 Electrical installation 3.Connect inverter 4.Communication interface connection

3.2.1 Floor installation

When the battery system is placed directly on the ground, a fixed support must be used
to fix the top of the battery box on the wall.
1 Use the positioning cardboard (provided in accessory package) and mark the screw hole positions on the wall, as shown in the four holes on the left.
2 The bottom of board must be good connection with the ground level while marking the holes.

3 Press the marked position with the electric drill and trepanning 4 holes with a diameter of 10mm on the wall. The hole depth shall be greater than 70mm for fitting the expansion bolt of M6.

15

Powerbox F series User Manual

4 Fixing the expansion bolt M6 into the bottom of the hole on the wall.
5 Use the M6 bolt to fixing the Support bracket to the wall and control the torque at 6NM.

6 Carry the battery box to the installation site, and place it about 15mm away from the wall surface, fixing the Support bracket and the upper part of the battery box with M6 bolts.
3.2.2 Mounted on the wall
The following accessories need to be added when install the powerbox on the wall.

Battery bottom bracket ×1

Expansion screw ×4
16

Powerbox F series User Manual Installation procedure

1 Use the positioning cardboard (provided in accessory package) and mark the screw hole positions on the wall, as shown in the four holes on the left.
2 The cardboard must be perpendicular to the ground while drawing the holes.
3 The bottom of the cardboard is about 300mm from the ground.
4. According to the position of the mark, 8 holes in diameter 10mm and depth of more than 70mm are hit on the wall with an electric drill, which are used for fitting expansion bolt M6.
5. Fixing the expansion bolt M6 into the bottom of the hole on the wall, and fix the Support bracket and Battery bottom bracket on the wall with M6 bolts, twisting force keeps 6NM.
6. Carry or hoist the battery box to the installed Battery bottom bracket. Fixing the Support bracket and the upper part of the battery box with M6 bolts, twisting force keeps 6NM. Then fixing the Battery bottom bracket and the bottom part of the battery box with M6 bolts, twisting force keeps 6NM.
17

Powerbox F series User Manual
3.2.3 Electrical installation
StatementFor Australian market, installations should be conducted in accordance with AS/NZS 3000 and AS/NZS 5139″. Before connecting the power cables, using multimeter to measure cable continuity, short circuit, confirm positive and negative, and accurately mark the cable labels. Measuring method:
· Power cable check: select the buzzer mode of multimeter and detect the both ends of the same color cable. If the buzzer calls, it means the cable is in good condition.
· Short circuit judgment: choose multimeter resistor file, probe the same end of positive and negative pole, if the resistor shows infinity, means that the cable is available.
· After visual testing of power line is connection, the positive and negative poles of the battery shall be connected respectively to the positive and negative poles of the opposite terminal.
Connect the battery box to the ground cable Customer needs to prepare a M6 OT terminals and ground cables. Ground the battery shell as shown below. The sectional area of the grounding cable shall be at least 6mm2 and the bolt locking torque is 6NM.
For Australian Market, an over-current protection and isolation device that isolates both positive and negative conductors is required between the inverter and battery. The selection of the circuit breaker requires:
Voltage: U>60V Inverter power
Current: I = 45V
The circuit breaker is installed between the battery module and the inverter, as shown in Figure 31:
18

Powerbox F series User Manual

Inverter Connection

Figure 3-1

caution:
If there is any question during installation, please contact your dealer to avoid damage to the equipment.
When the system is used independently:
Note: Before installation, please confirm whether the DIP switch mode of No. 1 module in POWERBOX is correct according to use’s inverter communication specification. For specific DIP operation methods, please refer to “3.2.4 Battery module DIP switch definition and description.” Except for the inverter specified by the customer’s special requirements, the factory default DIP switch mode of Module No.1 is DIP Switch mode 1 (ADD: 0010). If the inverter is equipped with other DIP switch mode, open the front panel and Set DIP switch mode of the Module No.1 to the correct mode. Before opening the cover to operate, you must contact DYNESS and inform the ID of the Powerbox. DYNESS records this battery ID and authorizes the opening operation. Except changing the DIP switch mode, no other operations can be done. · The battery is connected to the inverter, and it is required to use the dedicated power
cable and communication cable (as accessories shipped with the cargo, the standard
communication cable is a standard network cable. The applicable inverter is marked
19

Powerbox F series User Manual on the label of the network cable. If the inverter used by the customer is not covered by the standard communication cable, please contact DYNESS for the correct PIN Sequence) as follows:
· Keep the battery system at power off state, connect the power cable to the interface on the input side of the inverter first, and then connect the power cable to the interface on the battery side.
· The battery output interface is a quick connector, and the power cable (positive, negative) plug can be directly inserted into the battery socket. The power cable cross section is 25 mm2.
Connection of Communication interface Connect the CAN IN port of the battery to the CAN or RS485 communication interface of the inverter using the RJ45 cable.
20

Powerbox F series User Manual

Table 3-3 Pin Definition
Foot position PIN1 PIN2 PIN3 PIN4 PIN5 PIN6 PIN7 PIN8

Color Orange/white Orange Green/white Blue Blue/white Green Brown/white Brown

Definition 485A XGND 485B CANH CANL Reserved XIN Reserved

CAN communication connection
The battery is connected to the inverter– Power cable- negative
The battery is connected to the inverter– Power cable- positive

21

Powerbox F series User Manual

POWERB OX

+ –
CAN IN CAN OUT

Battery+ BatteryBattery CAN

INVERTER

When the system used in parallel: When the system is used in parallel, it supports up to 4 Powerbox in parallel. According to the number of parallel system (Take four Powerbox in parallel as an example), it needs to use: Power cable × 4 pair, Battery-Inverter communication cable × 1PCS, Battery-Battery communication cable × 3PCS, Distribution box × 1PCS.The over-current capacity of the distribution box should be much higher than the maximum nominal current value when the load is running..

PINOUT of system parallel communication cable: PINOUT of Battery-Battery communication cable diagram shown as below:
22

Powerbox F series User Manual

PPoOwWerEbRoBxOX MasNteor.1

+ –
CAN IN CAN OUT

Power distribution box

Battery+ BatteryBattery CAN

INVERTER

PPoOwWeErbRoBxOX SlavNe o1.2

+ –
CAN IN CAN OUT

PPoOwWeErbRoBxOX SlavNe o2.3

+ –
CAN IN CAN OUT

CAN resistor

3.2.4 Battery module DIP switch definition and description

Table 3-4 DIP switch Definition DIP switch position (master communication protocol and baud rate selection)

1

2

3

Define different protocols Distinguish between master and slave

4 Baud rate selection OFFCAN: 500K,485: 9600 ONCAN: 250K,485: 115200

DIP switch description:

For Powerbox F series system, the No. 1 module at the bottom of cabinet and near the front panel side is the master, the other modules are slaves.

23

Powerbox F series User Manual

Front panel

No.1 Module Master

Slave modules

When the batteries are connected in parallel, the master communicates with the slaves through the CAN interface. The master summarizes the information of the entire battery system and communicates with the inverter through CAN or 485.
Introduction of the initial state of DIP switch of the internal modules of Powerbox with DIP switch.

Slave setting 1 ADD:0000
Slave setting 2 ADD:0001

MasterSetting 1 Master Setting 2 MasterSetting 3 MasterSetting 4 MasterSetting 5

ADD:0010

ADD:0100

ADD:0110

ADD:1010

ADD:1001

24

Powerbox F series User Manual
1.For different inverter model,you need to set different DIP mode: (1) Ensure the communication cable that communicates with the inverter is correct. (2) When the battery works with GOODWESolisLUXSofarDEYEVICTRON IMEONSungrowSMARENACDELIOSSAJ(CAN Comm) inverters ,before connecting you need confirm that the DIP switch mode of the master module in Powerbox is 0010(“# 3” to “ON” ,generally factory default is this 0010 mode).
Master Setting 1
(3) If the battery communicate with the Axpert/VMIII/MAX,Infinisolar,Growatt SPH(CAN comm)GMDE,change the master module DIP switch to 0100(“#2″to”ON”) before connecting.
Master Setting 2
(4) If the battery communicate with the Growatt SPF HVM-P/ES/WPV by RS485 communication, change the master module DIP switch to 0110(“#2″&”#3″to”ON”) before connecting.
Master Setting 3
(5) If the battery communicates with the Schneider Conext Series, turn the master DIP switch “#1” and “#3” to “ON”.
Master Setting 4
(6) When you setup the master DIP as setting 1~4,all the slaves keep the DIP 0000,no need change. (7) If the battery communicate with the ICC by 485 communication, change the master module DIP switch to 1001(“#1″&”#4″to”ON”) before connecting,
Master Setting 5
the DIP switch of slaves need to turn the “#4” to “ON” at the same time while the master is setting 5.
Slave Setting 2
25

Powerbox F series User Manual
(8) If Powerbox needs to be used with ICC,the DIP on the light PCB of the Powerbox must be changed to ON,as shown in the figure below.The DIP on the light PCB of the Powerbox shipped by default is in “OFF” state(500K).
Factory default is in”OFF”state(500K)
Should be dialed to “ON”(250K) for ICC (9) Generally the DIP switch of the slave module no need to be changed,keep it 0000;But for ICC,it needs to be changed to 0001 . (10)When the Powerbox are used in parallel,you need set the master Powerbox DIP switch mode as above,and set all the modules DIP switch in slaves Powerbox to 0000(include the master module in slave Powerbox),that is 0001 for ICC,this is very important. Note: For more information of matching inverter brands, please subject to the latest document

. Caution 1\. The master DIP switch setting 5 and slave DIP switch setting 2 is only for ICC(a special communication device for some no-communication inverter), it’s a special firmware in POWERBOX,different from general firmware,so if customers want to use that,please contact dyness to confirm. 2. Generally factory default DIP switch status of the master module in Powerbox is setting 1. When they are used in parallel, all the slave Powerbox systems need to be opened the cover and change the DIP switch of the master module to Slave Setting 1 (i.e. ADD: 0000),the master powerbox no need change. Proceed as follows: a. Remove the six screws on the Powerbox and open the front panel. 26

Powerbox F series User Manual

No.1 Module

Bottom of Powerbox

Bottom of Powerbox

b. Find the red DIP switch on the No. 1 B4850 battery panel and confirm the status of the DIP

switch.

Bottom of Powerbox

No.1 Module

c. Change the DIP switch status to the original state (Mode5: i.e. ADD: 0000)

d. Re-install the front panel with six screws which were removed in step a.
27

Powerbox F series User Manual

Caution:

Before connection, the positive and negative pole of the inverter input interface and the battery output interface should be confirmed. The red power line is connected to the positive pole and the black power line is connected to the negative pole.
Before connection, it is necessary to confirm the charge and discharge parameters of the inverter interface. Voltage and current should meet the requirements of Table 2-2 battery performance parameters.
When you use battery in parallel, it doesn’t need to change the DIP switch of the master module in the master Powerbox which communicates with the inverter directly.
Note: For more information of matching inverter brands, please subject to the latest document .
The following operations can only be performed after being authorized by DYNESS: How to judge that the communication between POWERBOX and POWERBOX is
normal: 1. If there is communication between the inverter and battery system, it can be
judged by the maximum charge and discharge current value on the inverter sent by the battery.

(The maximum charge and discharge current value displed on the inverter) ( The maximum charge and discharge current value of one battery module )

=

number of modules

If the equation holds after calculation, it means communication between POWERBOX and POWERBOX is normal. 2. If the POWERBOX light board shows three different colors flash alternately,it means the communication between powerbox is fault.

Battery& Inverter power matching table

Table 3-3 Battery& Inverter power matching table

a) The battery’s long-term continuous charging current

Charging

should be 0.5C b) If the battery remaining capacity is empty, please charge it

Equipment

within 48 hours after the battery is empty.

Use

c) The long-term continuous discharge current of the battery

should be 0.5C Discharging
d) The recommend maximum depth of discharge (DOD)of

Battery PACK is no more than 85%.

28

Powerbox F series User Manual

Power of Hybrid Inverter/ Off-grid Inverter
1KW 2KW 3KW 4KW 5KW 6KW 8KW 10KW 12KW

Powerbox
Type
Powerbox F-2.5 Powerbox F-5.0 Powerbox F-5.0/Powerbox F-7.5 Powerbox F-7.5/Powerbox F-10.0 Powerbox F-10.0 2 Powerbox F-7.5 2Powerbox F-7.5/2 Powerbox F-10.0 2 Powerbox F-10.0/3Powerbox F-7.5 3 Powerbox F-10.0

System Energy (kWh)
2.4 4.8 4.8/7.2 7.2/9.6 9.6 14.4 14.4/19.2 19.2/21.6 28.8

3.2.5 Battery parameter settings on the inverter

Max Charging(Bulk) Voltage: 53.5V Absorption Voltage: 53V Float Voltage: 52.5V Shut Down(cut off) Voltage: 47V Shut Down(cut off) SOC: 20% Restart Voltage: 49V
Max Charge Current:Powerbox F5.0=50A,Powerbox F7.5=75A,Powerbox F10.0=100A Max Discharge Current: Powerbox F5.0=50A,Powerbox F7.5=75A,Powerbox F10.0=100A
CapacityF-5.0=100Ah, F-7.5=150Ah, F-10.0=200Ah Batteries and inverters must be installed in accordance with the compatibility listed in the “Dyness compatibal list-2022”;

Dyness compati bal list-2022.pdf

3.2.6 Register on the website after installation

After the battery system installation is completed and the running is normal,

you need to log in to the DYNESS official website to register the product

installation and use information to make the product warranty effective. Please

follow the instructions on the website to register.

http://www.dyness-tech.com

Service

Sign

29

Powerbox F series User Manual
4 Use, maintenance and troubleshooting
4.1 Battery system usage and operation instructions
After completing the electrical installation, follow the instruction below to start the battery system. 1) Check whether the DC breaker between the Powerbox and the DC Breaker on the left side of Powerbox system are both in “OFF” state.
2) Press the battery power button, the power button LED light is on, and 2 LED indicator lights will be on and show the green color after self-check.
3) Push the breaker on the left side of Powerbox system to the “ON” state, then push the DC breaker between the Powerbox and inverter to the “ON” state.
Note: If you need to shut down the system: Firstly, switch off the DC breaker between the battery and the inverter in “OFF” state, push the breaker on the left side of Powerbox system to the “OFF” state. Then please press the Power Switch button of Powebox system for 3s to shut down the battery system.
30

Powerbox F series User Manual

Caution:
After pressing the power button, if the battery status indicator lights shows abnormally, please refer to the “4.2 Alarm description and processing”. If the failure cannot be eliminated, please contact the retailer timely.
After pressing the power button, if the battery status indicator continues to be red, please refer to the “4.2 Alarm description and processing”. If the failure cannot be eliminated, please contact the retailer timely.
1 Use a voltmeter to measure whether the voltage across the BAT + / BAT- terminals of the inverter is higher than 42V, and check whether the voltage polarity is consistent with the input polarity of the inverter. If the voltage across the terminals BAT + / BAT- of the inverter is higher than 42V, which means the battery has begun to work normally.
2 After confirm the battery output voltage and polarity are correct, turn on the inverter, then turn on the circuit breaker switch.
3 Check whether the indicator light for the inverter and the battery connection (the communication indicator and the battery access status indicator) is in normal condition. If normal, the connection between the battery and the inverter is completed. If the indicator light show abnormal, please check the inverter manual or contact the local dealer.

4.2 Alarm description and processing

When protection mode is activated or system failure occurred, the ALM indicator on the front panel will alarm, through net management can query specific alarm class and take appropriate action.

4.2.1 Alarm and countermeasure for affecting system output

If there are any abnormalities affecting the output, such as battery cell in the battery module occurs over-current protection during charge/discharge, under-voltage protection, and temperature protection, in the system, please deal with them according to Table 4-1.

Table 4-1 Main alarm and Protection

Statue
Charge state

Alarm category Over-current when charging
High temp protection

Alarm indication RED light flashing Buzzer start RED light flashing

Processing
Reduce the charging current below the rated value.
Stop charging and find out the cause of the trouble.

31

Powerbox F series User Manual

Discharge state

Over-current protection when discharge High temp protection when discharge
Over-discharged protection
Low voltage alarm

RED light flashing Buzzer start RED light flashing RED light flashing Buzzer start Yellow light
on

Stop discharge and reduce discharge current below rated value. Stop discharging and find out the cause of the trouble.
Start charging.
Start charging.

4.2.2 Alarm and countermeasure for non-affecting system output

If a low SOC alarm occurs, the battery system also issues a corresponding alarm signal. Maintainer should check the equipment according to the prompt information, determine the type and location of the fault, and take corresponding countermeasures to ensure that the system is in the best working condition to avoid affecting the system output. The phenomena and countermeasures are shown in Table 4-2. Table 4-2 minor alarm

Alert category 0%SOC10%

Alarm indication
System working status: yellow light is always on

Countermeasure
Stop discharging, and charge the battery system in time.

4.3 Analysis and treatment of common faults

Table 4-3 Analysis and treatment of common faults

Item Fault phenomenon

Reason analysis

Solution

The indicator does not Make sure press and

1 respond after power on hold the power switch Check the power switch

the system

(Reset switch) for 3s.

No DC output after 2
power on the system

Check if the DC breaker is turned on

Check the status of the DC circuit breaker on the side of cabinet

No DC output and red light is Battery voltage is too

3

Charging the battery system

ON,buzzer beeping

low

The battery cannot be 4
fully charged

Charging voltage is too low

Adjust charging voltage within 53.5V~54V range

32

Powerbox F series User Manual

The power cable sparks Power connection
5 once power on and ALM short-circuit
indicated Red light on

Turn off the battery, check the cause of the short circuit

The master powerbox 6
LED1 is yellow flashing

Communication fault between powerbox and powerbox,or between internal modules in powerbox

Check the external communication cable firstly, Check the internal comms cable secondly

Check the external comms

Modules comms

The led 1,2,3,4 don’t stop

cable connection firstly.

7

address distribution is

changing alternately

Check the slave powerbox

fault

DIP setting.

If you need any technical help or have any question, please contact the dealer in time.

33

Daqin New Energy Tech (Taizhou) Co., Ltd. Address: Building 13, Kunshan Jiangyan Industrial Park, Chenzhuang West Road, Jiangyan District, Taizhou City, Jiangsu Province, China, 225500. Email: [email protected] Website: www.dyness-tech.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals