MITSUBISHI ELECTRIC MUFZ-KW Series Outdoor unit Hyper Heating console User Manual

June 4, 2024
Mitsubishi Electric

MUFZ-KW Series Outdoor unit Hyper Heating console

OUTDOOR UNIT
SERVICE MANUAL

HFC
utilized
R32

No. OBH895

Models
MUFZ-KW25VGHZ – E1 MUFZ-KW35VGHZ – E1 MUFZ-KW50VGHZ – E1 MUFZ-KW60VGHZ – E1

MUFZ-KW25VGHZ MUFZ-KW35VGHZ

Indoor unit service manual MFZ-KW·VG Series (OBH894)
CONTENTS
1. TECHNICAL CHANGES ······························ 2 2. SERVICING PRECAUTIONS FOR UNITS
USING REFRIGERANT R32························· 3 3. PART NAMES AND FUNCTIONS ·················· 5 4. SPECIFICATION ········································ 6 5. NOISE CRITERIA CURVES·························· 9 6. OUTLINES AND DIMENSIONS ··················· 10 7. WIRING DIAGRAM ··································· 12 8. REFRIGERANT SYSTEM DIAGRAM ··········· 13 9. PERFORMANCE CURVES ························ 15 10. ACTUATOR CONTROL ····························· 29 11. SERVICE FUNCTIONS ······························ 30 12. TROUBLESHOOTING ······························· 31 13. DISASSEMBLY INSTRUCTIONS················· 52
PARTS CATALOG (OBB895)

Use the specified refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker and pull the power plug. Discharge the capacitor before the work involving the electric parts. Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigeration cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to touch the live parts.
WARNING
· When the refrigeration circuit has a leak, do not execute pump down with the compressor.
· When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes. The compressor may burst if air etc. get into it.
· When opening or closing the valve below freezing temperatures, refrigerant may spurt out from the gap between the valve stem and the valve body, resulting in injuries.
1 TECHNICAL CHANGES
MUFZ-KW25VGHZ – E1 MUFZ-KW35VGHZ – E1 MUFZ-KW50VGHZ – E1 MUFZ-KW60VGHZ – E1
1. New model
2
OBH895

2 SERVICING PRECAUTIONS FOR UNITS USING REFRIGERANT R32
Servicing precautions for units using refrigerant R32 WARNING
This unit uses a flammable refrigerant. If refrigerant leaks and comes in contact with fire or heating part, it will create harmful gas and there is risk of fire.
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater.) Do not pierce or burn. Be aware that refrigerants may not contain an odor. Pipe-work shall be protected from physical damage. The installation of pipe-work shall be kept to a minimum. Compliance with national gas regulations shall be observed. Keep any required ventilation openings clear of obstruction. Servicing shall be performed only as recommended by the manufacturer. The appliance shall be stored so as to prevent mechanical damage from occurring.
Basic work procedures are the same as those for conventional units using refrigerant R410A. However, pay careful attention to the following points. 1. Information on servicing
(1) Checks on the Area Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized.
(2) Work Procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed.
(3) General Work Area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.
(4) Checking for Presence of Refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
(5) Presence of Fire Extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
(6) No Ignition Sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
(7) Ventilated Area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
(8) Checks on the Refrigeration Equipment Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants: · The charge size is in accordance with the room size within which the refrigerant containing parts are installed. · The ventilation machinery and outlets are operating adequately and are not obstructed. · If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant. · Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected. · Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being corroded.
(9) Checks on Electrical Devices Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include that: · capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking; · no live electrical components and wiring are exposed while charging, recovering or purging the system; · there is continuity of earth bonding
2. Repairs to Sealed Components (1) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation. (2) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that the apparatus is mounted securely. Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
3. Repair to intrinsically Safe Components Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
4. Cabling Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
3
OBH895

5. Detection of Flammable Refrigerants Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
6. Leak Detection Methods Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed, and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. For appliances containing flammable refrigerants, oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
7. Removal and Evacuation When breaking into the refrigerant circuit to make repairs – or for any other purpose conventional procedures shall be used. However, for flammable refrigerants it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: remove refrigerant purge the circuit with inert gas evacuate purge again with inert gas open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable refrigerants, the system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems. For appliances containing flammable refrigerants, flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe- work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and that ventilation is available.
8. Charging Procedures In addition to conventional charging procedures, the following requirements shall be followed: Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them. Cylinders shall be kept upright. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete (if not already). Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
9. Decommissioning Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced. (1) Become familiar with the equipment and its operation. (2) Isolate system electrically. (3) Before attempting the procedure, ensure that: mechanical handling equipment is available, if required, for handling refrigerant cylinders; all personal protective equipment is available and being used correctly; the recovery process is supervised at all times by a competent person; recovery equipment and cylinders conform to the appropriate standards. (4) Pump down refrigerant system, if possible. (5) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. (6) Make sure that cylinder is situated on the scales before recovery takes place. (7) Start the recovery machine and operate in accordance with manufacturer’s instructions. (8) Do not overfill cylinders. (no more than 80 % volume liquid charge). (9) Do not exceed the maximum working pressure of the cylinder, even temporarily. (10) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. (11) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
10. Labeling Equipment shall be labeled stating that it has been de- commissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
11. Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable, flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
4
OBH895

3 PART NAMES AND FUNCTIONS
MUFZ-KW25VGHZ MUFZ-KW35VGHZ
Air inlet (Back and side)
Piping Air outlet Drain hose Drain outlet
MUFZ-KW50VGHZ MUFZ-KW60VGHZ
Air inlet (Back and side)
Piping Drain hose
Air outlet Drain outlet
5
OBH895

4 SPECIFICATION

Outdoor model

MUFZ-KW25VGHZ

MUFZ-KW35VGHZ

Power supply

Single phase, 230 V, 50 Hz

Capacity Rated (Min.-Max.)

Cooling kW
Heating

2.5 (0.7 – 3.6) 3.4 (0.2 – 5.1)

3.5 (0.7 – 4.3) 4.3 (0.2 – 6.0)

Breaker Capacity

A

10

12

Cooling

570

Power input *1 (Set)

W

Heating

830

900 1,210

Electrical data

Cooling

3.0

4.3

Running current *1 (Set)

A

Heating

3.9

5.4

Cooling

82

91

Power factor *1 (Set)

%

Heating

92

97

Starting current *1 (Set)

A

3.9

5.4

Coefficient of performance

Cooling

4.38

3.88

(COP) *1 (Set)

Heating

4.09

3.55

Model

SVB130FBBMT

Output

W

900

Compressor

Cooling

2.57

3.87

Current *1

A

Heating

3.46

4.96

Refrigeration oil (Model)

L

0.35 (FW68S)

Model

RC0J50-NC

Fan motor

Cooling

0.25

0.25

Current *1

A

Heating

0.22

0.22

Dimensions W × H × D

mm

800 × 550 × 285

Weight

kg

35

Dehumidification

Cooling

L/h

0.6

1.4

Cooling

High Low

1,962 984

1,962 984

Airflow

High

m3/h

1,962

1,962

Heating

Medium

1,638

1,638

Special remarks

Low

1,356

1,356

Sound level *1

Cooling Heating

dB(A)

47 46

47 47

High

900

900

Cooling

Low

490

490

Fan speed

High

rpm

900

900

Heating

Medium

760

760

Low

640

640

Fan speed regulator

3

Refrigerant filling capacity (R32)

kg

1.00

NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Wet-bulb temperature 24°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C *1 Measured under rated operating frequency.

6
OBH895

Outdoor model

MUFZ-KW50VGHZ

MUFZ-KW60VGHZ

Power supply

Single phase, 230 V, 50 Hz

Capacity Rated (Min. – Max.)

Cooling kW
Heating

5.0 (1.0 – 5.8) 6.0 (1.2 – 8.4)

6.1 (1.0 – 6.5) 6.5 (1.2 – 9.0)

Breaker Capacity

A

16

16

Power input *1 (Set)

Cooling W
Heating

1,360 1,600

1,730 1,880

Electrical data

Cooling

6.2

7.7

Running current *1 (Set)

A

Heating

7.1

8.3

Cooling

95

97

Power factor *1 (Set)

%

Heating

97

98

Starting current *1 (Set)

A

7.1

8.3

Coefficient of performance

Cooling

3.67

3.52

(COP) *1 (Set)

Heating

3.75

3.45

Model

SVB172FCKMT

Output

W

1,200

Compressor

Cooling

5.25

6.32

Current *1

A

Heating

5.89

6.94

Refrigeration oil (Model)

L

0.40(FW68S)

Model

RC0J60-BC

Fan motor

Cooling

0.68

0.83

Current *1

A

Heating

0.74

0.84

Dimensions W × H × D

mm

840 × 880 × 330

Weight

kg

54

54

Dehumidification

Cooling

L/h

2.2

2.3

Cooling

High Low

2,628 1,716

2,928 1,716

Airflow

High

m3/h

3,078

3,078

Heating

Medium

2,778

3,078

Special remarks

Low

2,280

2,280

Cooling

50

52

Sound level *1

dB(A)

Heating

54

56

High

760

820

Cooling

Low

450

450

Fan speed

High

rpm

860

860

Heating

Medium

800

860

Low

650

650

Fan speed regulator

3

Refrigerant filling capacity (R32)

kg

1.30

NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Wet-bulb temperature 24°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C *1 Measured under rated operating frequency.

7
OBH895

Specifications and rated conditions of main electric parts

Model Item

Smoothing capacitor

(C61, C62, C63)

Diode module

(DB61) (DB65)

(F701, F801, F901)

Fuse

(F61)

(F62)

Defrost heater

(H)

Power module

(IC700) (IC932)

Expansion valve coil

(LEV)

Reactor
Switching power transistor
Circuit protection

(L61) (Q821) (PTC64, PTC65)

Terminal block

(TB1)

(X63)

Relay

(X64) (X66)

(X69)

R.V. coil

(21S4)

Heater protector

(26H)

MUFZ-KW25VGHZ MUFZ-KW35VGHZ
600 µF/ 620 µF 420 V 15 A 600 V 25A 600V
T3.15AL250V 25 A 250 V 15 A 250 V 230 V 60 W 20A 600V 5 A 600 V 12 V DC 23 mH
30A/37A 600V
33 5 P 3 A 250 V 20 A 250 V 3 A 250 V 10 A 230 V 220-240 V AC Open 45°C

Item Smoothing capacitor Fuse Switching power transistor Defrost heater
Power module
Expansion valve coil Reactor Diode Diode module Circuit protection Terminal block
Relay
R.V. coil Heater protector

Model
(CB1, CB2, CB3)
(F601, F880, F901)
(Q3A, Q3B)
(H) (IC932) (IC700)
(LEV) (L)
(D3A, D3B) (DB41A, DB41B) (PTC64, PTC65)
(TB1, TB2) (X64) (X65) (X69)
(X601) (X602) (21S4)
(26H)

OBH895

MUFZ-KW50VGHZ MUFZ-KW60VGHZ
560 µF 450 V T3.15AL250V
21 A 650 V
230V 120 W 5 A 600 V 20 A 600 V 12 V DC 282 µH 20 A 600 V 20 A 600 V 33 3 P 20 A 250 V 20 A 250 V 10 A 250 V 3 A 250 V 3 A 250 V
220-240 V AC Open 45°C
8

5 NOISE CRITERIA CURVES

MUFZ-KW25VGHZ
FUNCTION SPL(dB(A)) LINE

COOLING

47

HEATING

46

90

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR

80

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20

NC-10

NC-20

10 63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz

MUFZ-KW50VGHZ

FUNCTION SPL(dB(A)) LINE

COOLING

50

HEATING

54

90

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR

80

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20

NC-10

NC-20

10 63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz

MUFZ-KW35VGHZ
FUNCTION SPL(dB(A)) LINE

COOLING

47

HEATING

47

90

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR

80

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20

NC-10

NC-20

10 63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz

MUFZ-KW60VGHZ

FUNCTION SPL(dB(A)) LINE

COOLING

52

HEATING

56

90

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR

80

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20

NC-10

NC-20

10 63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz

Test conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT

1 m MICROPHONE

9
OBH895

6 OUTLINES AND DIMENSIONS
MUFZ-KW25VGHZ MUFZ-KW35VGHZ

Unit: mm

10
OBH895

360 Clear *1

MUFZ-KW50VGHZ MUFZ-KW60VGHZ
REQUIRED SPACE
*1. 500 mm or more when front and sides of the unit are clear

417.5 Air in
Air in

Drain hole 42 40

100 mm or more

330 50

Unit: mm
100 mm or more

Air out

175

500

840 109

2-holes 10 21 81

5o0r0mmomre *2

350 mm or more

*2. When any 2 sides of left, right and rear of the unit are clear
Service panel

Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 6.35

880 452

35 44

164.5 99.5

Gas refrigerant pipe joint
Refrigerant pipe (flared)
Ø 12.7 195

11
OBH895

7 WIRING DIAGRAM
MUFZ-KW25VGHZ MUFZ-KW35VGHZ
MUFZ-KW50VGHZ MUFZ-KW60VGHZ
12
OBH895

8 REFRIGERANT SYSTEM DIAGRAM
MUFZ-KW25VGHZ MUFZ-KW35VGHZ

Unit: mm

Refrigerant pipe ø9.52 (with heat insulator)

Muffler

Stop valve

Flared connection

4-way valve

Discharge temperature thermistor RT62

Muffler Compressor

Outdoor heat exchanger

Defrost thermistor RT61

Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65

Flared connection

Stop valve

Capillary tube LEV

(with strainer) ø4.0×ø2.4×240

Refrigerant pipe ø6.35 (with heat insulator)

Strainer #100

MUFZ-KW50VGHZ MUFZ-KW60VGHZ

Refrigerant pipe ø12.7 (with heat insulator)

4-way valve

Strainer #100
R.V. coil heating ON cooling OFF
Refrigerant flow in cooling Refrigerant flow in heating

Flared connection

Stop valve

Discharge temperature thermistor RT62

Defrost thermistor RT61

Outdoor heat exchanger

Ambient temperature thermistor RT65

Compressor

Flared connection

Strainer Capillary tube LEV Strainer

100 ø4.0×ø2.4×100

100

Stop valve

Muffler

Outdoor heat exchanger temperature thermistor RT68
R.V. coil heating ON cooling OFF

Refrigerant pipe ø6.35 (with heat insulator)

Refrigerant flow in cooling Refrigerant flow in heating

13
OBH895

MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE

Model
MUFZ-KW25VGHZ MUFZ-KW35VGHZ

Refrigerant piping: m

Max. Length A

Max. Height difference B

20

12

Piping size O.D: mm

Gas

Liquid

9.52

6.35

MUFZ-KW50VGHZ MUFZ-KW60VGHZ

30

15

12.7

6.35

Indoor unit

Max. Height difference
B

Max. Length A

Outdoor unit

ADDITIONAL REFRIGERANT CHARGE (R32: g)

Model

Outdoor unit

Refrigerant piping length (one way)

precharged 7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 16 m 17 m 18 m 19 m 20 m

MUFZ-KW25VGHZ MUFZ-KW35VGHZ

1,000

0 20 40 60 80 100 120 140 160 180 200 220 240 260

Calculation: X g = 20 g/m × (Refrigerant piping length(m) – 7)

Model

Outdoor unit

Refrigerant piping length (one way)

precharged 7 m

8 m

9 m

10 m

15 m

20 m

MUFZ-KW50VGHZ MUFZ-KW60VGHZ

1,300

0

20

40

60

160

260

Calculation: X g = 20 g/m × (Refrigerant piping length (m) ­ 7)

25 m 360

30 m 460

14
OBH895

9 PERFORMANCE CURVES

MUFZ-KW25VGHZ MUFZ-KW35VGHZ MUFZ-KW50VGHZ MUFZ-KW60VGHZ

The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi-

tions vary according to the areas where these units are installed, the following information has been provided to clarify the

operating characteristics of the air conditioner under the conditions indicated by the performance curve.

(1) GUARANTEED VOLTAGE

198 ~ 264V, 50 Hz

(2) AIRFLOW

Airflow should be set at MAX.

(3) MAIN READINGS

(1) Indoor intake air wet-bulb temperature: (2) Indoor outlet air wet-bulb temperature: (3) Outdoor intake air dry-bulb temperature:

} °C [WB] °C [WB] °C [DB]

Cooling

(4) Total input:

W

(5) Indoor intake air dry-bulb temperature: (6) Outdoor intake air wet-bulb temperature: (7) Total input:

} °C [DB] °C [WB]

Heating

W

Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the

indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at

service.

(4) GUARANTEED OUTDOOR TEMPERATURE

COOLING (DB/WB): -10/ ­ ~ 46/ ­

HEATING (DB/WB): -25/ ­ ~ 24/18

How to measure the indoor air wet and dry bulb temperature difference 1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high. 2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun. 3. Check that the air filter is cleaned. 4. Open windows and doors of room. 5. Press the emergency operation switch once (twice) to start the EMERGENCY COOL (HEAT) MODE. 6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature. 7. 10 minutes later, measure temperature again and check that the temperature does not change.

INDOOR UNIT

OUTDOOR UNIT

Wet and dry bulb thermometers
FRONT VIEW

Wet and dry bulb thermometers
BACK VIEW

15
OBH895

Indoor air Wet-bulb temperature difference (°C)
MUFZ-KW25VGHZ

9-1. CAPACITY AND INPUT CURVES

8.5 12.9 14.6 12.1 7.9 11.8 13.4 11.1 7.2 10.8 12.2 10.1 6.6 9.8 11.0 9.2 6.0 8.8 9.9 8.3 5.4 7.9 8.9 7.4 4.8 7.0 7.8 6.6

Capacity correction factors

Cooling capacity (at Rated frequency)
1.5

1.4

Indoor intake air Wet-bulb temperature( )

1.3

1.2

26

1.1 24
1.0

0.9 -10 -5 0

22 20 18
5 10 15 20 25 30 35 40 45

Outdoor intake air Dry-bulb temperature(°C)

MUFZ-KW60VGHZ

MUFZ-KW50VGHZ

MUFZ-KW35VGHZ

Input correction factors

1.3 1.2 1.1 1.0 0.9 0.8
-10

Total input (Cooling : at Rated frequency)
26

24

22 20

18

Indoor intake air Wet-bulb temperature( )
-5 0 5 10 15 20 25 30 35 40 45
Outdoor intake air Dry-bulb temperature (°C)

22.9 29.0 21.2 26.8 19.4 24.5 17.6 22.3 15.9 20.1 14.1 17.8 12.3 15.6 10.6 13.4
8.8 11.1 7.1 8.9

28.0 29.1 25.9 26.9 23.7 24.6 21.6 22.4 19.4 20.2 17.2 17.9 15.1 15.7 12.9 13.4 10.8 11.2
8.6 9.0

1.3 1.2 1.1 1.0 0.9 0.8 0.7 0.6 0.5 0.4
-25

Heating capacity (at Rated frequency)
Indoor intake air Dry-bulb temperature ( )

-20

-15

-10

-5

0

5

10

Outdoor intake air Wet-bulb temperature (°C)

15 20 26
15

Indoor air Dry-bulb temperature difference (°C)
MUFZ-KW25VGHZ MUFZ-KW35VGHZ MUFZ-KW50VGHZ MUFZ-KW60VGHZ
Capacity correction factor

Input correction factor

Total input (Heating : at Rated frequency) 1.3

1.2

26

1.1 1.0 0.9 0.8 0.7

Indoor intake air Dry-bulb temperature ( )

20 15

0.6

0.5

0.4

-25

-20

-15

-10

-5

0

5

10

15

Outdoor intake air Wet-bulb temperature (°C)

NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
16
OBH895

9-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR

MUFZ-KW25VGHZ
Correction of Cooling capacity 1.5

Correction of Cooling input 3.0

Correction of Heating capacity 1.5

Correction of Heating input 3.0

Input correction factors

Capacity correction factors

Input correction factors

Capacity correction factors

1.0

2.0

1.0

2.0

0.5

1.0

0.5

1.0

0.0

0

50

100

The operational frequency of compressor (Hz)

MUFZ-KW35VGHZ

Correction of Cooling capacity 1.5

0.0

0

50

100

The operational frequency of compressor (Hz)

Correction of Cooling input 3.0

0.0

0

50

100

The operational frequency of compressor (Hz)

Correction of Heating capacity 1.5

0.0

0

50

100

The operational frequency

of compressor (Hz)

Correction of Heating input 3.0

Input correction factors

Capacity correction factors

Input correction factors

Capacity correction factors

1.0

2.0

1.0

2.0

0.5

1.0

0.5

1.0

0.0

0

50

100

The operational frequency of compressor (Hz)

0.0

0

50

100

The operational frequency of compressor (Hz)

MUFZ-KW50VGHZ
Correction of Cooling capacity 1.5

Correction of Cooling input 3.0

0.0

0

50

100

The operational frequency of compressor (Hz)

1.5 Correction of Heating capacity

0.0

0

50

100

The operational frequency

of compressor (Hz)

Correction of Heating input 3.0

Input correction factors

Capacity correction factors

Input correction factors

Capacity correction factors

1.0

2.0

1.0

2.0

0.5

1.0

0.5

1.0

0.0

0

50

100

The operational frequency of compressor (Hz)

MUFZ-KW60VGHZ

0.0

0

50

100

The operational frequency of compressor (Hz)

1.5 Correction of Cooling capacity 3.0 Correction of Cooling input

0.0

0

50

100

The operational frequency of compressor (Hz)

1.5 Correction of Heating capacity

0.0

0

50

100

The operational frequency of compressor (Hz)

3.0 Correction of Heating input

Input correction factors

Capacity correction factors

Input correction factors

Capacity correction factors

1.0

2.0

1.0

2.0

0.5

1.0

0.5

1.0

0.0 0

0.0

50

100

0

50

100

The operational frequency of compressor (Hz)

The operational frequency of compressor (Hz)

0.0

0

50

100

The operational frequency of compressor (Hz)

0.0

0

50

100

The operational frequency of compressor (Hz)

9-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION

1\. Press the emergency operation switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice). 2. Test run operation starts and continues to operate for 30 minutes. 3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode. 4. Indoor fan operates at High speed. 5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies). 6. To cancel test run operation (EMERGENCY OPERATION), press the emergency operation switch or any button on remote controller. 17 OBH895

9-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT

COOL operation

Dry-bulb temperature (°C)

Both indoor and outdoor unit are under the same temperature/

20

humidity condition.

25

Operation: Test run operation (Refer to 9-3.)

30

Relative humidity (%) 50 60 70

Outdoor low pressure

MUFZ-KW25VGHZ

(kgf/cm2 [Gauge])(MPa [Gauge])

18.0

1.8

MUFZ-KW35VGHZ

(kgf/cm2 [Gauge])(MPa [Gauge])

15.0

1.5

1.6 16.0

13.0

1.3

14.2

1.4

11.0

1.1

12.0

1.2

9.0

0.9

10.0

1.0 15

20

25

30

35

7.0

50 60 70

Ambient temperature(°C)

Ambient humidity(%)

0.7
15 20 25 30 35 50 60 70
Ambient temperature(°C)
Ambient humidity(%)

MUFZ-KW50VGHZ

(kgf/cm2 [Gauge])(MPa [Gauge])

15.0

1.5

MUFZ-KW60VGHZ

(kgf/cm2 [Gauge])(MPa [Gauge])

15.0

1.5

1.3 13.0

1.3 13.0

11.0

1.1

11.0

1.1

9.0

0.9

9.0

0.9

7.0

0.7 15 20 25 30 35

7.0

0.7 15 20 25 30 35

50 60 70

50 60 70

Ambient temperature(°C)

Ambient temperature(°C)

Ambient humidity(%)

Ambient humidity(%)

NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system) The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm2 [Gauge])

Outdoor current (A)

Outdoor current (A)

Outdoor unit current MUFZ-KW25VGHZ
3.8
3.5
3.2
2.9
2.6
2.3 15 20 25 30 35 50 60 70 Ambient temperature(°C) Ambient humidity(%)
MUFZ-KW50VGHZ
7.0
6.5
6.0
5.5
5.0
4.5 15 20 25 30 35 50 60 70 Ambient temperature(°C) Ambient humidity(%)
OBH895

Outdoor current (A)

Outdoor current (A)

MUFZ-KW35VGHZ
5.0
4.6
4.2
3.8
3.4
3.0 15 20 25 30 35 50 60 70 Ambient temperature(°C) Ambient humidity(%)
MUFZ-KW60VGHZ
9.0
8.4
7.8
7.2
6.6
6.0 15 20 25 30 35 50 60 70 Ambient temperature(°C) Ambient humidity(%)
18

HEAT operation

Condition:

Indoor

Dry bulb temperature (°C) 20.0 2

Wet bulb temperature (°C) 14.5 1

Operation: Test run operation (Refer to 9-3.)

Outdoor 7 15 20.0 6 12 14.5

Outdoor current (A)

Outdoor current (A)

Outdoor unit current MUFZ-KW25VGHZ
6.2
5.8
5.4
5.0
4.6
4.2 0 5 10 15 20 25 Ambient temperature (°C)
MUFZ-KW50VGHZ
8.5
8.0
7.5
7.0
6.5
6.0 0 5 10 15 20 25 Ambient temperature (°C)

Outdoor current (A)

Outdoor current (A)

MUFZ-KW35VGHZ
6.2 5.8 5.4 5.0 4.6 4.2
0 5 10 15 20 25 Ambient temperature (°C)
MUFZ-KW60VGHZ
8.0 7.5 7.0 6.5 6.0 5.50 5 10 15 20 25
Ambient temperature (°C)

19
OBH895

PERFORMANCE DATA COOL operation at Rated frequency

MUFZ-KW25VGHZ

CAPACITY: 2.5 kW

SHF: 0.84

INPUT: 570 W

OUTDOOR DB (°C)

INDOOR INDOOR DB (°C) WB (°C)

21

25

27

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q

21

18 2.94 1.94 0.66 456 2.81 1.86 0.66 479 2.70 1.78 0.66 502 2.60

21

20 3.06 1.65 0.54 479 2.94 1.59 0.54 507 2.85 1.54 0.54 519 2.75

22

18 2.94 2.06 0.70 456 2.81 1.97 0.70 479 2.70 1.89 0.70 502 2.60

22

20 3.06 1.78 0.58 479 2.94 1.70 0.58 507 2.85 1.65 0.58 519 2.75

22

22 3.19 1.47 0.46 496 3.08 1.41 0.46 527 3.00 1.38 0.46 542 2.88

23

18 2.94 2.17 0.74 456 2.81 2.08 0.74 479 2.70 2.00 0.74 502 2.60

23

20 3.06 1.90 0.62 479 2.94 1.82 0.62 507 2.85 1.77 0.62 519 2.75

23

22 3.19 1.59 0.50 496 3.08 1.54 0.50 527 3.00 1.50 0.50 542 2.88

24

18 2.94 2.29 0.78 456 2.81 2.19 0.78 479 2.70 2.11 0.78 502 2.60

24

20 3.06 2.02 0.66 479 2.94 1.94 0.66 507 2.85 1.88 0.66 519 2.75

24

22 3.19 1.72 0.54 496 3.08 1.66 0.54 527 3.00 1.62 0.54 542 2.88

24

24 3.35 1.41 0.42 519 3.23 1.35 0.42 547 3.15 1.32 0.42 564 3.05

25

18 2.94 2.41 0.82 456 2.81 2.31 0.82 479 2.70 2.21 0.82 502 2.60

25

20 3.06 2.14 0.70 479 2.94 2.06 0.70 507 2.85 2.00 0.70 519 2.75

25

22 3.19 1.85 0.58 496 3.08 1.78 0.58 527 3.00 1.74 0.58 542 2.88

25

24 3.35 1.54 0.46 519 3.23 1.48 0.46 547 3.15 1.45 0.46 564 3.05

26

18 2.94 2.53 0.86 456 2.81 2.42 0.86 479 2.70 2.32 0.86 502 2.60

26

20 3.06 2.27 0.74 479 2.94 2.17 0.74 507 2.85 2.11 0.74 519 2.75

26

22 3.19 1.98 0.62 496 3.08 1.91 0.62 527 3.00 1.86 0.62 542 2.88

26

24 3.35 1.68 0.50 519 3.23 1.61 0.50 547 3.15 1.58 0.50 564 3.05

26

26 3.45 1.31 0.38 547 3.35 1.27 0.38 576 3.30 1.25 0.38 593 3.20

27

18 2.94 2.64 0.90 456 2.81 2.53 0.90 479 2.70 2.43 0.90 502 2.60

27

20 3.06 2.39 0.78 479 2.94 2.29 0.78 507 2.85 2.22 0.78 519 2.75

27

22 3.19 2.10 0.66 496 3.08 2.03 0.66 527 3.00 1.98 0.66 542 2.88

27

24 3.35 1.81 0.54 519 3.23 1.74 0.54 547 3.15 1.70 0.54 564 3.05

27

26 3.45 1.45 0.42 547 3.35 1.41 0.42 576 3.30 1.39 0.42 593 3.20

28

18 2.94 2.76 0.94 456 2.81 2.64 0.94 479 2.70 2.54 0.94 502 2.60

28

20 3.06 2.51 0.82 479 2.94 2.41 0.82 507 2.85 2.34 0.82 519 2.75

28

22 3.19 2.23 0.70 496 3.08 2.15 0.70 527 3.00 2.10 0.70 542 2.88

28

24 3.35 1.94 0.58 519 3.23 1.87 0.58 547 3.15 1.83 0.58 564 3.05

28

26 3.45 1.59 0.46 547 3.35 1.54 0.46 576 3.30 1.52 0.46 593 3.20

29

18 2.94 2.88 0.98 456 2.81 2.76 0.98 479 2.70 2.65 0.98 502 2.60

29

20 3.06 2.63 0.86 479 2.94 2.53 0.86 507 2.85 2.45 0.86 519 2.75

29

22 3.19 2.36 0.74 496 3.08 2.28 0.74 527 3.00 2.22 0.74 542 2.88

29

24 3.35 2.08 0.62 519 3.23 2.00 0.62 547 3.15 1.95 0.62 564 3.05

29

26 3.45 1.73 0.50 547 3.35 1.68 0.50 576 3.30 1.65 0.50 593 3.20

30

18 2.94 2.94 1.00 456 2.81 2.81 1.00 479 2.70 2.70 1.00 502 2.60

30

20 3.06 2.76 0.90 479 2.94 2.64 0.90 507 2.85 2.57 0.90 519 2.75

30

22 3.19 2.49 0.78 496 3.08 2.40 0.78 527 3.00 2.34 0.78 542 2.88

30

24 3.35 2.21 0.66 519 3.23 2.13 0.66 547 3.15 2.08 0.66 564 3.05

30

26 3.45 1.86 0.54 547 3.35 1.81 0.54 576 3.30 1.78 0.54 593 3.20

31

18 2.94 2.94 1.00 456 2.81 2.81 1.00 479 2.70 2.70 1.00 502 2.60

31

20 3.06 2.88 0.94 479 2.94 2.76 0.94 507 2.85 2.68 0.94 519 2.75

31

22 3.19 2.61 0.82 496 3.08 2.52 0.82 527 3.00 2.46 0.82 542 2.88

31

24 3.35 2.35 0.70 519 3.23 2.26 0.70 547 3.15 2.21 0.70 564 3.05

31

26 3.45 2.00 0.58 547 3.35 1.94 0.58 576 3.30 1.91 0.58 593 3.20

32

18 2.94 2.94 1.00 456 2.81 2.81 1.00 479 2.70 2.70 1.00 502 2.60

32

20 3.06 3.00 0.98 479 2.94 2.88 0.98 507 2.85 2.79 0.98 519 2.75

32

22 3.19 2.74 0.86 496 3.08 2.64 0.86 527 3.00 2.58 0.86 542 2.88

32

24 3.35 2.48 0.74 519 3.23 2.39 0.74 547 3.15 2.33 0.74 564 3.05

32

26 3.45 2.14 0.62 547 3.35 2.08 0.62 576 3.30 2.05 0.62 593 3.20

NOTE Q : Total capacity (kW)

SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

30 SHC SHF 1.72 0.66 1.49 0.54 1.82 0.70 1.60 0.58 1.32 0.46 1.92 0.74 1.71 0.62 1.44 0.50 2.03 0.78 1.82 0.66 1.55 0.54 1.28 0.42 2.13 0.82 1.93 0.70 1.67 0.58 1.40 0.46 2.24 0.86 2.04 0.74 1.78 0.62 1.53 0.50 1.22 0.38 2.34 0.90 2.15 0.78 1.90 0.66 1.65 0.54 1.34 0.42 2.44 0.94 2.26 0.82 2.01 0.70 1.77 0.58 1.47 0.46 2.55 0.98 2.37 0.86 2.13 0.74 1.89 0.62 1.60 0.50 2.60 1.00 2.48 0.90 2.24 0.78 2.01 0.66 1.73 0.54 2.60 1.00 2.59 0.94 2.36 0.82 2.14 0.70 1.86 0.58 2.60 1.00 2.70 0.98 2.47 0.86 2.26 0.74 1.98 0.62

INPUT 524 542 524 542 564 524 542 564 524 542 564 593 524 542 564 593 524 542 564 593 610 524 542 564 593 610 524 542 564 593 610 524 542 564 593 610 524 542 564 593 610 524 542 564 593 610 524 542 564 593 610

20
OBH895

PERFORMANCE DATA COOL operation at Rated frequency

MUFZ-KW25VGHZ

CAPACITY: 2.5 kW

SHF: 0.84

INPUT: 570 W

OUTDOOR DB (°C)

INDOOR INDOOR DB (°C) WB (°C)

35

40

46

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT

21

18 2.45 1.62 0.66 559 2.25 1.49 0.66 593 2.08 1.37 0.66 616

21

20 2.58 1.39 0.54 581 2.40 1.30 0.54 610 2.23 1.20 0.54 644

22

18 2.45 1.72 0.70 559 2.25 1.58 0.70 593 2.08 1.45 0.70 616

22

20 2.58 1.49 0.58 581 2.40 1.39 0.58 610 2.23 1.29 0.58 644

22

22 2.73 1.25 0.46 604 2.55 1.17 0.46 638 2.38 1.09 0.46 661

23

18 2.45 1.81 0.74 559 2.25 1.67 0.74 593 2.08 1.54 0.74 616

23

20 2.58 1.60 0.62 581 2.40 1.49 0.62 610 2.23 1.38 0.62 644

23

22 2.73 1.36 0.50 604 2.55 1.28 0.50 638 2.38 1.19 0.50 661

24

18 2.45 1.91 0.78 559 2.25 1.76 0.78 593 2.08 1.62 0.78 616

24

20 2.58 1.70 0.66 581 2.40 1.58 0.66 610 2.23 1.47 0.66 644

24

22 2.73 1.47 0.54 604 2.55 1.38 0.54 638 2.38 1.28 0.54 661

24

24 2.88 1.21 0.42 627 2.70 1.13 0.42 656 2.55 1.07 0.42 684

25

18 2.45 2.01 0.82 559 2.25 1.85 0.82 593 2.08 1.70 0.82 616

25

20 2.58 1.80 0.70 581 2.40 1.68 0.70 610 2.23 1.56 0.70 644

25

22 2.73 1.58 0.58 604 2.55 1.48 0.58 638 2.38 1.38 0.58 661

25

24 2.88 1.32 0.46 627 2.70 1.24 0.46 656 2.55 1.17 0.46 684

26

18 2.45 2.11 0.86 559 2.25 1.94 0.86 593 2.08 1.78 0.86 616

26

20 2.58 1.91 0.74 581 2.40 1.78 0.74 610 2.23 1.65 0.74 644

26

22 2.73 1.69 0.62 604 2.55 1.58 0.62 638 2.38 1.47 0.62 661

26

24 2.88 1.44 0.50 627 2.70 1.35 0.50 656 2.55 1.28 0.50 684

26

26 3.03 1.15 0.38 650 2.85 1.08 0.38 678 2.68 1.02 0.38 707

27

18 2.45 2.21 0.90 559 2.25 2.03 0.90 593 2.08 1.87 0.90 616

27

20 2.58 2.01 0.78 581 2.40 1.87 0.78 610 2.23 1.74 0.78 644

27

22 2.73 1.80 0.66 604 2.55 1.68 0.66 638 2.38 1.57 0.66 661

27

24 2.88 1.55 0.54 627 2.70 1.46 0.54 656 2.55 1.38 0.54 684

27

26 3.03 1.27 0.42 650 2.85 1.20 0.42 678 2.68 1.12 0.42 707

28

18 2.45 2.30 0.94 559 2.25 2.12 0.94 593 2.08 1.95 0.94 616

28

20 2.58 2.11 0.82 581 2.40 1.97 0.82 610 2.23 1.82 0.82 644

28

22 2.73 1.91 0.70 604 2.55 1.79 0.70 638 2.38 1.66 0.70 661

28

24 2.88 1.67 0.58 627 2.70 1.57 0.58 656 2.55 1.48 0.58 684

28

26 3.03 1.39 0.46 650 2.85 1.31 0.46 678 2.68 1.23 0.46 707

29

18 2.45 2.40 0.98 559 2.25 2.21 0.98 593 2.08 2.03 0.98 616

29

20 2.58 2.21 0.86 581 2.40 2.06 0.86 610 2.23 1.91 0.86 644

29

22 2.73 2.02 0.74 604 2.55 1.89 0.74 638 2.38 1.76 0.74 661

29

24 2.88 1.78 0.62 627 2.70 1.67 0.62 656 2.55 1.58 0.62 684

29

26 3.03 1.51 0.50 650 2.85 1.43 0.50 678 2.68 1.34 0.50 707

30

18 2.45 2.45 1.00 559 2.25 2.25 1.00 593 2.08 2.08 1.00 616

30

20 2.58 2.32 0.90 581 2.40 2.16 0.90 610 2.23 2.00 0.90 644

30

22 2.73 2.13 0.78 604 2.55 1.99 0.78 638 2.38 1.85 0.78 661

30

24 2.88 1.90 0.66 627 2.70 1.78 0.66 656 2.55 1.68 0.66 684

30

26 3.03 1.63 0.54 650 2.85 1.54 0.54 678 2.68 1.44 0.54 707

31

18 2.45 2.45 1.00 559 2.25 2.25 1.00 593 2.08 2.08 1.00 616

31

20 2.58 2.42 0.94 581 2.40 2.26 0.94 610 2.23 2.09 0.94 644

31

22 2.73 2.23 0.82 604 2.55 2.09 0.82 638 2.38 1.95 0.82 661

31

24 2.88 2.01 0.70 627 2.70 1.89 0.70 656 2.55 1.79 0.70 684

31

26 3.03 1.75 0.58 650 2.85 1.65 0.58 678 2.68 1.55 0.58 707

32

18 2.45 2.45 1.00 559 2.25 2.25 1.00 593 2.08 2.08 1.00 616

32

20 2.58 2.52 0.98 581 2.40 2.35 0.98 610 2.23 2.18 0.98 644

32

22 2.73 2.34 0.86 604 2.55 2.19 0.86 638 2.38 2.04 0.86 661

32

24 2.88 2.13 0.74 627 2.70 2.00 0.74 656 2.55 1.89 0.74 684

32

26 3.03 1.88 0.62 650 2.85 1.77 0.62 678 2.68 1.66 0.62 707

NOTE Q : Total capacity (kW)

SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

21
OBH895

PERFORMANCE DATA COOL operation at Rated frequency

MUFZ-KW35VGHZ

CAPACITY: 3.5 kW

SHF: 0.72

INPUT: 900 W

OUTDOOR DB (°C)

INDOOR INDOOR DB (°C) WB (°C)

21

25

27

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q

21

18 4.11 2.22 0.54 720 3.94 2.13 0.54 756 3.78 2.04 0.54 792 3.64

21

20 4.29 1.80 0.42 756 4.11 1.73 0.42 801 3.99 1.68 0.42 819 3.85

22

18 4.11 2.39 0.58 720 3.94 2.28 0.58 756 3.78 2.19 0.58 792 3.64

22

20 4.29 1.97 0.46 756 4.11 1.89 0.46 801 3.99 1.84 0.46 819 3.85

22

22 4.46 1.52 0.34 783 4.31 1.46 0.34 833 4.20 1.43 0.34 855 4.03

23

18 4.11 2.55 0.62 720 3.94 2.44 0.62 756 3.78 2.34 0.62 792 3.64

23

20 4.29 2.14 0.50 756 4.11 2.06 0.50 801 3.99 1.99 0.50 819 3.85

23

22 4.46 1.70 0.38 783 4.31 1.64 0.38 833 4.20 1.60 0.38 855 4.03

24

18 4.11 2.71 0.66 720 3.94 2.60 0.66 756 3.78 2.49 0.66 792 3.64

24

20 4.29 2.32 0.54 756 4.11 2.22 0.54 801 3.99 2.15 0.54 819 3.85

24

22 4.46 1.87 0.42 783 4.31 1.81 0.42 833 4.20 1.76 0.42 855 4.03

24

24 4.69 1.41 0.30 819 4.52 1.35 0.30 864 4.41 1.32 0.30 891 4.27

25

18 4.11 2.88 0.70 720 3.94 2.76 0.70 756 3.78 2.65 0.70 792 3.64

25

20 4.29 2.49 0.58 756 4.11 2.39 0.58 801 3.99 2.31 0.58 819 3.85

25

22 4.46 2.05 0.46 783 4.31 1.98 0.46 833 4.20 1.93 0.46 855 4.03

25

24 4.69 1.59 0.34 819 4.52 1.53 0.34 864 4.41 1.50 0.34 891 4.27

26

18 4.11 3.04 0.74 720 3.94 2.91 0.74 756 3.78 2.80 0.74 792 3.64

26

20 4.29 2.66 0.62 756 4.11 2.55 0.62 801 3.99 2.47 0.62 819 3.85

26

22 4.46 2.23 0.50 783 4.31 2.15 0.50 833 4.20 2.10 0.50 855 4.03

26

24 4.69 1.78 0.38 819 4.52 1.72 0.38 864 4.41 1.68 0.38 891 4.27

26

26 4.83 1.26 0.26 864 4.69 1.22 0.26 909 4.62 1.20 0.26 936 4.48

27

18 4.11 3.21 0.78 720 3.94 3.07 0.78 756 3.78 2.95 0.78 792 3.64

27

20 4.29 2.83 0.66 756 4.11 2.71 0.66 801 3.99 2.63 0.66 819 3.85

27

22 4.46 2.41 0.54 783 4.31 2.32 0.54 833 4.20 2.27 0.54 855 4.03

27

24 4.69 1.97 0.42 819 4.52 1.90 0.42 864 4.41 1.85 0.42 891 4.27

27

26 4.83 1.45 0.30 864 4.69 1.41 0.30 909 4.62 1.39 0.30 936 4.48

28

18 4.11 3.37 0.82 720 3.94 3.23 0.82 756 3.78 3.10 0.82 792 3.64

28

20 4.29 3.00 0.70 756 4.11 2.88 0.70 801 3.99 2.79 0.70 819 3.85

28

22 4.46 2.59 0.58 783 4.31 2.50 0.58 833 4.20 2.44 0.58 855 4.03

28

24 4.69 2.16 0.46 819 4.52 2.08 0.46 864 4.41 2.03 0.46 891 4.27

28

26 4.83 1.64 0.34 864 4.69 1.59 0.34 909 4.62 1.57 0.34 936 4.48

29

18 4.11 3.54 0.86 720 3.94 3.39 0.86 756 3.78 3.25 0.86 792 3.64

29

20 4.29 3.17 0.74 756 4.11 3.04 0.74 801 3.99 2.95 0.74 819 3.85

29

22 4.46 2.77 0.62 783 4.31 2.67 0.62 833 4.20 2.60 0.62 855 4.03

29

24 4.69 2.34 0.50 819 4.52 2.26 0.50 864 4.41 2.20 0.50 891 4.27

29

26 4.83 1.84 0.38 864 4.69 1.78 0.38 909 4.62 1.76 0.38 936 4.48

30

18 4.11 3.70 0.90 720 3.94 3.54 0.90 756 3.78 3.40 0.90 792 3.64

30

20 4.29 3.34 0.78 756 4.11 3.21 0.78 801 3.99 3.11 0.78 819 3.85

30

22 4.46 2.95 0.66 783 4.31 2.84 0.66 833 4.20 2.77 0.66 855 4.03

30

24 4.69 2.53 0.54 819 4.52 2.44 0.54 864 4.41 2.38 0.54 891 4.27

30

26 4.83 2.03 0.42 864 4.69 1.97 0.42 909 4.62 1.94 0.42 936 4.48

31

18 4.11 3.87 0.94 720 3.94 3.70 0.94 756 3.78 3.55 0.94 792 3.64

31

20 4.29 3.52 0.82 756 4.11 3.37 0.82 801 3.99 3.27 0.82 819 3.85

31

22 4.46 3.12 0.70 783 4.31 3.01 0.70 833 4.20 2.94 0.70 855 4.03

31

24 4.69 2.72 0.58 819 4.52 2.62 0.58 864 4.41 2.56 0.58 891 4.27

31

26 4.83 2.22 0.46 864 4.69 2.16 0.46 909 4.62 2.13 0.46 936 4.48

32

18 4.11 4.03 0.98 720 3.94 3.86 0.98 756 3.78 3.70 0.98 792 3.64

32

20 4.29 3.69 0.86 756 4.11 3.54 0.86 801 3.99 3.43 0.86 819 3.85

32

22 4.46 3.30 0.74 783 4.31 3.19 0.74 833 4.20 3.11 0.74 855 4.03

32

24 4.69 2.91 0.62 819 4.52 2.80 0.62 864 4.41 2.73 0.62 891 4.27

32

26 4.83 2.41 0.50 864 4.69 2.34 0.50 909 4.62 2.31 0.50 936 4.48

NOTE Q : Total capacity (kW)

SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

30 SHC SHF 1.97 0.54 1.62 0.42 2.11 0.58 1.77 0.46 1.37 0.34 2.26 0.62 1.92 0.50 1.53 0.38 2.40 0.66 2.08 0.54 1.69 0.42 1.28 0.30 2.55 0.70 2.23 0.58 1.85 0.46 1.45 0.34 2.69 0.74 2.39 0.62 2.01 0.50 1.62 0.38 1.16 0.26 2.84 0.78 2.54 0.66 2.17 0.54 1.79 0.42 1.34 0.30 2.98 0.82 2.69 0.70 2.33 0.58 1.96 0.46 1.52 0.34 3.13 0.86 2.85 0.74 2.50 0.62 2.13 0.50 1.70 0.38 3.28 0.90 3.00 0.78 2.66 0.66 2.31 0.54 1.88 0.42 3.42 0.94 3.16 0.82 2.82 0.70 2.48 0.58 2.06 0.46 3.57 0.98 3.31 0.86 2.98 0.74 2.65 0.62 2.24 0.50

INPUT 828 855 828 855 891 828 855 891 828 855 891 936 828 855 891 936 828 855 891 936 963 828 855 891 936 963 828 855 891 936 963 828 855 891 936 963 828 855 891 936 963 828 855 891 936 963 828 855 891 936 963

22
OBH895

PERFORMANCE DATA COOL operation at Rated frequency

MUFZ-KW35VGHZ

CAPACITY: 3.5 kW

SHF: 0.72

INPUT: 900 W

OUTDOOR DB (°C)

INDOOR INDOOR DB (°C) WB (°C)

35

40

46

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT

21

18 3.43 1.85 0.54 882 3.15 1.70 0.54 936 2.91 1.57 0.54 972

21

20 3.61 1.51 0.42 918 3.36 1.41 0.42 963 3.12 1.31 0.42 1017

22

18 3.43 1.99 0.58 882 3.15 1.83 0.58 936 2.91 1.68 0.58 972

22

20 3.61 1.66 0.46 918 3.36 1.55 0.46 963 3.12 1.43 0.46 1017

22

22 3.82 1.30 0.34 954 3.57 1.21 0.34 1008 3.33 1.13 0.34 1044

23

18 3.43 2.13 0.62 882 3.15 1.95 0.62 936 2.91 1.80 0.62 972

23

20 3.61 1.80 0.50 918 3.36 1.68 0.50 963 3.12 1.56 0.50 1017

23

22 3.82 1.45 0.38 954 3.57 1.36 0.38 1008 3.33 1.26 0.38 1044

24

18 3.43 2.26 0.66 882 3.15 2.08 0.66 936 2.91 1.92 0.66 972

24

20 3.61 1.95 0.54 918 3.36 1.81 0.54 963 3.12 1.68 0.54 1017

24

22 3.82 1.60 0.42 954 3.57 1.50 0.42 1008 3.33 1.40 0.42 1044

24

24 4.03 1.21 0.30 990 3.78 1.13 0.30 1035 3.57 1.07 0.30 1080

25

18 3.43 2.40 0.70 882 3.15 2.20 0.70 936 2.91 2.03 0.70 972

25

20 3.61 2.09 0.58 918 3.36 1.95 0.58 963 3.12 1.81 0.58 1017

25

22 3.82 1.75 0.46 954 3.57 1.64 0.46 1008 3.33 1.53 0.46 1044

25

24 4.03 1.37 0.34 990 3.78 1.29 0.34 1035 3.57 1.21 0.34 1080

26

18 3.43 2.54 0.74 882 3.15 2.33 0.74 936 2.91 2.15 0.74 972

26

20 3.61 2.23 0.62 918 3.36 2.08 0.62 963 3.12 1.93 0.62 1017

26

22 3.82 1.91 0.50 954 3.57 1.78 0.50 1008 3.33 1.66 0.50 1044

26

24 4.03 1.53 0.38 990 3.78 1.44 0.38 1035 3.57 1.36 0.38 1080

26

26 4.24 1.10 0.26 1026 3.99 1.04 0.26 1071 3.75 0.97 0.26 1116

27

18 3.43 2.68 0.78 882 3.15 2.46 0.78 936 2.91 2.27 0.78 972

27

20 3.61 2.38 0.66 918 3.36 2.22 0.66 963 3.12 2.06 0.66 1017

27

22 3.82 2.06 0.54 954 3.57 1.93 0.54 1008 3.33 1.80 0.54 1044

27

24 4.03 1.69 0.42 990 3.78 1.59 0.42 1035 3.57 1.50 0.42 1080

27

26 4.24 1.27 0.30 1026 3.99 1.20 0.30 1071 3.75 1.12 0.30 1116

28

18 3.43 2.81 0.82 882 3.15 2.58 0.82 936 2.91 2.38 0.82 972

28

20 3.61 2.52 0.70 918 3.36 2.35 0.70 963 3.12 2.18 0.70 1017

28

22 3.82 2.21 0.58 954 3.57 2.07 0.58 1008 3.33 1.93 0.58 1044

28

24 4.03 1.85 0.46 990 3.78 1.74 0.46 1035 3.57 1.64 0.46 1080

28

26 4.24 1.44 0.34 1026 3.99 1.36 0.34 1071 3.75 1.27 0.34 1116

29

18 3.43 2.95 0.86 882 3.15 2.71 0.86 936 2.91 2.50 0.86 972

29

20 3.61 2.67 0.74 918 3.36 2.49 0.74 963 3.12 2.30 0.74 1017

29

22 3.82 2.37 0.62 954 3.57 2.21 0.62 1008 3.33 2.06 0.62 1044

29

24 4.03 2.01 0.50 990 3.78 1.89 0.50 1035 3.57 1.78 0.50 1080

29

26 4.24 1.61 0.38 1026 3.99 1.52 0.38 1071 3.75 1.42 0.38 1116

30

18 3.43 3.09 0.90 882 3.15 2.83 0.90 936 2.91 2.61 0.90 972

30

20 3.61 2.81 0.78 918 3.36 2.62 0.78 963 3.12 2.43 0.78 1017

30

22 3.82 2.52 0.66 954 3.57 2.36 0.66 1008 3.33 2.19 0.66 1044

30

24 4.03 2.17 0.54 990 3.78 2.04 0.54 1035 3.57 1.93 0.54 1080

30

26 4.24 1.78 0.42 1026 3.99 1.68 0.42 1071 3.75 1.57 0.42 1116

31

18 3.43 3.22 0.94 882 3.15 2.96 0.94 936 2.91 2.73 0.94 972

31

20 3.61 2.96 0.82 918 3.36 2.76 0.82 963 3.12 2.55 0.82 1017

31

22 3.82 2.67 0.70 954 3.57 2.50 0.70 1008 3.33 2.33 0.70 1044

31

24 4.03 2.33 0.58 990 3.78 2.19 0.58 1035 3.57 2.07 0.58 1080

31

26 4.24 1.95 0.46 1026 3.99 1.84 0.46 1071 3.75 1.72 0.46 1116

32

18 3.43 3.36 0.98 882 3.15 3.09 0.98 936 2.91 2.85 0.98 972

32

20 3.61 3.10 0.86 918 3.36 2.89 0.86 963 3.12 2.68 0.86 1017

32

22 3.82 2.82 0.74 954 3.57 2.64 0.74 1008 3.33 2.46 0.74 1044

32

24 4.03 2.50 0.62 990 3.78 2.34 0.62 1035 3.57 2.21 0.62 1080

32

26 4.24 2.12 0.50 1026 3.99 1.99 0.50 1071 3.75 1.87 0.50 1116

NOTE Q : Total capacity (kW)

SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

23
OBH895

PERFORMANCE DATA COOL operation at Rated frequency

MUFZ-KW50VGHZ

CAPACITY: 5.0 kW

SHF: 0.70

INPUT: 1360 W

OUTDOOR DB (°C)

INDOOR INDOOR DB (°C) WB (°C)

21

25

27

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q

21

18 5.88 3.05 0.52 1088 5.63 2.92 0.52 1142 5.40 2.81 0.52 1197 5.20

21

20 6.13 2.45 0.40 1142 5.88 2.35 0.40 1210 5.70 2.28 0.40 1238 5.50

22

18 5.88 3.29 0.56 1088 5.63 3.15 0.56 1142 5.40 3.02 0.56 1197 5.20

22

20 6.13 2.69 0.44 1142 5.88 2.58 0.44 1210 5.70 2.51 0.44 1238 5.50

22

22 6.38 2.04 0.32 1183 6.15 1.96 0.32 1258 6.00 1.92 0.32 1292 5.75

23

18 5.88 3.52 0.60 1088 5.63 3.37 0.60 1142 5.40 3.24 0.60 1197 5.20

23

20 6.13 2.94 0.48 1142 5.88 2.82 0.48 1210 5.70 2.73 0.48 1238 5.50

23

22 6.38 2.29 0.36 1183 6.15 2.21 0.36 1258 6.00 2.16 0.36 1292 5.75

24

18 5.88 3.76 0.64 1088 5.63 3.60 0.64 1142 5.40 3.45 0.64 1197 5.20

24

20 6.13 3.18 0.52 1142 5.88 3.05 0.52 1210 5.70 2.96 0.52 1238 5.50

24

22 6.38 2.55 0.40 1183 6.15 2.46 0.40 1258 6.00 2.40 0.40 1292 5.75

24

24 6.70 1.87 0.28 1238 6.45 1.80 0.28 1306 6.30 1.76 0.28 1346 6.10

25

18 5.88 3.99 0.68 1088 5.63 3.82 0.68 1142 5.40 3.67 0.68 1197 5.20

25

20 6.13 3.43 0.56 1142 5.88 3.29 0.56 1210 5.70 3.19 0.56 1238 5.50

25

22 6.38 2.80 0.44 1183 6.15 2.70 0.44 1258 6.00 2.64 0.44 1292 5.75

25

24 6.70 2.14 0.32 1238 6.45 2.06 0.32 1306 6.30 2.01 0.32 1346 6.10

26

18 5.88 4.23 0.72 1088 5.63 4.05 0.72 1142 5.40 3.89 0.72 1197 5.20

26

20 6.13 3.67 0.60 1142 5.88 3.52 0.60 1210 5.70 3.42 0.60 1238 5.50

26

22 6.38 3.06 0.48 1183 6.15 2.95 0.48 1258 6.00 2.88 0.48 1292 5.75

26

24 6.70 2.41 0.36 1238 6.45 2.32 0.36 1306 6.30 2.26 0.36 1346 6.10

26

26 6.90 1.65 0.24 1306 6.70 1.60 0.24 1374 6.60 1.58 0.24 1414 6.40

27

18 5.88 4.46 0.76 1088 5.63 4.27 0.76 1142 5.40 4.10 0.76 1197 5.20

27

20 6.13 3.92 0.64 1142 5.88 3.76 0.64 1210 5.70 3.65 0.64 1238 5.50

27

22 6.38 3.31 0.52 1183 6.15 3.19 0.52 1258 6.00 3.12 0.52 1292 5.75

27

24 6.70 2.68 0.40 1238 6.45 2.58 0.40 1306 6.30 2.52 0.40 1346 6.10

27

26 6.90 1.93 0.28 1306 6.70 1.87 0.28 1374 6.60 1.84 0.28 1414 6.40

28

18 5.88 4.70 0.80 1088 5.63 4.50 0.80 1142 5.40 4.32 0.80 1197 5.20

28

20 6.13 4.16 0.68 1142 5.88 3.99 0.68 1210 5.70 3.87 0.68 1238 5.50

28

22 6.38 3.57 0.56 1183 6.15 3.44 0.56 1258 6.00 3.36 0.56 1292 5.75

28

24 6.70 2.94 0.44 1238 6.45 2.83 0.44 1306 6.30 2.77 0.44 1346 6.10

28

26 6.90 2.20 0.32 1306 6.70 2.14 0.32 1374 6.60 2.11 0.32 1414 6.40

29

18 5.88 4.93 0.84 1088 5.63 4.72 0.84 1142 5.40 4.53 0.84 1197 5.20

29

20 6.13 4.41 0.72 1142 5.88 4.23 0.72 1210 5.70 4.10 0.72 1238 5.50

29

22 6.38 3.82 0.60 1183 6.15 3.69 0.60 1258 6.00 3.60 0.60 1292 5.75

29

24 6.70 3.21 0.48 1238 6.45 3.09 0.48 1306 6.30 3.02 0.48 1346 6.10

29

26 6.90 2.48 0.36 1306 6.70 2.41 0.36 1374 6.60 2.37 0.36 1414 6.40

30

18 5.88 5.17 0.88 1088 5.63 4.95 0.88 1142 5.40 4.75 0.88 1197 5.20

30

20 6.13 4.65 0.76 1142 5.88 4.46 0.76 1210 5.70 4.33 0.76 1238 5.50

30

22 6.38 4.08 0.64 1183 6.15 3.93 0.64 1258 6.00 3.84 0.64 1292 5.75

30

24 6.70 3.48 0.52 1238 6.45 3.35 0.52 1306 6.30 3.27 0.52 1346 6.10

30

26 6.90 2.76 0.40 1306 6.70 2.68 0.40 1374 6.60 2.64 0.40 1414 6.40

31

18 5.88 5.40 0.92 1088 5.63 5.17 0.92 1142 5.40 4.97 0.92 1197 5.20

31

20 6.13 4.90 0.80 1142 5.88 4.70 0.80 1210 5.70 4.56 0.80 1238 5.50

31

22 6.38 4.33 0.68 1183 6.15 4.18 0.68 1258 6.00 4.08 0.68 1292 5.75

31

24 6.70 3.75 0.56 1238 6.45 3.61 0.56 1306 6.30 3.52 0.56 1346 6.10

31

26 6.90 3.03 0.44 1306 6.70 2.94 0.44 1374 6.60 2.90 0.44 1414 6.40

32

18 5.88 5.64 0.96 1088 5.63 5.40 0.96 1142 5.40 5.18 0.96 1197 5.20

32

20 6.13 5.14 0.84 1142 5.88 4.93 0.84 1210 5.70 4.79 0.84 1238 5.50

32

22 6.38 4.59 0.72 1183 6.15 4.42 0.72 1258 6.00 4.32 0.72 1292 5.75

32

24 6.70 4.02 0.60 1238 6.45 3.87 0.60 1306 6.30 3.78 0.60 1346 6.10

32

26 6.90 3.31 0.48 1306 6.70 3.21 0.48 1374 6.60 3.16 0.48 1414 6.40

NOTE Q : Total capacity (kW)

SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

30 SHC SHF 2.70 0.52 2.20 0.40 2.91 0.56 2.42 0.44 1.84 0.32 3.12 0.60 2.64 0.48 2.07 0.36 3.33 0.64 2.86 0.52 2.30 0.40 1.71 0.28 3.53 0.68 3.08 0.56 2.53 0.44 1.95 0.32 3.74 0.72 3.30 0.60 2.76 0.48 2.19 0.36 1.53 0.24 3.95 0.76 3.52 0.64 2.99 0.52 2.44 0.40 1.79 0.28 4.16 0.80 3.74 0.68 3.22 0.56 2.68 0.44 2.04 0.32 4.37 0.84 3.96 0.72 3.45 0.60 2.93 0.48 2.30 0.36 4.57 0.88 4.18 0.76 3.68 0.64 3.17 0.52 2.56 0.40 4.78 0.92 4.40 0.80 3.91 0.68 3.41 0.56 2.81 0.44 4.99 0.96 4.62 0.84 4.14 0.72 3.66 0.60 3.07 0.48

INPUT 1251 1292 1251 1292 1346 1251 1292 1346 1251 1292 1346 1414 1251 1292 1346 1414 1251 1292 1346 1414 1455 1251 1292 1346 1414 1455 1251 1292 1346 1414 1455 1251 1292 1346 1414 1455 1251 1292 1346 1414 1455 1251 1292 1346 1414 1455 1251 1292 1346 1414 1455

24
OBH895

PERFORMANCE DATA COOL operation at Rated frequency

MUFZ-KW50VGHZ

CAPACITY: 5.0 kW

SHF: 0.70

INPUT: 1360 W

OUTDOOR DB (°C)

INDOOR INDOOR DB (°C) WB (°C)

35

40

46

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT

21

18 4.90 2.55 0.52 1333 4.50 2.34 0.52 1414 4.15 2.16 0.52 1469

21

20 5.15 2.06 0.40 1387 4.80 1.92 0.40 1455 4.45 1.78 0.40 1537

22

18 4.90 2.74 0.56 1333 4.50 2.52 0.56 1414 4.15 2.32 0.56 1469

22

20 5.15 2.26 0.44 1387 4.80 2.11 0.44 1455 4.45 1.96 0.44 1537

22

22 5.45 1.74 0.32 1442 5.10 1.63 0.32 1523 4.75 1.52 0.32 1578

23

18 4.90 2.94 0.60 1333 4.50 2.70 0.60 1414 4.15 2.49 0.60 1469

23

20 5.15 2.47 0.48 1387 4.80 2.30 0.48 1455 4.45 2.13 0.48 1537

23

22 5.45 1.96 0.36 1442 5.10 1.83 0.36 1523 4.75 1.71 0.36 1578

24

18 4.90 3.13 0.64 1333 4.50 2.88 0.64 1414 4.15 2.65 0.64 1469

24

20 5.15 2.68 0.52 1387 4.80 2.49 0.52 1455 4.45 2.31 0.52 1537

24

22 5.45 2.18 0.40 1442 5.10 2.04 0.40 1523 4.75 1.90 0.40 1578

24

24 5.75 1.61 0.28 1496 5.40 1.51 0.28 1564 5.10 1.43 0.28 1632

25

18 4.90 3.33 0.68 1333 4.50 3.06 0.68 1414 4.15 2.82 0.68 1469

25

20 5.15 2.88 0.56 1387 4.80 2.69 0.56 1455 4.45 2.49 0.56 1537

25

22 5.45 2.40 0.44 1442 5.10 2.24 0.44 1523 4.75 2.09 0.44 1578

25

24 5.75 1.84 0.32 1496 5.40 1.73 0.32 1564 5.10 1.63 0.32 1632

26

18 4.90 3.53 0.72 1333 4.50 3.24 0.72 1414 4.15 2.99 0.72 1469

26

20 5.15 3.09 0.60 1387 4.80 2.88 0.60 1455 4.45 2.67 0.60 1537

26

22 5.45 2.61 0.48 1442 5.10 2.45 0.48 1523 4.75 2.28 0.48 1578

26

24 5.75 2.07 0.36 1496 5.40 1.94 0.36 1564 5.10 1.83 0.36 1632

26

26 6.05 1.45 0.24 1550 5.70 1.37 0.24 1618 5.35 1.28 0.24 1686

27

18 4.90 3.72 0.76 1333 4.50 3.42 0.76 1414 4.15 3.15 0.76 1469

27

20 5.15 3.29 0.64 1387 4.80 3.07 0.64 1455 4.45 2.85 0.64 1537

27

22 5.45 2.83 0.52 1442 5.10 2.65 0.52 1523 4.75 2.47 0.52 1578

27

24 5.75 2.30 0.40 1496 5.40 2.16 0.40 1564 5.10 2.04 0.40 1632

27

26 6.05 1.69 0.28 1550 5.70 1.59 0.28 1618 5.35 1.50 0.28 1686

28

18 4.90 3.92 0.80 1333 4.50 3.60 0.80 1414 4.15 3.32 0.80 1469

28

20 5.15 3.50 0.68 1387 4.80 3.26 0.68 1455 4.45 3.02 0.68 1537

28

22 5.45 3.05 0.56 1442 5.10 2.85 0.56 1523 4.75 2.66 0.56 1578

28

24 5.75 2.53 0.44 1496 5.40 2.37 0.44 1564 5.10 2.24 0.44 1632

28

26 6.05 1.93 0.32 1550 5.70 1.82 0.32 1618 5.35 1.71 0.32 1686

29

18 4.90 4.11 0.84 1333 4.50 3.78 0.84 1414 4.15 3.48 0.84 1469

29

20 5.15 3.71 0.72 1387 4.80 3.45 0.72 1455 4.45 3.20 0.72 1537

29

22 5.45 3.27 0.60 1442 5.10 3.06 0.60 1523 4.75 2.85 0.60 1578

29

24 5.75 2.76 0.48 1496 5.40 2.59 0.48 1564 5.10 2.45 0.48 1632

29

26 6.05 2.18 0.36 1550 5.70 2.05 0.36 1618 5.35 1.92 0.36 1686

30

18 4.90 4.31 0.88 1333 4.50 3.96 0.88 1414 4.15 3.65 0.88 1469

30

20 5.15 3.91 0.76 1387 4.80 3.65 0.76 1455 4.45 3.38 0.76 1537

30

22 5.45 3.49 0.64 1442 5.10 3.26 0.64 1523 4.75 3.04 0.64 1578

30

24 5.75 2.99 0.52 1496 5.40 2.81 0.52 1564 5.10 2.65 0.52 1632

30

26 6.05 2.42 0.40 1550 5.70 2.28 0.40 1618 5.35 2.14 0.40 1686

31

18 4.90 4.51 0.92 1333 4.50 4.14 0.92 1414 4.15 3.82 0.92 1469

31

20 5.15 4.12 0.80 1387 4.80 3.84 0.80 1455 4.45 3.56 0.80 1537

31

22 5.45 3.70 0.68 1442 5.10 3.47 0.68 1523 4.75 3.23 0.68 1578

31

24 5.75 3.22 0.56 1496 5.40 3.02 0.56 1564 5.10 2.85 0.56 1632

31

26 6.05 2.66 0.44 1550 5.70 2.51 0.44 1618 5.35 2.35 0.44 1686

32

18 4.90 4.70 0.96 1333 4.50 4.32 0.96 1414 4.15 3.98 0.96 1469

32

20 5.15 4.32 0.84 1387 4.80 4.03 0.84 1455 4.45 3.74 0.84 1537

32

22 5.45 3.92 0.72 1442 5.10 3.67 0.72 1523 4.75 3.42 0.72 1578

32

24 5.75 3.45 0.60 1496 5.40 3.24 0.60 1564 5.10 3.06 0.60 1632

32

26 6.05 2.90 0.48 1550 5.70 2.73 0.48 1618 5.35 2.57 0.48 1686

NOTE Q : Total capacity (kW)

SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

25
OBH895

PERFORMANCE DATA COOL operation at Rated frequency

MUFZ-KW60VGHZ

CAPACITY: 6.1 kW

SHF: 0.74

INPUT: 1730 W

OUTDOOR DB (°C)

INDOOR INDOOR DB (°C) WB (°C)

21

25

27

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q

21

18 7.17 4.03 0.56 1384 6.86 3.86 0.56 1453 6.59 3.70 0.56 1522 6.34

21

20 7.47 3.30 0.44 1453 7.17 3.17 0.44 1540 6.95 3.07 0.44 1574 6.71

22

18 7.17 4.32 0.60 1384 6.86 4.13 0.60 1453 6.59 3.97 0.60 1522 6.34

22

20 7.47 3.60 0.48 1453 7.17 3.46 0.48 1540 6.95 3.35 0.48 1574 6.71

22

22 7.78 2.82 0.36 1505 7.50 2.72 0.36 1600 7.32 2.65 0.36 1644 7.02

23

18 7.17 4.60 0.64 1384 6.86 4.41 0.64 1453 6.59 4.23 0.64 1522 6.34

23

20 7.47 3.90 0.52 1453 7.17 3.74 0.52 1540 6.95 3.63 0.52 1574 6.71

23

22 7.78 3.13 0.40 1505 7.50 3.02 0.40 1600 7.32 2.94 0.40 1644 7.02

24

18 7.17 4.89 0.68 1384 6.86 4.68 0.68 1453 6.59 4.49 0.68 1522 6.34

24

20 7.47 4.20 0.56 1453 7.17 4.03 0.56 1540 6.95 3.91 0.56 1574 6.71

24

22 7.78 3.44 0.44 1505 7.50 3.32 0.44 1600 7.32 3.24 0.44 1644 7.02

24

24 8.17 2.63 0.32 1574 7.87 2.53 0.32 1661 7.69 2.48 0.32 1713 7.44

25

18 7.17 5.18 0.72 1384 6.86 4.96 0.72 1453 6.59 4.76 0.72 1522 6.34

25

20 7.47 4.50 0.60 1453 7.17 4.32 0.60 1540 6.95 4.19 0.60 1574 6.71

25

22 7.78 3.75 0.48 1505 7.50 3.62 0.48 1600 7.32 3.53 0.48 1644 7.02

25

24 8.17 2.96 0.36 1574 7.87 2.85 0.36 1661 7.69 2.78 0.36 1713 7.44

26

18 7.17 5.46 0.76 1384 6.86 5.23 0.76 1453 6.59 5.02 0.76 1522 6.34

26

20 7.47 4.80 0.64 1453 7.17 4.60 0.64 1540 6.95 4.47 0.64 1574 6.71

26

22 7.78 4.06 0.52 1505 7.50 3.92 0.52 1600 7.32 3.82 0.52 1644 7.02

26

24 8.17 3.29 0.40 1574 7.87 3.16 0.40 1661 7.69 3.09 0.40 1713 7.44

26

26 8.42 2.37 0.28 1661 8.17 2.31 0.28 1747 8.05 2.27 0.28 1799 7.81

27

18 7.17 5.75 0.80 1384 6.86 5.50 0.80 1453 6.59 5.28 0.80 1522 6.34

27

20 7.47 5.10 0.68 1453 7.17 4.89 0.68 1540 6.95 4.74 0.68 1574 6.71

27

22 7.78 4.37 0.56 1505 7.50 4.22 0.56 1600 7.32 4.11 0.56 1644 7.02

27

24 8.17 3.61 0.44 1574 7.87 3.48 0.44 1661 7.69 3.40 0.44 1713 7.44

27

26 8.42 2.71 0.32 1661 8.17 2.63 0.32 1747 8.05 2.59 0.32 1799 7.81

28

18 7.17 6.04 0.84 1384 6.86 5.78 0.84 1453 6.59 5.55 0.84 1522 6.34

28

20 7.47 5.40 0.72 1453 7.17 5.18 0.72 1540 6.95 5.02 0.72 1574 6.71

28

22 7.78 4.68 0.60 1505 7.50 4.52 0.60 1600 7.32 4.41 0.60 1644 7.02

28

24 8.17 3.94 0.48 1574 7.87 3.79 0.48 1661 7.69 3.71 0.48 1713 7.44

28

26 8.42 3.05 0.36 1661 8.17 2.96 0.36 1747 8.05 2.92 0.36 1799 7.81

29

18 7.17 6.32 0.88 1384 6.86 6.05 0.88 1453 6.59 5.81 0.88 1522 6.34

29

20 7.47 5.69 0.76 1453 7.17 5.46 0.76 1540 6.95 5.30 0.76 1574 6.71

29

22 7.78 4.99 0.64 1505 7.50 4.82 0.64 1600 7.32 4.70 0.64 1644 7.02

29

24 8.17 4.27 0.52 1574 7.87 4.11 0.52 1661 7.69 4.01 0.52 1713 7.44

29

26 8.42 3.38 0.40 1661 8.17 3.29 0.40 1747 8.05 3.24 0.40 1799 7.81

30

18 7.17 6.61 0.92 1384 6.86 6.33 0.92 1453 6.59 6.07 0.92 1522 6.34

30

20 7.47 5.99 0.80 1453 7.17 5.75 0.80 1540 6.95 5.58 0.80 1574 6.71

30

22 7.78 5.31 0.68 1505 7.50 5.12 0.68 1600 7.32 4.99 0.68 1644 7.02

30

24 8.17 4.59 0.56 1574 7.87 4.42 0.56 1661 7.69 4.32 0.56 1713 7.44

30

26 8.42 3.72 0.44 1661 8.17 3.61 0.44 1747 8.05 3.56 0.44 1799 7.81

31

18 7.17 6.90 0.96 1384 6.86 6.60 0.96 1453 6.59 6.34 0.96 1522 6.34

31

20 7.47 6.29 0.84 1453 7.17 6.04 0.84 1540 6.95 5.86 0.84 1574 6.71

31

22 7.78 5.62 0.72 1505 7.50 5.42 0.72 1600 7.32 5.29 0.72 1644 7.02

31

24 8.17 4.92 0.60 1574 7.87 4.74 0.60 1661 7.69 4.63 0.60 1713 7.44

31

26 8.42 4.06 0.48 1661 8.17 3.94 0.48 1747 8.05 3.88 0.48 1799 7.81

32

18 7.17 7.17 1.00 1384 6.86 6.86 1.00 1453 6.59 6.59 1.00 1522 6.34

32

20 7.47 6.59 0.88 1453 7.17 6.32 0.88 1540 6.95 6.13 0.88 1574 6.71

32

22 7.78 5.93 0.76 1505 7.50 5.72 0.76 1600 7.32 5.58 0.76 1644 7.02

32

24 8.17 5.25 0.64 1574 7.87 5.05 0.64 1661 7.69 4.94 0.64 1713 7.44

32

26 8.42 4.40 0.52 1661 8.17 4.27 0.52 1747 8.05 4.20 0.52 1799 7.81

NOTE Q : Total capacity (kW)

SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

30 SHC SHF 3.57 0.56 2.97 0.44 3.82 0.60 3.23 0.48 2.54 0.36 4.07 0.64 3.50 0.52 2.82 0.40 4.33 0.68 3.77 0.56 3.10 0.44 2.40 0.32 4.58 0.72 4.04 0.60 3.38 0.48 2.69 0.36 4.83 0.76 4.31 0.64 3.66 0.52 2.99 0.40 2.20 0.28 5.09 0.80 4.58 0.68 3.94 0.56 3.29 0.44 2.51 0.32 5.34 0.84 4.85 0.72 4.22 0.60 3.59 0.48 2.83 0.36 5.60 0.88 5.11 0.76 4.50 0.64 3.89 0.52 3.14 0.40 5.85 0.92 5.38 0.80 4.78 0.68 4.18 0.56 3.45 0.44 6.10 0.96 5.65 0.84 5.07 0.72 4.48 0.60 3.76 0.48 6.34 1.00 5.92 0.88 5.35 0.76 4.78 0.64 4.08 0.52

INPUT 1592 1644 1592 1644 1713 1592 1644 1713 1592 1644 1713 1799 1592 1644 1713 1799 1592 1644 1713 1799 1851 1592 1644 1713 1799 1851 1592 1644 1713 1799 1851 1592 1644 1713 1799 1851 1592 1644 1713 1799 1851 1592 1644 1713 1799 1851 1592 1644 1713 1799 1851

26
OBH895

PERFORMANCE DATA COOL operation at Rated frequency

MUFZ-KW60VGHZ

CAPACITY: 6.1 kW

SHF: 0.74

INPUT: 1730 W

OUTDOOR DB (°C)

INDOOR INDOOR DB (°C) WB (°C)

35

40

46

Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT

21

18 5.98 3.36 0.56 1695 5.49 3.09 0.56 1799 5.06 2.85 0.56 1868

21

20 6.28 2.78 0.44 1765 5.86 2.59 0.44 1851 5.43 2.40 0.44 1955

22

18 5.98 3.60 0.60 1695 5.49 3.31 0.60 1799 5.06 3.05 0.60 1868

22

20 6.28 3.03 0.48 1765 5.86 2.82 0.48 1851 5.43 2.62 0.48 1955

22

22 6.65 2.41 0.36 1834 6.22 2.25 0.36 1938 5.80 2.10 0.36 2007

23

18 5.98 3.84 0.64 1695 5.49 3.53 0.64 1799 5.06 3.25 0.64 1868

23

20 6.28 3.28 0.52 1765 5.86 3.06 0.52 1851 5.43 2.83 0.52 1955

23

22 6.65 2.67 0.40 1834 6.22 2.50 0.40 1938 5.80 2.33 0.40 2007

24

18 5.98 4.08 0.68 1695 5.49 3.74 0.68 1799 5.06 3.45 0.68 1868

24

20 6.28 3.53 0.56 1765 5.86 3.29 0.56 1851 5.43 3.05 0.56 1955

24

22 6.65 2.94 0.44 1834 6.22 2.75 0.44 1938 5.80 2.56 0.44 2007

24

24 7.02 2.26 0.32 1903 6.59 2.12 0.32 1990 6.22 2.00 0.32 2076

25

18 5.98 4.32 0.72 1695 5.49 3.96 0.72 1799 5.06 3.66 0.72 1868

25

20 6.28 3.78 0.60 1765 5.86 3.53 0.60 1851 5.43 3.27 0.60 1955

25

22 6.65 3.21 0.48 1834 6.22 3.00 0.48 1938 5.80 2.79 0.48 2007

25

24 7.02 2.54 0.36 1903 6.59 2.39 0.36 1990 6.22 2.25 0.36 2076

26

18 5.98 4.56 0.76 1695 5.49 4.18 0.76 1799 5.06 3.86 0.76 1868

26

20 6.28 4.03 0.64 1765 5.86 3.76 0.64 1851 5.43 3.49 0.64 1955

26

22 6.65 3.47 0.52 1834 6.22 3.25 0.52 1938 5.80 3.03 0.52 2007

26

24 7.02 2.82 0.40 1903 6.59 2.65 0.40 1990 6.22 2.50 0.40 2076

26

26 7.38 2.08 0.28 1972 6.95 1.96 0.28 2059 6.53 1.84 0.28 2145

27

18 5.98 4.79 0.80 1695 5.49 4.40 0.80 1799 5.06 4.06 0.80 1868

27

20 6.28 4.29 0.68 1765 5.86 3.99 0.68 1851 5.43 3.70 0.68 1955

27

22 6.65 3.74 0.56 1834 6.22 3.50 0.56 1938 5.80 3.26 0.56 2007

27

24 7.02 3.10 0.44 1903 6.59 2.91 0.44 1990 6.22 2.75 0.44 2076

27

26 7.38 2.38 0.32 1972 6.95 2.24 0.32 2059 6.53 2.10 0.32 2145

28

18 5.98 5.03 0.84 1695 5.49 4.62 0.84 1799 5.06 4.26 0.84 1868

28

20 6.28 4.54 0.72 1765 5.86 4.23 0.72 1851 5.43 3.92 0.72 1955

28

22 6.65 4.00 0.60 1834 6.22 3.75 0.60 1938 5.80 3.49 0.60 2007

28

24 7.02 3.38 0.48 1903 6.59 3.18 0.48 1990 6.22 3.00 0.48 2076

28

26 7.38 2.67 0.36 1972 6.95 2.52 0.36 2059 6.53 2.36 0.36 2145

29

18 5.98 5.27 0.88 1695 5.49 4.84 0.88 1799 5.06 4.47 0.88 1868

29

20 6.28 4.79 0.76 1765 5.86 4.46 0.76 1851 5.43 4.14 0.76 1955

29

22 6.65 4.27 0.64 1834 6.22 4.00 0.64 1938 5.80 3.72 0.64 2007

29

24 7.02 3.66 0.52 1903 6.59 3.44 0.52 1990 6.22 3.25 0.52 2076

29

26 7.38 2.97 0.40 1972 6.95 2.80 0.40 2059 6.53 2.62 0.40 2145

30

18 5.98 5.51 0.92 1695 5.49 5.06 0.92 1799 5.06 4.67 0.92 1868

30

20 6.28 5.04 0.80 1765 5.86 4.70 0.80 1851 5.43 4.35 0.80 1955

30

22 6.65 4.54 0.68 1834 6.22 4.24 0.68 1938 5.80 3.95 0.68 2007

30

24 7.02 3.94 0.56 1903 6.59 3.70 0.56 1990 6.22 3.50 0.56 2076

30

26 7.38 3.26 0.44 1972 6.95 3.07 0.44 2059 6.53 2.89 0.44 2145

31

18 5.98 5.75 0.96 1695 5.49 5.28 0.96 1799 5.06 4.87 0.96 1868

31

20 6.28 5.29 0.84 1765 5.86 4.93 0.84 1851 5.43 4.57 0.84 1955

31

22 6.65 4.80 0.72 1834 6.22 4.49 0.72 1938 5.80 4.18 0.72 2007

31

24 7.02 4.22 0.60 1903 6.59 3.97 0.60 1990 6.22 3.75 0.60 2076

31

26 7.38 3.56 0.48 1972 6.95 3.35 0.48 2059 6.53 3.15 0.48 2145

32

18 5.98 5.98 1.00 1695 5.49 5.49 1.00 1799 5.06 5.06 1.00 1868

32

20 6.28 5.54 0.88 1765 5.86 5.17 0.88 1851 5.43 4.79 0.88 1955

32

22 6.65 5.07 0.76 1834 6.22 4.74 0.76 1938 5.80 4.42 0.76 2007

32

24 7.02 4.50 0.64 1903 6.59 4.23 0.64 1990 6.22 4.00 0.64 2076

32

26 7.38 3.85 0.52 1972 6.95 3.63 0.52 2059 6.53 3.41 0.52 2145

NOTE Q : Total capacity (kW)

SHF : Sensible heat factor DB : Dry-bulb temperature

SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature

27
OBH895

PERFORMANCE DATA HEAT operation at Rated frequency
MUFZ-KW25VGHZ

CAPACITY: 3.4 kW

INPUT: 830 W

INDOOR DB (°C)
15 21 26

OUTDOOR WB (°C)

-25

-20

-15

-10

-5

0

5

10

15

20

Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT

0.85 224 1.29 332 1.70 432 2.14 540 2.58 647 3.03 730 3.47 789 3.91 838 4.32 863 4.76 880

0.78 241 1.19 349 1.60 457 2.04 581 2.45 689 2.89 764 3.30 822 3.74 863 4.15 888 4.57 921

0.54 266 0.95 374 1.39 498 1.84 623 2.28 730 2.69 805 3.13 863 3.57 905 3.98 930 4.42 955

MUFZ-KW35VGHZ

CAPACITY: 4.3 kW

INPUT: 1210 W

INDOOR DB (°C)
15 21 26

OUTDOOR WB (°C)

-25

-20

-15

-10

-5

0

5

10

15

20

Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT

1.08 327 1.63 484 2.15 629 2.71 787 3.27 944 3.83 1065 4.39 1150 4.95 1222 5.46 1258 6.02 1283

0.99 351 1.51 508 2.02 666 2.58 847 3.10 1004 3.66 1113 4.17 1198 4.73 1258 5.25 1295 5.78 1343

0.69 387 1.20 545 1.76 726 2.32 908 2.88 1065 3.40 1174 3.96 1258 4.52 1319 5.03 1355 5.59 1392

MUFZ-KW50VGHZ

CAPACITY: 6.0 kW

INPUT: 1600 W

INDOOR DB (°C)
15 21 26

OUTDOOR WB (°C)

-25

-20

-15

-10

-5

0

5

10

15

20

Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT

1.50 432 2.28 640 3.00 832 3.78 1040 4.56 1248 5.34 1408 6.12 1520 6.90 1616 7.62 1664 8.40 1696

1.38 464 2.10 672 2.82 880 3.60 1120 4.32 1328 5.10 1472 5.82 1584 6.60 1664 7.32 1712 8.07 1776

0.96 512 1.68 720 2.46 960 3.24 1200 4.02 1408 4.74 1552 5.52 1664 6.30 1744 7.02 1792 7.80 1840

MUFZ-KW60VGHZ

CAPACITY: 6.5 kW

INPUT: 1880 W

INDOOR DB (°C)
15 21 26

OUTDOOR WB (°C)

-25

-20

-15

-10

-5

0

5

10

15

20

Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT

1.63 508 2.47 752 3.25 978 4.10 1222 4.94 1466 5.79 1654 6.63 1786 7.48 1899 8.26 1955 9.10 1993

1.50 545 2.28 790 3.06 1034 3.90 1316 4.68 1560 5.53 1730 6.31 1861 7.15 1955 7.93 2012 8.74 2087

1.04 602 1.82 846 2.67 1128 3.51 1410 4.36 1654 5.14 1824 5.98 1955 6.83 2049 7.61 2106 8.45 2162

NOTE: Q: Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature

28
OBH895

10 ACTUATOR CONTROL

MUFZ-KW25VGHZ MUFZ-KW35VGHZ MUFZ-KW50VGHZ MUFZ-KW60VGHZ
10-1. OUTDOOR FAN MOTOR CONTROL The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.

ON Compressor

5 seconds

15 seconds

OFF

Outdoor fan motor

ON OFF

10-2. R.V. COIL CONTROL Heating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFF Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before startup of the compressor.

5 seconds

5 seconds

ON Compressor OFF

R.V.coil

ON OFF

Outdoor fan ON

motor

OFF

10-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR

Sensor

Purpose

Actuator

Compressor

LEV

Outdoor fan motor

R.V. coil

Indoor fan motor

Defrost heater

Discharge temperature thermistor

Protection

Indoor coil temperature

Cooling: Coil frost prevention

thermistor

Heating: High pressure protection

Defrost thermistor Fin temperature thermistor

Heating: Defrosting Protection

Ambient temperature

Cooling: Low ambient temperature operation

thermistor

Heating: Defrosting (Heater)

Cooling: Low ambient temperaOutdoor heat exchanger tem- ture operation

perature thermistor

Cooling: High pressure protection

29
OBH895

11 SERVICE FUNCTIONS

MUFZ-KW25VGHZ MUFZ-KW35VGHZ MUFZ-KW50VGHZ MUFZ-KW60VGHZ

11-1. CHANGE IN DEFROST SETTING

Changing defrost finish temperature To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board.
(Refer to 12-6.1)

Jumper wire

Defrost finish temperature (°C)

MUFZ-KW25VGHZ MUFZ-KW35VGHZ

MUFZ-KW50VGHZ MUFZ-KW60VGHZ

JS

Soldered (Initial setting) None (Cut)

5 10

10 18

11-2. PRE-HEAT CONTROL SETTING PRE-HEAT CONTROL MUFZ-KW25/35 When moisture gets into the refrigerant cycle, it may interfere the startup of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermistor is 20°C or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W) MUFZ-KW50/60 Prolonged low load operation, in which the thermostat is OFF for a long time, at low outside temperature (0°C or less) may cause the following troubles. To prevent those troubles, activate the pre-heat control. 1) If moisture gets into the refrigerant cycle and freezes, it may interfere the startup of the compressor. 2) If liquid refrigerant collects in the compressor, a failure in the compressor may occur.
The pre-heat control turns ON when the compressor temperature is 20°C or below. When the pre-heat control turns ON, the compressor is energized. (About 70 W)
Pre-heat control setting ON: To activate the pre-heat control, cut the JK wire of the inverter P.C. board. OFF: To deactivate the pre-heat control, solder the JK wire of the inverter P.C. board. (Refer to 12-6.1)
NOTE: When the inverter P.C. board is replaced, check the jumper wires, and cut/solder them if necessary.

30
OBH895

12 TROUBLESHOOTING

MUFZ-KW25VGHZ MUFZ-KW35VGHZ MUFZ-KW50VGHZ MUFZ-KW60VGHZ

12-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2. Take care of the following during servicing

  1. Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug. 2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board. 3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor. 4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components. 5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.

Lead wiring

Connector housing

3. Troubleshooting procedure 1) Check if the OPERATION INDICATOR lamp on the indoor unit is blinking on and off to indicate an abnormality. To make sure, check how many times the OPERATION INDICATOR lamp is blinking on and off before starting service work. 2) Before servicing, verify that all connectors and terminals are connected properly. 3) When the electronic control P.C. board seems to be defective, check for disconnection of the copper foil pattern and burnt or discolored components. 4) Refer to 12-2 and 12-3.

31
OBH895

12-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (12-3.) disappears, the memorized failure details can be recalled.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply.
While pressing Operation select button and TEMP button on the remote controller at the same time, press RESET button. First, release RESET button. Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right figure are all displayed. Then release the buttons.

Press OFF/ON (stop/operate) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. *1

*1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.

AM PM

AM PM

Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is
emitted at the same timing as the blinking of POWER lamp. *2

No (OFF)

Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnormalities that cannot be recalled with this way. Check if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 12-2.2)

Judgment of indoor/outdoor abnormality

Yes (Blinks)

Before blinking, does POWER lamp stay ON for 3 seconds?

When it stays ON for 3 seconds (without beep): The outdoor unit is abnormal.

Yes

No

The indoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the table of indoor unit failure mode recall function. (Refer to indoor unit service manual.) Make sure to check at least 2 consecutive blinking cycles. *2

The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the table of outdoor unit failure mode recall function. (Refer to 12-2.3) Make sure to check at least 2 consecutive blinking cycles. *3

Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.

Repair the failure parts.

Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to “Setting up the failure mode recall function” mentioned above. Press OFF/ON (stop/operate) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. Press the emergency operation switch so that the memorized abnormal condition is deleted. *4 Release the failure mode recall function according to “Releasing the failure mode recall function” mentioned above.

*4 The information regarding whether the connected outdoor unit is a low-standby-power model or a non-low-standby-power model will also be initialized. (Default= compatible with a low-standby-power model)

NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

*2. Blinking pattern when the indoor unit is abnormal:

Blinking at 0.5-

Blinking at 0.5-

2.5-second OFF second interval 2.5-second OFF second interval

ON OFF

Beeps Repeated cycle

Beeps Repeated cycle

*3. Blinking pattern when the outdoor unit is abnormal:

Blinking at 0.5-

2.5-second OFF 3-second ON

second interval

2.5-second OFF

Beeps Repeated cycle
3-second ON

Blinking at 0.5second interval

ON OFF

No beep Repeated cycle

Beeps

No beep Repeated cycle

Beeps

Repeated cycle

32
OBH895

2. Flow chart of the detailed outdoor unit failure mode recall function Operational procedure
The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures.
Make sure that the remote controller is set to the failure mode recall function.

With the remote controller headed towards the indoor unit, press TEMP button to adjust the set temperature to 25°C. *1

Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of POWER lamp. *2
Yes (Blinks)

No (OFF)

The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the table of outdoor unit failure mode recall function (12-2.3.). Make sure to check at least 2 consecutive blinking cycles. *2

*1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
NOTE: It takes up to 1 minute to indicate the outdoor unit abnormality. Even if POWER lamp is not lit, keep checking at least 1 minute or longer.
The outdoor unit is normal.

Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.

Release the failure mode recall function according to the left mentioned procedure.

Repair the failure parts.

Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to “Setting up the failure mode recall function” (12-2.1.). Press OFF/ON (stop/operate) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. Press the emergency operation switch so that the memorized abnormal condition is deleted. *3 Release the failure mode recall function according to “Releasing the failure mode recall function” mentioned above.

*3 The information regarding whether the connected outdoor unit is a low-standbypower model or a non-low-standby-power model will also be initialized. (Default= compatible with a low-standbypower model)

NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

*2 Blinking pattern when outdoor unit is abnormal:

Blinking at 0.5-

2.5-second OFF 3-second ON

second interval

ON OFF

No beep Repeated cycle

Beeps

2.5-second OFF 3-second ON

Blinking at 0.5second interval

No beep Repeated cycle

Beeps

Repeated cycle

33
OBH895

3. Table of outdoor unit failure mode recall function NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (12-3.).

POWER lamp

Abnormal point

LED indication

(Indoor unit) (Failure mode/protection) (Outdoor P.C. board)

Condition

Remedy

Indoor/outdoor unit failure mode recall function

Outdoor unit failure mode recall function

OFF

None (Normal)

1-time blink 2.5 seconds OFF

Indoor/outdoor communication, receiving error
Indoor/outdoor communication, receiving error

Any signals from the inverter P.C.

·Refer to 12-5. How

board cannot be received normally for to check miswiring and

3 minutes. Although the inverter P.C. board

serial signal error. ·Refer to 12-5. How

sends signal “0”, signal “1” has been to check miswiring and

received 30 consecutive times.

serial signal error.

2-time blink Outdoor power system 2.5 seconds OFF

Overcurrent protection cut-out

· Reconnect

operates 3 consecutive times within connectors.

1 minute after the compressor gets started.

·Refer to 12-5. “How to check inverter/

compressor”.

·Check stop valve.

3-time blink Discharge temperature

1-time blink every Thermistor shorts or opens during

·Refer to 12-5.

2.5 seconds thermistor

2.5 seconds

compressor running.

“Check of outdoor

OFF

Defrost thermistor

thermistors”.

Fin temperature thermistor
P.C. board temperature thermistor Ambient temperature

3-time blink 2.5 seconds OFF
4-time blink 2.5 seconds OFF
2-time blink

Defective outdoor

thermistors can be

identified by checking the blinking pattern of

LED.

thermistor

2.5 seconds OFF

Outdoor heat exchanger temperature thermistor

4-time blink Overcurrent 2.5 seconds OFF

11-time blink

Large current flows into power module ·Reconnect

2.5 seconds OFF (IC700).

compressor connector.

·Refer to 12-5. “How to check inverter/

compressor”.

·Check stop valve.

Compressor synchronous 12-time blink

Waveform of compressor current is ·Reconnect

abnormality (Compressor startup failure protection)

2.5 seconds OFF distorted.

compressor connector.

·Refer to 12-5. “How

to check inverter/

compressor”.

5-time blink Discharge temperature 2.5 seconds OFF

Temperature of discharge temperature ·Check refrigerant

thermistor exceeds 116°C, compressor circuit and refrigerant

stops.

amount.

Compressor can restart if discharge ·Refer to 12-5. “Check

temperature thermistor reads 100°C or of LEV”.

less 3 minutes later.

6-time blink High pressure 2.5 seconds OFF

Temperature of indoor coil thermistor ·Check refrigerant

exceeds 70°C in HEAT mode. Temperature of defrost thermistor

circuit and refrigerant amount.

exceeds 70°C in COOL mode.

·Check stop valve.

7-time blink Fin temperature/P.C. board 7-time blink

Temperature of fin temperature thermistor ·Check around outdoor

2.5 seconds temperature

2.5 seconds OFF on the inverter P.C. board exceeds 75 ~ unit.

OFF

86°C (KW25/35) / 75 ~ 80°C (KW50/60), ·Check outdoor unit air

or temperature of P.C. board temperature passage.

thermistor on the inverter P.C. board

·Refer to 12-5. “Check

exceeds 72 ~ 85°C (KW25/35) / 70 ~

of outdoor fan motor”.

75°C (KW50/60).

8-time blink Outdoor fan motor 2.5 seconds OFF

Outdoor fan has stopped 3 times in a ·Refer to 12-5. “Check

row within 30 seconds after outdoor fan startup.

of outdoor fan motor”. Refer to 12-5. “Check

of inverter P.C. board”.

9-time blink Nonvolatile memory data 2.5 seconds

5-time blink 2.5 seconds OFF

Nonvolatile memory data cannot be read properly.

·Replace the inverter P.C. board.

OFF

Power module (IC700)

6-time blink

The interface short circuit occurs in the ·Refer to 12-5. “How

2.5 seconds OFF output of the power module (IC700). to check inverter/

The compressor winding shorts circuit. compressor”.

34
OBH895

NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (12-3.).

POWER lamp

Abnormal point

LED indication

(Indoor unit) (Failure mode/protection) (Outdoor P.C. board)

Condition

Remedy

Indoor/outdoor unit failure mode recall function

Outdoor unit failure mode recall function

10-time blink Discharge temperature 2.5 seconds OFF

Temperature of discharge temperature ·Refer to 12-5. “Check

thermistor has been 50°C or less for of LEV”.

20 minutes.

·Check refrigerant

circuit and refrigerant

amount.

11-time blink Bus-bar voltage (DC)

8-time blink

Bus-bar voltage of inverter cannot be ·Refer to 12-5. “How

2.5 seconds

OFF

Each phase current of

2.5 seconds OFF detected normally.

9-time blink

Each phase current of compressor

to check inverter/ compressor”.

compressor

2.5 seconds OFF cannot be detected normally.

14-time blink Stop valve (Closed valve) 2.5 seconds OFF *1

14-time blink 2.5 seconds OFF

·Closed valve is detected by compressor current.
·An abnormality of the indoor thermistors, the defrost thermistor or
ambient temperature thermistor is
detected.

·Check stop valve. ·Refer to “TEST POINT DIAGRAM AND VOLTAGE” on the service manual of indoor and outdoor unit for the characteristics of the thermistors. (Do not start the operation again without repair to prevent hazards.)

4-way valve/ Pipe temperature

16-time blink 2.5 seconds OFF

·The 4-way valve does not work

·Check the 4-way

properly.

valve.

·The indoor coil thermistor detects an ·Replace the inverter

abnormal temperature.

P.C. board.

·An abnormality of the indoor

·Refer to “TEST

thermistor is detected.

POINT DIAGRAM

AND VOLTAGE” on

the service manual of

indoor and outdoor unit

for the characteristics

of the thermistors. (Do

not start the operation

again without repair to

prevent hazards.)

16-time blink Outdoor refrigerant system
2.5 seconds abnormality OFF *1

1-time blink 2.5 seconds OFF

·A closed valve and air trapped in the ·Check for a gas leak

refrigerant circuit are detected based in a connecting piping

on the temperature sensed by the

etc.

indoor and outdoor thermistors and ·Check the stop valve.

the current of the compressor.

·Refer to 12-5.

·An abnormality of the indoor

“Check of outdoor

thermistors, the defrost thermistor or refrigerant circuit”.

ambient temperature thermistor is detected.

·Refer to “TEST POINT DIAGRAM

AND VOLTAGE” on

the service manual of

indoor and outdoor unit

for the characteristics

of the thermistors. (Do

not start the operation

again without repair to

prevent hazards.)

*1 There is possibility that diesel explosion may occur due to the air mixed in the refrigerant circuit. First, ensure that there are no leakage points on the valves, flare connections, etc. that allow the air to flow into the refrigerant circuit, or no blockage points (e.g. clogged or closed valves) in the refrigerant circuit that cause an increase in pressure. If there is no abnormal point like above and the system operates cooling and heating modes normally, the indoor thermistor might have a problem, resulting in false detection. Check both the indoor coil thermistor and the room temperature thermistor, and replace faulty thermistor(s), if any. NOTE: Do not start the operation again without repair to prevent hazards.

35
OBH895

12-3. TROUBLESHOOTING CHECK TABLE

No. Symptom

LED indication

Abnormal point/ Condition

Condition

Remedy

Outdoor unit 1-time blink every Outdoor power sys- Overcurrent protection cut- out operates 3 consecutive times ·Reconnect connector of compres-

does not op- 2.5 seconds

tem

within 1 minute after the compressor gets started.

sor.

1 erate.

·Refer to 12-5. “How to check inverter/compressor”.

·Check stop valve.

Outdoor thermistors Discharge temperature thermistor, fin temperature thermistor, ·Refer to 12-5. “Check of outdoor

defrost thermistor, P.C. board temperature thermistor, outdoor thermistors”.

2

heat exchanger temperature thermistor or ambient tempera-

ture thermistor shorts or opens during compressor running.

Outdoor control sys- Nonvolatile memory data cannot be read properly.

·Replace inverter P.C. board.

3

tem

(POWER lamp of the indoor unit lights up or blinks 7-time.)

4

6-time blink

Serial signal

2.5 seconds OFF

The communication fails between the indoor and outdoor unit ·Refer to 12-5. “How to check

for 3 minutes.

miswiring and serial signal error.

5

11-time blink

Stop valve/

2.5 seconds OFF Closed valve

Closed valve is detected by compressor current.

·Check stop valve.

14-time blink

Outdoor unit

Outdoor unit is defective.

6

2.5 seconds OFF (Other abnormality)

·Refer to 12-2.2. “Flow chart of the detailed outdoor unit failure mode recall function”.

16-time blink

4-way valve/

The 4-way valve does not work properly.

·Refer to 12-5. “Check of R.V.

7

2.5 seconds OFF Pipe temperature The indoor coil thermistor detects an abnormal temperature. coil”.

·Replace the inverter P.C. board.

17-time blink

Outdoor refrigerant A closed valve and air trapped in the refrigerant circuit are

·Check for a gas leak in a

2.5 seconds OFF system abnormality detected based on the temperature sensed by the indoor and connecting piping etc.

outdoor thermistors and the current of the compressor.

·Check the stop valve.

8

·Refer to 12-5. “Check of outdoor

refrigerant circuit”.

‘Outdoor unit 2-time blink

Overcurrent protec- Large current flows into power module (IC700).

· Reconnect connector of compressor.

9

stops and restarts 3

2.5 seconds OFF tion

·Refer to 12-5. “How to check inverter/compressor”.

minutes later’

·Check stop valve.

is repeated. 3-time blink

Discharge tem-

Temperature of discharge temperature thermistor exceeds ·Check refrigerant circuit and refrig-

10

2.5 seconds OFF perature overheat 116°C, compressor stops. Compressor can restart if discharge erant amount.

protection

temperature thermistor reads 100°C or less 3 minutes later. ·Refer to 12-5. “Check of LEV”.

4-time blink

Fin temperature / Temperature of fin temperature thermistor on the heat sink ex- ·Check around outdoor unit.

2.5 seconds OFF P.C. board tem-

ceeds 75 ~ 86°C (KW25/35)/75 ~ 80°C (KW50/60) or tempera- ·Check outdoor unit air passage.

11

perature thermistor ture of P.C. board temperature thermistor on the inverter P.C. ·Refer to 12-5. “Check of outdoor

overheat protection board exceeds 72 ~ 85°C (KW25/35)/70 ~ 75°C (KW50/60).

fan motor”.

5-time blink

High pressure pro- Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost ·Check refrigerant circuit and refrig-

12

2.5 seconds OFF tection

thermistor exceeds 70°C in COOL mode.

erant amount.

·Check stop valve.

8-time blink

Compressor syn- The waveform of compressor current is distorted.

· Reconnect connector of compressor.

13

2.5 seconds OFF chronous abnormal-

·Refer to 12-5. “How to check

ity

inverter/compressor”.

10-time blink

Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds ·Refer to 12-5. “Check of outdoor

14

2.5 seconds OFF

after outdoor fan startup.

fan motor. ·Refer to 12-5. “Check of inverter

P.C. board.

15

12-time blink

Each phase current Each phase current of compressor cannot be detected nor-

2.5 seconds OFF of compressor

mally.

·Refer to 12-5. “How to check inverter/compressor”.

13-time blink

Bus-bar voltage

2.5 seconds OFF (DC)

Bus-bar voltage of inverter cannot be detected normally.

·It occurs with following case. Instantaneous power voltage drop. (Short time power failure)

16

(KW50/60) ·Refer to 12-5. “Check of power

supply”. (KW50/60)

·Refer to 12-5. “How to check in-

verter/compressor”.

Outdoor unit 1-time blink

Frequency drop by KW25/35

When the input current exceeds approximately The unit is normal, but check the

operates. 17

2.5 seconds OFF current protection

3-time blink

Frequency drop by

2.5 seconds OFF high pressure pro-

10A, compressor frequency lowers.

KW50/60

Current from power outlet is nearing breaker capacity.

Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.

following. ·Check if indoor filters are clogged. ·Check if refrigerant is short. ·Check if indoor/outdoor unit air circulation is short cycled.

tection

18

Frequency drop by Indoor coil thermistor reads 8°C or less in COOL mode, com-

defrosting in COOL pressor frequency lowers.

mode

4-time blink

Frequency drop by Temperature of discharge temperature thermistor exceeds ·Check refrigerant circuit and refrig-

2.5 seconds OFF discharge tempera- 111°C, compressor frequency lowers.

erant amount.

19

ture protection

·Refer to 12-5. “Check of LEV”.

·Refer to 12-5. “Check of outdoor

thermistors”.

KW25/35

Outside temperature When the outside temperature thermistor shorts or opens,

·Refer to 12-5. Check of outdoor

20

5-time blink

thermistor protec- protective operation without that thermistor is performed.

thermistors.

2.5 seconds OFF tion

36
OBH895

No. Symptom Outdoor unit
21 operates.
22
23

LED indication

Abnormal point/ Condition

Condition

7-time blink

Low discharge tem- Temperature of discharge temperature thermistor has been

2.5 seconds OFF perature protection 50°C or less for 20 minutes.

8-time blink 2.5 seconds OFF

KW25/35 PAM protection
PAM: Pulse Ampli-
tude Modulation

The overcurrent flows into PFC (Power factor correction: IC820) or the bus-bar voltage reaches 394 V or more, PAM stops and restarts.

KW50/60

Zero cross signal cannot be detected.

Zero cross detecting

circuit

9-time blink

Inverter check mode The connector of compressor is disconnected, inverter check

2.5 seconds OFF

mode starts.

Remedy
·Refer to 12-5. “Check of LEV”. ·Check refrigerant circuit and refrigerant amount.
This is not malfunction. PAM protection will be activated in the following cases: 1 Instantaneous power voltage
drop. (Short time power failure) 2 When the power supply voltage
is high.
·It occurs with following cases. 1 Instantaneous power voltage drop. (Short time power failure) 2 Distortion of primary voltage
·Refer to 12-5. “Check of power supply”.
·Check if the connector of the compressor is correctly connected. Refer to 12-5. “How to check inverter/compressor”.

NOTE: 1. The location of LED is illustrated at the right figure. Refer to 12-6.1. 2. LED is lit during normal operation.

The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the blinking frequency is “2”.

0.5-second ON

0.5-second ON

Inverter P.C. board MUFZ-KW25/35VGHZ
LED Blinking

ON OFF

2.5-second OFF

2.5-second OFF

MUFZ-KW50/60VGHZ
Blinking LED

37
OBH895

12-4. TROUBLESHOOTING CRITERION OF MAIN PARTS
MUFZ-KW25VGHZ MUFZ-KW35VGHZ MUFZ-KW50VGHZ MUFZ-KW60VGHZ

Part name

Check method and criterion

Defrost thermistor (RT61) Measure the resistance with a tester.

Figure

Fin temperature thermistor (RT64)

Refer to 12-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.

Ambient temperature thermistor (RT65)

Outdoor heat exchanger temperature thermistor (RT68) Discharge temperature thermistor (RT62)
Compressor

Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.

Refer to 12-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.

Measure the resistance between terminals using a tester. (Temperature: -10 to 40°C)

U-V U-W V-W

Normal () MUFZ-KW25VGHZ MUFZ-KW50VGHZ MUFZ-KW35VGHZ MUFZ-KW60VGHZ

0.82 – 1.11

0.87 – 1.18

WHT

RED BLK
W

V

U

Outdoor fan motor

Measure the resistance between lead wires using a tester. (Temperature: -10 ~ 40°C)

Color of lead wire

Normal ()
MUFZ-KW25VGHZ MUFZ-KW50VGHZ MUFZ-KW35VGHZ MUFZ-KW60VGHZ

RED ­ BLK BLK ­ WHT WHT ­ RED

32 – 43

25 – 34

WHT RED BLK
W

V

U

R.V. coil (21S4)
Expansion valve coil (LEV)
Defrost heater

Measure the resistance using a tester. (Temperature: -10 to 40°C)

Normal (k)

MUFZ-KW25VGHZ MUFZ-KW50VGHZ MUFZ-KW35VGHZ MUFZ-KW60VGHZ

1.41 – 2.00

1.17 – 1.66

Measure the resistance using a tester. (Temperature: -10 to 40°C)

Color of lead wire RED ­ ORN

Normal ()

RED ­ WHT RED ­ BLU RED ­ YLW

37 – 54

Measure the resistance using a tester. (Temperature: -10 to 40°C)

Normal ()

MUFZ-KW25VGHZ MUFZ-KW50VGHZ MUFZ-KW35VGHZ MUFZ-KW60VGHZ

802 – 990

376 – 461

WHT

LEV

ORN RED (+12V)

YLW BLU

38
OBH895

12-5. TROUBLESHOOTING FLOW
A How to check inverter/compressor
Disconnect the connector between the compressor and the power module (IC700).

Check the voltage between terminals.
Are the voltages balanced? Yes
Check the compressor.

See 12-5. “Check of open phase”.

No

Replace the inverter P.C. board.

See 12-5. “Check of compressor”.

B Check of open phase

With the connector between the compressor and the power module (IC700) disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between the terminals.

Output voltage is 50 – 130V. (The voltage may differ according to the tester.)

<< Operation method>>

Start cooling or heating operation by pressing the emergency operation switch on the indoor unit. (TEST RUN OPERATION:

Refer to 9-3.)

<>

At 3 points

BLK (U)-WHT (V)

  • Measure AC voltage between the lead wires at 3 points.

BLK (U)-RED (W)

WHT(V)-RED (W)

NOTE: 1. Output voltage varies according to power supply voltage. 2. Measure the voltage by analog type tester. 3. During this check, LED of the inverter P.C. board blinks 9 times. (Refer to 12-6.1.)

C Check of compressor

Refer to 12-5. “Check of compressor

winding”. Is the compressor normal?

No

Yes

Refer to 12-5. “Check of compressor

operation time”. Does the compressor operate continuously?

No

Yes

OK

Replace the compressor. Refer to 12-5. “Check of compressor start failure.

39
OBH895

D Check of compressor winding

Disconnect the connector between the compressor and the power module (IC700), and measure the resistance between the

compressor terminals.

<>

At 3 points

BLK-WHT BLK-RED

  • Measure the resistance between the lead wires at 3 points.

WHT-RED

<>

Refer to 12-4.

0 [] ················Abnormal [short]

Infinite [] ·······Abnormal [open]

NOTE: Be sure to zero the ohmmeter before measurement.

E Check of compressor operation time

Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to overcurrent. <> Start heating or cooling operation by pressing the emergency operation switch on the indoor unit. (Test run operation: Refer to
9-3.) <> Measure the time from the start of compressor to the stop of compressor due to overcurrent.

<> 0 second 1 second 2 seconds

10 seconds

10 minutes

Compressor starts Abnormal (IC700 failure) (Compressor winding short) Abnormal (Compressor lock out) (Starting defect) Abnormal (Poor contact) (Inverter P.C. board defect) (Disconnected connector) Abnormal (Refrigerant circuit defect) (Closed valve)
Normal

F Check of compressor start failure

Confirm that ~ is normal. ·Electrical circuit check
. Contact of the compressor connector . Output voltage of inverter P.C. board and balance of them (See 12-5. ) . Direct current voltage between DB61(+) and (-) (MUFZ-KW25/35VGHZ)/
IC700 (P) and (N) (MUFZ-KW50/60VGHZ) on the inverter P.C. board . Voltage between outdoor terminal block S1-S2

Does the compressor run for 10 seconds or

more after it starts?

Yes

No

After the compressor is heated with a drier,

does the compressor start? *1

No

Yes

Compressor start failure. Activate pre-heat control. (Refer to 11-2. “PRE-HEAT CONTROL SETTING”)

Check the refrigerant circuit. Check the stop valve.
Replace the compressor.

*1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part

40
OBH895

G Check of outdoor thermistors

Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor.

Is the resistance of thermistor normal?

(Refer to 12-6.1.)

No

Yes

Reconnect the connector of thermistor. Turn ON the power supply and press the emergency operation switch.

Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.

Does the unit operate for 10 minutes or more

without showing thermistor abnormality?

No

Yes

OK (Cause is poor contact.)

Replace the inverter P.C. board.

MUFZ-KW25VGHZ MUFZ-KW35VGHZ

Thermistor

Symbol

Connector, Pin No.

Defrost

RT61 Between CN641 pin1 and pin2

Discharge temperature Fin temperature Ambient temperature

RT62 Between CN641 pin3 and pin4 RT64 Between CN642 pin1 and pin2 RT65 Between CN643 pin1 and pin2

Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3

Board Inverter P.C. board

MUFZ-KW50VGHZ MUFZ-KW60VGHZ

Thermistor

Symbol

Connector, Pin No.

Defrost

RT61 Between CN671 pin1 and pin2

Discharge temperature Fin temperature

RT62 Between CN671 pin3 and pin4 RT64 Between CN673 pin1 and pin2

Ambient temperature

RT65 Between CN672 pin1 and pin2

Outdoor heat exchanger temperature RT68 Between CN671 pin5 and pin6

Board Inverter P.C. board

41
OBH895

H Check of R.V. coil

MUFZ-KW25VGHZ MUFZ-KW35VGHZ

  • First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 12-4. * In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
    although no signal is being transmitted to R.V. coil. Check if CN721 is connected.

Unit operates in COOL mode even if it is set to HEAT mode.

Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press the emergency operation switch twice (HEAT mode).

Is there 230 V AC between CN721 and

on the inverter P.C. board 3 minutes after the power supply is turned ON?

No

Yes

Replace the inverter P.C. board.

Replace the 4-way valve.

Unit operates in HEAT mode even if it is set to COOL mode.

Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press the emergency operation switch once (COOL mode).

Is there 230 V AC between CN721 and on the inverter P.C. board 3 minutes
after the power supply is turned ON?

Yes

Replace the inverter P.C. board.

No

Replace the 4-way valve.

MUFZ-KW50VGHZ MUFZ-KW60VGHZ

  • First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 12-4. * In case CN602 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
    although no signal is being transmitted to R.V. coil. Check if CN602 is connected.

Unit operates in COOL mode even if it is set to HEAT mode.

Disconnect connector between the compressor and the power module (IC700). Turn ON the power supply and press the emergency operation switch twice (HEAT mode).

Is there 230 V AC between CN602 and

on the inverter P.C. board 3 minutes after the power supply is turned ON?

No

Yes

Replace the inverter P.C. board.

Replace the 4-way valve.

Unit operates in HEAT mode even if it is set to COOL mode.

Disconnect connector between the compressor and the power module (IC700). Turn ON the power supply and press the emergency operation switch once (COOL mode).

Is there 230 V AC between CN602 and on the inverter P.C. board 3 minutes
after the power supply is turned ON?

Yes

Replace the inverter P.C. board.

No

Replace the 4-way valve.

42
OBH895

I Check of outdoor fan motor
Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932.

Is the resistance between each ter-

minal of outdoor fan motor normal? (Refer to 12-4.)

Yes

No

Disconnect CN932 from the inverter P.C. board, and turn on the power supply.

Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)

(Fixed to either 5 or 0 V DC) No
No Replace the outdoor fan motor.

Does the voltage between each terminal become 5 and 0V DC repeatedly?
Yes
Does the outdoor fan motor rotate smoothly? Yes
Replace the inverter P.C. board.

43
OBH895

J Check of power supply

Disconnect the connector between the compressor and the power module (IC700). Turn ON power supply and press the emergency operation switch.

Rectify indoor/outdoor connecting wire.

Does POWER lamp on the indoor

unit light up?

No

Yes

Is there bus-bar voltage 260 – 370V

DC between DB61 (+) and DB61 (­)

(MUFZ-KW25/35VGHZ)/325 – 370 V

DC between IC700 (P) and (N)

Yes

(MUFZ-KW50/60VGHZ) on the

inverter P.C. board? (Refer to 12-6.1.)

No

Check the electric parts in main circuit.

Yes
Is there voltage 230 V AC between the indoor terminal block S1 and S2?

Replace the indoor

No

electronic control P.C. board.

Does LED on the inverter P.C. board light up or blink? (Refer to 12-6.1.)

No

Replace the inverter P.C. board.

Yes

If lights up, OK. If blinks, refer to 12-3.

DB61

260 – 370 V DC

Inverter P.C. board (Solder side)
MUFZ-KW25/35VGHZ

325 -370 V DC

IC700
N
P

MUFZ-KW50/60VGHZ

44
OBH895

K Check of LEV (Expansion valve)

Turn ON the power supply.
While pressing both Operation select button and TEMP button on the remote controller at the same time, press RESET button. First, release RESET button. Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right figure are all displayed. Then release the buttons.

Press OFF/ON (stop/operate) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. *1

AM PM

AM PM

Expansion valve operates in full-opening direction.

Do you hear the expansion valve “click,

click·······”? Do you feel the expansion valve vibrate Yes

OK

when touching it ?

No

*1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.

Is LEV coil properly fixed to

the expansion valve?

No

Yes

Does the resistance of LEV

coil have the characteristics? (Refer to 12-4.)

Yes

No

Replace the LEV coil.

Properly fix the LEV coil to the expansion valve.

Measure each voltage between connector pins of CN724 on the inverter P.C. board. 1. Pin (-) — Pin (+) 2. Pin (-) — Pin (+) 3. Pin (-) — Pin (+) 4. Pin (-) — Pin (+) Is there about 3 – 5 V AC between each? NOTE: Measure the voltage by an analog
tester.
Yes

Replace the inverter P.C. No board.

Replace the expansion valve.

NOTE: After check of LEV, take the following steps. 1. Turn OFF the power supply and turn it ON again. 2. Press RESET button on the remote controller.

45
OBH895

L Check of inverter P.C. board
Check the outdoor fan motor. (Refer to 12-5. .)

Is the fuse (F901) blown on the in-

verter P.C. board?

Yes

No

Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct.

Operate the outdoor unit by starting EMERGENCY OPERATION.

Check the LED indication on the in-

verter P.C. board. Does the LED blink 10 times?

No

Yes (10-time blink)

Check the corresponding parts following LED indication. (Refer to 12-3.)

Replace the inverter P.C. board.

46
OBH895

M How to check miswiring and serial signal error

Turn the power supply OFF.

Is there rated voltage of 230 V AC in the

power supply?

No

Yes

Turn the power supply ON.

Is there 230 V AC between outdoor terminal

block S1 and S2?

No

Yes

Press the emergency operation switch once.

Check the power supply.
Check for miswiring, broken wires, and loose wire connection between the power supply and outdoor terminal block S1 and between the power supply and outdoor terminal block S2.

Does the left lamp of OPERATION INDICATOR lamp light up?

Yes

Is the serial signal error indicated 6 minutes

later?

No

Yes

No

Is there any miswiring, poor con-

tact, or wire disconnection of the indoor/outdoor connecting wire?

Yes Correct them.

No

A

Turn OFF the power supply. Check once again if the indoor/outB door connecting wire is not wrongly connected.
Short-circuit the outdoor terminal block S2 and S3. *1
Turn the power supply ON.

*1 Miswiring may damage indoor electronic control P.C. board during operation.
Be sure to confirm the wiring is correct before theoperation starts.

Wait for 2 or more minutes after the power supply is turned on. Touch S2 and S3 with tester probes and start the emergency operation.

When the emergency operation starts, does the rated voltage occur for 2 seconds between indoor terminal block S2 and S3?
Yes

Does the left lamp of OPERATION INDICATOR lamp on indoor unit blink continuously 6 minutes after No the emergency operation starts?
Yes

Does the outdoor LED light up?
Yes Confirm that the thermostat is OFF and wiring is not loose.

No No

Does the outdoor LED blink 6

times?

No

Yes

Does DC (6 V or more) occur

between indoor terminal block S2 and S3?

No

Yes

Turn the power supply OFF. Replace the indoor power P.C. board.

Replace the outdoor inverter P.C. board.2
Replace the outdoor inverter P.C. board.
2
*2 Electric charge may remain immediately after the power supply is turned OFF. Perform the procedure after 3 minutes.

Turn the power supply OFF.

Turn the power supply ON.

Wait for 2 or more minutes after the power supply is turned ON. Touch CN202 and GND with tester probes and start the emergency operation.

During the emergency operation, does DC (2V or less) occur for 2 seconds between CN202
and GND on the indoor power No P.C. board?

Yes

Replace the indoor power P.C. board.

Replace the indoor electronic control P.C. board.

Turn the power supply ON. Start the emergency operation.

Does the left lamp of OPERATION INDICATOR lamp on indoor unit blink continuously 6 minutes after No the emergency operation starts?
Yes

Does DC (20 V or more) occur

between indoor terminal block S2

and S3?

No

Yes

Replace the indoor electronic control P.C. board.

Repair completed. Replace the outdoor inverter P.C. board.

47
OBH895

A
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press the emergency operation switch.

· Reinstall

either the unit

or the light

away from

Is serial signal

each other.

error indicated 6 minutes later?

No

·Attach a filter on remote

Yes

control receiv-

ing section

of the indoor

B

unit.

N Check of the outdoor refrigerant circuit
Has the operation stopped during pump down? Yes No

The operation has stopped to prevent the diesel explosion caused by air trapped in the refrigerant circuit. Close the stop valve, and disconnect the power plug or turn the breaker OFF.
CAUTION: Do not start the operation again to prevent hazards.

Was the operation started with the stop valve closed, and was it opened during operation? Yes
No

The unit occasionally stops when the stop valve is opened or closed during operation. Open the stop valve and start the cooling operation again.

The refrigerant gas amount may be 60% or less than the normal amount. Identify where the gas is leaking from, and fix the leak.

48
OBH895

O Electromagnetic noise enters into TV sets or radios

Is the unit earthed?

No

Yes

Earth the unit.

Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the Yes outdoor unit within 3 m?
No

Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.

Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or Yes radios and the outdoor unit within 3 m?
No

Extend the distance between the TV sets and/ or radios and the indoor unit, or the TV sets or radios and the outdoor unit.

Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten- Yes na wiring?
No

Replace or repair the antenna. Replace or repair the coaxial cable.

Is the indoor/outdoor connecting wire

of the air conditioner and the wiring of

the antennas close?

Yes

No

Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.

Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise 3. Channel, frequency, broadcast station unaffected by the electromagnetic noise 4. Layout of:
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric field intensity of the broadcast station affected by the electromagnetic noise 6. Presence or absence of amplifier such as booster 7. Operation condition of air conditioner when the electromagnetic noise enters in

  1. Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic
    noise.
  2. Within 3 minutes after turning ON the power supply, press OFF/ON (stop/operate) button on the remote controller for
    power ON, and check for the electromagnetic noise.
  3. After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the
    electromagnetic noise.
  4. Press OFF/ON (stop/operate) button on the remote controller for power OFF, when the outdoor unit stops but the
    indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.

49
OBH895

12-6. TEST POINT DIAGRAM AND VOLTAGE 1. Inverter P.C. board
MUFZ-KW25VGHZ MUFZ-KW35VGHZ

Back side of unit 230 V AC

DB61

260 – 370 V DC

(-)

(+)

Smoothing Smoothing Smoothing

capacitor capacitor capacitor (C61)

(C63)

(C62)

R.V.coil (CN721) 230 V AC

Fuse (F901) T3.15AL250V

Fuse (F801) T3.15AL250V

Fuse (F701) T3.15AL250V

Fuse (F62) 15 A 250 V Output to drive compressor (LDU, LDV, LDW)
Output to drive outdoor fan motor (CN932)
Front side of unit

Fuse (F61) 25 A 250V
230 V AC

LED

Jumper wire for pre-heat control setting (JK)

Jumper wire for changing defrost setting (JS)

Fin temperature thermistor/RT64 (CN642) Signal of outdoor fan motor (CN931) Ambient temperature thermistor/RT65 (CN643) Defrost thermistor /RT61(CN641) Discharge temperature thermistor/RT62 (CN641) Outdoor heat exchanger temperature thermistor /RT68 (CN644) LEV (CN724)

Resistance(k ) Resistance (k)
Resistance(k )

Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68) 100

90

80 70 60 50 40 30 20 10
0 -20 -10 0 10 20 30 40
Temperature( )

Discharge temperature thermistor (RT62) 800 700 600 500 400 300 200 100
0 0 10 20 30 40 50 60 70 80 90 100 110 120 Temperature (°C)

50
OBH895

Fin temperature thermistor(RT64) 200 180 160 140 120 100
80 60 40 20
0 0 10 20 30 40 50 60 70 80 Temperature( )

MUFZ-KW50VGHZ MUFZ-KW60VGHZ
LEV (CN724)
Ambient temperature thermistor/RT65 (CN672)
Outdoor heat exchanger temperature thermistor /RT68 (CN671) Discharge temperature thermistor/RT62 (CN671) Defrost thermistor /RT61 (CN671) Fin temperature thermistor/RT64 (CN673)
LED
Signal of outdoor fan motor (CN931)
IC700 (N) 325 – 370 V DC
IC700 (P)
Fuse (F901) T3.15AL250V Output to drive outdoor fan motor (CN932)

Jumper wire for pre-heat control setting (JK) Jumper wire for changing defrost setting (JS)
Heater (CN601) 230 V AC R.V. coil (CN602) 230 V AC
Fuse (F601) T3.15AL250V
Fuse (F880) T3.15AL250V
230 V AC

Resistance(k ) Resistance (k)
Resistance(k )

Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68) 100

90

80

Discharge temperature thermistor (RT62)

70

800

700 60
600

50

500

40

400

30

300

20

200

10
0 -20 -10 0 10 20 30 40
Temperature (°C)

100
0 0 10 20 30 40 50 60 70 80 90 100 110 120 Temperature (°C)

51
OBH895

200 Fin temperature thermistor(RT64) 180 160 140 120 100
80 60 40 20
0 0 10 20 30 40 50 60 70 80 Temperature(°C)

13 DISASSEMBLY INSTRUCTIONS

The terminal which has the locking mechanism can be detached as shown below. There are 2 types of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.

(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve

(2) The terminal with the connector shown below has the locking mechanism.

Locking lever

Slide the sleeve. Pull the terminal while pushing the locking lever.

Hold the sleeve, and pull out the terminal slowly.
Connector

13-1. MUFZ-KW25VGHZ MUFZ-KW35VGHZ
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE

: Indicates the visible parts in the photos/figures. : Indicates the invisible parts in the photos/figures.
PHOTOS/FIGURES

1. Removing the cabinet (1) Remove the screws fixing the service panel. (2) Pull down the service panel and remove it. (3) Disconnect the power supply cord and indoor/outdoor connecting wire. (4) Remove the screws fixing the top panel. (5) Remove the top panel. (6) Remove the screws fixing the cabinet. (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the screws of the terminal block support and the back panel. (10) Remove the back panel.

Photo 1 Screws of the top panel

Screws of the top panel
Back panel
Screw of the service panel

Photo 2

Screw of the cabinet

Screws of the cabinet

Service panel

Photo 3 Screws of the terminal block support and the back panel

Screws of the cabinet
OBH895

Direction to remove
Hooks of the service panel
52

Screws of the back panel

OPERATING PROCEDURE

PHOTOS/FIGURES

2. Removing the inverter assembly and inverter P.C.

Photo 4

Screw of the P.B. support

board

Ambient temperature

(1) Remove the cabinet and panels. (Refer to section 1.)

thermistor

(2) Disconnect the lead wire to the reactor and the following con-

and the separator
Screws of the terminal block

nectors:

support and

the back panel

CN721 (R.V. coil)

CN722 (Base heater)

CN931, CN932 (Fan motor)

CN641 (Defrost thermistor and discharge temperature ther-

mistor)

CN643 (Ambient temperature thermistor)

CN644 (Outdoor heat exchanger temperature thermistor)

CN724 (Expansion valve coil)

(3) Remove the compressor connector (CN61).

(4) Remove the screws fixing the heat sink support and the sep-

arator.

(5) Remove the fixing screw of the P.B. support and the separa-

tor.

(6) Remove the fixing screws of the terminal block support and the back panel.
(7) Remove the inverter assembly.

Screw of the heat sink support and the separator

(8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the Photo 5

inverter P.C. board from the P.C. board support.

  • Connection procedure when attaching the inverter P.C.
    board (Photo 5)

Lead wires of the heat exchanger temperature thermistor

Lead wires of the expansion valve coil

1. Connect the lead wires of the heat exchanger temperature thermistor to the connector on the inverter P.C. board. Pull the lead wires of the heat exchanger temperature thermistor toward you and put them on the left hook on the P.C. board support so that the other lead wires are bundled up as shown in Photo 5.
2. Connect the lead wires of the expansion valve coil to the connector on the inverter P.C. board. Pull the lead wires of the expansion valve coil toward you and put them on the right hook on the P.C. board support so that the other lead wires are bundled up as shown in Photo 5.

Photo 6 (Inverter assembly)

Heat sink support

Heat sink

P.C. board support

Screws of the earth wire

Inverter P.C. board support

Inverter P.C. board Screw of the inverter P.C. board
53
OBH895

OPERATING PROCEDURE
3. Removing R.V. coil (1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the following connectors: CN721 (R.V. coil) (3) Remove the R.V. coil.

Photo 7

PHOTOS/FIGURES

Outdoor heat exchanger temperature thermistor

Defrost thermistor

4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the lead wire to the reactor and the following connectors: CN641 (Defrost thermistor and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) (3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor from its holder. (6) Pull out the ambient temperature thermistor from its holder.

Photo 8

Screws of the outdoor fan motor

5. Removing outdoor fan motor (1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the following connectors: CN931, CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.

Propeller fan nut

Propeller fan

54
OBH895

OPERATING PROCEDURE
6. Removing the compressor and 4-way valve (1) Remove the cabinet and panels. (Refer to section 1.) (2) Remove the inverter assembly. (Refer to section 2.) (3) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa). (4) Detach the brazed part of the suction and the discharge pipe connected with compressor. (5) Remove the compressor nuts. (6) Remove the compressor. (7) Detach the brazed part of pipes connected with 4-way valve.

PHOTOS/FIGURES
Photo 9 Discharge pipe brazed part

Suction pipe brazed part

Discharge temperature thermistor

Brazed parts of 4-way valve

55
OBH895

13-2. MUFZ-KW50VGHZ MUFZ-KW60VGHZ
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE
1. Removing the cabinet (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Disconnect the power supply cord and indoor/outdoor connecting wire. (8) Remove the screws of the cabinet. (9) Remove the cabinet. (10) Remove the screws of the back panel. (11) Remove the back panel.

PHOTOS/FIGURES
Photo 1 Screws of the top panel

Photo 2 Screws of the top panel

Screws of the cabinet

Screws of the cabinet

Screws of the cabinet

Screw of

Screws of

the valve cover the service panel

Screws of the back panel

56
OBH895

OPERATING PROCEDURE

PHOTOS/FIGURES

2. Removing the inverter assembly and inverter P.C.

Photo 3

board

Inverter P.C board

(1) Remove the cabinet and the service panel. (Refer to section

1.)

(2) Disconnect the lead wire to the reactor and the following

connectors:

CN601 (Base heater)

CN602 (R.V. coil)

CN931, CN932 (Fan motor)

CN671 (Defrost thermistor, discharge temperature thermistor

and outdoor heat exchanger temperature thermistor)

CN672 (Ambient temperature thermistor)

CN724 (Expansion valve coil)

(3) Remove the compressor connector.

(4) Remove the earth wires and the lead wires of the inverter P.C. Screws of

board.

the P.B.

(5) Remove the screws of the P.B. support.

support

(6) Remove the P.B. support from the relay panel.

(7) Remove the screws of the inverter P.C. board.

(8) Remove the inverter P.C. board from P.B. support.

  • Notes about attaching the inverter P.C. board
    1. When attaching the inverter P.C. board, clip the lead wires of the reactor to the wire saddles on the bottom of relay panel.
    2. After attaching the inverter P.C. board, make sure that the lead wires are connected and placed as shown in Photo 3.

Screw of the relay panel

Earth wires

Screws of the relay panel Screw of the P.B. support

Photo 4

57
OBH895

Screws of the inverter P.C. board

OPERATING PROCEDURE
3. Removing R.V. coil (1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the following connector: CN602 (R.V. coil) (3) Remove the R.V. coil.

Photo 5

PHOTOS

Screw of the R.V. coil

Brazed parts of 4-way valve

4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to section 1.) (2) Disconnect the lead wire to the reactor and the following connectors: CN671 (Defrost thermistor, discharge temperature thermistor and outdoor heart exchanger temperature thermistor) CN672 (Ambient temperature thermistor) (3) Pull out the discharge temperature thermistor from its holder. (Photo 9) (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor from its holder. (6) Pull out the ambient temperature thermistor from its holder.

Photo 6
Outdoor heat exchanger temperature thermistor

Ambient temperature thermistor

Defrost thermistor

58
OBH895

OPERATING PROCEDURE
5. Removing outdoor fan motor (1) Remove the top panel, cabinet and service panel. (Refer to section 1.)
(2) Disconnect the following connectors: CN931, CN932 (Fan motor)
(3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.

Photo 7

PHOTOS/FIGURES
Propeller fan nut Propeller fan

Screws of the outdoor fan motor

6. Removing the compressor and 4-way valve (1) Remove the top panel, cabinet and service panel. (Refer to section 1.) (2) Remove the back panel. (Refer to section 1.) (3) Remove the screws fixing the relay panel. (4) Remove the relay panel. (5) Remove the inverter assembly. (Refer to section 2.) (6) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa). (7) Detach the brazed part of the suction and the discharge pipe connected with compressor. (8) Remove the compressor nuts. (9) Remove the compressor. (10) Detach the brazed parts of 4-way valve and pipe. (Photo 6)

Photo 8

Brazed part of the discharge pipe

Brazed part of the suction pipe

Discharge temperature thermistor

59
OBH895

HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

© Copyright 2021 MITSUBISHI ELECTRIC CORPORATION Published: Jul. 2021. No. OBH895
Made in Japan

Specifications are subject to change without notice.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Mitsubishi Electric User Manuals

Related Manuals