TASSERON THHOSD5B Humidity Sensors with Temp Transmitter Instruction Manual

June 14, 2024
TASSERON

TASSERON THHOSD5B Humidity Sensors with Temp Transmitter

Overview

TASSERON-THHOSD5B-Humidity-Sensors-with-Temp-Transmitter-
fig-1

Technical Data

  • Transmitter Element: Pt1000 IEC 751
  • Loop Supply Voltage: 8 – 36 VDC, 100 Ohm load 10.5 – 36 VDC, 250 Ohm load 14.25 – 36 VDC
  • Supply Current: 4 – 24 mA
  • Resolution: 0.05% FS
  • Accuracy: 0.1% – 0.4% FSR
  • Connection: 2-pole AWG 22-16 / 0.35 – 1.5mm2 spring-loaded, Quick Connect Terminals
  • Operating Env. – 25°C- 50°C
  • Temp. Transmitter Ranges:
  • Range 1 (Range T): 0°C – 100°C / 32°F – 212°F
  • Range 2 (Range U): -7°C – 49°C / 20°F – 120°F
  • Range 3 (Range V): -18°C – 38°C / 0ºF – 100°F

Configuration Instructions for Tasseron Humidity Sensors
For an optional passive temperature sensor, connect one wire to each quick- connect terminal labeled “TEMP” (non-polar).

Instructions for 4 to 20 mA Output

TASSERON-THHOSD5B-Humidity-Sensors-with-Temp-Transmitter-
fig-2

DIP Switch Configuration

Step 1
Be sure the white Output mode DIP switches are in the proper configuration. For 4-20mA output, DIP switch #2 must be in the LEFT position. Switch #1 has no function in this mode.

Step 2
Terminate control wires in quick connects as indicated in the table above. Only 2 wires are needed for 4-20mA output mode; main power supply and signal output. These wires terminate at “VIN” and “4-20mA”.

Step 3
Power on control.

Instructions for 0-5V or 0-10V Output

TASSERON-THHOSD5B-Humidity-Sensors-with-Temp-Transmitter-
fig-4
DIP Switch Configuration

Step 1
Be sure the white Output mode DIP switch is in the proper configuration. For 0-5V output, DIP switch #1 must be in the LEFT position and DIP switch #2 must be in the RIGHT position. For 0-10V output, both #1 and #2 DIP switches must be in the RIGHT positions.

Step 2
Terminate control wires in quick connects as indicated in the table above. Three wires are needed for the Voltage output mode; main power supply (VIN), Common (COM), and signal output (VOUT).

Step 3
Power on control.

140 Choate Circle Montoursville, PA 17754  570.601.1971
sales@tasseronusa.com www.tasseronusa.com

Read User Manual Online (PDF format)

Loading......