TASSERON THHOSD5B Humidity Sensors
SAFE BOX HANDLING NOTES – PLEASE READ FIRST
To Open
- Depress the bottom latch with a slotted screwdriver and the lid will pop out.
- Pull the top of the lid straight out from the housing without lifting it.
- Once entirely pulled out, lift the lid and it will remain in the open position until closed.
To Close
- Push the lid down without latching the bottom.
- Push in the top hinges until they snap into place.
- Close the bottom until it latches.
- Optional screw provided to more permanently secure lid to housing.
Mounting Instructions
Step 1 – Drill a 15/16″ hole in the desired location in the duct
.
Step 2 – Align the opening in the mounting flange with the hole induct
and attach the mounting flange to the duct using self-tapping screws. (Insert
set screw if desired.)
Step 3 – Insert the sensor probe in the mounting flange and push until
the sensor snaps into place (unless using adjustable set screw mounting). Wire
through provided bottom or side access points. Additional snap-in conduit
adapters are available if necessary. Proceed to Configuration Instructions.
Step 1
Determine wiring location (north side of the building if possible). Drill a
hole, if necessary, then center and attach the mounting flange to the
building.
Step 2
If wiring from the rear, feed the wire from the hole into the rear access
point on the sensor. Snap the sensor onto the mounting flange.
Step 3
If wiring through side access points, pierce the grommet with a knife or
remove and snap in the conduit adapter. Additional conduit adapters were
available if necessary. Proceed to Configuration Instructions.
Step 1 – Feed wires through the hole in the rear of the sensor.
Step 2 – Mount with screws, then make connections.
Step 3 – Snap on the cover. Depress hooks through vents with a tool to
remove them.
Configuration Instructions for ALL Tasseron Humidity Sensors
For an optional passive temperature sensor, connect one wire to each quick-
connect terminal labeled “TEMP” (non-polar).
Instructions for 4 to 20 mA Output
**DIP Switch Configuration
**
Step 1 – Be sure the white Output mode DIP switches are in the proper
configuration (see Fig 1). For 4-20mA output, DIP switch #2 must be in the
LEFT/OFF position. Switch #1 has no function in this mode and is OFF by
default.
Step 2 – Terminate control wires in quick connects as indicated in the
table above. Only 2 wires are needed for 4-20mA output mode: 1. main power
supply and 2. signal output. These wires terminate at “VIN” and “4-20mA”.
Step 3 – Power on the control/power supply to the sensor.
Instructions for 0-5V or 0-10V Output
DIP Switch Configuration
Step 1 – Be sure the white Output mode DIP switch is in the proper
configuration. For 0-5V output, DIP switch #1 must be in the LEFT position and
DIP switch #2 must be in the RIGHT position (see Fig 2). For 0-10V output,
both #1 and #2 DIP switches must be in the RIGHT positions (see Fig 3).
Step 2 – Terminate control wires in quick connects as indicated in
the table above. Three wires are needed for Voltage output mode: main power
supply (VIN), common (COM), and signal output (VOUT).
Step 3 – Power on control/power supply to the sensor.