TASSERON THHOSD5B Humidity Sensors with Passive Temp Signal
WIRING DIAGRAM
- Temp Element: Interchangeable NTC thermistor, 2-wire
- RTD Pt100, Pt1000, 2-wire RTD Ni1000-891, Ni1000-TC5, 2 wire
- Sensor Value: NTC 10K Ohm type 2 25°C / 77°F
- NTC 10K Ohm type 3 25°C / 77°F
- NTC 20K Ohm 25°C / 77°F
- NTC 3K Ohm 25°C / 77°F
- RTD Pt1000 1000 Ohm 0°C / 32°F RTD
- Pt100 100 Ohm 0°C / 32°F RTD
- Ni1000-891 891 Ohm 0°C / 32°F RTD
- Ni1000-TC5 1000 Ohm 0°C / 32°F
- (Other elements on request)
Configuration Instructions for Tasseron Humidity Sensors
For an optional passive temperature sensor, connect one wire to each quick-
connect terminal labeled “TEMP” (non-polar).
Instructions for 4 to 20 mA Output
DIP Switch Configuration
Step 1 – Be sure the white Output mode DIP switches are in the proper
configuration. For 4-20mA output, DIP switch #2 must be in the LEFT position.
Switch #1 has no function in this mode.
Step 2 – Terminate control wires in quick connects as indicated in the
table above. Only 2 wires are needed for 4-20mA output mode; main power supply
and signal output. These wires terminate at “VIN” and “4-20mA”.
Step 3 – Power on control.
Instructions for 0-5V or 0-10V Output
DIP Switch Configuration
Step 1 – Be sure the white Output mode DIP switch is in the proper
configuration. For 0-5V output, DIP switch #1 must be in the LEFT position and
DIP switch #2 must be in the RIGHT position. For 0-10V output, both #1 and #2
DIP switches mu be in the RIGHT positions.
Step 2 – Terminate control wires in quick connects as indicated in the
table above. Three wires are needed for Voltage output mode; main power supply
(VIN), Common (COM), and signal output (VOUT).
Step 3 – Power on control.