APC EPDU1016S Switched Rack Power Distribution Unit Installation Guide
- June 14, 2024
- APC
Table of Contents
APC EPDU1016S Switched Rack Power Distribution Unit
Overview
This sheet provides installation information for your Easy PDU. Read the instructions carefully.
-
Receiving
Inspect the package and contents for shipping damage. Make sure all parts were sent. Immediately report any shipping damage to the shipping agent. Report missing contents, product damage, or other problems with the product to APC by Schneider Electric or your APC by Schneider Electric reseller. -
Material recycling
The shipping materials are recyclable. Please save them for later use, or dispose of them appropriately.
Safety
Read the following information before installing or operating your APC by Schneider Electric Rack Power Distribution Unit (PDU).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- The Rack PDU is intended to be installed and operated by a skilled person in a controlled location.
- Do not operate the Rack PDU with the covers removed.
- This Rack PDU is intended for indoor use only.
- Do not install this Rack PDU where excessive moisture or heat is present.
- Never install any wiring, equipment, or Rack PDUs during a lightning storm.
- Plug this Rack PDU into a grounded power outlet only. The power outlet must be connected to the appropriate branch circuit/mains protection (fuse or circuit breaker). Connection to any other type of power outlet may result in a shock hazard.
- Do not use extension cords or adapters with this Rack PDU.
- If a socket outlet is not accessible to the equipment, a socket outlet shall be installed.
- Do not work alone under hazardous conditions.
- Check that the power cord, plug, and socket are in good condition.
- Disconnect the Rack PDU from the power outlet before you install or connect equipment to reduce the risk of electric shock when you cannot verify grounding. Reconnect the Rack PDU to the power outlet only after you make all connections.
- Do not handle any kind of metallic connector before the power has been removed.
- Use one hand, whenever possible, to connect or disconnect signal cables to avoid a possible shock from touching two surfaces with different grounds.
- This unit does not have any user-serviceable parts. Repairs are to be performed only by factory-trained service personnel.
Failure to follow these instructions will result in death or serious injury.
WARNING FIRE HAZARD
- This equipment should be connected to a single-outlet dedicated circuit protected by a circuit breaker or fuse with the same current rating as the Rack PDU.
- The plug or inlet serves as the disconnect for the Rack PDU. Make sure the utility power outlet for the Rack PDU will be close to the Rack PDU and readily accessible.
- Some models of Rack PDUs are provided with IEC C14 or C20 inlets. Use of the proper power cord is the user’s responsibility.
Failure to follow these instructions can result in death or serious injury.
Installation
Mount the Rack PDU in a 19-inch NetShelter™ rack or other EIA-310-D standard 19-inch rack.
-
Choose a mounting position for the Rack PDU with either the front or the rear of the unit facing out of the rack. Your Rack PDU will occupy one (1) U-space.
NOTE: A notched hole on the NetShelter rack’s vertical rail indicates the middle of a U space.
NOTE: Install the cage nuts properly. See the illustration for proper cage nut orientation. -
Mount the unit in the NetShelter rack or EIA-310-D standard 19-inch rack with the provided hardware, four (4) M6 x 16 mm screws, and four (4) cage nuts.
Display Interface
Item | Function | Description |
---|---|---|
1 | LCD Display | View functional data |
2 | Run Indicator LED | Indicates the status when the power is on |
3
| ****
Outlet Status LED
| The LED illuminates when the outlet is energized Each status LED is numbered
and represents the numbered outlet on the back of the device.
4| Network Port| Connect the Rack PDU to your network
5| Temp/Humidity Port| Temp/Humidity Sensor connection port
6| Out Port| RS485 port sharing connection
7| In Port| RS485 port sharing connection
8| Down Function Button| Scroll for function status, press for Alarm status
(Press and hold for 10 seconds to reboot)
9| Up Function Button| Scroll for function status, Alarm shutoff
10| Reset Button| Press and hold for 4 seconds to reset to the default
settings
Press the Up or Down buttons to scroll through the displayed information.
To configure the network settings and access the Rack PDU
Connect the network cable to the network port 4 and apply power to the unit.
When you hear a “Beep” sound and the status LED 2 for the network connection
is flashing green, press the Up 9 or Down 8 function button until the IP
address appears.
To access the Rack PDU software interface, enter the IP address in your
browser address field. You will be prompted for a user name and password.
Enter the default “apc” for each. See the User Guide for this device online at
www.apc.com for more detailed information.
Specifications
Electrical
Nominal Input Voltage| 200 – 240 VAC
Maximum Input Current (Phase)| 16A
Input Frequency| 50/60Hz
Input Connection| IEC320 C20 16A
Output Voltage| 200 – 240 VAC
Output Connections| Eight (8) IEC-320-C13
Max. output current 10A
Circuit Breakers| None
Physical
Dimensions (H x W x D)| 44.4 x 482 x 200 mm (1.75 x 19 x 7.87 in)
Input power cord length| 2.5 m (8.2 ft)
Shipping dimensions (H x W x D)| 80 x 560 x 260 mm
(3.15 x 22.0 x 10.2 in)
Weight/Shipping weight| 2.8 kg (6.17 lb)/
3.6 kg (7.93 lb)
Environmental
Maximum elevation (above MSL) Operating/Storage|
0–3000 m (0–10,000 ft) /
0–15000 m (0–50,000 ft)
Temperature: Operating/Storage| –5 to 45°C (23 to 113°F)/
–25 to 65°C (–13 to 149°F)
Humidity: Operating/Storage| 5–95% RH, non-condensing
Compliance
EMC verification| CE EN55035, EN55032, EN55024
Safety verification| CE, TUV, EN/IEC62368-1
CE EU Contact Address| Schneider Electric, 35 rue Joseph Monier 92500 Rueil
Malmaison France
Environmental| RoHS & Reach
Life Support Policy
General policy
APC by Schneider Electric does not recommend the use of any of its products in
the following situations:
- In life-support applications where failure or malfunction of the APC by Schneider Electric product can be reasonably expected to cause failure of the life-support device or to affect significantly its safety or effectiveness.
- In direct patient care.
APC by Schneider Electric will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to APC by Schneider Electric that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) the liability of APC by Schneider Electric is adequately protected under the circumstances.
Examples of life-support devices
The term life-support device includes but is not limited to neonatal oxygen
analyzers, nerve stimulators (whether used for anesthesia, pain relief, or
other purposes), autotransfusion devices, blood pumps, defibrillators,
arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal
dialysis systems, neonatal ventilator incubators, ventilators (for adults and
infants), anesthesia ventilators, infusion pumps, and any other devices
designated as “critical” by the U.S. FDA.
Hospital-grade wiring devices and leakage current protection may be ordered as
options on many APC by Schneider Electric UPS systems. APC by Schneider
Electric does not claim that units with these modifications are certified or
listed as hospital-grade APC by Schneider Electric or any other organization.
Therefore these units do not meet the requirements for use in direct patient
care.
Radio frequency interference
Changes or modifications to this unit not expressly approved by the party
responsible for compliance could void the user’s authority to operate this
equipment.
1-Year Factory Warranty
This warranty applies only to the products you purchase for your use in accordance with this manual.
Terms of warranty
APC by Schneider Electric warrants its products to be free from defects in
materials and workmanship for a period of one year from the date of purchase.
APC by Schneider Electric will repair or replace defective products covered by
this warranty. This warranty does not apply to equipment that has been damaged
by accident, negligence or misapplication or has been altered or modified in
any way. Repair or replacement of a defective product or part thereof does not
extend the original warranty period. Any parts furnished under this warranty
may be new or factory-remanufactured.
Non-transferable warranty
This warranty extends only to the original purchaser who must have properly
registered the product. The product may be registered at the APC by Schneider
Electric’s website, www.apc.com.
Exclusions
APC by Schneider Electric shall not be liable under the warranty if its
testing and examination disclose that the alleged defect in the product does
not exist or was caused by the end user’s or any third person’s misuse,
negligence, improper installation or testing. Further, APC by Schneider
Electric shall not be liable under the warranty for unauthorized attempts to
repair or modify wrong or inadequate electrical voltage or connection,
inappropriate on-site operation conditions, corrosive atmosphere, repair,
installation, exposure to the elements, Acts of God, fire, theft, or
installation contrary to APC by Schneider Electric recommendations or
specifications or in any event if the APC by Schneider Electric serial number
has been altered, defaced, or removed, or any other cause beyond the range of
the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. APC BY SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION, AND FITNESS FOR A PARTICULAR PURPOSE. APC BY SCHNEIDER ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC BY SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC BY SCHNEIDER ELECTRIC’S SOLE LIABILITY AND THE PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. WARRANTIES EXTEND ONLY TO PURCHASERS AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL APC BY SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC BY SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, APC BY SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUENTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE. NO SALESMAN, EMPLOYEE OR AGENT OF APC BY SCHNEIDER ELECTRIC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY AN APC BY THE SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.
Warranty claims
Customers with warranty claims issues may access the APC by Schneider Electric
customer support network through the Support page of the APC by Schneider
Electric website, www.apc.com/support. Select your country from the country
selection pull-down menu at the top of the Web page. Select the Support tab to
obtain contact information for customer support in your region.
Worldwide Customer Support
Customer support for this product is available at www.apc.com
Trademarks
© 2020 APC by Schneider Electric. APC and NetShelter are trademarks owned
by Schneider Electric SE. All other trademarks are the property of their
respective owners.
FAQs
What is the APC EPDU1016S Switched Rack PDU?
The APC EPDU1016S is a switched rack power distribution unit designed to distribute power to multiple devices in a server rack environment.
How many outlets does the APC EPDU1016S have?
The number of outlets may vary, please refer to the product specifications for the exact number.
Can I remotely manage the APC EPDU1016S?
Yes, it offers remote management capabilities, allowing for power cycling and monitoring of connected devices.
Does the APC EPDU1016S provide surge protection?
It typically includes surge protection to safeguard connected equipment against power surges and spikes.
What is the maximum power capacity of the APC EPDU1016S?
The power capacity can depend on the model. Refer to the unit's specifications for the maximum load capacity.
Is the APC EPDU1016S rack-mountable?
Yes, it is designed to be mounted in a standard 19-inch server rack.
What kind of network connectivity does the APC EPDU1016S support?
The PDU supports Ethernet connectivity for network integration and remote management.
Can I control individual outlets on the APC EPDU1016S?
Switched PDUs like the EPDU1016S typically allow for individual outlet control, enabling on/off scheduling and load management.
Does the APC EPDU1016S have an LCD display?
Please check the product specifications to see if it includes an LCD display for real-time monitoring and control.
What kind of cable management features does the APC EPDU1016S offer?
It usually includes cable management features to help organize and route the power cables connected to the PDU.
Is there a warranty for the APC EPDU1016S?
The APC EPDU1016S Switched Rack PDU typically comes with a warranty of 1 year from the date of purchase.
What is the input voltage range for the APC EPDU1016S?
The input voltage range for this PDU will be specified in the technical specifications provided by APC.
References PDF:APC EPDU1016S Switched Rack Power Distribution Unit – Device.report
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>