Sioux Chief ProPlate Valved Plates-Panels Instruction Manual
- June 3, 2024
- Sioux Chief
Table of Contents
Fire-Rated ProPlate™
Installation Instructions
-
Install the ProPlate™ to a stud or to a bracket securely. Integral top/bottom track works with common flat brackets. To fix plate position, install a screw between plate and bracket. NOTE: Be sure “699 Series” mark on product is facing unfinished wall side.
-
Align tabs on valve base with socket and push valve into place. On back side of ProPlate™ snap clip of fire-rated bracket onto valve. Install ProPlate™ and fire-rated bracket to a stud or bracket. Integral plate track and fire-rated bracket track works with common flat brackets. Connect valve to water supply, and make all other connections per ASTM standard. NOTE: See instructions below to change valve orientation.
-
As desired, place the appropriate color clip to indicate hot (red) or cold (blue) water supply.
-
Be sure valve is in OFF position and test.
Replace any defective product. -
Install debris cover onto plate. Flush the water line, downstream of the valve, before operation.
-
At finish, remove debris cover and nylon valve cap. Check for leaks and replace any defective product. Install frame.
VALVE OUTLET REORIENTATION (AFTER DRYWALL)
- Holding the valve in place, loosen the swivel nut ½ turn.
- Re-orient the valve outlet to the desired direction. Hold valve firmly in place.
- Holding the valve in place, tighten the swivel nut completely.
- Be sure valve is in OFF position and perform pressure test. Replace any defective product.
|
---|---
IS-OMEGA FIRE RATED
Supply | Drainage | Support | Specialties |
---|
14940 Thunderbird Road
Kansas City, MO 64147
P 1.800.821.3944
F 1.800.758.5950
FIRE-RATED SINGLE-VALVE OUTLET PLATE
DESIGN SPECIFICATION
-
WALL CONSTRUCTION
a. Wood or metal stud construction
b. 16″ on-center stud construction.
c. Double-layer ⅝” gypsum construction with 2-hour fire rating. Single-layer ⅝” gypsum construction with 1-hour fire rating.
d. Plates cannot be installed back to back.
Fire-Rated escutcheon available separately (Item No. 699RF) -
PIPE/PLATE SUPPORT
a. Maximum 2 plates installed in a 16″ O.C. stud cavity secured to brackets when centered or direct mounted to stud.
b. ProPlate ™ Fire-rated bracket (back side of plate)
c. Common flat brackets. -
PIPE MATERIAL
a. Metallic or plastic water supply pipe.
b. Supply lines to be installed using ordinary methods. -
FIRE-RATED RESINS
Sioux Chief fire-rated ProPlate uses fire-rated resin.
NOTE: Gaps up to ½” around plate can be sealed with drywall plaster.
Larger gaps require firestop sealant applied to opening spanning entire drywall depth
THE FIRE-RATED PROPLATE IS CERTIFIED BY INTERTEK
TO THE FOLLOWING FIRE RATING STANDARDS:
Intertek
Control No. 5006619
ASTM E814 *SC/PF 120
bpdirectory.intertek.com
ASTM E-814 | UL1479
CAN/ULC S115
1hr (F), 56min (T) for 1-hour design Design No: SCMC/PF 60-01
2hrs (F), 2hrs (T) for 2-hour design Design No: SCMC/PF-120-1
FINISH INSTALLATION Sioux Chief Manufacturing Company
P: 1.800.821.3944
F: 1.800.758.5950
www.siouxchief.com