Circutor CEM M-ETH Communications Interface Instruction Manual
- June 15, 2024
- Circutor
Table of Contents
- SAFETY PRECAUTIONS
- DISCLAIMER
- VERIFICATION UPON RECEPTION
- PRODUCT DESCRIPTION
- DEVICE INSTALLATION
- DEVICE TERMINALS
- CONNECTION DIAGRAM
- OPERATION
- TECHNICAL FEATURES
- MAINTENANCE AND TECHNICAL SERVICE
- GUARANTEE
- EU DECLARATION OF CONFORMITY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Circutor CEM M-ETH Communications Interface Instruction Manual
SAFETY PRECAUTIONS
Follow the warnings described in this manual with the symbols shown below
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a specific point.
If you must handle the unit for its installation, start-up or maintenance, the following should be taken into consideration:
Incorrect handling or installation of the device may result in injury to personnel as well as damage to the device. In particular, handling with voltages applied may result in electric shock, which may cause death or serious injury to personnel. Defective installation or maintenance may also lead to the risk of fire.
Read the manual carefully prior to connecting the device. Follow all installation and maintenance instructions throughout the device’s working life. Pay special attention to the installation standards of the National Electrical Code.
Refer to the instruction manual before using the device
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can result in injury or damage to the device and /or installations.
CIRCUTOR S.A.U. reserves the right to modify features or the product manual without prior notification
DISCLAIMER
CIRCUTOR S.A.U. reserves the right to make modifications to the device or
the unit specifications set out in this instruction manual without prior
notice.
CIRCUTOR S.A.U. on its web site, supplies its customers with the latest
versions of the device specifications and the most updated manuals.
CIRCUTOR S.A.U. recommends using the original cables and accessories that are supplied with the device.
Note: The images of the devices are solely for the purpose of illustration and may differ from the original unit.
Table 1: Revision log
Date | Revision | Description |
---|---|---|
11/14 | M060B01-03-14A | Initial Version |
04/21 | M060B01-03-21A | Circutor logo change |
06/21 | M060B01-03-21B | Changes in the following sections: 5. |
11/22 | M060B01-03-22A | Changes in the following sections: 4.5. |
VERIFICATION UPON RECEPTION
Check the following points upon receiving the device:
- a) The device meets the specifications described in your order.
- b) The device has not suffered any damage during transport.
- c) Perform an external visual inspection of the device prior to switching it on.
- d) Check that it has been delivered with the following:
- An installation guide.
If any problem is noticed upon reception, immediately contact the transport company and/or CIRCUTOR’s after-sales service.
PRODUCT DESCRIPTION
The CEM M-ETH optical-electric interface converts the optical service port of
any device of the CEM range into an Ethernet port with MODBUS/TCP protocol.
The unit features:
- 3 indicator LEDs: POWER, LINK and LINK/ACT
The device is installed on 2-step DIN rails, on the left of any device of the CEM range
DEVICE INSTALLATION
PRELIMINARY RECOMMENDATIONS
In order to use the device safely, it is critical that the individuals who handle it follow the safety measures set out in the standards of the country where it is being used, use the necessary personal protective equipment and pay attention to the various warnings indicated in this instruction manual.
The CEM M-ETH device must be installed by authorised and qualified staff.
The power supply plug must be disconnected before handling, altering the connections or replacing the device. It is dangerous to handle the unit while it is powered.
Also, it is critical to keep the cables in perfect condition in order to avoid accidents, personal injury and damage to installations.
The manufacturer of the device is not responsible for any damage resulting from failure by the user or installer to observe the warnings and/or recommendations set out in this manual, nor for damage resulting from the use of non-original products or accessories or those made by other manufacturers.
If an anomaly or malfunction is detected in the device, do not use the device to take any measurements. Inspect the work area before taking any measurements. Do not take measurements in dangerous areas or where there is a risk of explosion.
Disconnect the device from the power supply (unit and measuring system power
supply) before maintaining, repairing or handling the device’s connections.
Please contact the after-sales service if you suspect that there is an
operational fault in the device.
INSTALLATION
On the side of the device are all of the indications adjusted to the CEI
62052-11 standard.
The device is installed on a DIN rail.
Before connecting the device, you must couple it to a CEM energy meter as
shown in Figure 1 and Figure 2.
Figure 1: Coupling the CEM M-ETH to a CEM energy meter.
Figure 2: Coupled CEM M-ETH and CEM.
Terminals, opening covers or removing elements can expose parts that are
hazardous to the touch while the unit is powered. Do not use the device until
it is fully installed.
The device must be connected to a power circuit that is protected with gL
fuses (IEC 60269) or M fuses, with a rating of 0.5 to 2 A. It must be fitted
with a circuit breaker switch or equivalent device for disconnecting the
device from the power supply mains.
The RCCB or equivalent device must be in the immediate vicinity of the device
and must be easily accessible.
The power circuit is connected with a cable with a section measuring up to 2.5
mm2 .
The device’s operating temperature is between -25ºC and +70ºC; always use
connection cables that can withstand these temperatures.
DEVICE TERMINALS
Table 2: List of CEM M-ETH terminals
Device terminals
1: Auxiliary power supply.
2: Auxiliary power supply.
3: Ethernet.
Figure 3: CEM M-ETH terminals.
CONNECTION DIAGRAM
The connection between the CEM M-ETH and the Ethernet network must be made
with a twisted pair cable (100Base-TX: 100Mbit/s on two pairs of wires of
Category 5 or higher). The segment length of the 100Base-T, 10BaseT and
1000Base-T cables is limited to 100 m.
Figure 4: CEM M-ETH connection diagram
OPERATION
The CEM M-ETH is designed to be used as a Ethernet port for any device in the CEM family, using the mechanical coupling next to the optical port.
OPERATING PRINCIPLE
The CEM M-ETH is an optional accessory for electrical energy meters from
the CEM range that are mounted on DIN rails.
The CEM M-ETH provides CEM units with Ethernet communications with the
MODBUS/TCP protocol.
Once the device is coupled to the CEM energy meter (See “3.2.-
INSTALLATION”) the LINK LED turns green to let the user know that the link has
been made correctly.
From this point onward, the new CEM energy meter + CEM M-ETH assembly
functions as a single device.
LED INDICATORS
The device has three indicator LEDs:”
Figure 5: CEM M-ETH indicator LEDs
- POWER LED: Indicates that the device is connected to a power supply.
LINK LED: Indicates the status of the link with the CEM unit. (Table 3)
Table 3: LINK LED, colour codes
LINK LED
Colour| Status
Flashing red| Device not linked
Steady green| Device linked
- LED LINK/ACT, indicates the state of the Ethernet connection, Table 4
Table 4: LED LINK/ACT
LED LINK/ ACT
Colour| Status
On| Ethernet link
Off| No Ethernet link
Flashing| Activity on this port
OPTICAL COMMUNICATIONS PORT
The device has an optical serial communications port on its right side, in
accordance with the UNE EN 62056-21:2003 standard, in order to communicate
with other devices in the CEM family.
RS-485 COMMUNICATIONS
MODBUS/TCP PROTOCOL
The MODBUS/TPC protocol is the MODBUS RTU protocol with a TCP interface that
runs on Ethernet.
MODBUS/TCP uses TCP/IP and Ethernet to manage the data of MODBUS messages
between compatible devices.
The MODBUS/TCP protocol embeds a standard MODBUS data frame in a TCP frame
without the Modbus checksum, as shown in the diagram in the figure.
(This information is embedded into the data portion of the TCP frame)
Figure 6: Construction of a MODBUS/TCP data frame.
Table 5 shows the format of the MODBUS/TCP frame.
Table 5: MODBUS/TCP frame format
Name | Length | Function |
---|---|---|
Transaction identifier | 2 | For message synchronisation between the server and |
client.
Protocol identifier| 2| Value 0 for MODBUS/TCP
Field length| 2| Number of bytes remaining in the frame
Unit identifier| 1| Peripheral number
Function code| 1| Modbus function number
Data bytes| n| Response or command data
The MODBUS functions implemented in the device are:
Functions 03 and 04: Reading of logs.
Function 10: Writing of multiple logs.
VARIABLES MODBUS
All MODBUS map addresses are hexadecimal.
Configuration variables
The Read and Write functions are implemented for these variables.
Table 6: Modbus configuration variables CEM M-RS485.
Description| Address| Size| Valid data range| Default
value
---|---|---|---|---
Impulse output type| 0x0080| 16 bits| 0: Active energy , 1:
Reactive energy| 0
Impulse output weight| 0x0081| 16 bits| Wh/impulse 0 … 99999| –
Cost per kWh| 0x00B0| 32 bits| 0.0000… 9999.9999 with 4 decimal places
ofresolution| –
KgCO2| 0x00B2| 32 bits| 0.0000… 9.0000 with 4 decimal places ofresolution| –
Note: Some MODBUS variables may not be available depending on the CEM energy meter coupled to the CEM M-ETH. See “4.4.2.7.- Available addresses by device”.
Energy
The Read function is implemented for these variables.
Table 7: Modbus variables: Energy
Description | Address | Size | Units |
---|
Total values
Imported active energy| 0x0000| 32 bits| Wh
Exported active energy| 0x0002| 32 bits| Wh
Q1 reactive energy| 0x0004| 32 bits| varh
Q2 reactive energy| 0x0006| 32 bits| varh
Q3 reactive energy| 0x0008| 32 bits| varh
Q4 reactive energy| 0x000A| 32 bits| varh
Partial values
Partial imported active energy| 0x0030| 32 bits| Wh
Partial exported active energy| 0x0032| 32 bits| Wh
Q1 partial reactive energy| 0x0034| 32 bits| varh
Q2 partial reactive energy| 0x0036| 32 bits| varh
Q3 partial reactive energy| 0x0038| 32 bits| varh
Q4 partial reactive energy| 0x003A| 32 bits| varh
Note: Some MODBUS variables may not be available depending on the CEM
energy meter coupled to the CEM M-ETH. See “4.4.2.7.- Available addresses by
device”.
Operating time, cost and KgCO2 atmospheric emissions
The Read function is implemented for these variables.
Table 8: Modbus variables: Operating time, costs and KgCO2
Description | Address | Size | Units |
---|---|---|---|
Cost of the partial consumption | 0x00C0 | 32 bits | – |
KgCO2 atmospheric emissions of the partial consumption | 0x00C2 | 32 bits | – |
Hours of partial operation | 0x00C4 | 32 bits | ( 1 decimal place) |
Hours of total operation | 0x00C6 | 32 bits | ( 1 decimal place) |
Note: Some MODBUS variables may not be available depending on the CEM
energy meter coupled to the CEM M-ETH. See “4.4.2.7.- Available addresses by
device”.
Instantaneous values
The Read function is implemented for these variables.
Table 9: Modbus variables: Instantaneous values�
Description | Address | Size | Units |
---|---|---|---|
Phase 1 voltage | 0x0732 | 32 bits | V (1 primary decimal place) |
Phase 2 voltage | 0x0734 | 32 bits | V (1 primary decimal place) |
Phase 3 voltage | 0x0736 | 32 bits | V (1 primary decimal place) |
Phase 1 current | 0x0738 | 32 bits | A (2 primary decimal places) |
Phase 2 current | 0x073A | 32 bits | A (2 primary decimal places) |
Phase 3 current | 0x073C | 32 bits | A (2 primary decimal places) |
Phase 1 cos φ | 0x073E | 32 bits | 2 decimal places |
Table 9 (Continuation): Modbus variables: Instantaneous values.
Description | Address | Size | Units |
---|---|---|---|
Phase 2 cos φ | 0x0740 | 32 bits | 2 decimal places |
Phase 3 cos φ | 0x0742 | 32 bits | 2 decimal places |
Phase 1 active power | 0x0746 | 32 bits | W |
Phase 2 active power | 0x0748 | 32 bits | W |
Phase 3 active power | 0x074A | 32 bits | W |
Total active power | 0x074C | 32 bits | W |
Phase 1 reactive power | 0x074E | 32 bits | var |
Phase 2 reactive power | 0x0750 | 32 bits | var |
Phase 3 reactive power | 0x0752 | 32 bits | var |
Total reactive power | 0x0754 | 32 bits | var |
Phase 1 apparent power | 0x0756 | 32 bits | VA |
Phase 2 apparent power | 0x0758 | 32 bits | VA |
Phase 3 apparent power | 0x075A | 32 bits | VA |
Total apparent power | 0x075C | 32 bits | VA |
Note: Some MODBUS variables may not be available depending on the CEM
energy meter coupled to the CEM M-ETH. See “4.4.2.7.- Available addresses by
device”.
Other parameters
The Read function is implemented for these variables.
Table 10: Modbus variables: Other parameters./
Description | Address | Size | Units |
---|---|---|---|
Energy meter model 1) | 0xF010 | 6×16 bits | 12 bytes in ASCII format |
Serial no | 0x2710 | 32 bits | – |
Transformation ratios
Voltage primary| 0x044C| 32 bits| V (1 decimal place)
Voltage secondary| 0x044E| 32 bits| V (1 decimal place)
Current primary| 0x0450| 32 bits| A (1 decimal place)
Current secondary| 0x0452| 32 bits| A (1 decimal place)
Energy meter firmware version
Higher firmware version| 0x0050| 16 bits| –
Lower firmware version| 0x0051| 16 bits| –
Revised firmware version| 0x0052| 16 bits| –
Communications module firmware version
Higher firmware version| 0x0578| 16 bits| –
Lower firmware version| 0x0579| 16 bits| –
Revised firmware version| 0x057A| 16 bits| –
Note: Some MODBUS variables may not be available depending on the CEM energy meter coupled to the CEM M-ETH. See “4.4.2.7.- Available addresses by device”.
- Energy meter model description table, Table 11.
Table 11: Energy meter model description table.
Options | C10 | C20 | C30 | bytes in ASCII format | |
---|---|---|---|---|---|
Connection mode | 2 wires | ü | 2 | ||
4 wires | ü | ü | 4 | ||
**Accuracy** | Class B active / Does not measure reactive energy | ü | ü | ||
ü | 10 | ||||
Class B active / Class 2.0 reactive | ü | ü | ü | 12 | |
**Measurement voltage** | 1×230 | ü | E | ||
1×127 | ü | B | |||
3×127/220 … 3×230/400 V | ü | U | |||
3×127/220 V | ü | ü | N | ||
3×230/400 V | ü | ü | Q | ||
3×57/100 … 3×230/400 V | ü | V | |||
3×57/100 V | ü | L | |||
3×63.5/110 V | ü | M | |||
**Current measurement** | Shunt 10(60) A | ü | S4 | ||
Shunt 5(65) A | ü | S7 | |||
Direct 10(60)A | ü | D4 | |||
Direct 5(65)A | ü | D7 | |||
Transformer 5(10) A | ü | T5 | |||
Transformer 5(6) A | ü | T6 | |||
**Frequency** | 50Hz | ü | ü | ü | A |
60 Hz | ü | ü | ü | B | |
Automatic (50/60Hz) | ü | ü | ü | C | |
Communications | Without communications | ü | ü | ü | 0 |
Side optical service port | ü | ü | ü | 1 | |
Expansion | Without inputs/outputs | ü | ü | ü | 0 |
Input/ Output (Optocoupler) | ü | ü | ü | 1 | |
Model | Box for assembly on DIN rail | ü | ü | ü | E |
**Number of quadrants** | 2 quadrants | ü | ü | ü | 0 |
4 quadrants | ü | ü | ü | 1 | |
Storage in both directions | ü | ü | ü | 2 | |
Additional features | No special features | ü | ü | ü | 0 |
Partial energy reset
The 0x05 function is implemented for this variable.
Table 12: Modbus variables: Energy
Description | Address | Activation |
---|---|---|
Partial energy reset | 0x0800 | 0xFF00 |
Available addresses by device
Table 13: Modbus variables: Available addresses by device.
Address | C10 | C20 | C30 | Description |
---|---|---|---|---|
0x03E8 | ü | ü | ü | Modbus Address |
0x03E9 | ü | ü | ü | Transmission speed |
0x03EA | ü | ü | ü | Communications configuration |
0x0080 | ü | ü | ü | Impulse output type |
0x0081 | ü | ü | ü | Impulse output weight |
0x00B0 | ü | ü | ü | Cost per kWh |
0x00B2 | ü | ü | ü | KgCO2 |
0x0000 | ü | ü | ü | Imported active energy |
0x0002 | ü | ü | ü | Exported active energy |
0x0004 | ü | ü | ü | Q1 reactive energy |
0x0006 | ü | ü | ü | Q2 reactive energy |
0x0008 | ü | ü | ü | Q3 reactive energy |
0x000A | ü | ü | ü | Q4 Reactive energy |
0x0030 | ü | ü | ü | Partial imported active energy |
0x0032 | ü | ü | ü | Partial exported active energy |
0x0034 | ü | ü | ü | Q1 partial reactive energy |
0x0036 | ü | ü | ü | Q2 partial reactive energy |
0x0038 | ü | ü | ü | Q3 partial reactive energy |
0x003A | ü | ü | ü | Q4 partial reactive energy |
0x00C0 | ü | ü | ü | Cost of the partial consumption |
0x00C2 | ü | ü | ü | KgCO2 atmospheric emissions of the partial consumption |
0x00C4 | ü | ü | ü | Partial operating time |
0x00C6 | ü | ü | ü | Total operating time |
0x0732 | ü | ü | ü | Phase 1 voltage |
0x0734 | ü | ü | Phase 2 voltage | |
0x0736 | ü | ü | Phase 3 voltage | |
0x0738 | ü | ü | ü | Phase 1 current |
0x073A | ü | ü | Phase 2 current | |
0x073C | ü | ü | Phase 3 current | |
0x073E | ü | ü | ü | Phase 1 cos φ |
0x0740 | ü | ü | Phase 2 cos φ | |
0x0742 | ü | ü | Phase 3 cos φ | |
0x0746 | ü | ü | ü | Phase 1 active power |
0x0748 | ü | ü | Phase 2 active power | |
0x074A | ü | ü | Phase 3 active power | |
0x074C | ü | ü | ü | Total active power |
0x074E | ü | ü | ü | Phase 1 reactive power |
0x0750 | ü | ü | Phase 2 reactive power | |
0x0752 | ü | ü | Phase 3 reactive power | |
0x0754 | ü | ü | ü | Total reactive power |
0x0756 | ü | ü | ü | Phase 1 apparent power |
0x0758 | ü | ü | Phase 2 apparent power | |
0x075A | ü | ü | Phase 3 apparent power |
Table 13 (Continuation): Modbus variables: Available addresses by device.
Address | C10 | C20 | C30 | Description |
---|---|---|---|---|
0x075C | ü | ü | ü | Total apparent power |
0xF010 | ü | ü | ü | Energy meter model |
0x2710 | ü | ü | ü | Serial no. |
0x044C | ü | Voltage primary | ||
0x044E | ü | Voltage secondary | ||
0x0450 | ü | Current primary | ||
0x0452 | ü | Current secondary | ||
0x0050 | ü | ü | ü | Higher firmware version |
0x0051 | ü | ü | ü | Lower firmware version |
0x0052 | ü | ü | ü | Revised firmware version |
CONFIGURATION WEBSITE
To access the internal configuration website, the device’s IP address has
to be entered into the browser address bar.
To access the configuration website, open the screen shown in Figure 7 and
enter the Username and Password. The default values are shown in Table 14.
Figure 7: Accessing the configuration website.
Table 14: Accessing the configuration website.
Accessing the configuration website
Username| admin
Password| circuitry
Note: For security reasons, you need to change the login password. You
can change it on the Security screen, Figure 10.
The website of the device can be used to:
-
On the Device Info screen, view the device’s information and settings for Ethernet communications (Figure 8).
-
On the Communications screen, edit the Ethernet communications settings (Figure 9).
-
On the Security screen (Figure 10) change the login password to the configuration website.
-
On the Firmware screen, update the device’s firmware (Figure 11).
TECHNICAL FEATURES
Power supply
Rated voltage| 230 V~ ± 20%
Consumption| 2.4… 2.7 VA
Frequency| 50/60 Hz with no differentiation
Installation category| CAT III 300 V
Insulation
AC voltage| 4kV RMS 50Hz during 1 minute
Overimpulse
1.2/50ms 0 Ω source impedance| 6 kV at 60º and 240º, with
positive and negative polarization
Memory
Setup, events, load curve| Non-volatile EEPROM memory
User interface
~~ LED| ~~3 LEDs ( POW ER – LINK – LINL/ACT)
Communication
Communications protocol| Modbus/TCP
Environmental features
Operating temperature| -25ºC… +70ºC
Storage temperature| -35ºC… +80ºC
Relative humidity (non-condensing)| 5 … 95%
Maximum altitude| 2,000 m
Protection degree IP| IP 51 installedIP 40 in the terminal area
Protection degree IK| IK08
Pollution degree| 2
Use| indoor
Mechanical features
Dimensions (mm)| Figure 12
Enclosure| ABS + V0 polycarbonate
Weight| 100 g.
Standards
Safety requirements for electrical units for measurement, control and
laborato- ry use. Part 1: General requirements.| EN 61010-1: 2010
Electromagnetic compatibility (CEM). Part 6-2: Generic standards. Immunity for
industrial environments.| EN 61000-6-2: 2005
Electromagnetic compatibility (CEM). Part 6-3: Generic standards. Emission
standard for residential, commercial and light industry environments.| EN
61000-6-3: 2007
MAINTENANCE AND TECHNICAL SERVICE
The device does not need any type of maintenance.
In the case of any query in relation to device operation or malfunction, please contact the CIRCUTOR S.A.U Technical Support Service.
Technical Assistance Service
Vial Sant Jordi, s/n, 08232 – Viladecavalls (Barcelona)
Tel: 902 449 459 (Spain) / +34 937 452 919 (outside of Spain)
email: sat@circutor.com
GUARANTEE
-
CIRCUTOR guarantees its products against any manufacturing defect for two years after the delivery of the units.
CIRCUTOR will repair or replace any defective factory product returned during the guarantee period. -
No returns will be accepted and no unit will be repaired or replaced if it is not accompanied by a report indicating the defect detected or the reason for the return.
-
The guarantee will be void if the units has been improperly used or the storage, installation and maintenance instructions listed in this manual have not been followed. “Improper usage” is defined as any operating or storage condition contrary to the national electrical code or that surpasses the limits indicated in the technical and environmental features of this manual.
-
CIRCUTOR accepts no liability due to the possible damage to the unit or other parts of the installation, nor will it cover any possible sanctions derived from a possible failure, improper installation or “improper usage” of the unit. Consequently, this guarantee does not apply to failures occurring in the following cases:
- Overvoltages and/or electrical disturbances in the supply;
- Water, if the product does not have the appropriate IP classification;
- Poor ventilation and/or excessive temperatures;
- Improper installation and/or lack of maintenance;
- Buyer repairs or modifications without the manufacturer’s authorization.
EU DECLARATION OF CONFORMITY
Madecals (Spain) 20/09/2017 General Manager: Ferran G Tome
CIRCUTORS.A.U.
Vial Sant Jordi, s/n
08232 -Viladecavalls (Barcelona)
Tel.: (+34) 93 745 29 00 – Fax: (+34) 93 745 29 14
www.circutor.com
central@circutor.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>