EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Centre Installation Guide

June 13, 2024
EPH CONTROLS

EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Centre Installation Guide
EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring
Centre

Factory Default Settings

Zone 9 Switch: UFH
Zone 10   Switch: UFH

Grey and Orange terminals of the UFH valve are electrically linked. If UFH valve is fitted, remove this link.

Specifications

Power supply: 230Vac 50-60Hz
Number of Zones: 10
Power Supply Indication: Yes
Heat Enable Indication: Yes
UFH Valve Indication: Yes
Zone 1 to Zone 10 Indication: Yes
Ambient temperature: 0…45°C
Admissible ambient humidity: 5-95%RH
Dimensions: 380 x 165 x 50 mm
Heat Enable contact rating: 3A
UFH Pump contact rating: 3A
IP rating: IP20
Max. No. of actuators per zone: 4
Max. Permissible Load 5A: Resistive

Mounting and Installation

  1. Remove the UFH10 from its packaging.
  2. The UFH10 can be directly mounted on a wall using the fixing holes on the base of the unit or it can be directly mounted on DIN rail.
    Mounting and Installation

Wiring Centre Terminals

Power Supply

L 230Vac Live
E Earth
N Neutral

Programmer

L 230Vac to the programmer.
E Earth to the programmer.
N Neutral to the programmer.
1 Zone 1 output from programmer to the wiring centre.
2 Zone 2 output from programmer to the wiring centre.
3 Zone 3 output from programmer to the wiring centre.
4 Zone 4 output from programmer to the wiring centre.

Thermostats (Zone 1 to Zone 8)

L Live supply to the thermostat.
1 Timed switch live to room stat from programmer zone 1.
2 Timed switch live to room stat from programmer zone 2.
E Earth.
N Neutral supply to the thermostat.
S/L Switch live from the thermostat to the wiring centre.

Note: With thermostats 1 to 8, you have an option of; one of two time inputs.

Thermostats (Zone 9 and Zone 10)

L Live supply to the thermostat.
1 Timed switch live to room stat from programmer zone 1
2 Timed switch live to room stat from programmer zone 2
3 Timed switch live to room stat from programmer zone 3
4 Timed switch live to room stat from programmer zone 4
E Earth.
N Neutral supply to the thermostat.
S/L Switch live from the thermostat to the wiring centre.

Note: With thermostats 9 & 10, you have an option of; one of four time inputs.

Heat Enable (Boiler / Heat Pump On)

LS Live supply
E Earth
LR Live return

This is a volt free relay which is switched on when there is a call for heat.

If 230V is applied to terminal LS and there is a call for heat, 230V will come back on terminal LR.

UFH Pump (Underfloor Heating Pump)

L 230Vac Live
E Earth
N Neutral

When an underfloor heating zone calls for heat, 230V is sent to the underfloor heating manifold pump.

Best practice is to wire the underfloor heating manifold pump through a high limit thermostat which is mounted on the manifold.

UFH Valve (Underfloor Heating Valve)

GR Grey Switch Live
OR Orange Permanent Live
L Live
E Earth
N Neutral

When an underfloor heating zone calls for heat, 230V is sent to the Underfloor heating valve.
The valves auxiliary contacts are wired to the GR and OR terminals.
Note: Please refer to factory default settings on page 1.

Actuators (Zone 1 to Zone 8)

L 230V Live supply to the actuator.
N Neutral supply to the actuator.

There are two terminals marked L & N for each zone.

Actuators (Zone 9 and Zone 10)

. Live supply to the actuator.
N Neutral supply to the actuator.

There are two terminals marked L and two terminals marked N for each zone.

Both zones 9 and 10 have a switch associated with each zone.

This allows the installer to use these zones as underfloor heating zones or radiator / hot water zones.

Operation of Zone 9 & 10 UFH – RAD / HW switches

If set to UFH – When the thermostat calls for heat, the actuator, boiler and pump / valve outputs are enabled.

If set to RAD / HW – When the thermostat calls for heat, the actuator is enabled.

To enable the boiler output, the actuator auxiliary contacts (Grey and Orange wires) must be connected to the LS & LR terminals of the Heat Enable.

SWITCH SELECTED| HEAT ENABLE| UFH PUMP| UFH VALVE| ZONE VALVE ACTUATOR
---|---|---|---|---
UFH| On| On| On| On
RAD| Off| Off| Off| On

UFH10 – 10 x Underfloor Heating Zones

c/w Mains Operated Programmable Thermostats.

Options:
Underfloor Heating Zones

Note: Please refer to individual thermostat wiring diagrams.

CONTROLS INSTALLED
UFH Pump Yes
UFH Valve Yes
UFH Actuators Yes
Programmer
RAD Valve
HW Valve

Underfloor Heating Zones

230V on OR & L when a UFH zone calls for heat.
If no valve is fitted, GR & OR must be linked out.

UFH10 – 10 x Underfloor Heating Zones

c/w Mains Operated Non- Programmable Thermostats. Options:

Note: Please refer to individual thermostat wiring diagrams.

CONTROLS INSTALLED
UFH Pump Yes
UFH Valve Yes
UFH Actuators Yes
Programmer R47
RAD Valve
HW Valve

In this example:

  • Zone 1 on the programmer is controlling thermostats 1, 2, 3 & 4
  • Zone 2 on the programmer is controlling thermostats 5, 6, 7 & 8
  • Zone 3 on the programmer is controlling thermostat 9
  • Zone 4 on the programmer is controlling thermostat 10
    Underfloor Heating Zones

230V on OR & L when a UFH zone calls for heat.
If no valve is fitted, GR & OR must be linked out

c/w Mains Operated Non- Programmable Setback Thermostats.

Options:

Note: Please refer to individual thermostat wiring diagrams.

CONTROLS INSTALLED
UFH Pump Yes
UFH Valve Yes
UFH Actuators Yes
Programmer R47
RAD Valve
HW Valve

In this example:

  • Zone 1 on the programmer is controlling thermostats 1, 2, 3 & 4
  • Zone 2 on the programmer is controlling thermostats 5, 6, 7 & 8
  • Zone 3 on the programmer is controlling thermostat 9
  • Zone 4 on the programmer is controlling thermostat 10
    Underfloor Heating Zones

UFH10 – 8 x Underfloor Heating Zones

  • 1 x Radiator Zone
  • 1 x Hot Water Zone
    Underfloor Heating Zones

Note: Please refer to individual thermostat wiring diagrams.

CONTROLS INSTALLED
UFH Pump Yes
UFH Valve Yes
UFH Actuators Yes
Programmer R47
RAD Valve V22_P
HW Valve V22_P

In this example:

  • Zone 1 on the programmer is controlling thermostats 1, 2, 3 & 4
  • Zone 2 on the programmer is controlling thermostats 5, 6, 7 & 8
  • Zone 3 on the programmer is controlling thermostat 9
  • Zone 4 on the programmer is controlling thermostat 10
    Underfloor Heating Zones

UFH10 is compatible with the following EPH thermostats

Electro – Mechanical Thermostats
Electro - Mechanical Thermostats

Programmable Thermostats
Programmable Thermostats

Non Programmable Thermostats
Non Programmable Thermostats

Cylinder Thermostats
Cylinder Thermostats

EPH Controls IE

technical@ephcontrols.com
www.ephcontrols.com/contact-us
T +353 21 471 8440
QR Code

EPH Controls UK

technical@ephcontrols.co.uk
www.ephcontrols.co.uk/contact-us
T +44 1933 322 072
QR Code

Documents / Resources

| EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Centre [pdf] Installation Guide
UFH10, UFH10 10 Zone Underfloor Heating Wiring Centre, 10 Zone Underfloor Heating Wiring Centre, Underfloor Heating Wiring Centre, Wiring Centre, Centre
---|---
| EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Centre [pdf] User Guide
UFH10 10 Zone Underfloor Heating Wiring Centre, UFH10, 10 Zone Underfloor Heating Wiring Centre, Underfloor Heating Wiring Centre, Heating Wiring Centre, Wiring Centre, Centre

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals