APC EPDU1016B Power Distribution Unit Installation Manual

June 13, 2024
APC

APC EPDU1016B Power Distribution Unit

Easy PDU Basic Rack PDU Installation EPDU1016B

Worldwide Customer Support

Customer support for this product is available at www.apc.com

© 2021 APC by Schneider Electric. APC and NetShelter are trademarks owned by Schneider Electric SE. All other trademarks are property of their respective owners.

990-6249A

11/2021

Overview

This sheet provides installation information for your Easy PDU. Read the instructions carefully.

  • Receiving
    Inspect the package and contents for shipping damage. Make sure all parts were sent. Immediately report any shipping damage to the shipping agent. Report missing contents, product damage, or other problems with the product to APC by Schneider Electric or your APC by Schneider
Electric reseller
  • Material recycling
    The shipping materials are recyclable. Please save them for later use, or dispose of them appropriately.

  • Safety
    Read the following information before installing or operating your APC by Schneider Electric Rack Power Distribution Unit (PDU).

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • The Rack PDU is intended to be installed and operated by a skilled person in a controlled location.
  • Do not operate the Rack PDU with the covers removed.
  • This Rack PDU is intended for indoor use only.
  • Do not install this Rack PDU where excessive moisture or heat is present.
  • Never install any wiring, equipment, or Rack PDUs during a lightning storm.
  • Plug this Rack PDU into a grounded power outlet only. The power outlet must be connected to appropriate branch circuit/mains protection (fuse or circuit breaker). Connection to any other type of power outlet may result in a shock hazard.
  • Do not use extension cords or adapters with this Rack PDU.
  • If a socket-outlet is not accessible to the equipment, a socket-outlet shall be installed.
  • Do not work alone under hazardous conditions.
  • Check that the power cord, plug, and socket are in good condition.
  • Disconnect the Rack PDU from the power outlet before you install or connect equipment to reduce the risk of electric shock when you cannot verify grounding. Reconnect the Rack PDU to the power outlet only after you make all connections.
  • Do not handle any kind of metallic connector before the power has been removed.
  • Use one hand, whenever possible, to connect or disconnect signal cables to avoid a possible shock from touching two surfaces with different grounds.
  • This unit does not have any user-serviceable parts. Repairs are to be performed only by factory-trained service personnel.

Failure to follow these instructions will result in death or serious injury.

WARNING

FIRE HAZARD

  • This equipment should be connected to a single-outlet dedicated circuit protected by a circuit breaker or fuse with the same current rating as the Rack PDU.
  • The plug or inlet serves as the disconnect for the Rack PDU. Make sure the utility power outlet for the Rack PDU will be close to the Rack PDU and readily accessible.
  • Some models of Rack PDUs are provided with IEC C14 or C20 inlets. Use of the proper power cord is the user’s responsibility.

Failure to follow these instructions can result in death or serious injury.

Installation

Mount the Rack PDU in a 19-inch NetShelter™ rack or other EIA-310-D standard 19-inch rack.

  1. Choose a mounting position for the Rack PDU with either the front or the rear of the unit facing out of the rack. Your Rack PDU will occupy one (1) U-space.

    • NOTE: A notched hole on the NetShelter rack’s vertical rail indicates the middle of a U-space. NOTE: Install cage nuts properly. See the illustration for proper cage nut orientation.
  2. Use the provided hardware, four (4) M6 x 16 mm screws and four (4) cage nuts.

Specifications

Electrical

Nominal Input Voltage| 200 – 240 VAC
Maximum Input Current (Phase)| 16A
Input Frequency| 50/60Hz
Input Connection| IEC-320 C20 (16A)
Output Voltage| 200 – 240 VAC
Maximum Output Current (Outlet)| 10A
Maximum Output Current (Phase)| 16A
Output Connections| IEC 320 C13 (10A)
Output Quantities| Eight (8)
Physical
Dimensions (H x W x D)| 44.4 x 482 x 44.4 mm (1.75 x 19 x 1.75 in)
Input power cord length| 2.5 m (8.2 ft)
Shipping dimensions (H x W x D)| 150 x 560 x 80 mm (3.8 x 22.8 x 3.15 in)
Weight/Shipping weight| 0.58 kg (1.27 lb) / 1.18kg (2.60 lb)
Environmental
Maximum elevation (above MSL) Operating/Storage| 0– 3000 m (0–10,000 ft) / 0–15000 m (0–50,000 ft)
Temperature: Operating/Storage| –5 to 45°C (23 to 113°F) / –25 to 65°C (–13 to 149°F)
Humidity: Operating/Storage| 5–95% RH, non-condensing
Compliance
EMC verification| CE EN55035, EN55032, EN55024
Safety verification| CE, TUV, UKCA, EN/IEC62368-1
CE EU Contact Address| Schneider Electric, 35 rue Joseph Monier 92500 Rueil Malmaison France
Environmental| RoHS & Reach

Life Support Policy

General policy

APC by Schneider Electric does not recommend the use of any of its products in the following situations:

  • In life-support applications where failure or malfunction of the APC by Schneider Electric product can be reasonably expected to cause failure of the life-support device or to affect significantly its safety or effectiveness.
  • In direct patient

APC by Schneider Electric will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to APC by Schneider Electric that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) the liability of APC by Schneider Electric is adequately protected under the circumstances.

Examples of life-support devices

The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), autotransfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults and infants), anesthesia ventilators, infusion pumps, and any other devices designated as “critical” by the U.S. FDA.

Hospital-grade wiring devices and leakage current protection may be ordered as options on many APC by Schneider Electric UPS systems. APC by Schneider Electric does not claim that units with these modifications are certified or listed as hospital-grade APC by Schneider Electric or any other organization. Therefore these units do not meet the requirements for use in direct patient care.

Radio frequency interference

Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.

Factory Warranty

This warranty applies only to the products you purchase for your use in accordance with this manual.

Terms of warranty

APC by Schneider Electric warrants its products to be free from defects in materials and workmanship for a period of one year from the date of purchase. APC by Schneider Electric will repair or replace defective products covered by this warranty. This warranty does not apply to equipment that has been damaged by accident, negligence or misapplication or has been altered or modified in any way. Repair or replacement of a defective product or part thereof does not extend the original warranty period. Any parts furnished under this warranty may be new or factory-remanufactured.

Non-transferable warranty

This warranty extends only to the original purchaser who must have properly registered the product. The product may be registered at the APC by Schneider Electric website, www.apc.com.

Exclusions

APC by Schneider Electric shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user’s or any third person’s misuse, negligence, improper installation or testing. Further, APC by Schneider Electric shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection, inappropriate on-site operation conditions, corrosive atmosphere, repair, installation, exposure to the elements, Acts of God, fire, theft, or installation contrary to APC by Schneider Electric recommendations or specifications or in any event if the APC by Schneider Electric serial number has been altered, defaced, or removed, or any other cause beyond the range of the intended use.

THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. APC BY SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APC BY SCHNEIDER ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC BY SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC BY SCHNEIDER ELECTRIC’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. WARRANTIES EXTEND ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.

IN NO EVENT SHALL APC BY SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC BY SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, APC BY SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUENTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.

NO SALESMAN, EMPLOYEE OR AGENT OF APC BY SCHNEIDER ELECTRIC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY AN APC BY SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.

Warranty claims

Customers with warranty claims issues may access the APC by Schneider Electric customer support network through the Support page of the APC by Schneider Electric website, www.apc.com/support. Select your country from the country selection pull-down menu at the top of the Web page. Select the Support tab to obtain contact information for customer support in your region.

Frequently Asked Questions

What is the maximum input voltage for the APC EPDU1016B Power Distribution Unit?

The maximum input voltage for this unit is 200 - 240 VAC.

What is the maximum output current for the outlets on this Power Distribution Unit?

The maximum output current for the outlets is 10A, and the maximum output current per phase is 16A.

How many outlets are there on the APC EPDU1016B Power Distribution Unit?

There are a total of eight (8) IEC 320 C13 outlets.

Can I use extension cords or adapters with this Power Distribution Unit?

No, it is not recommended to use extension cords or adapters with this unit.

Is this Power Distribution Unit suitable for outdoor use?

No, this unit is intended for indoor use only and should not be installed in locations with excessive moisture or heat.

Can I install this Power Distribution Unit during a lightning storm?

No, you should never install any wiring, equipment, or Rack PDUs during a lightning storm.

Does APC by Schneider Electric provide a warranty for this product?

Yes, APC by Schneider Electric offers a one-year warranty for this product. Please refer to the terms of warranty for more details.

Are there any user-serviceable parts in this unit?

No, this unit does not have any user-serviceable parts, and repairs should only be performed by factory-trained service personnel.

Can I connect this unit to a single-outlet dedicated circuit?

Yes, it is recommended to connect this equipment to a single-outlet dedicated circuit protected by a circuit breaker or fuse with the same current rating as the Rack PDU.

What should I do if I encounter shipping damage or missing contents?

If you encounter shipping damage or missing contents, immediately report the issue to the shipping agent and APC by Schneider Electric or your APC by Schneider Electric reseller.

Can I mount the APC EPDU1016B Power Distribution Unit in a 19-inch NetShelter™ rack?

Yes, you can mount this Power Distribution Unit in a 19-inch NetShelter™ rack or any other EIA-310-D standard 19-inch rack.

What is the length of the input power cord for this Power Distribution Unit?

The input power cord for this unit is 2.5 meters (8.2 feet) in length and comes with IEC-320 C19 to C20 (16A) connectors.

Reference:APC EPDU1016B Power Distribution Unit Installation Manual- Device.Report

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals