ESBE VTA500 Series Thermostatic Mixing Valve Instructions

June 13, 2024
ESBE

ESBE VTA500 Series Thermostatic Mixing Valve

Product Information

  • Product Name: ESBE SERIES VTA500/VTS500
  • Product Series: VTA520, VTA530, VTA550, VTA560, VTS520, VTS550
  • Compliance: PED 2014/68/EU, article 4.3; SI 2016 No. 1105
  • Maximum Pressure: 1.0 MPa/10 bar

Product Usage Instructions

  • Installation:
    • All installation work should be performed by qualified personnel in accordance with applicable codes and ordinances.
    • Flush the pipes clean, shut off the water supply, and drain the pipes.
    • When connecting the VTA500/VTS500, follow the general directions outlined in Fig B.
    • Pay special attention to the instructions provided.
  • Temperature Adjustment:
    • To set the mixed water temperature, follow the steps described in Fig. G.
    • Verify the set temperature by measuring the water temperature at the tap closest to the valve.
    • The valve’s temperature setting should be checked annually to ensure accuracy.
  • Service and Maintenance:
    • Under normal conditions, maintenance is not required.
    • If maintenance becomes necessary, the gasket (O-rings), sensing element, and valve plug can be easily replaced.
    • Before dismantling the valve, shut off the water supply.
    • If the valve is fitted below the calorifier, drain it first.
    • Cleaning internal parts can restore proper operating conditions in case of scale deposits caused by hard water.
    • Clean and/or restore the valve by following these steps:
    • Remove the cap (1) and parts 2-4 (Fig. A).
    • Carefully remove any scaling or foreign particles from all internal parts.
    • If necessary, remove and clean the seat assembly in the same way.
    • Assemble the valve using only silicone grease approved for drinking water applications.
    • Adjust the temperature as needed (Fig. G1-G3).
      Note: The application examples provided in the manual are for reference only. Always consider local laws and regulations. Please let me know if you need any further assistance.

ESBE-VTA500-Series-Thermostatic-Mixing-Valve-FIG-2 ESBE-VTA500-Series-Thermostatic-Mixing-Valve-
FIG-3
ESBE-VTA500-Series-Thermostatic-Mixing-Valve-FIG-4
ESBE-VTA500-Series-Thermostatic-Mixing-Valve-FIG-5

ESBE-VTA500-Series-Thermostatic-Mixing-Valve-FIG-9
ESBE-VTA500-Series-Thermostatic-Mixing-Valve-FIG-15

INSTALLATION

All work must be performed by qualified personnel and in accordance with applicable codes and ordinances.

  • Flush the pipes clean, shut off water supply and drain the pipes.
  •  When connecting the VTA500/VTS500, please follow the general directions outlined in Fig B, and pay special attention to:
    • the recommended use of shut-off valves (Fig C)
    • installing the valve under the calorifier or using heat traps (Fig. D)
    • installing the valve in a correct manner to avoid damage (Fig. E)
    • the installation of non-return valves where applicable (Fig.B,F)
      After installation, deposit this leaflet with the owner of the valve for future reference.

ESBE-VTA500-Series-Thermostatic-Mixing-Valve-FIG-10
ESBE-VTA500-Series-Thermostatic-Mixing-Valve-FIG-11
ESBE-VTA500-Series-Thermostatic-Mixing-Valve-FIG-12
ESBE-VTA500-Series-Thermostatic-Mixing-Valve-FIG-13

TEMPERATURE ADJUSTMENT

  • To set the mixed water temperature, follow the steps described in Fig. G. Make sure to verify the set temperature by measuring the water temperature at the tap closest to the valve.
  • The temperature should be checked annually to ensure that the setting of the valve is correct.

SERVICE AND MAINTENANCE

Under normal conditions maintenance will not be required. If, however, it should prove necessary, the gasket (O-rings), the sensing element and the valve plug are easily replaced.
NOTE! Before dismantling the valve the water supply should be shut off. Where the valve is fitted below the calorifier this should be drained first.

  • Hard water conditions may result in scale deposits causing sticking of internal parts in extreme cases. Cleaning the internal parts will usually restore the valve to proper operating conditions.
  • It may be necessary also to clean the seat and/or to exchange the thermostat.
  • To clean and/or restore the valve, shut off the water and:
    1. Remove the cap (1) and the parts 2-4 (Fig. A
    2. Remove carefully all scaling (calcium deposits) or foreign particles from all internal parts.
    3. When necessary remove and clean the seat assembly in the same way.
    4. Assemble the valve. Only silicone grease approved for drinking water applications is allowed to be used.
    5. Adjust the temperature. (Fig. G1-G3)
      The application examples inside this instruction manual are overall idea sketches. Always also take locally laws and regulations into consideration.