ESBE GRB300 Manifolds for 2 Circulation Units Instruction Manual

June 4, 2024
ESBE

ESBE GRB300 Manifolds for 2 Circulation Units

Function

Cabling & Dimensions

Electric installation

ESBE GRB300 Manifolds for 2 Circulation Units fig
3

  1. Remove knob Disassembly insulation

  2. Pull up insulation 7mm Remove

  3. Assembling on wall
    Adjust wallbracket

  4. Fit supply pipesESBE GRB300 Manifolds for 2 Circulation Units fig 10

  5. Assemble insulationESBE GRB300 Manifolds for 2 Circulation Units fig 11

  6. Assemble actuator/controllerESBE GRB300 Manifolds for 2 Circulation Units fig 12

Mounting position actuator/controller

ESBE GRB300 Manifolds for 2
Circulation Units fig 13

Mounting positionESBE GRB300 Manifolds for 2 Circulation Units fig
14

**Commissioning

ESBE GRB300 Manifolds for 2 Circulation Units fig
15**

Commissioning actuator/controllerESBE GRB300 Manifolds for 2 Circulation
Units fig 16

Display

ESBE GRB300 Manifolds for 2 Circulation Units fig
17 ESBE GRB300 Manifolds for 2 Circulation
Units fig 18

VentingESBE GRB300 Manifolds for 2 Circulation Units fig
19

Manual restartESBE GRB300 Manifolds for 2 Circulation Units fig
20

WILO Faults, Causes and Remedies

LED Indicator Faults Causes Remedies
Pump is not running although the power supply is switched on Electrical fuse
defective Check fuses
Pump has no voltage Resolve the power interruption
Pump making noises Cavitation due to insufficient suc- tion pressure

Increase the system pressure within the permissible range
Check the delivery head and set it to a lower head if necessary
Building does not get warm| Thermal output of the heating surfaces is too low| Increase setpoint
Set control mode to Δp-c
Warning signals is indicated by the LED display. Fault signal LED does not light up.
E07| Generator operation| Water is flowing through the pump hydraulics, but pump has no mains voltage| Check mains voltage
E11| Dry run| Air in the pump| Check volumetric flow rate/water pressure
E21| Overload| Sluggish motor, pump is opera- ted outside of its specifications (e.g. high module temperature). The speed is lower than during normal operation.| Check the ambient conditions
Fault signals is indicated by the LED display. Fault signal LED lights up red.
E04| Undervoltage| Power supply too low on mains side| Check mains voltage
E05| Overvoltage| Power supply too high on mains side| Check mains voltage
E10| Blocking| Rotor blocked| Activate manual restart or con- tact customer service
E23| Short-circuit| Motor current too high| Request customer service
E25| Contacting/ winding| Winding defective| Request customer service
E30| Excessive temperature of module| Module interior too warm| Check conditions of use
E36| Module defective| Electronics defective| Request customer service

Expose application info using leaflet

ESBE GRB300 Manifolds for 2
Circulation Units fig 21

Dimensioning, Pump Capacity diagram Series GRB301

ESBE GRB300 Manifolds
for 2 Circulation Units fig 22