MEAN WELL HDR-150-12 150W Ultra Slim Step Shape DIN Rail Owner’s Manual
- June 13, 2024
- MEAN WELL
Table of Contents
MEAN WELL HDR-150-12 150W Ultra Slim Step Shape DIN Rail Owner’s Manual
Features
- Ultra slim design with 105mm(6SU) width
- Universal input 85~264VAC(277VAC operational)
- No load power consumption<0.3W
- Isolation class II
- DC output voltage adjustable
- Protections: Short circuit / Overload / Over voltage
- Cooling by free air convection
- DIN rail TS-35/7.5 or 15 mountable
- Over voltage category III
- LED indicator for power on
- 3 years warranty
Applications
- Household control system
- Building automation
- Industrial control system
- Factory automation
- Electro-mechanical apparatus
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
HDR-150 is an economical ultra slim 150W DIN rail power supply series, adapt
to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed
105mm(6SU) in width, which allows space saving inside the cabinets. The entire
series adopts the full range AC input from 85VAC to 264VAC (277VAC
operational) and conforms to BS EN/EN61000-3-2, the norm the European Union
regulates for harmonic current.
HDR-150 is designed with plastic housing that it can effectively prevent user
from electric hazards. With working efficiency up to 90.5%, the entire series
can operate at the ambient temperature between -30°C and 70°C under air
convection. The complete protection functions and relevant certificates for
home automations and industrial control apparatus
(IEC62368-1,UL62368-1,UL61010, BS EN/EN61558-2-16) make HDR-150 a very
competitive power supply solution for household and industrial applications.
Model Encoding
SPECIFICATION
MODEL | HDR-150-12 | HDR-150-15 | HDR-150-24 | HDR-150-48 |
---|---|---|---|---|
OUTPUT | DC VOLTAGE | 12V | 15V | 24V |
RATED CURRENT | 115VAC | 10.2A | 8.55A | 5.31A |
230VAC | 11.3A | 9.5A | 6.25A | 3.2A |
RATED POWER | 115VAC | 122.4W | 128.3W | 127.4W |
230VAC | 135.6W | 142.5W | 150W | 153.6W |
RIPPLE & NOISE (max.) Note.2 | 100mVp-p | 120mVp-p | 150mVp-p | 200mVp-p |
VOLTAGE ADJ. RANGE | 10.8~ 13.8V | 13.5 ~ 18V | 21.6 ~ 29V | 43.2 ~ 55.2V |
VOLTAGE TOLERANCE **Note.3** | ±2.0% | ±1.0% | ±1.0% | ±1.0% |
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% |
SETUP, RISE TIME | 500ms, 60ms/230VAC 500ms, 60ms/115VAC at |
full load
HOLD UP TIME (Typ.)| 30ms/230VAC 12ms/115VAC at full load
INPUT| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational )
120 ~ 370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 89%| 89.5%| 90.5%| 90.5%
AC CURRENT (Typ.)| 3A/115VAC 1.6A/230VAC
INRUSH CURRENT (Typ.)| COLD START 35A/115VAC 70A/230VAC
PROTECTION| OVERLOAD| 105 ~ 135% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault
condition is removedConstant current limiting within 50% ~100% rated output
voltage, recovers automatically after fault condition is removed
OVER VOLTAGE| 14.2 ~ 16.2V| 18.8 ~ 22.5V| 30 ~ 36V| 56.5 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
ENVIRONMENT| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 45℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters (Note 4 )
OVER VOLTAGE CATEGORY| Ⅲ; According to EN62368,EN61558,
EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters
SAFETY & **EMC ( Note.7 )| SAFETY STANDARDS| IEC62368-1,
UL62368-1, UL61010, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, EAC TP TC 004
approved;Design refer to BS EN/EN50178, TUV BS EN/EN62368-1
WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32)| Class B
Radiated| BS EN/EN55032(CISPR32)| Class B (note 5)
Harmonic Current (Note 6 )| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| ——-
EMC IMMUNITY| BS EN/EN55024, BS EN/EN61000-6-2
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods,>95% interruptions 250 periods
OTHERS| MTBF| 3046.3K hrs min. Telcordia SR-332 (Bellcore) ;
535.9K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 1059054.5mm (WHD)
PACKING| 0.31Kg; 32pcs/11Kg/1.0CUFT
NOTE**| 1. All parameters NOT specially mentioned are measured at 230VAC
input, rated load and 25℃ of ambient temperature.2. Ripple noise are
measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with
a 0.1μf 47μf parallel capacitor.3. Tolerance : includes set up tolerance,
line regulation and load regulation.4. The ambient temperature derating of
3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating
altitude higher than 2000m(6500ft).5. When the input voltage is
230VAC,delivers EMI Class B for radiated emission for the power supply; When
the input voltage is 110VAC, delivers EMI Class A for radiated emission for
the power supply.6. Harmonic current test at 70% load .7. The power supply is
considered as an independent unit, but the final equipment still need to re-
confirm that the whole system complies with the EMC directives. For guidance
on how to perform these EMC tests, please refer to EMI testing of component
power supplies. (as available on http://www.meanwell.com)※ Product
Liability Disclaimer For detailed information, please refer to
https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve VS Ambient Temperature
AMBIENT TEMPERATURE ()
Output Derating VS Input Voltage
INPUT VOLTAGE (VAC) 60Hz
Mechanical Specification
(Unit: mm , tolerance ± 0.5mm)
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Terminal Pin No. Assignment
Pin No | Assignment | Pin No | Assignment |
---|---|---|---|
1 | AC/N | 3,4 | -V |
2 | AC/L | 5,6 | +V |
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
User’s Manual
Read User Manual Online (PDF format)