MEAN WELL HDR-150-12 150W Ultra Slim Step Shape DIN Rail Owner’s Manual

June 13, 2024
MEAN WELL

MEAN WELL HDR-150-12 150W Ultra Slim Step Shape DIN Rail Owner’s Manual
MEAN WELL HDR-150-12 150W Ultra Slim Step Shape DIN
Rail

Symbols

Features

  • Ultra slim design with 105mm(6SU) width
  • Universal input 85~264VAC(277VAC operational)
  • No load power consumption<0.3W
  • Isolation class II
  • DC output voltage adjustable
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • DIN rail TS-35/7.5 or 15 mountable
  • Over voltage category III
  • LED indicator for power on
  • 3 years warranty

Symbols

Applications

  • Household control system
  • Building automation
  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

HDR-150 is an economical ultra slim 150W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 105mm(6SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC (277VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current.
HDR-150 is designed with plastic housing that it can effectively prevent user from electric hazards. With working efficiency up to 90.5%, the entire series can operate at the ambient temperature between -30°C and 70°C under air convection. The complete protection functions and relevant certificates for home automations and industrial control apparatus (IEC62368-1,UL62368-1,UL61010, BS EN/EN61558-2-16) make HDR-150 a very competitive power supply solution for household and industrial applications.

Model Encoding

Model Encoding

SPECIFICATION

MODEL HDR-150-12 HDR-150-15 HDR-150-24 HDR-150-48
OUTPUT DC VOLTAGE 12V 15V 24V
RATED CURRENT 115VAC 10.2A 8.55A 5.31A
230VAC 11.3A 9.5A 6.25A 3.2A
RATED POWER 115VAC 122.4W 128.3W 127.4W
230VAC 135.6W 142.5W 150W 153.6W
RIPPLE & NOISE (max.) Note.2 100mVp-p 120mVp-p 150mVp-p 200mVp-p
VOLTAGE ADJ. RANGE 10.8~ 13.8V 13.5 ~ 18V 21.6 ~ 29V 43.2 ~ 55.2V
VOLTAGE TOLERANCE **Note.3** ±2.0% ±1.0% ±1.0% ±1.0%
LINE REGULATION ±1.0% ±1.0% ±1.0% ±1.0%
LOAD REGULATION ±1.0% ±1.0% ±1.0% ±1.0%
SETUP, RISE TIME 500ms, 60ms/230VAC            500ms, 60ms/115VAC at

full load
HOLD UP TIME (Typ.)| 30ms/230VAC     12ms/115VAC at full load
INPUT| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational ) 120 ~ 370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 89%| 89.5%| 90.5%| 90.5%
AC CURRENT (Typ.)| 3A/115VAC      1.6A/230VAC
INRUSH CURRENT (Typ.)| COLD START 35A/115VAC             70A/230VAC
PROTECTION| OVERLOAD| 105 ~ 135% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removedConstant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed
OVER VOLTAGE| 14.2 ~ 16.2V| 18.8 ~ 22.5V| 30 ~ 36V| 56.5 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
ENVIRONMENT| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 45℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters (Note 4 )
OVER VOLTAGE CATEGORY| Ⅲ; According to EN62368,EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters
SAFETY & **EMC ( Note.7 )| SAFETY STANDARDS| IEC62368-1, UL62368-1, UL61010, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, EAC TP TC 004 approved;Design refer to BS EN/EN50178, TUV BS EN/EN62368-1
WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32)| Class B
Radiated| BS EN/EN55032(CISPR32)| Class B (note 5)
Harmonic Current (Note 6 )| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| ——-
EMC IMMUNITY| BS EN/EN55024, BS EN/EN61000-6-2
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30% dip 25 periods,>95% interruptions 250 periods
OTHERS| MTBF| 3046.3K hrs min.       Telcordia SR-332 (Bellcore) ; 535.9K hrs min.       MIL-HDBK-217F (25℃)
DIMENSION| 1059054.5mm (WHD)
PACKING| 0.31Kg; 32pcs/11Kg/1.0CUFT
NOTE**| 1.  All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.2.  Ripple  noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1μf  47μf parallel capacitor.3.  Tolerance : includes set up tolerance, line regulation and load regulation.4.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).5.  When the input voltage is 230VAC,delivers EMI Class B for radiated emission for the power supply; When the input voltage is 110VAC, delivers EMI Class A for radiated emission for the power supply.6.  Harmonic current test at 70% load .7. The power supply is considered as an independent unit, but the final equipment still need to re- confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.  (as available on http://www.meanwell.com)※ Product Liability Disclaimer For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

Block Diagram

Derating Curve VS Ambient Temperature

AMBIENT TEMPERATURE ()

Derating Curve

Output Derating VS Input Voltage

INPUT VOLTAGE (VAC) 60Hz
Output Derating

Mechanical Specification

(Unit: mm , tolerance ± 0.5mm)

Mechanical

Mechanical
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15

Terminal Pin No. Assignment

Pin No Assignment Pin No Assignment
1 AC/N 3,4 -V
2 AC/L 5,6 +V