WATTS LFM513-5 Large Pump Control Valve with Mechanical Check Feature Instruction Manual
- June 13, 2024
- WATTS
Table of Contents
Submittal Package
Engineering Specification, Installation, Operation and Maintenance
Series LFM513-5 — Large
Pump Control Valve with Mechanical Check Feature
Sizes: 20 and 24″
13-5 Large Pump Control Valve with Mechanical Check Feature
WARNING
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can result in death,
serious personal injury, property damage, or damage to the equipment.
Keep this Manual for future reference.
WARNING
Local building or plumbing codes may require modifications to the information
provided. You are required to consult the local building and plumbing codes
prior to installation. If the information provided here is not consistent with
local building or plumbing codes, the local codes should be followed. This
product must be installed by a licensed contractor in accordance with local
codes and ordinances.
WARNING
Need for Periodic Inspection/Maintenance: This product must be tested
periodically in compliance with local codes, but at least once per year or
more as service conditions warrant. All products must be retested once
maintenance has been performed. Corrosive water conditions and/or unauthorized
adjustments or repair could render the product ineffective for the service
intended. Regular checking and cleaning of the product’s internal and external
components helps assure maximum life and proper product function.
If installed on a fire sprinkler system, all mechanical checks, such as alarm
checks and backflow preventers, should be flow tested and inspected internally
in accordance with NFPA 13 and NFPA 25.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Engineering Specification
*LEAD FREE
Series LFM513-5 – Large
Pump Control Valve with Mechanical Check Feature
Full Port Ductile Iron Single Chamber Valve
Features
**
- Opens at adjustable rate on pump start-up
- Closes at adjustable rate on pump shut-off
- Limit Switch turns pump off when valve closes
- Built-in Mechanical Lift-Check Feature prevents flow reversal
- Solenoid equipped with Manual Operator
Standard Components
1— Main Valve – M518 Dual Chamber
2 — Four-Way Solenoid
3 — Check Valve
4 — Limit Switch
5 — ACS – Adjustable Closing Speed (Globe Valve)
6 — AOS – Adjustable Opening Speed (Globe with Check)
7 —Pressure Gauges
X — Isolation Cocks
Y — Wye strainer
Options and Accessories
O L | Dual Limit Switch |
---|
The Pump Control Valve is designed to minimize the surges associated with the
starting and stopping of pumps. The valve slowly opens and closes as required
to control pumping related surges. The pump starts and stops against a closed
valve.
Pump start up: When the pump is signaled to start, the 4-Way Solenoid is
energized and directs fluid and pressure into the power chamber (below the
diaphragm), and relieves fluid and pressure from the cover chamber (above the
diaphragm). The fluid and pressure relieved from the cover chamber is vented
to atmosphere or available floor drain. The valve opens at an adjustable rate,
gradually admitting pumping pressure into the distribution system. Rate of
valve opening is controlled by the adjustable opening speed control, which
restricts the speed at which fluid and pressure evacuate the cover chamber.
The valve remains fully open during the pumping cycle.
Pump shutdown: When the pump is signaled to shut-off, the 4-Way Solenoid is
de-energized, and directs fluid and pressure into the cover chamber (above the
diaphragm), and relieves fluid and pressure from the power chamber (below the
diaphragm). The fluid and pressure relieved from the power chamber is vented
to atmo- sphere or available floor drain. The valve closes at an adjustable
rate, gradually reducing pumping pressure. Rate of valve closure is controlled
by the adjustable closing speed control, which restricts the speed at which
fluid and pressure evacuate the power chamber. When the valve reaches the
closed position, the limit switch is actuated, turning the pump off.
Emergency Closure: The valve is equipped with a Mechanical Check Feature,
which acts independent of diaphragm position, and provides immediate closure
when flow ceases.
Manual Operation: Engaging the Solenoid Manual operator simulates power to the
solenoid, manually opening the main valve. Disengaging the Solenoid Manual
operator returns the valve to the closed position.
- The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
ACV Schematic – Series LFM513-5 – Large
M Series Basic Valves
Pump Control Valve with Mechanical Check Feature
Full Port Ductile Iron Single Chamber Basic Valve
This Watts Automatic Control Valve (ACV) is a full port, single chamber basic
valve that incorporates a one-piece disc and diaphragm assembly. This assembly
is the only moving part within the valve allowing it to open, close, or
modulate as commanded by the pilot control system.
Watts ACV Main Valves are Lead Free. The Watts ACV piloting system contains
Lead Free* components, ensuring all of our configurations are Lead Free
compliant.
Globe Pattern Single Chamber Basic Valve (M100)
Standard Materials
Body and Cover: | Ductile Iron ASTM A536 |
---|---|
Coating: | NSF Listed Fusion Bonded Epoxy Lined and Coated |
Trim: | 316 Stainless Steel |
Elastomers: | Buna-N (standard) |
Nut, Spring and Stem: | Stainless Steel |
Anti-Scale: | Xylan Coated Stem and Seat (Optional) |
Operating Pressure
150# Flanged = 250psi (17.2 bar)
300# Flanged = 400psi (27.6 bar)
Operating Temperature
Buna-N: 160°F (71°C) Maximum
Epoxy Coating: 225°F (107°C) Maximum
Valves can be provided without internal epoxy coating consult factory
Basic Valve Body Options
- The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
ACV Schematic – Series LFM513-5 – Large
Flow Data
| Valve Size – Inches| 1 1/4| 1 1/2| 2| 2 1/2| 3| 4| 6| 8| 10| 12| 14| 16| 20|
24
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Suggested| Maximum Continuous Flow Rate Gpm (Water)| 95| 130| 210| 300| 485|
800| 1850| 3100| 5000| 7000| 8500| 11100| 19600| 28200
Maximum Intermittent Flow Rate Gpm (Water)| 119| 161| 265| 390| 590| 1000|
2300| 4000| 6250| 8900| 10800| 14100| 24500| 35250
Minimum Flow Rate Gpm (Water)| 3| 5| 6| 9| 15| 16| 17| 25| 55| 70| 190| 400| |
315
CV| CV Factor GPM (Globe)| 26| 26| 48| 75| 112| 188| 387| 764| 1215| 1734|
2234| 3131| | 7447
CV Factor GPM (Angle)| 26| 27| 57| 91| 125| 207| 571| 889| 1530| 1945| | | |
-
Maximum continuous flow based on velocity of 20 ft. per second.
-
Maximum intermittent flow based on velocity of 25 ft. per second.
-
Minimum flow rates based on a 20-40 psi pressure drop.
-
The Cv Factor of a value is the flow rate in US GPM at 60°F that will cause a 1psi drop in pressure.
-
Cv factor can be used in the following equations to determine Flow (Q) and Pressure Drop (∆P):
Q (Flow) = Cv√∆P ∆P (Pressure Drop) = (Q/Cv)² -
The Cv factors stated are based upon a fully open valve.
-
Many factors should be considered in sizing control valves including inlet pressure, outlet pressure and flow rates.
-
For sizing questions including cavitation analysis consult Watts with system details.
Valve Cover Chamber Capacity – Dual
Valve Size – Inches | 20 | 24 |
---|---|---|
U.S. Gal | 45 | 64.9 |
Liter | 170.3 | 245.7 |
Valve Travel
Valve Size – Inches | 20 | 24 |
---|---|---|
in. | cm. | in. |
Travel – Inches | 5.62 | 14.3 |
ACV Schematic – Series LFM513-5 – Large
Basic Valve
Item | Description | Material |
---|---|---|
1 | 150# Body | Epoxy Coated Ductile Iron – ASTM A536 |
2 | Dowel Pin | Stainless Steel 18-8 |
3 | Insert | Epoxy Coated Ductile Iron – ASTM A536 |
3 | Cover | Epoxy Coated Ductile Iron – ASTM A536 |
4 | Diaphragm | Buna-N |
5 | Nut Lifting Eye | Steel |
6a | Flange Screws x4 | Stainless Steel 18-8 |
6b | 3/4 Lock Washer | Stainless Steel 18-8 |
6c | Flange 11/2 NPT, 300 CL | Stainless Steel – UNS S30400 |
6d | Gasket 1 1/2 Pipe | Buna-N |
7a | Guide Cover Screws | Stainless Steel 18-8 |
7b | Guide Cover | Stainless Steel – UNS S30400 |
7c | O-Ring | Buna-N – 70 DURO |
8 | Cover Bearing with O-Ring | ASTM A276 UNS S30400, Buna-N |
10-Sep | Cover Stud, Hex Nut | ASTM A193 GRB7 Yellow Zinc PLT |
11 | Flat Washer | Carbon Steel Zinc Plated |
12 | Insert Gasket Seal | Buna-N |
13 | Stem Nut with Set Screw | Stainless Steel ASTM A276 304; Stainless Steel – |
18-8
14| Stem Nut Washer| Stainless Steel – UNS S30400
15a – 15b| Upper Stem and Lower Stem| Xylan Coated Stainless Steel – UNS
S30400
16| Sleeve Bearing| Bronze – SAE 841
17| Upper & Lower Diaphragm Washer| Ductile Iron ASTM A536 65-45-12
18| O-Rings x2| Buna-N
19| O-Ring| Buna-N
20| Stem Bearing with O-Rings| Brass; Buna N
21| Retaining Ring| Stainless Steel 18-8
22| O-Ring| Buna-N
23| Disc Retainer| Epoxy Coated Ductile Iron – ASTM A536
24| Stem Nut Washer| Stainless Steel 304
25| Disc| Buna-N
26| Disc Guide Plate with Screws| Stainless Steel – UNS S31600
27| Seat with Seat Screws| ASTM A743 CF8M; Stainless Steel 18-8
28| Seat O-Ring| Buna-N
29| Stem Nut with Screw| Stainless Steel ASTM A276 304; Stainless Steel – 18-8
- Contained in Main Valve Repair Kit
NOTICE
Installation: If unit is installed in any orientation other than horizontal (cover up) OR extreme space constraints exist, consult customer service prior to or at the time of order.
ACV Schematic – Series LFM513-5 – Large
Dimensions
Valve Size| Globe 150#| Globe 300#| Cover To Center|
Port Size NPT| Port Size NPT| **Shipping Weights*
---|---|---|---|---|---|---
| A| B| C| D| F**|
in.| in.| mm| in.| mm| in.| mm| in.| mm| in.| mm| lbs.| kgs.
20| 52| 1320.8| 53 5/8| 1362.1| 49 1/2| 1257.3| 1 1/2| 38.1| 1 1/2| 38.1|
5803| 2632.2
24| 61 1/2| 1562.1| 63 1/4| 1606.5| 57 1/4| 1454.2| 1 1/2| 38.1| 1 1/2| 38.1|
8411| 3815.2
ACV Standard Components – Series LFM513-5 – Large
Model S4W
3-Way Solenoid
Size: 1/8″ – 1/2″ NPT
Model S4W are pilot system 4-way solenoids. The solenoids can control
valves independently or in combination with other control circuit pilots or
accessories. Product is available with a wide range of options including:
voltage (24VDC, 24VAC or 120VAC), and a range of enclosures (general service
to watertight to explosion proof).
|
---|---
Specifications
Body Material: | Brass (standard)*** |
---|---|
Elastomers: | Nitrile (standard) |
EPDM (optional)
Viton™ (optional)
Voltage:| 24VDC, 24VAC or 120VAC
Enclosure:| General Purpose – NEMA 4 (standard)
Explosion Proof – NEMA 6, 6P, 7, 9 (optional)
Action:| 4-Way Actuation
**Solenoid Action only. Main valve action (energize-to-open or energize-to-
close) is dependent on the particulars of the pilot system.
***Brass solenoids are not lead free and it is illegal to use them in potable
services in the United States such as drinking water, handwashing, food
preparation, and dishwashing. However, brass solenoids may be used as a
replacement component in a lead free Watts ACV main valve, as the wetted
surface of a lead free Watts ACV main valve including installed brass
solenoids contains less than 0.25% of lead by weight.
Viton™ is a trademark of The Chemours Company FC, LLC
*ACV Standard Components – Series LFM513-5 – Large
LEAD FREE
Model CK
Check Valve
Size: ¼” – 1″ NPT
** Model CK Check Valves are pilot line check valves. In typical applications
these low cracking pressure in-line checks provide a hydraulic check feature
to a pilot system. When the main valve outlet pressure exceeds inlet pressure,
fluid is directed from the outlet to the main valve cover. This causes the
main valve to close until inlet pressure is again greater than outlet.
|
---|---
Specifications
Standard Material:| Brass Housing and Body
Stainless Steel Indicating Rod
---|---
Optional Material:| Stainless Steel Housing and Body Disc Viton® (1/4″ – ½”)
PTFF (1″)
Pressure Rating:| 400psi (27.6 bar)
Viton® is a registered trademark of DuPont Dow Elastomers.
- The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
*ACV Standard Components – Series LFM513-5 – Large
LEAD FREE
Model 51
Single Limit Switch**
The Model 51 Single Limit Switch provides visual indication of valve position,
as well as remote electrical indication of “valve open” or “valve closed”. The
single pole double throw MicroSwitch can be connected to open or close an
electrical circuit when the valve opens or closes.
The adjustable collar is normally set to contact the trip arm when the main
valve is closed. The collar can be positioned on the stem by loosening the
set-screw to actuate the switch at the desired point of valve travel.
|
---|---
Specifications
Body Material: | Stainless Steel |
---|---|
Elastomers: | Buna-N (standard) |
EPDM (optional)
Viton™ (optional)
Enclosure:| NEMA 1, 3, 4 and 13 General Purpose (standard)
NEMA 1,7 and 9 Explosion Proof (optional)
Electrical:| Form C SPDT Switch
15 amp. 125, 250 or 480 VAC
½ amp. 125 VDC
¼ amp. 250 VDC
½” Conduit Connection
Viton™ is a trademark of The Chemours Company FC, LLC
- The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
Parts List
Item | Description |
---|---|
1 | Limit Switch |
2 | Bracket |
3 | Stem |
4 | Trip collar |
5 | Set Screw |
6 | Cap |
7 | Wiper Ring* |
8 | O-Ring* |
9 | Guide |
10 | O-Ring* |
11 | Polypak* |
12 | Locknut |
13 | Body |
14 | Pin |
15 | Coupling |
*Included in Repair Kit
*ACV Standard Components – Series LFM513-5 – Large
LEAD FREE
Series LF622F/FT/UF/UFT
*Lead Free Bronze, Full Port Ball Valves
Size: 1⁄2″ – 2″
Features
- The FEBCO Series LF622FT/LF622UFT available with tapped side outlet suitable for installation of pressure gauges or test cocks. LF622UF/UFT with Union Ends.
- Lead Free construction to comply with Lead Free installation requirements.
- Tee handle standard on 1⁄2″ through 1 1 ⁄4″ sizes (15mm – 32mm).
- Lever handle standard on 1 1⁄2″ through 2″ sizes (40mm – 50mm).
- Full port design for low pressure drop.
- Pressure rated at 600psi (41.4 bar) WOG, (non-shock) 1⁄2″-2″ (15mm – 50mm) (DN15-DN50) and 125psi (8.6 bar) saturated steam.
- Suitable for temperature from 0ºF to +350ºF (-18ºC to 177ºC) at 50psi (345 kPa).
- PTFE stem packing seal, thrust washer and seat.
- Plated carbon steel handle with vinyl insulator.
- Quarter-turn open or close operation. (Not intended for throttling applications.)
- Ideal for throttling and balancing applications of non-abrasive fluids where minimum flow is 20% to 100% of valve capacity.
- Low operating torque.
- Adjustable stem packing gland.
- Bottom loaded, pressure retaining stem.
Options
LF622F: | Full Port Thread x Thread Ball Valve |
---|---|
LF622FT: | Full Port Thread x Thread Ball Valve with Tapped Side Outlet |
LF622 UF: | Full Port Thread x Thread Ball Valve with (1) Union End |
LF622 UFT: | Full port Thread x Thread Ball Valve with (1) Union End with |
Tapped Side Outlet
Specification
Approved valves shall have bottom loaded pressure retaining stems, PTFE seats
and full port. Valve shall be pressure rated at 600psi (41.4 bar) WOG (non-
shock), 125psi (8.6 bar) saturated steam. Valve must conform to Federal
Specification WW-V-35C, Type II, Composition, BZ, Style 3, End Connection A.
The Lead Free* copper silicon alloy full port ball valves shall comply with
state codes and standards, where applicable, requiring reduced lead content.
Valve shall be a FEBCO Series LF622F.
Series LF622F/FT/UF/UFT
Lead Free* Bronze, Full Port Ball Valves
Size: 1⁄2″ – 2″
Dimensions – Weights
Size: 1⁄2″ – 2″
Size | Series LF622FT / UFT Dimensions | Weight |
---|---|---|
in. | A | A1 (union) |
in. | mm | in. |
in. | mm | in. |
lbs. | kgs. | |
1⁄2 | 23⁄8 | 61 |
n/a | .6 | .3 |
3⁄4 | 25⁄8 | 67 |
.8 | .4 | 1.1 |
1 | 31⁄8 | 79 |
1.3 | .6 | 1.6 |
11⁄4 | 35⁄8 | 92 |
18 | n/a | 2.3 |
11⁄2 | 37⁄8 | 99 |
1⁄4 – 18 | n/a | 3.2 |
2 | 47⁄16 | 113 |
21 | 1⁄4 – 18 | n/a |
Size: 1⁄2″ – 2″
Size | Series LF622F / LF622UF Dimensions | Weight |
---|---|---|
in. | A | A1 |
in. | mm | in. |
in. | mm | in. |
1⁄2 | 23⁄16 | 55 |
3⁄4 | 23⁄8 | 61 |
1 | 27⁄8 | 73 |
11⁄4 | 31⁄4 | 83 |
1.1
11⁄2| 35⁄8| 92| 43⁄4| 120| 8| 206| 9| 231| | 3| 76| 23⁄16| 55| 3.1| 1.4| 3.6|
1.7
2| 43⁄16| 106| 53⁄8| 137| 83⁄8| 213| 911⁄16| 246| 31⁄2| 89| 23⁄4| 70| 5.3|
2.4| 6.3| 2.9
LEAD FREE
Series LF777, LFS777
Wye-Pattern Lead Free
Bronze Strainers
Sizes: 1⁄4″ – 4″
Series LF777, LFS777 Wye-Pattern Lead Free cast copper silicon alloy
Strainers are designed to protect system components from dirt, rust and other
damaging debris in the piping system.
This series features a solid retainer cap with gasket. The LF777 and LFS777
features Lead Free construction to comply with Lead Free* installation
requirements.
Features
- Lead Free* cast copper silicon alloy body
- Wye-pattern
- Solid retainer cap with gasket
Models
LF777 | 1⁄4″ – 4″ threaded connections |
---|---|
LFS777 | 1⁄2″ – 2″ solder connections |
Specifications
A wye-pattern Lead Free cast copper silicon alloy strainer to be installed as
indicated on the plans. The strainer must have a solid retainer cap with
gasket. Strainer shall be rated to 400psi (27.6 bar) WOG @ 210ºF (99ºC);
125psi (8.6 bar) WSP @ 353ºF (178ºF) for sizes 1⁄4″ – 3″ and 300psi (20.7 bar)
WOG @ 210ºF (99ºC); 125psi (8.6 bar) @ 353ºF (178ºC) for size 4″. Lead Free
WyePattern cast copper silicon alloy Strainers shall be constructed using Lead
Free* materials. Lead Free strainers shall comply with state codes and
standards, where applicable, requiring reduced lead content. Strainer shall be
a Watts Series LF777 (threaded ends) or LFS777 (solder ends).
Materials
Body: | Lead Free* cast copper silicon alloy |
---|---|
Retainer Cap: | 1⁄4″ – 4″: Lead Free copper silicon alloy |
Cap Seal: | 1⁄4″ – 3″: EPDM O-Ring |
4″: Garlock® gasket
Standard Screen:| 1⁄2″ – 21⁄2″: 304 stainless steel #20 mesh,
3″:3⁄64″ (1.2mm) 304 stainless steel perforated screen
4″: 1⁄8″ (3mm) 304 stainless steel perforated screen
Series LF777, LFS777
Wye-Pattern Lead Free* Bronze Strainers
Dimensions – Weights
LF777
SIZE | DIMENSIONS | WEIGHT |
---|---|---|
in. | in. | A |
1⁄4 | 2 11⁄16 | |
3⁄8 | 2 11⁄16 | |
1⁄2 | 3 | |
3⁄4 | 3 5⁄16 | |
1 | 4 1⁄2 | |
11⁄4 | 5 1⁄8 | |
11⁄2 | 5 7⁄8 | |
2 | 6 3⁄16 | |
21⁄2 | 8 1⁄8 | |
3 | 10 1⁄8 | |
4 | 13 |
LFS777
SIZE | DIMENSIONS | WEIGHT | |||||
---|---|---|---|---|---|---|---|
in. | in. | A | mm | in. | B | mm | lbs. |
1⁄2 | 33⁄8 | 86 | 21⁄16 | 52 | 1.5 | ||
3⁄4 | 33⁄4 | 95 | 27⁄16 | 63 | 1.6 | ||
1 | 5 | 127 | 3 | 76 | 2.5 | ||
11⁄4 | 55⁄8 | 143 | 31⁄4 | 82 | 2.8 | ||
11⁄2 | 67⁄16 | 164 | 313⁄16 | 97 | 4.0 | ||
2 | 71⁄2 | 191 | 45⁄8 | 118 | 7.4 |
*ACV Options and Accessories – Series LFM513-5 – Large
LEAD FREE
Model 51-1
Dual Limit Switch
Size: 2″ – 8″ NPT**
The Model 51-1 Dual Limit Switch provides visual indication of valve position,
as well as remote electrical indication of “valve open” and “valve closed”.
The single pole double throw MicroSwitches can be connected to open or close
an electrical circuit when the valve opens or closes.
The adjustable collars are normally set to contact the trip arms to indicate
“valve open” and “valve closed”. The collars can be positioned on the stem by
loosening the set-screws to actuate the switches at the desired point of valve
travel.
Single Pole Double Throw Switch|
---|---
Specifications
Body Material: | Stainless Steel |
---|---|
Elastomers: | Buna-N (standard) |
EPDM (optional)
Viton™ (optional)
Enclosure:| NEMA 1, 3, 4 and 13 General Purpose (standard)
NEMA 1,7 and 9 Explosion Proof (optional)
Electrical:| Form C SPDT Switch
15 amp. 125, 250 or 480 VAC
½ amp. 125 VDC
¼ amp. 250 VDC
½” Conduit Connection
Viton™ is a trademark of The Chemours Company FC, LLC
- The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
Parts List
Item | Description |
---|---|
1 | Limit Switch |
2 | Bracket |
3 | Stem |
4 | Trip collar |
5 | Set Screw |
6 | Cap |
7 | Wiper Ring* |
8 | O-Ring* |
9 | Guide |
10 | O-Ring* |
11 | Polypak* |
12 | Locknut |
13 | Body |
14 | Pin |
15 | Coupling |
Installation, Operation and Maintenance – Series LFM513-5 – Large
Installation
- Prior to installation, flush line to remove debris.
- Install valve so the flow arrow matches flow through the line, and gauges to monitor valve inlet and outlet pressures.
- Install isolation valves upstream and downstream of the main valve.
- Provide adequate clearance for valve servicing and maintenance. Refer to valve servicing dimensions on next page. Avoid installing valves 6″ and larger in the vertical position (main valve stem horizontal). Automatic Control Valves (ACVs) are designed for horizontal in-line installation, with the cover facing up (main valve stem vertical). Slow operation or premature stem and guide wear may occur if valve is not installed according to factory recommendations. Consult factory for detailed engineering review prior to ordering if valve is to be installed other than horizontally in-line.
- If valve is equipped with a pilot control system, extra precautions should be made during installation to protect the piping circuit from damage. Only remove the pilot control system from the valve if necessary. Tubing and fittings should be kept clean and replaced exactly as removed. Consult appropriate hydraulic schematic to ensure proper re-assembly.
- Connect solenoid wiring leads to desired switching device, using safe, standard electrical practices.
- Wire the limit switch contacts to the proper relay connections, using safe, standard electrical practices. Adjust the limit switch collar to the approximate make/break contact position.
Valve Servicing Dimensions
The following tables detail the recommended minimum valve servicing
dimensions.
Globe
Size (in) | 20 | 24 |
---|---|---|
in. | cm. | in. |
A (in) | 82 | 209 |
B (in) | 48 | 209 |
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to
be free from defects in material and workmanship under normal usage for a
period of one year from the date of original shipment. In the event of such
defects within the warranty period, the Company will, at its option, replace
or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY
GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL
OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute
the sole and exclusive remedy for breach of warranty, and the Company shall
not be responsible for any incidental, special or consequential damages,
including without limitation, lost profits or the cost of repairing or
replacing other property which is damaged if this product does not work
properly, other costs resulting from labor charges, delays, vandalism,
negligence, fouling caused by foreign material, damage from adverse water
conditions, chemical, or any other circumstances over which the Company has no
control. This warranty shall be invalidated by any abuse, misuse,
misapplication, improper installation or improper maintenance or alteration of
the product.
Some States do not allow limitations on how long an implied warranty lasts,
and some States do not allow the exclusion or limitation of incidental or
consequential damages. Therefore the above limitations may not apply to you.
This Limited Warranty gives you specific legal rights, and you may have other
rights that vary from State to State. You should consult applicable state laws
to determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW,
ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE
LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
USA: T:978-689-6066 • F:
978-975-8350 •
Watts.com
Canada: T:888-208-8927 • F:
905-481-2316 •
Watts.ca
Latin America: T: (52) 55-4122-0138 •Watts.com
ES-ACV-LFM513-5-L 2217
© 2022 Watts
Documents / Resources
|
WATTS LFM513-5 Large Pump Control Valve with Mechanical Check
Feature
[pdf] Instruction Manual
LFM513-5 Large Pump Control Valve with Mechanical Check Feature, LFM513-5,
Large Pump Control Valve with Mechanical Check Feature, Control Valve with
Mechanical Check Feature, Valve with Mechanical Check Feature, with Mechanical
Check Feature, Mechanical Check Feature, Check Feature, Feature
---|---